1 OFFICE OF INFORMATION TECHNOLOGY/ NETWORKING AND TELECOMMUNICATIONS SERVICES (OIT/NTS) EQUIPMENT, INFRASTRUCTURE, AND WIRING STANDARDS 1 INTRODUCTION GENERAL STANDARDS SPECIAL REQUIREMENTS ENTRANCE FACILITIES TELECOMMUNICATIONS ROOMS GENERAL REQUIREMENTS MAIN EQUIPMENT ROOM (MDF) COMMUNICATIONS ROOMS (IDF OR RISER ROOMS) TERMINAL SPACE/SATELLITE ROOMS ELECTRICAL POWER REQUIREMENTS AIR CONDITIONING REQUIREMENTS BONDING AND GROUNDING BUSBARS TELECOMMUNICATIONS BONDING BACKBONE CABLES RACK GROUNDING PATHWAY GROUNDING EQUIPMENT GROUNDING ELECTRICAL SERVICE COMPRESSION FITTINGS TESTING AND DOCUMENTATION INTRABUILDING BACKBONE RISER FACILITIES DESIGN CONSIDERATIONS INTRABUILDING BACKBONE COPPER (RISER) Cabling Terminations INTRABUILDING BACKBONE FIBER OPTIC (RISER) Cabling Fiber Terminations Fiber-Optic Enclosures INTRABUILDING BACKBONE PATHWAYS COMMUNICATIONS/TERMINAL ROOM TERMINATION REQUIREMENTS WALL TERMINATION OF COPPER WIRING EQUIPMENT RACKS PATCH PANELS HORIZONTAL MANAGEMENT... 25

2 9 RACEWAY/TRAY SYSTEMS J-HOOKS HORIZONTAL WIRING FACILITIES OUTLETS HORIZONTAL CONDUIT HORIZONTAL WIRING Horizontal Copper Wire Horizontal Fiber Optic Wire Small Form/Modular Style Fiber Standards JACKS TESTING CATEGORY 5E WIRING CATEGORY 6 WIRING FIBER OPTIC CABLE TO OUTLET INTRABUILDING BACKBONE RISER CABLE TESTING AS-BUILT DOCUMENTATION OIT/NTS OUTLET LABELING SCHEME (JACKS) PRODUCTS INSTALLED THAT ARE NOT COVERED BY THESE STANDARDS DEFINITIONS OF ABBREVIATIONS CONTAINED IN THESE STANDARDS Introduction The Office of Information Technology/Networking and Telecommunications Services (OIT/NTS) is responsible for providing voice, data, and video services for the University of Minnesota. Every effort is being made to keep the rates for these services as low as possible while still providing service and maintenance in a timely manner. OIT/NTS is constantly evaluating emerging technologies and equipment so that we can continue to offer the most reliable, up to date, and cost-effective services. It is essential to design the telecommunications systems to meet present and future voice and data communication needs. Horizontal and vertical wiring and the pathways and communication rooms should be considered an integral part of the building infrastructure and therefore capable of future growth as new technology and customer needs change. Refer to the NTS Web page at www1.umn.edu/nts/wiring3.shtml for the most recent revision of these standards. The standards herein apply to the technologies in use at the time of the latest update to this document. The implementation of newer technologies shall require adherence to the standards written at the time of that implementation. 2

3 2 General Standards Introduction Voice and data projects that are released for bid should be bid separately from and not included with security, audiovisual, building control systems, or other equipment or materials that are not directly associated with the independent high speed data or voice communications system. Telecommunications systems include vertical and horizontal copper and fiber optic wiring as well as the associated termination hardware on both ends. The system includes pathways and conduits; equipment racks; frames; wire management systems; communication rooms; and the electrical, mechanical, and environmental equipment required to support them. The space and facilities in these specifications are designed to meet the telecommunications requirements (voice and data networking) for university buildings only. These specifications are intended to allow OIT/NTS to meet the telecommunications requirements of the University over the lifetime of the buildings. It is essential that OIT/NTS shall be consulted prior to and throughout the planning and design process to ensure that present and future voice and data service requirements can be met. OIT/NTS MUST provide prior written approval for any deviations from these standards, or OIT/NTS will not assume financial responsibility to upgrade the facility to performance expectations. Where ambiguity or questions arise to specific details not mentioned in these standards, appropriate TIA/EIA, NEC, and BICSI standards shall apply. All applicable building codes must be strictly adhered to in regards to telecommunications services. OIT/NTS cannot authorize variations to any building codes. Construction specifications are a main ingredient of an Information Technology system. Information Technology systems shall adhere to these specifications in order to be functional in a wide variety of communications applications. This document does not allow or condone the avoidance of following any of the Laws, Standards, or Procedures of any, but not limited to the following: o National Electrical Code (NEC) o Uniform Building Code (UBC) o Uniform Fire Code (UFC) o Minnesota State Low Voltage Laws o Building Industry Consulting Services International (BICSI) Certification A BICSI-certified Registered Communications Distribution Designer (RCDD) shall design, engineer, and sign off on all projects, and he or she shall provide oversight during the project. 3

4 3 Special Requirements Introduction The OIT/NTS Wiring Standards publication is intended to address standard University installation practices, with safety and performance being the most important factors. While these standards are carefully monitored to ensure that the hardware and practices are technologically current, it is possible that some applications may require special consideration. University of Minnesota buildings frequently contain special purpose facilities and equipment with unique telecommunications requirements. Special telecommunications requirements may require deviation from these specifications. OIT/NTS needs to be notified of these special requirements as early in the design process as possible. The following is a short (but not all-inclusive) list of facilities and equipment that commonly have special telecommunications requirements: o Data centers or computer rooms o Computer labs or classrooms o Video conferencing rooms o Video equipment o Laboratories o Medical imaging equipment o Scientific equipment o Public telephones o Internet kiosks o Wireless networking Installation designs and practices not specifically identified as standard in this document will require appropriate OIT/NTS approval before connection to the campus voice or data network. To that end, any department requesting a non-standard installation of cabling infrastructure, voice/data jacks, or other items not specified in these standards should submit a written explanation of the requested variance to an OIT/NTS project coordinator for review. 4 Entrance Facilities Introduction The entrance facility is the location where the pathways for communications services penetrate the building to connect to the voice and data systems within the building. The entrance facilities are generally 4-inch rigid steel conduit that extend from the perimeter of the building to the telecommunications main equipment room (MDF). OIT/NTS shall designate the shortest practical route for the communications cable to connect from the building to the point of connection with the university telephone and 4

5 network cabling systems. Conduit shall be installed within the facility from the point of entry to the telecommunications main equipment room. Diverse facilities entrances are required for all new buildings that will house voice and data equipment when the scope and importance of the facility are determined to require it by OIT/NTS and the end-user. In the event that diverse cable facility entrances are not deemed necessary, provisions shall be made for four 4-inch conduits for access from the university cable system to the telecommunications main equipment room. Each of these conduits must be labeled "TELE MDF ONLY." Entrance facilities must adhere to all BICSI requirements in Chapter 6 of the Telecommunications Distributions Methods Manual (TDMM), (11th edition or subsequent releases). (Visit for purchasing information.) OIT/NTS must approve any deviations from the BICSI TDMM. 5 Telecommunications Rooms 5.1 General Requirements Introduction Telecommunications rooms are special-purpose rooms that house telecommunications equipment and wiring. These rooms have specific requirements due to the nature, size, and complexity of the equipment and wiring housed in these rooms. There may be up to three types of telecommunications rooms within a building, each supporting critical functions as part of the building wiring and telecommunications systems. In general, each room must be large enough to accommodate the wiring and equipment that will be located within it, plus provide additional space for growth over the lifetime of the building. The three types of rooms are: o Main equipment room/main Distribution Frame (MDF) o Communications rooms/intermediate Distribution Frame (IDF or riser rooms) o Terminal space/satellite rooms The following standards apply to all three types of telecommunications rooms: PROHIBITED: Using telecommunications rooms as a route for other facilities to pass through. PROHIBITED: Using boiler rooms, air exchange rooms, janitorial closets, electrical distribution closets, or areas with water heaters and wet sinks for 5

