PROFINET CPU 314C-2 PN/DP, 315-2 PN/DP, 317-2 PN/DP, 319-3 PN/DP: Configuring the PROFINET interface



Similar documents
CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

SIMATIC. PROFINET IO Getting Started: Collection. CPU PN/DP: Configuring PROFINET interface X2

SIMATIC. S7 300 PLC CPU 317T-2 DP: Controlling a virtual axis. Introduction. Preparation. Learning units 3. Further information 4.

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4

WinCC Runtime Professional Readme SIMATIC HMI. WinCC V11 SP1. Readme WinCC Runtime Professional. Special considerations for Windows 7.

PROFINET IRT: Getting Started with The Siemens CPU 315 PLC

Validity 1. Installation 2 SIMATIC. WinCC flexible Tag simulator Update 1. Readme

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1

Creating the project and hardware. TIA Portal. SIMATIC Creating the project and hardware. Introduction to the TIA Portal 1. Creating a project

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3. Simatic. Readme. Readme

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Programming and Operating Manual

S SIMATIC S Welcome. Automation task. Hardware section 2. Software section 3. Security. Getting Started 05/2014 A5E AC

LOGO! LOGO! App V.10. LOGO! app 1. Making basic settings and establishing a connection to LOGO! Using the device overview 3. Creating controls 4

Information Server Documentation SIMATIC. Information Server V8.0 Update 1 Information Server Documentation. Introduction 1. Web application basics 2

PROFINET IO Diagnostics 1

SIMATIC PDM V6.0. Getting Started Edition 12/2004

1 Application Description Objective Goals... 3

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

Service & Support. How can you establish a connection between an S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

Connecting to the Internet

SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

Service & Support. How can you establish a connection between a S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DB Administration COMOS. Platform DB Administration. Trademarks 1. Prerequisites. MS SQL Server 2005/ Oracle. Operating Manual 09/2011

SIMATIC. SIMATIC Logon. User management and electronic signatures. Hardware and Software Requirements. Scope of delivery 3.

AXIS 205 Network Camera Quick Installation Guide

SIMATIC. WinCC V7.0. Getting started. Getting started. Welcome 2. Icons 3. Creating a project 4. Configure communication 5

Operating Instructions (Compact) Edition 02/2006

How-To-Do. Hardware Configuration SLIO CPU 014

Web server SIMATIC. S Web server. Preface. Documentation guide. General information. Websites 3. Function Manual 12/2014 A5E AD

COMOS. Lifecycle COMOS Snapshots. "COMOS Snapshots" at a glance 1. System requirements for installing "COMOS Snapshots" Database management 3

ENET-710. ENET Ethernet Module ENET-710 JAN / 06 FOUNDATION

Cover sheet PROFINET IO. SIMATIC MV440 Code Reading System. FAQ February Service & Support. Answers for industry.

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

SIMATIC. Process Control System PCS 7 Configuration Symantec Endpoint Protection (V12.1) Preface 1. Virus scanner administration 2.

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

SIMATIC HMI. WinCC flexible 2008 Getting Started - First-Time Users Getting Started. Printout of the Online Help 06/2008 A5E

WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01

Performing an automated installation

ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4

3.5 EXTERNAL NETWORK HDD. User s Manual

Automation License Manager

Quick Start Guide. Cisco Small Business. 300 Series Managed Switches

Installation and Operation Guide

Acano solution. Acano Solution Installation Guide. Acano. January B

Easy Setup Guide for the Sony Network Camera

SIMATIC NET. IE/PB Link Gateway Manual. Contents. Properties and Services. Compatibility with the Previous Product. Design How to Commission the IE/PB

2 Counter Module SIMATIC. S7-300 FM Counter module. Preface. Product Overview. How the FM Counts 2. Installing and Removing the FM 350-

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A

Patch management and security. updates SIMATIC. Process Control System PCS 7 Patch management and security updates. Preface 1