6 communications. It is essential that telecommunication rooms be dedicated solely to telecommunications. PROHIBITED: Placing voice or data rooms in or near areas of high electromagnetic interference (EMI) or radio frequency interference (RFI). Both adversely affect the system performance and the reliability of electronic equipment. Non-OIT/NTS resources shall not be located in telecommunications rooms without OIT/NTS approval. Communications rooms shall be located in common building areas that are readily accessible. Telecommunications rooms should be centrally located in the building to minimize the distance of all cable runs. Rooms must be spaced so that no horizontal run exceeds 90 meters (as per TIA-568B). OIT/NTS shall be consulted for any deviations. All main, communications, and terminal/satellite rooms shall have a ground buss and meet all requirements of J-STD-607 Commercial Building Grounding and Bonding Requirements, TIA/EIA-942, the NEC, and Chapter 10 of BICSI TDMM (11th edition or subsequent releases). Refer to Section 6 of this appendix for Bonding and Grounding Requirements. Fire suppression systems for all of these rooms shall be two-stage water systems; no Halon or gas systems shall be used. Pipes must be insulated to prevent water condensation from forming and possibly damaging telecommunications equipment. Fire suppression system pipes shall not be installed directly over equipment, but rather they shall be placed near the walls with the manifold pipes in ceiling corners. All penetrations into fire walls, conduits, and sleeves through floors and cable trays that pass through a fire-rated wall must be properly fire-stopped in accordance with the National Fire Protection Association (NFPA), ANSI/NFPA-70, the NEC, TIA- 569, and Chapter 7 of BICSI TDMM (11th edition or subsequent releases). The manufacturer's recommended installation practices must be followed. Each installation of fire-stopping material must only be used in applications as specified by the fire-stop manufacturer. When installing additional cabling/wiring, the fire stop system must be reevaluated, and if necessary, a new firestop system must be installed to restore the firewall integrity with the appropriate UL-classified system. Only use of UL-classified firestop systems is acceptable. All telecommunications rooms require overhead lighting with a minimum intensity of 50 foot-candles measured at 1 meter from the floor, and with a convenience switch at room entry. 6

7 All MDF, IDF, and Satellite/Terminal rooms whose size allows the placement of active electronics must be secured with an electronic card key access reader approved by University of Minnesota Access Services and OIT/NTS. All walls must be covered with 8-foot by 4-foot wide by 3/4-inch thick, unpainted, fire-retardant, CD grade or better plywood backboard, mounted with the smooth side out from the floor to a height of 8 feet. Electrical outlets shall be placed above the top edge of the plywood backboard and spaced every 6 feet. Working clearances around electrical equipment shall adhere to the NEC. OIT/NTS shall perform all buildout work in telecommunications rooms, including MDF, IDF, and Terminal Space/Satellite rooms. This includes all associated voice and data hardware. 5.2 Main Equipment Room (MDF) Introduction The main equipment room is the main room in a building into which all outside facilities are routed and terminate. This room serves as the primary telecommunications room and may house the PBX equipment and/or backbone network-related electronic equipment. All other communications rooms are fed from the main equipment room. Main equipment facilities shall be installed in a separate and secure room. The main equipment room shall serve as the primary copper and fiber-optic cable distribution center for the building. All voice and data distribution shall emanate from this room. PROHIBITED: Installing false ceilings in main equipment rooms. The size and location of this area shall be determined in feet with a minimum room size of 400 square feet and no dimension smaller than 20 feet. The minimum ceiling height shall be 8 feet 6 inches if no sprinklers/fire suppression nozzles are located within the room. If sprinklers/fire suppression nozzles are located within the room, the ceiling height must be adjusted to accommodate the racks and the tray located above the racks. Clearance shall be specified by the NEC. For additional information on room area based on useable building floor area, refer to Chapter 6 of BICSI TDMM, (11th edition or subsequent releases), and consult with OIT/NTS during the design phase. Rooms must be spaced so that no horizontal Cat 5E or Cat 6 cable exceeds 90 meters (as per TIA-568B). 7

8 Main equipment rooms require overhead lighting with a minimum intensity of 50 foot-candles measured at 1 meter from the floor, with (a) convenience switch(es) at room ingress and egress points. The room number shall be designated on the door or outside wall using University room numbering standards/specifications. The door on the communications room shall be a minimum of 3 feet wide, with a minimum height of 6 feet, 8 inches. It shall be equipped with a University U-Card reader and a Best core lockset that is keyed per OIT/NTS specifications. Main equipment rooms shall be free from high ambient temperature, excessive humidity, possible dripping pipes, dirt, and flooding. Main equipment rooms must be well ventilated and environmentally controlled 24 hours a day, seven days a week. The main equipment room must also maintain a positive pressure with a minimum of one complete air exchange per hour. It must maintain a heat dissipation rating of 225 BTUs/hour per square foot and maintain a constant temperature between 64 and 75 degrees Fahrenheit with a relative humidity range between 30% and 55%. Main equipment rooms must have drainage capabilities and must be equipped with a one-way drain, per TIA/EIA-942. All walls shall be covered with 8-foot by 4-foot wide by 3/4-inch thick, unpainted, fire-retardant, CD grade or better plywood backboard. It should be mounted with the smooth side out from the floor to a height of 8 feet. Electrical outlets shall be placed above the top edge of the plywood backboard; they are not to exceed 6 inches form the top edge of the plywood. One 120-volt AC dedicated duplex receptacle shall be provided for every 6 linear feet of floor perimeter. No more than three receptacles shall be dedicated per branch circuit. Installation of these receptacles shall be in consultation with OIT/NTS. Working clearances around electrical equipment shall adhere to the NEC. A Panduit NetFrame Rack System or prior OIT/NTS-approved equivalent shall be used in main equipment rooms to accommodate the fiber-optic cabling. Fiber optic cabinets shall be Panduit FRME4 Series or a prior OIT/NTS-approved equivalent. A Reliant/Marconi frame system or prior OIT/NTS-approved equivalent shall be used in this room to accommodate the copper cabling. 8

9 A Telecommunications Main Grounding Busbar (TMGB) shall be provided and attached to an approved building ground (as per the NEC). Refer to Section 6 of this appendix for Bonding and Grounding Requirements. When a main equipment room is to be used as a PBX equipment room, it must have a minimum of two redundant air conditioners. The air conditioners cannot be dependent on the same supporting equipment (such as a chiller, piping, motors, and power breakers). Each air conditioner must be able to support the room on its own and must be sized 50% larger than the BTU rating of the total installed equipment. The unit must cycle on and off at a 50% rate. Consult OIT/NTS for the exact type and capacity of air handling equipment. The power feed to the Uninterruptible Power Supply (UPS) systems must be included in the building generator distribution system, and appropriate transfer switches must be installed. If no generator is provided, emergency generator planning must be completed. This may include OIT/NTS placing a generator onsite or installing an emergency power coupler in a location that is accessible by OIT/NTS portable generators. Full-circuit documentation must be provided prior to starting up the switch room. A battery backup system located in a separate room specifically designed for that purpose may also be required. Where there is battery backup in rooms, they must include the required Occupational Safety and Health Administration (OSHA) containment system for sealed and spill-proof batteries. Environmental alarms must meet state, federal, and university codes and be interfaced to OIT/NTS card access/alarm panels. Panel inputs include all UPS alarms; generator active alarms; fire, temperature, humidity, A/C unit transition switch; floor water detection; battery damper; and door breech. Refer to Section 5.5 of this appendix for additional information on power requirements. Building requirements vary. It is essential that you consult with OIT/NTS prior to finalizing building plans. 5.3 Communications Rooms (IDF or Riser Rooms) Introduction A communications room is an enclosed and secured space specifically intended for housing telecommunications cables, termination hardware, cross-connect facilities, and equipment for riser facilities. Riser facilities shall be installed in a separate and secure IDF room specifically intended for this purpose. Riser cables shall be distributed in one or more riser shafts enclosed in a series of vertically aligned closets beginning in the basement and extending throughout the 9

10 height of the building. These shafts shall be aligned vertically to facilitate cable pulling. Communications rooms are intended for exclusive use by OIT/NTS. PROHIBITED: Installing false ceilings in communications rooms. The minimum size for a communications room is 100 square feet, with no dimension less than 8 feet. Minimum ceiling height shall be 8 feet, 6 inches. Clearance shall be specified by the NEC. To determine proper size of communications rooms, refer to Chapter 6 of BICSI TDMM (11th edition or subsequent releases), and consult with OIT/NTS during the design phase. Rooms must be spaced so that no horizontal Cat 5E or Cat 6 cable exceeds 90 meters (as per TIA-568B). Communications rooms require overhead lighting with a minimum intensity of 50 foot-candles measured at 1 meter from the floor, and with a convenience switch at room entry. The room number shall be designated on the door or outside wall using University room numbering standards/specifications. The door on the communications room shall be a minimum of 3 feet wide, with a minimum height of 6 feet, 8 inches. It shall be equipped with a University U-Card reader and a Best core lockset that is keyed per OIT/NTS specifications. The communications rooms must have adequate ventilation, and be environmentally controlled 24 hours a day, seven days a week. The rooms shall maintain a positive pressure with a minimum of one complete air exchange per hour, as well as maintain heat dissipation rating of 48 BTUs/hour per square foot. The rooms also must maintain a constant temperature between 64 and 75 degrees Fahrenheit, with a relative humidity between 30% and 55%. All walls must be covered with 8-foot by 4-foot wide by 3/4-inch thick, unpainted, fire-retardant, CD grade or better plywood backboard, mounted with the smooth side out from the floor to a minimum height of 8 feet. Electrical outlets shall be placed above the top edge of the plywood backboard; they are not to exceed 6 inches form the top edge of the plywood. One 120-volt AC dedicated duplex receptacle shall be provided for every 6 linear feet of floor perimeter. No more than three receptacles shall be dedicated per branch circuit. Installation of these receptacles shall be in consultation with OIT/NTS. Working clearances around electrical equipment shall adhere to the NEC. 10

11 A Telecommunications Grounding Busbar (TGB) shall be provided and attached to the TMGB in the Main Equipment room. Refer to Section 6 of this document for Bonding and Grounding Requirements. Communications rooms shall be interconnected by four 4-inch sleeves with bushings that extend a minimum of 2 inches to a maximum of 3 inches above the floor and a UL-classified fire stop system. The sleeves shall be for exclusive use by OIT/NTS, and each of these sleeves must be labeled TELE RISER ONLY. The sleeves shall be located at the left edge of the terminal board, as close to the wall as possible. Sleeves shall never be placed in the center of the terminal board. If closets cannot be aligned vertically, six conduits of 4-inch size or 4-inch by 24-inch cable tray shall be placed between them for exclusive OIT/NTS use. All conduits and sleeves must be labeled TELE RISER ONLY. The termination for station cabling shall be labeled with the corresponding jack number in accordance with the jack-labeling scheme as outlined in Section 13 of this document. OIT/NTS recommends that all floor penetrations be sleeved for the following reasons: o Ease of fire-stopping o To prevent water from leaking and spilling to lower floors o To prevent cables being installed between floors from chafing 5.4 Terminal Space/Satellite Rooms Introduction Terminal space/satellite rooms are communication facility spaces that are used for riser distribution. They are connected to a communication room and connect directly back to the main equipment room via the IDF and riser rooms. Satellite rooms can be used to pick up an outlying area that is greater than 90 meters away from an IDF. Terminal spaces/satellite rooms shall be installed in a separate and secure area. These rooms are designed exclusively for OIT/NTS use. PROHIBITED: Installing false ceilings in terminal rooms. The minimum size for terminal rooms shall be 80 square feet, with no dimension shorter than 8 feet. Minimum ceiling height shall be 8 feet, 6 inches. Clearance shall be specified by the NEC. To determine the proper size of a terminal room, refer to Chapter 6 of BICSI TDMM (11th edition or subsequent releases), and consult with OIT/NTS during the design phase. 11

12 Rooms must be spaced so that no horizontal Cat 5E or Cat 6 cable exceeds 90 meters (as per TIA-568B). Satellite rooms require overhead lighting with a minimum intensity of 50 footcandles measured at 1 meter from the floor, and with a convenience switch at room entry. The room number shall be designated on the door or outside wall using University room numbering standards. The door for Terminal facilities shall be a minimum of 3 feet wide, with a minimum height of 6 feet, 8 inches. Terminal facilities shall be equipped with access via a Best core lockset that is keyed per OIT/NTS specifications. Terminal facilities must have space ventilation or air conditioning in order to maintain recommended operating temperature and humidity levels for the equipment. Refer to Chapter 6 of BICSI TDMM (11th edition or subsequent releases). The terminal room must be well ventilated, and environmentally controlled 24 hours a day, seven days a week. It must maintain a positive pressure with a minimum of one complete air exchange per hour, and maintain a heat dissipation rating of 60 BTUs/hour per square foot. The terminal room must maintain a constant temperature between 64 and 75 degrees Fahrenheit, with a relative humidity between 30% and 55%. All walls must be covered with 8-foot by 4-foot wide by 3/4-inch thick, unpainted, fire-retardant, CD grade or better plywood backboard, mounted with the smooth side out from the floor to a height of 8 feet. Electrical outlets shall be placed above the top edge of the plywood backboard; they are not to exceed 6 inches from the top edge of the plywood. One 120-volt AC dedicated duplex receptacle shall be provided for every 6 linear feet of floor perimeter. No more than three receptacles shall be dedicated per branch circuit. Installation of these receptacles shall be in consultation with OIT/NTS. Working clearances around electrical equipment shall adhere to the NEC. A Telecommunications Grounding Busbar (TGB) shall be provided and attached to the TMGB in the Main Equipment room. Refer to Section 6 of this appendix for Bonding and Grounding Requirements. There shall be no more than 80 meters from the center of the terminal space to the center of the nearest communications room. Connections from the communications 12

13 room to the terminal facilities shall adhere to the raceway specifications. Refer to Section 9, "Raceway/Tray Systems." The termination for station cabling shall be labeled with the corresponding jack number in accordance with the jack-labeling scheme as outlined in Section 13 of this document. OIT/NTS recommends that all floor penetrations be sleeved for the following reasons: o Ease of fire-stopping o To prevent water from leaking and spilling to lower floors o To prevent cables being installed between floors from chaffing 5.5 Electrical Power Requirements Power to terminal rooms shall be installed using dedicated circuits to these areas. UPS system equipment shall be incorporated only if identified and budgeted in the project in consultation with OIT/NTS. Where UPS systems are required, the following criteria apply: Space ventilation or air conditioning shall be provided to maintain the recommended operating temperature of equipment. The systems shall be completely isolated from the line. The neutral shall be bonded to ground. Voltage spikes shall have attenuation of 2,000:1 from line for lightning protection. Surges shall be suppressed to safe levels as described by IEEE (Institute of Electrical and Electronics Engineers) 587 A and B (guide to surge voltages). Common mode noise rejection shall be better than 120 db. Transverse mode noise rejection shall be greater than 60 db. The wave shape shall be sine. It shall be limited to 3% single harmonic distortion, and 5% total harmonic distortion. Loss of power shall be less than 2 milliseconds in transfer to the UPS and return. The waveform shall remain in phase. The unit shall run at full load without input power for 20 minutes. OIT/NTS shall review this timeframe. 13

14 There shall be a method of bypassing AC so the UPS may be maintained and repaired without loss of power to equipment. It is not necessary to condition power in this mode. The UPS shall be capable of handling a 25% overload for five minutes and a surge overload of 50%. There shall be a delay of more than 15 seconds before the UPS returns to normal line conditioning mode. The output waveform shall have less than 3% single harmonic distortion, and 5% total harmonic distortion. 5.6 Air Conditioning Requirements o PBX o Core Node o Data Center o Video o Other High Concentrations of Heat-producing Electronic Equipment 6 Bonding and Grounding Introduction The NEC defines bonding as, The permanent joining of metallic parts to form an electrically conductive path that ensures electrical continuity and the capacity to conduct safely any current likely to be imposed. A ground is defined as, A conducting connection, whether intentional or accidental, between an electrical circuit or equipment and the earth or to some conducting body that serves in place of the earth. The purpose of the grounding system is to direct potentially damaging currents away from people and sensitive network equipment by creating a low impedance path to earth ground for electrical surges and transient voltages. This serves to minimize the detrimental effects of these currents (which include degraded network performance and reliability, as well as increased safety risks). The grounding system must be intentional, visually verifiable, and adequately sized to handle expected currents safely. The grounding system shall be designed and installed in accordance with the NEC and with the BICSI TDMM, Chapter 8 (11 th edition or subsequent releases), TIA/EIA-942, and J-STD-607-A. 14

15 6.1 Busbars Each communications room in a building shall have a grounding busbar, typically installed in a lower corner of the plywood backboard at least 6 inches above the finished floor, and as close as practicable to any electrical panelboard serving the room. The main equipment room or entrance facility shall house the Telecommunications Main Grounding Busbar (TMGB), and each other equipment room shall house a Telecommunications Grounding Busbar (TGB). Busbars shall be a minimum of ¼ inch thick, of electrolytic tin plated copper construction, and must be predrilled to accept standard two-hole lugs. The TMGB shall be 4 inches high, a minimum of 20 inches long, and of variable length to accommodate the expected number of lugs and allow for future growth. The TGB shall be 2 inches high, a minimum of 12 inches long, and of variable length. Currently approved busbars are Panduit GB4 series for MDF and GB2 series for IDF. 6.2 Telecommunications Bonding Backbone The busbars on each floor shall be bonded to the Telecommunications Bonding Backbone (TBB). The TBB shall be routed in as straight a line as possible and be continuous, with no splices, from the TMGB to the top floor TGB. It shall be sized in accordance with J-STD-607-A (See Table 1). The bend radius on any necessary bends in this cable should be greater than 8 inches. Table 1: Sizing of the TBB TBB Length in Linear meters TBB Size (AWG) (feet) Less than 4 (13) (14-20) (21-26) (27-33) (34-41) (42-52) 1/ (53-66) 2/0 Greater than 20 (66) 3/0 The TMGB shall be bonded to an approved grounding electrode and to the building s main electrical ground system. This grounding electrode conductor shall 15

16 6.3 Cables be no smaller than the TBB. Connections to the TGBs at every floor except the top floor shall be made via copper compression H-Tap (see section 6.8) and a conductor no smaller than the TBB. In the event that more than one TBB exists in a building, the TGBs shall be connected at the top floor and at a minimum of every third floor below by a Grounding Equalizer (GE), which is equal in size to the TBB. Each conductive multipair cable in a building shall be grounded at both ends via a bond attached to the cable armor (which accepts a standard two-hole lug). The bond shall be Electric Motion Company s EM 2BBx bond, unless a substitute is approved in advance by OIT/NTS. 6.4 Rack Grounding Electrical continuity throughout each rack or cabinet is required to minimize safety risks. The racks shall be assembled using paint-piercing grounding washers (Panduit Part no. RGW, or an OIT/NTS-approved substitute) and antioxidant (per the recommendations of the manufacturer). An electrostatic discharge port kit (Panduit RGESD, or an OIT/NTS-approved substitute) shall be placed on the rack (on the right side when facing the rack) at 48 inches above the floor. All bonding connections to the rack shall be made with thread-forming screws (Panduit Part no. RGTS, or an OIT/NTS-approved substitute), or the threads must be cleaned of all paint or residue (per the NEC). In locations with multiple racks, the rack shall be connected to the common bonding network with a 6 AWG conductor and a copper compression HTAP. In locations with single racks, a 6 AWG conductor to the busbar is sufficient. The common bonding network is a 2 AWG continuous conductor placed below or above the racks. Refer to TIA/EIA-942 and IEEE-1100 for design recommendations. 6.5 Pathway Grounding Any metallic component, including equipment, ladder racks, enclosures, cable trays, etc., must be bonded to the grounding system. Provisions must be made to bond individual segments of ladder rack and basket tray together in order to make them electrically continuous. Any metallic conduit that carries a grounding conductor and is greater than 3 feet long must have both ends bonded to the conductor with a bonding jumper no longer than 12 inches and fastened with a compression HTAP to the conductor on one side and to the conduit on the other. 16

17 6.6 Equipment Grounding Although AC-powered equipment typically has a power cord that contains a ground wire, the integrity of this path cannot be easily verified. Thus, many equipment manufacturers require grounding above and beyond that which is specified by local electrical codes, such as the NEC. Always follow the grounding recommendations of the manufacturer when installing equipment. 6.7 Electrical Service When an electrical panelboard is located in a telecommunications room, a 6 AWG bonding conductor shall be run from the busbar to the electrical service ground. When an electrical panelboard is not located in the room, a 6 AWG bonding conductor should be run from the busbar to the nearest electrical panelboard (where feasible). 6.8 Compression Fittings Lugs and HTAPs must be manufactured of tin plated copper and fastened via irreversible compression (crimped). Lugs shall have spacing to fit Panduit GB series predrilled busbars and a window to allow for inspection of the crimp. HTAPs shall be contained in clear covers that allow inspection of the die marks to ensure that the proper die was used. 6.9 Testing and documentation o Approved lugs: Panduit LCC or LCCX series Burndy YAZ series CPI Electric Motion Company CCL Series o Approved HTAPS: Panduit HTWC series Burndy YH series (when used with clear covers) or an OIT/NTSapproved substitute. The grounding system shall be documented by means of a diagram showing the locations of the busbars and the size of the conductors, indicating all connections between conductors from the busbars or TBB back to the building electrical grounding system. This includes: connections to building AC panelboards, building steel, the building electrical service ground, connections between the busbar(s) and the TBB. If not connected with a two-hole lug, the connection type of any bonding connection 17

18 (HTAP, clamp, etc) between the busbar and the building ground point should be specified on the drawing. To ensure that bonding connections from the busbar to infrastructure within the telecommunications spaces are of low resistance and that the impedance to ground is as low as possible, the following checks shall be performed. Lugs: Visually check that the conductor is visible in the window of the lug to ensure that it was fully inserted, and that the lug is properly crimped. Check that the lug is fastened through both mounting holes, that the connection is tight, and that antioxidant was used (if necessary). HTAPs: Ensure that the mark left on the HTAP indicates that the appropriate manufacturer-recommended die was used for that HTAP, and that the connection is protected by a clear cover that allows visual inspection. Racks: Visually check that the racks have been assembled with paint-piercing washers or are constructed so as to make such measures unnecessary (i.e. welded). Conduits: If a bonding conductor is routed through a metallic conduit more than three feet long, ensure that both ends of the conduit are bonded to the conductor with a suitable method, avoiding sharp bends in the cable. Looping the conductor itself through the conduit bonding collar is prohibited. Measurements: Ensure that the resistance of the following connections is less than 0.1 ohms: o Lug to HTAP for any connections to Common Bonding Network o Rack bonding lug to any rack section (the paint-piercing washers make good test points) o Bonding lugs to busbar, cable tray, and cable bond 7 Intrabuilding Backbone Riser Facilities 7.1 Design Considerations OIT/NTS designs the intrabuilding backbone distribution system to meet or exceed the requirements of TIA/EIA-568-B, BICSI TDMM Chapter 5 (11 th edition or subsequent releases), the NEC, and all applicable local and national codes and regulations. The intrabuilding backbone shall be comprised of both copper and optical fiber. Cable sizing shall be in consultation with OIT/NTS for specific building requirements. 18

19 Intrabuilding backbone fiber and copper cables shall be sized to include 50% spare for future use. Consult with OIT/NTS for cable sizing requirements on a per building basis. Intrabuilding backbone cables comprised of steel or metallic parts must be grounded on both ends of the cable (as specified in section 6, Bonding and Grounding ). Proper firestopping of all backbone pathways shall be maintained as specified in section 5.1, General Telecommunications Rooms Requirements. Intrabuilding copper and backbone cables shall be installed without exceeding the minimum bend radius and the maximum vertical rise recommended by the cable manufacturer and must not exceed the maximum allowed pulling tension of the cable(s). 7.2 Intrabuilding Backbone Copper (Riser) Cabling The intrabuilding copper backbone cable(s) shall be 100 ohm unshielded, balanced, twisted-pair, Category 3 riser-rated cable with 24 AWG round solid conductors. It shall also be armored. Copper backbone cabling shall be type CMR (Communications Riser). Where used in plenum spaces, copper backbone cabling shall be type CMP (Communications Plenum). The cable shall be UL tested and listed, and it shall meet or exceed the requirements of Category 3 cable as specified in TIA/EIA-568-B.1 and all applicable national and municipal fire codes. Copper backbone riser cable specifications are as follows: Terminations o Communications Riser: Category 3 Copper Cable ARMM (Alpeth, Expanded polyethylene polyvinyl chloride, 24 AWG, ALVYN) o Communications Plenum: Category 3 Copper Cable 24 AWG Plenum Rated Intrabuilding backbone copper cabling shall be terminated on 110 termination blocks in the telecommunications riser room. Main 19

20 Communication room terminations must be done in accordance with OIT/NTS. Terminations must be in accordance with TIA/EIA-568-B. The cable shall be continuous without splices, unless specified differently by OIT/NTS. Intrabuilding copper backbone cables must be properly secured to the walls to prevent horizontal movement as specified in BICSI TDMM Chapter 5 (11 th edition or subsequent releases), the NEC, and all applicable national and municipal codes. 7.3 Intrabuilding Backbone Fiber Optic (Riser) Cabling The intrabuilding optical fiber backbone cable(s) shall be a hybrid (singlemode/multi-mode) cable consisting of 8.3/125 μm singlemode and 62.5/125 μm multi-mode optical fiber consisting of a minimum of 12 strands of singlemode and 12 strands of multi-mode. All backbone fiber optic cabling must use Corning glass (SMF-28e for singlemode and Infinicor CL-1000 for multi-mode fiber). Cable sizing shall be in consultation with OIT/NTS. Optical fiber riser shall be type OFNR (optical fiber non-conductive riser). Where used in plenum spaces, optical fiber shall be type OFNP (optical fiber non-conductive plenum). Singlemode cable jackets shall be yellow in color, while multi-mode and hybrid cable jackets shall be orange in color. Optical fiber cables shall meet or exceed all applicable national and local building fire codes. Optical fiber backbone riser cable specifications are as follows: o Fiber Riser Cable: Corning (part number 024XW7-CK539D20) or an OIT/NTS-approved substitute. o Fiber Riser Cable Plenum Rated: Corning (part number: 024XWP- CK540D20) or an OIT/NTS-approved substitute. 20

21 7.3.2 Fiber Terminations The intrabuilding optical fiber backbone cable(s) shall be installed with a service loop of 25 feet at each end. Intrabuilding fiber backbone cables must be properly secured to the walls to prevent movement as specified in BICSI TDMM Chapter 5 (11 th edition or subsequent releases), the NEC, and all applicable national and local building codes. Velcro cable ties shall be used for securing fiber optic cable. All fiber optic cables are to be continuous without splicing, unless otherwise specified by OIT/NTS. Fiber optic terminations are to be field-connectorized using ST 3M Hotmelt connectors. Splicing of pigtails is not allowed. The singlemode strands of each intrabuilding backbone fiber optic cable shall be placed first in the fiber optic cabinet, followed by the multi-mode strands of the corresponding cable. Fiber optic cabinets shall be labeled according to OIT/NTS labeling scheme. Contact OIT/NTS for the correct designation Fiber-Optic Enclosures Fiber-optic rack-mounted enclosures shall consist of an EIA-approved 19- inch enclosure (with optional extensions to fit in a 23-inch rack) that is four rack units tall (7 inches) with a minimum of 72 duplex port capacity. Individual fiber couplers must be removable from the panel. Individual couplers must be replaceable without causing interruption of service to adjacent fiber strands. Dust covers must be provided for any unused couplers in each enclosure. The enclosure shall be black. Specify Panduit product FRME-enhanced series or prior OIT/NTSapproved substitute. Enclosures shall be labeled per OIT/NTS specifications. 21

22 7.4 Intrabuilding Backbone Pathways Intrabuilding backbone cabling shall be distributed using a series of conduits, cable trays, sleeves, and slots. Refer to section 5.3 ( Communications Rooms ) and section 9 ( Raceway/Tray Systems ) of this document for information on pathways. All conduits, cable trays, sleeves, and slots shall conform to TIA-569-B, BICSI TDMM Chapter 5 (11 th edition or subsequent releases), the NEC, and all applicable national and municipal codes. The cable must be properly supported as defined by the cable manufacturer s specifications and shall conform to TIA/EIA-568, the NEC, and all applicable national and municipal codes. 8 Communications/Terminal Room Termination Requirements For all new construction, Category 5E and/or Category 6 installations shall terminate voice on 110-style punch blocks and terminate data on patch panels. Figure A: Typical Backboard Layout for Riser Rooms 22

23 8.1 Wall Termination of Copper Wiring Provide 110 IDC systems mounted to the 8-foot by 4-foot wide by 3/4-inch thick unpainted, fire-retardant, CD grade or better plywood backboard that is mounted with the smooth side out. Install terminal blocks so that they are vertically plumb and securely fastened to the plywood backboards. Install the top jumper trough 2 feet down from the top of the plywood. Install a wire basket-style tray that is designed for no more than 40% fill at the top of the plywood for the length of the termination field. Install a wire basket-style tray 8 inches below the bottom of the lowest jumper trough (Refer to Figure A). This tray must be bonded and attached to the ground buss, and it must meet all of the requirements of J-STD-607 Commercial Building Grounding and Bonding Requirements, the NEC, and Chapter 8 of BICSI TDMM (11th edition or subsequent releases). Refer to Section 6 of this appendix for Bonding and Grounding Requirements. Install cables without violating the minimum bend radius specified by the cable manufacturer. Route station cables in brackets, troughs, and wire ways that are specifically designed for Cat 5E/Cat 6 applications. Fasten cables securely with Velcro-style tie wraps to prevent strain at the terminations. Wall-mounted copper connectivity specifications are as follows: 8.2 Equipment Racks o Cat 5E Systimax 5E 110 Connecting Block w/o legs Systimax Jumper Trough w/o legs Seltek 110 Cable Guide (backchannel) CG300 o Cat 6 Systimax 110 Connecting Block Systimax Jumper Trough w/o legs Seltek 110 Cable Guide (backchannel) CG300 Allow for a minimum of two floor-mounted (7-foot tall by 23-inch wide) equipment racks per room. Equipment racks shall be self-supported and floor-mounted. Equipment racks must be securely mounted to the floor with expansion anchors. 23

24 Equipment racks must have cable management with 6-inch vertical channels and must have pass-through holes and slots for additional cable management accessories. Wire management must accept removable, hinged doors. Racks must include movable, plastic D rings for flexible cable management. The rack system is to be installed per OIT/NTS requirements and shall be a Panduit NetFrame or a Chatsworth Rack System. Provide a horizontal wire basket-style tray that is designed for no more than 40% fill and that is mounted above all equipment racks. The tray must be properly bonded and grounded. All equipment racks shall be grounded to the ground buss and meet all of the requirements of J-STD-607 Commercial Building Grounding and Bonding Requirements, the NEC, and Chapter 8 of the BICSI TDMM (11th edition or subsequent releases). Equipment racks must meet all EIA requirements as defined in EIA-310-D. 8.3 Patch Panels Category 5E/Category 6 patch panels shall consist of EIA-approved 19-inch patch panels with optional extensions to fit a 23-inch rack. Panels must accommodate 24 jacks per 1¾ inch rack unit. Each eight-pin modular jack must provide proper strain relief by encompassing the insulation of the cable within the back of the jack. Each eight-pin modular jack must be removable from the panel. Individual jacks must be replaceable without causing any interruption of service to any other jack. Panels shall be UL 1863-listed and black in color. A labeling area shall be included on the front for jack identification. Patch panels shall be a Systimax or Leviton H24 (or an OIT/NTS-approved substitute). 24

25 8.4 Horizontal Management Design to support Category 5E/Category 6 cables without compressing or kinking the cables. Horizontal cable management panels must be included on the racks and shall have an EIA-compliant 19-inch wiring management duct that is one rack space tall (with optional extensions to fit a 23 inch wide rack). A wire management panel must be placed above the first patch panel, every third rack unit thereafter, and below the last patch panel. The wire management panel shall have a 1½ inch by 2-inch front wire management duct, and a 1-inch by 4-inch rear wire management duct. Covers for each duct shall be removable/hinged. The entire panel shall be black. Specify Panduit product code number NCMH2 or an OIT/NTS-approved substitute. Consult with OIT/NTS with regards to the needs and design of vertical wire management ducts. 9 Raceway/Tray Systems The general requirements for raceway/tray systems are as follows: Communication tray systems shall be for exclusive use by OIT/NTS. The systems shall be designed for no more than 40% fill. The systems must be metallic and continuous, and all separate pieces must be bonded where they are joined. The systems must be grounded to the building grounding system with a minimum 6 AWG copper conductor. Refer to Section 6 for specific Bonding and Grounding requirements. Use insulated metallic bushings for attached metallic conduits. Ground and bond the conduits to the tray (Figure B). The tray shall be ladder or wire basket style. 25

26 The ladder-style tray shall have a rail on each side, and the rungs shall be enclosed and welded into place. The wire basket-style tray shall be U shaped and constructed of round wire mesh. The basket tray shall be installed trapeze-style or wall-mounted. It must not be center hung. End-of-tray cable waterfalls must be used where wire drops down to prevent abrasions and cuts from metal tray edges. The tray must be no closer than 6 inches from the structural ceiling, ducts, pipes, or any other possible obstructions. A minimum separation of 5 inches from lighting, especially fluorescent lighting, is required. The tray must maintain 18-inch clearance from sprinkler heads. The complete cable tray system must meet OIT/NTS approval. Compliance to this standard requires that the end of rigid or flex conduit must: o Have a bushing o Lie within the side and end planes of the cable tray o Lie within the tolerated distance as illustrated (Figure B) o Be anchored to a rigid support o Be grounded and bonded to the cable tray with a minimum 14 AWG copper conductor. Refer to Section 6 of this appendix for Bonding and Grounding Requirements. 26

27 Figure B: Conduit to Cable Tray Configurations 9.1 J-Hooks The use of J-Hooks to support horizontal wiring in lieu of continuous conduit or a combination of conduit and wire basket tray is currently under study by OIT/NTS. At this time, OIT/NTS cannot document any advantages to using J-Hooks other than for economic reasons. Numerous questions and concerns have arisen regarding the affects of EMI (Electromagnetic Interference) on high speed data transmissions when J-Hooks are used to suspend horizontal wiring systems. Compatibility concerns (including bend radius control and loading limitations) and EMI susceptibility between cable manufacturers and J-Hook manufacturers have not been adequately addressed, given the large number of products and the various combinations that can be used. When J-Hooks are to be installed as a substitution for continuous conduit or a combination of conduit and wire basket tray, it is the responsibility of the Architect, Electrical Engineer, Owners Representative, Professional Voice and Data Consultant, or other requesting party to provide documentation from both the cable manufacturer and the J-Hook manufacturer stating that their wire and J-Hooks are compatible and will address bend radius control, loading limitations, and EMI rejection. A plan showing the placement of each J-Hook including load capacity and bend radius control must also be provided to OIT/NTS. OIT/NTS must review the documentation and approve of the J- 27

28 Hook System, or OIT/NTS will not bear the responsibility of insuring that the voice and data systems and services perform to the required data and voice transmission speeds. 10 Horizontal Wiring Facilities PROHIBITED: Daisy chaining of conduit from outlet to outlet. PROHIBITED: Splitting copper pairs between jacks. TIA/EIA-568-B-1 states that "Each 4-pair cable shall be terminated in an eight-position modular jack at the work area." PROHIBITED: Sharing the outlet and conduit pathway with other nontelecommunications facilities. PROHIBITED: Using traditional nylon synch-style tie wraps to bundle cables. Only Velcro-style tie wraps are acceptable. Horizontal wiring technicians and installers shall be certified by the manufacturer of all horizontal wiring and termination components that they will be installing. Telecommunications outlets shall be wired with unshielded, twisted pair 24 AWG wire (UTP) with suitable insulation and sheath material to meet or exceed TIA/EIA-568-B.2 or equivalent. The wire shall be type communications riser cable (CMR) or communications plenum cable (CMP) (UL) with rating dependent on the NEC, and it shall be OIT/NTS approved. When pulling cable in Patient Care areas, it is critical that care is taken to control dust, odors, noise, and aisle clearances. In addition, strict adherence should be given to patient confidentiality policies of the University of Minnesota. The current position of OIT/NTS on horizontal cabling is to recommend the installation of Category 5E cable. Because of the variety of infrastructure on campus, OIT/NTS cannot guarantee performance without an upgrade of the infrastructure to support higher bandwidth requirements of new technology. For example, installing Category 6 cabling does not guarantee performance at increased bandwidths without an upgrade of the installed infrastructure/backbone system. Any cable lubricant to be used during cable installation must meet both performance and compatibility standards for the cable as specified by the cable manufacturer. If a building initially is wired with Category 6 cabling, any subsequent wiring shall be done exclusively with Category 6 cable. Deviation of wiring levels when the original is installed with Category 6 is not recommended unless OIT/NTS pre-approves in advance in writing. Any movement, additions, or changes after the initial installation shall require 28

29 Category 6 cable to be used. One manufacturer's brand shall be used for each component type throughout a building if the Category 6 wiring system requires the same vendor products in order to retain Category 6 performance standards and successful testing Outlets Telecommunication outlets shall be 4-inch by 4-inch by 2-1/2 inch boxes with a minimum 1-inch Inside Diameter continuous metallic conduit provided to the nearest terminal or ceiling raceway system. Refer to Section 9 for raceway/tray system requirements. Standard telecommunications outlets shall be installed at a minimum of 15 inches above a finished floor and at the same height as the electrical outlets as specified in the Construction Standards Institute (CSI) Division 16. Standard telecommunications outlets for wall phones shall be 48 inches above a finished floor. All measurements are from the floor to the center of the outlet. Floor-mounted outlets used for modular furniture shall be a Walker RCI RC3 flush poke-through unit, with Panduit 2 position adapter CRC3A2BL-X or dual Systimax (AT&T) 2A-U2ATT or a prior OIT/NTS-approved substitute. The Americans with Disabilities Act (ADA) requires that phone outlets be accessible at 48 inches to the highest operable mechanism for forward reach and 54 inches to the highest operable mechanism for side reach. All other outlet facilities specifications for people with disabilities shall be compliant with CABO/ANSI A117.1 standards. Telecommunications outlets shall not be placed in a back-to-back location, but shall be separated by a minimum of 12 inches. Telecommunications outlets in firerated walls shall be separated by 24 inches. UBC Chapter 43 states that openings in fire-resistive walls for steel outlet boxes not exceeding 16 square inches in area cannot aggregate more than 100 square inches for any 100 square feet of wall or partition. Totals must include electrical switches or outlets, or any other openings when totaling 100 square inches. Inspectors have accepted a UL Rated Fiberglass box as a substitute for a steel box. It must be appropriately fire-stopped. Telecommunications outlet boxes shall be used solely for low-voltage wiring for telecommunications. 29

30 All wall outlet boxes shall be equipped with two-gang cover plates. Only the following outlets shall be equipped with a one-gang cover plate: o Outlets designated for wall telephones o Outlets designated for pay telephones Two collocated 4-inch by 4-inch by 2-1/2-inch boxes shall be provided with terminations. Distribution of fiber/copper between the two boxes shall be in consultation with OIT/NTS. The boxes shall be adjacent, but separated by a minimum of 12 inches. Cat 5E A minimum of 12 inches of slack for Cat 5E copper and 1 meter of fiber shall be left in each outlet. Cat 6 12 inches of slack for each outlet is required. However, the slack cannot remain in the box behind the outlet. The slack must be loosely coiled and remain in the cable tray. For homerun conduits, the slack must remain in the communications/terminal rooms. The number of wires or fiber strands installed to each communication outlet shall be determined in consultation with OIT/NTS. OIT/NTS recommends a minimum of four Category 5E cables at each copper outlet: two for voice and two for data Horizontal Conduit Each conduit shall be installed in a home-run configuration from the outlet to the cable tray or telecommunications room. No conduit shall exceed 100 feet without installation of a pull box. Conduits shall be placed in the straightest run possible with no more than the equivalent of two 90 bends per run. When additional bends are required, pull boxes shall be installed. Conduit sizes shall be adequate for the cable needed to serve voice and data instruments. The minimum size for conduit is 1 inch. 1¼-inch conduit is recommended if Cat 6 or Cat 6A is to be installed. For information on conduit sizing and routing, refer to Chapter 5 of BICSI TDMM (11th edition or subsequent releases). 30

31 10.3 Horizontal Wiring Horizontal Copper Wire Category 3 and Category 5 wiring is no longer recommended for installation. Copper wiring specifications are as follows: o Blue Cat5E plenum BerkTech product code General product code Mohawk product code M56168 Superior Essex product code o Blue Cat5E PVC BerkTech product code General product code Mohawk product code M56167 Superior Essex product code o Green Cat6 plenum BerkTech product code General product code Mohawk product code M57197 Superior Essex product code B o Green Cat6 PVC BerkTech product code General product code Mohawk product code M57206 Superior Essex product code A All copper wiring and connectors must conform to the following specifications: o Category 5E: TIA/EIA-568-B-2 o Category 6: TIA/EIA-568-B-2, TSB-36, TSB-40A, NEMA XF, UL Level IV Wire shall meet or exceed TIA/EIA-568-B-2 Category 5E and NEMA low-loss extended frequency requirements. 31

32 The amount of slack in the terminal room from the jack location shall be determined in consultation with OIT/NTS. Each cable in the terminal room from the jack shall be tagged with the current designation from the current architectural drawings. Station cabling shall be terminated to the standards and specifications required for that particular category of cable. Station cables shall be terminated in order according to jack number wherever and whenever possible. Refer to Section 13 for more information on the outlet-labeling scheme. Wire each jack configuration designation according to TIA-EIA-568-B (Designation T568B). All copper and fiber cable must be continuously supported by conduit or a cable tray. All Category 5E and Category 6 installations must also conform to the component configurations and installation practices contained in TIA/EIA-568-B. Fiber optic cables shall comply with TIA/EIA-568-B and performance measurements of TIA/EIA-455, Section 46, 53, or Horizontal Fiber Optic Wire Fiber optics shall be 62.5 mm and 125 um to meet or exceed ANSI/TIA/EIA-492 AAAA. Each strand of fiber must be housed in its own buffer tube throughout the length of the fiber cable. Each cable in the terminal room from the jack shall be tagged with the current designation from the current architectural drawings. Consult with OIT/NTS to determine the amount of slack in the terminal room from the location of the jack. Fiber specifications are as follows: o Multi-mode plenum BerkTek product number ICP002CB3510/55 General product number CT0021PNU Mohawk/CDT product number M9B043 32

33 o Multi-mode PVC BerkTek product number ICR002CB3510/55 General product number CT0021PNR Mohawk/CDT product number M9B037 o Singlemode plenum BerkTek product number ICP0X0AB0707 General product number AP0021PNR Mohawk/CDT product number M93043 Siecor product number 002R o Singlemode PVC BerkTek product number ICR0X0AB0707 General product number AP0021PNU Mohawk/CDT product number M93037 Siecor product number 002R Note: Due to technological advances and changes in vendors' part numbers, please refer to the online version of these standards ( for updated part numbers. Labeling shall be in consultation with OIT/NTS Small Form/Modular Style Fiber Standards All small form, multi-mode, modular style, duplex fiber connectors must meet or exceed TIA/EIA 455 and ISO/IEC performance specifications. All small form singlemode, modular style, duplex fiber connectors must meet or exceed TIA/EIA 455, ISO/IEC 874-1, and Bellcore 326-CORE performance specifications. The manufacturer shall have a TIA/EIA Fiber Optic Connector Intermateability Standard (FOCIS) document. This is a component standard written for manufacturers to follow to ensure that their connectors will be intermateable with other connectors of the same type. Each small form fiber connector must contain two strands of fiber that meet or exceed the singlemode or multi-mode performance standards specified in this document. Each fiber shall be housed in its own separate ferrule within the jack. 33

34 The jack must have separate alignment sleeves for each ferrule. The small form fiber jack shall fit into the same manufacturer's flush faceplate that accommodates its copper jacks so that any combination of two, four, or six outlets of copper or fiber cables may be used at any location. Small form factor plugs/jacks shall accommodate either singlemode or multi-mode fiber strands. Both singlemode and multi-mode jack and plugs shall be able to be field terminated. High-density fiber jack multi-mode Panduit product number FJJGM5CEI (Electrical Ivory) or Avaya product number P1001A-Z-125 shall be used (or a prior OIT/NTS-approved substitute). High-density fiber jack singlemode Panduit product number FJJGS9CBU or Avaya product number P1101A-Z-125 shall be used (or a prior OIT/NTS-approved substitute) Jacks Jacks shall be mounted in a 106-type frame (Systimax product number ), a mounting frame (Leviton QP), or a prior OIT/NTS-approved substitute. The jack cover plate shall be 302 stainless steel or other OIT/NTS-approved cover or housing. Each copper outlet shall contain the following jacks: Voice jacks o Category 5E Systimax product code number (gray) Leviton product code number 5G110-RG5 (gray) o Category 6 Systimax product code number (gray) Leviton product code number RG6 (gray) 34

35 Data jacks o Category 5E Systimax product code number (orange) Leviton product code number 5G110-RO5 (orange) o Category 6: Systimax product code number (orange) Leviton product code number RO6 (orange) 11 Testing 11.1 Category 5E Wiring Every cabling link in the installation shall be tested in accordance with TIA/EIA- 568-B.1. All of the installed cables must be tested and must pass the specifications of TIA/EIA-568-B.1. The horizontal cabling shall be tested from the communications rooms/terminal spaces to the wall outlet using the Permanent Link specification of TIA/EIA-568- B.1. Any cable that fails these tests shall be re-terminated and tested again. If the cable does not meet specifications after being re-terminated, replace the cable, terminate, and test again. The test equipment shall comply with or exceed the accuracy requirements for enhanced Level II (Level II-E) field testers (as defined in TIA/EIA-568-B, Annex 1, Section 1.4). The pass or fail condition for the link being tested is determined by the results of the required individual tests. Any fail result yields failure for the link being tested. The test results for each link shall be recorded in the memory of the field tester upon completion of the test. The test results saved by the tester shall be transferred to a CD-ROM. A guarantee must be made that the results of the measurement shall be transferred to the CD- ROM unaltered that is, as saved by the tester at the end of each test. The guarantee must also specify that the results cannot be modified at a later time. 35

36 The test results for the completed job shall be stored and delivered to OIT/NTS on a CD-ROM, along with the software tools required to view, inspect, and print any selection of the test reports. A paper copy of the test results shall be provided to OIT/NTS in a three-ring binder Category 6 Wiring Every Category 6 cable in the installation shall be tested in accordance with the field test specifications defined in the most recent draft of the "Transmission Performance Specifications for 4-pair 100 Category 6 Cabling" (under development by the TIA). At the time of publication of the 2002 Standards and Procedures for Construction, PN 3727 TIA/EIA Draft Standard - Draft 11B represents the most recent version. Within these standards, this specification shall be referred to as the TIA Cat 6 Draft Standard. All of the installed cables must be tested and must pass the specifications of TIA/EIA-568-B. The horizontal cabling shall be tested from the communications rooms/terminal spaces to the wall outlet using the Permanent Link specification in the TIA Cat 6 Standard. Any cable that fails these tests shall be re-terminated and tested again. If the cable does not meet specifications after being re-terminated, replace the cable, terminate, and test again. The test equipment shall comply with or exceed the accuracy requirements for the proposed Level III field testers as defined in the Cat 6 Standard. The pass or fail condition for the link being tested is determined by the results of the required individual tests. Any fail result yields failure for the link being tested. The test results for each link shall be recorded in the memory of the field tester upon completion of the test. The test results saved by the tester shall be transferred to a CD-ROM. A guarantee must be made that the measurement results are transferred to the CD-ROM unaltered that is, as saved by the tester at the end of each test. The guarantee must also specify that the results cannot be modified at a later time. The test results for the completed job shall be stored and delivered to OIT/NTS on a CD-ROM along with the software tools required to view, inspect, and print any selection of the test reports. 36

37 A paper copy of the test results shall be provided to OIT/NTS in a three-ring binder Fiber Optic Cable to Outlet Every fiber optic cable in the installation shall be tested in accordance with field test specifications as defined in TIA/EIA-568-B and TSB-140. All of the installed fiber optic cables must be tested and must pass the specifications of TIA/EIA-568-B. Any cable that fails these tests must be diagnosed and corrected. The corrective action shall be followed with a new test to prove that the corrected link meets the performance requirements. The final and passing test must be saved and included in the final test results documentation. Field test instruments for multi-mode fiber cabling shall meet the requirements of TIA A. The light source shall meet the launch requirements of TIA/EIA B, Method A. Field test instruments for singlemode fiber cabling shall meet the requirements of TIA The test results for each link shall be recorded in the memory of the field tester upon completion of the test. The test results saved by the tester shall be transferred to a CD-ROM. A guarantee must be made that the measurement results are transferred to the CD-ROM unaltered that is, as saved by the tester at the end of each test. The guarantee must also specify that these results cannot be modified at a later time. The test results for the completed job shall be stored and delivered to OIT/NTS on a CD-ROM along with the software tools required to view, inspect, and print any selection of the test reports. A paper copy of the test results shall be provided to OIT/NTS in a three-ring binder Intrabuilding Backbone Riser Cable Testing Every installed intrabuilding backbone cable shall be tested in accordance with TIA/EIA-568-B.1 (for copper); with TIA/EIA-526-7, TIA/EIA A, and TIA/EIA-568-B.3 (for fiber); and with BICSI TDMM Chapter 11 (11 th edition or subsequent releases). 37

38 All of the installed intrabuilding backbone cables must be tested and must pass the specifications of TIA/EIA-568-B.1 (for copper); TIA/EIA-526-7, TIA/EIA A, and TIA/EIA-568-B.3 (for fiber). Any cable that fails shall be re-terminated and tested again. The test equipment shall comply with or exceed the accuracy requirements for enhanced Level III field testers. The pass or fail condition for the cable being tested is determined by the results of the required individual tests. Any fail result yields failure for the cable being tested. The test results for each cable shall be recorded in the memory of the tester upon completion of the test. The test results saved by the tester shall be transferred to a CD-ROM. A guarantee must be made that the results of the measurement shall be transferred to the CD- ROM unaltered that is, as saved by the tester at the end of each test. The guarantee must also specify that the results cannot be modified at a later time. The test results for the completed job shall be stored and delivered to OIT/NTS on a CD-ROM along with the software tools required to view, inspect, and print any selection of the test reports. A paper copy of the test results shall be provided to OIT/NTS in a three-ring binder. For individual installations, provide one project manual that is assembled in looseleaf binders and contains the following: o As-Built AutoCAD prints (as listed in Section 12 of this document) o A CD-ROM copy of all copper and fiber optic test results, along with the software tools required to view, inspect, and print any selection of the test reports o Warranty information and any vendor certification of the installed infrastructure 12 As-Built Documentation Provide complete CAD As-Built floor plans in AutoCAD 2000 that contain the following information: o Architectural floor plans with finalized room names and numbers 38

39 o The location and identification of all voice, data, and fiber optic outlets o A legend on the plans to readily identify the voice, data, and fiber optic cables (cable routing) o Conduit sizes and routing for all cables installed in conduit o Cable size and locations o Bonding and grounding locations and connections o Detailed communication riser diagrams (separate for fiber and copper), showing the following: terminal room locations; pathway route and size; cable size, construction, length, and pair counts; and fiber termination labeling. o Large-scale drawing of all communications/terminal rooms, indicating elevation views and plan views of including but not limited to all termination blocks, equipment racks, patch panels, and fiber optic enclosures o Terminal backboard layout with labeling and pair identification 13 OIT/NTS Outlet Labeling Scheme (Jacks) Each jack location in an outlet facility shall be labeled in accordance with OIT/NTS jacklabeling practices. The labeling follows a standard format, indicating the room followed by the location within the room. The general requirements for outlet facilities include the following: The jack naming standard is: XXXX-XX-XXXXX-XX 4 characters 2 characters 5 characters 2 characters The first four characters are the Building Number. Each building in MySoft has a building number affiliated with it. The second set of characters is the floor. Typically these characters are numeric, indicating the floor number that a jack resides on. Some of the variations from the numeric floor number are: o 0B indicating the Basement Level o 0G indicating the Ground Floor o LL Indicating the Lower Level o MZ or 0M indicating Mezzanine o 0P indicating Plaza o SB indicating Sub-Basement o SP indicating Sub-Plaza 39

40 Please note that the above 0 are a zero not a capital letter O. That is important when searching the MySoft database. The third set of characters is the room identifier. These characters indicate the Room Number that a jack is located within. These should always be 5 characters in length. We use 0 to fill any unnecessary place holders. For example if the jack is in room 12, the five characters would be entered as Some of the variations from the numeric room number (according to MySoft Standards) are as follows: o OS indicating outside of room (i.e.: OS146 indicates the jack is outside of room 146). o 0C indicating a cubicle area in room (i.e.: 0C210 indicates the jack is in a cubicle in room 210). o HL or 0H indicating a hallway area near room (i.e.: HL532 indicates the jack is in the hallway outside of room 532). The last set of characters is the specific jack identifier. These two characters specifically identify a jack within a room. The jack labeling scheme begins with AA, incrementing to AB, etc. so that each jack within a room has its own unique identification. Following are examples of some Exceptions to the Jack Naming Standard: CODEB-LU This indicates this jack is for a Code Blue location near Building CAMPH-AA This indicates this jack is for a Campus Telephone location near Building COINS-AA This indicates a pay telephone location in or near Building CRDKY-AA This indicates a Card Key location in or near Building VATOR-AA This indicates an Elevator location in Building TRAIL-AA This indicates a construction trailer at Building XX CF The XX is used for the floor to show this is not a legitimate jack location there is NO jack at all. This jack indicates that this is service for Building 1204, forwarding callers to Refer to Remote Call Forwarding procedure for more details CX CF The CX is used for the floor to show this is not a legitimate jack location there is NO jack at all. This jack indicates that this is service for Building 1728; forwarding callers to a (CX) Centrex line Refer to Remote Off-Campus Call Forwarding procedure for more details. 40

41 Any time we have to deviate from the Jack Naming Standard, typically the floor should be 00. This helps as a quick aid to indicate that this is not a standard jack. The rule of thumb is that when the Jack Naming Standard has to be deviated from, that we need to think about whether or not 911 could find this location solely based upon the Jack ID. If not, don t make it a jack!! The prefix field is always 5 digits. Rooms within a larger room may be designated as Room 100A, and their jacks may thus be labeled as 0100A-AA. For larger rooms, it may be necessary to continue the labeling sequence beyond AZ so that the next installed jack would be labeled BA, BB and so on, and if necessary, continued throughout the alphabet (CA, CB and so on). The official U of M Facilities management (FM) room numbers shall be used to determine the labeling. For this reason, room numbers shall not change due to the extensive labor involved in re-labeling each jack location and changing it in its associated database. The labeling information that OIT/NTS installs upon the voice and data jacks are used within the OIT/NTS database and forwarded to the police for location information to the response of emergency 911 staff (police, fire, etc.). Therefore it is imperative that this information be kept current. If the room numbers are to be changed during the course of the project, charges will be incurred to pick up this additional labor and to process the order so as to retain accuracy for the Life/Safety 911 database. Please contact your OIT/NTS liaison to coordinate these efforts. Jacks must be neatly labeled with a printed self-adhesive label that OIT/NTS has approved in advance. The labels must be typed/printed and are not to be drawn by hand. As-Built drawings that show jack numbers and locations shall be submitted to OIT/NTS upon completion of the project/building. 14 Products Installed That are Not Covered by These Standards University departments that purchase their own equipment, goods, and services shall consult with OIT/NTS before making such purchases in order to ensure that OIT/NTS is able and prepared to provide support. OIT/NTS cannot guarantee that voice and/or data wiring (including all associated termination hardware, electrical or electronic equipment, installation services, or maintenance agreements) that deviates from these standards will be interoperable with current or future network designs. 41

42 Furthermore, deviation from these standards limits the ability of OIT/NTS to support said installation. OIT/NTS shall provide its best effort to support, although it should be recognized that the normal response and resolution metrics of OIT/NTS shall not apply. OIT/NTS is not responsible for assurances of performance, guarantees, or warrantees implied or written that manufacturers or contractors make to non-oit/nts departments. If possible, OIT/NTS shall provide support to university departments that purchase their own equipment. OIT/NTS shall train department engineers and technicians at the department's expense, as well as stock additional equipment necessary for adds, moves, or changes; testing; and repair at the department's expense. Long lead times on non-standard equipment are possible. 15 Definitions of Abbreviations Contained in these Standards o ADA - Americans with Disabilities Act o ANSI - American National Standards Institute o AWG - American Wire Gauge o BICSI - Building Industry Consulting Services International o CABO - Council of American Building Officials o CMP - Communications Plenum Cable o CMR - Communications Riser Cable o CSI - Construction Standards Institute o EIA - Electronic Industry Association o EMI - Electromagnetic Interference o FM - Facilities management o FOCIS - Fiber Optic Connector Intermateability Standard o GE - Grounding Equalizer o HTAP - Irreversible compression fitting for connecting copper conductors o IDF - Intermediate Distribution Frame o IEC - International Electromechanical Commission o IEEE - Institute of Electrical and Electronics Engineers o ISO - International Organization for Standardization o LAN - Local Area Networks o MDF - Main Distribution Frame o NEC - National Electric Code o NECA - National Electrical Contractors Association o NEMA - National Electrical Manufacturers Association o NFPA - National Fire Protection Association o NTS - Networking and Telecommunications Services o OFNP - Optical Fiber Non-conductive Plenum o OFNR - Optical Fiber Non-conductive Riser o OIT - Office of Information Technology (University of Minnesota) 42

43 o OSHA - Occupational Safety and Health Administration o PBX - Primary Branch Exchange o RCDD - Registered Communications Distribution Designer o RFI - Radio Frequency Interference o TBB - Telecommunications Bonding Backbone o TGB - Telecommunications Grounding Busbar o TMGB - Telecommunications Main Grounding Busbar o TIA - Telecommunications Industry Association o TDMM - Telecommunications Distribution Methods Manual o TSB - Telecommunications System Bulletin o UBC - Uniform Building Code o UFC - Uniform Fire Code o UL - Underwriters Laboratories o UPS - Uninterruptible Power Supply o UTP - Unshielded Twisted Pair (c) 2005 by OIT and the Regents of the University of Minnesota The University of Minnesota is an equal opportunity educator and employer. 43

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011 TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...

More information

SECTION 25110 TELECOMMUNICATION ROOMS

SECTION 25110 TELECOMMUNICATION ROOMS PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

This presentation to be used in conjunction with:

This presentation to be used in conjunction with: 1 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 8/16/2012 2 Network Bonding and Grounding: TIA-607-B Generic Telecommunications

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Section 27 05 26 Grounding and Bonding for Communications

Section 27 05 26 Grounding and Bonding for Communications Part 1 General 1.1 General 1.1.1 Summary A. This section governs the products and execution requirements relating to furnishing and installing grounding and bonding for the communication systems. B. Description

More information

Electrical. This section applies to the design and installation of building power distribution systems.

Electrical. This section applies to the design and installation of building power distribution systems. Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions

More information

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

UT Southwestern Medical Center Information Resources Cable Installation Standard

UT Southwestern Medical Center Information Resources Cable Installation Standard UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE SECTION 270526 TELECOMMUNICATIONS GROUNDING & BONDING (-TAB) PART 1 GENERAL 1.01 SCOPE SUMMARY Designer shall provide a detailed narrative of the tasks to be performed under this specification section.

More information

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Telecommunications Systems Narrative Page 1 The Engineering Enterprise I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000

More information

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below: Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

More information

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

Specifications for Communication Cabling Distribution Systems

Specifications for Communication Cabling Distribution Systems Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

Cable Installation Project

Cable Installation Project Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280

More information

Document Purpose: Document Scope:

Document Purpose: Document Scope: Document Purpose: Washington University School of Medicine, BJC and Telecommunications Facility Corporation Low Voltage Voice and Data Pathways and Spaces Standard February 13, 2015 The purpose of this

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication

More information

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6 050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY

More information

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section. SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District

Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District 15579 Eighth Street Victorville, CA 92392 Phone 760. 245-1691 Fax 760.245-6245 www.vesd.net 02-26-03 TABLE OF CONTENTS Introduction 3 Overview of Standards 3 Equipment Specifications 4 Material Specifications

More information

The Telecommunications Closet and Building Services

The Telecommunications Closet and Building Services APPENDIX G Telecommunications Building & Network Standards 1. Expectations...2 2. Definitions...2 3. Contractor Requirements...2 4. Design Elements...3 4.1. Spaces...3 4.1.1. Building Service Entrance...3

More information

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District

More information

Intelligent Cable Management Systems

Intelligent Cable Management Systems Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication

More information

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

Electrical Code Regulation

Electrical Code Regulation Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

Errata NFPA 70. Proposed 2014 Edition

Errata NFPA 70. Proposed 2014 Edition Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes

More information

LOS ANGELES CITY COLLEGE Technology Design Standards

LOS ANGELES CITY COLLEGE Technology Design Standards LOS ANGELES CITY COLLEGE Technology Infrastructure Final January, 2007 Prepared for: Los Angeles City College Los Angeles City College TABLE OF CONTENTS Section Page INTRODUCTION 1 DESIGN STANDARDS FOR

More information

Power Management Module 2. Installation

Power Management Module 2. Installation Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

Requirements for Electrical Installations

Requirements for Electrical Installations ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This

More information

Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman

Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman This document defines the standards used for voice and data wiring in buildings used by MSU

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces May 1, 2014 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

ADC Structured Cabling Solutions

ADC Structured Cabling Solutions ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution

More information

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6) SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

FiberGuide Fiber Management Systems. 4th Edition

FiberGuide Fiber Management Systems. 4th Edition FiberGuide Fiber Management Systems 4th Edition Table of Contents Introduction Introduction...1 A Variety of Solutions...2 Innovative Products...3 Features and Benefits... 4 Applications Combining System

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Cabinets 101: Configuring A Network Or Server Cabinet

Cabinets 101: Configuring A Network Or Server Cabinet Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What

More information

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

About the BitStorm 6051 POTS Splitter

About the BitStorm 6051 POTS Splitter BitStorm 6051 Installation Instructions Document Number 6051-A2-GZ40-10 July 2002 About the BitStorm 6051 The BitStorm system enables simultaneous high-speed digital data access and analog voice service

More information

Special Specification 6033 Computerized Transportation Management System

Special Specification 6033 Computerized Transportation Management System 6033 Special Specification 6033 Computerized Transportation Management System 1. DESCRIPTION Relocate computerized transportation management system (CTMS) equipment as shown on the plans and as described

More information

CDGRD-10. Grounding. Solutions For Comm/Data Applications

CDGRD-10. Grounding. Solutions For Comm/Data Applications CDGRD-10 Grounding Solutions For Comm/Data Applications Overview & Table of Contents Cooper B-Line s Grounding products for rack & runway provide a complete solution for grounding metal supports. The offering

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada

Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are

More information

Installation Instructions

Installation Instructions Installation Instructions Built-In Dishwasher If you have questions, call 1-800-4-MY-HOME (1-800-469-4663) or visit our website at: www.sears.com BEFORE YOU BEGIN Read these instructions completely and

More information

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532. SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information