Quick Start Guide. DVR DS-7200HWI-SH Series DVR. First Choice For Security Professionals

WIRELESS INTERNET TROUBLESHOOTING GUIDE Help Desk

Quick Start Guide. Cisco Small Business. 200 Series 8-Port Smart Switches

Quick Start Guide. Cisco Small Business. 200E Series Advanced Smart Switches

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DSL Installation Guide

Quick Start Guide. Cisco SPA232D Mobility Enhanced ATA

DE1600 DSA E-Series iscsi Disk Arrays. en Quick Install Guide

ProSAFE 8-Port and 16-Port Gigabit Click Switch

Modicon M340 Firmware

10/ English Edition 1. Quick Start Guide. NWA1100N-CE CloudEnabled Business N Wireless Access Point

Security basics and application SIMATIC NET. Industrial Ethernet Security Security basics and application. Preface. Introduction and basics

HP UPS R1500 Generation 3

Addendum to the Operating Instructions

CP SIMATIC NET. S Telecontrol CP Preface. Application and properties. Displays and connectors 2

FAQ Communication over IE

LIEBERT VNSA Installation Sheet


1. Hardware Installation

Adding or replacing a mesh node in an existing mesh network

How To Install A Cisco Cisco 520-T1 Router On A Network Card (Cisco) With A Network Cable (Cio) And A Network (Cnet) (Coconc) (Net) And An Ipo (

PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7

HP ProLiant DL380 G5 High Availability Storage Server

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

PCI/PXI ETHERNET ADAPTERS

HWg-STE HWg-STE PoE MANUAL

RouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP

Quick Start Guide. RV0xx Series Routers

Setting Up the ZigBee Ethernet Gateway

connecdim Gateway G1 Ethernet TCP/IP to DALI

How To Use Mview On A Powerline 2.2 (Powerline) On A Pc Or Macbook 2 (Powerplst) On An Iphone Or Ipa 2 (Aldo) On Your Iphon 2 (

PCS300 Universal IP Reporting Module V1.0

MAX-306M1 Series. WiMAX MIMO Outdoor Simple CPE DEFAULT LOGIN DETAILS. Models: MAX-306M1 (2.5 GHz) and MAX-316M1 (3.5 GHz)

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

EMBEDDED ACCESS CONTROL Hardware Installation Guide

Getting Started Edition 04/2001

Universal Serial Bus (USB) to DH-485 Interface Converter

CCNA Discovery Networking for Homes and Small Businesses Student Packet Tracer Lab Manual

1 Application Description System Topology Hardware and Software Requirements... 3

Network Installation Guide. WorkForce 600 Series Artisan 700 Series Artisan 800 Series

ilan Ethernet Box for 9100 Installation Manual

How to Set Up Your NSM4000 Appliance

SIMATIC The Process Device Manager Manual Edition 12/2004 A5E

Transcription:

CPU 314C-2 PN/DP, 315-2 PN/DP, Introduction 1 317-2 PN/DP, 319-3 PN/DP: Configuring the PROFINET interface SIMATIC PROFINET CPU 314C-2 PN/DP, 315-2 PN/DP, 317-2 PN/DP, 319-3 PN/DP: Configuring the PROFINET interface Preparation 2 Learning units 3 Further Information 4 Getting Started 08/2011 A5E00268410-04

Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the relevant information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY A5E00268410-04 P 09/2011 Copyright Siemens AG 2011. Technical data subject to change

Table of contents 1 Introduction... 5 2 Preparation... 7 3 Learning units... 11 3.1 1. Step: Mount mounting rails and modules...11 3.2 2. Step: Wiring the power supply and CPU...13 3.3 3. Step: Commissioning the hardware...14 3.4 4. Step: Set up the PG/PC interface...15 3.5 5. Step: Configuring hardware in HW-Configuration of STEP 7...16 3.6 6. Step: To insert CPU 317-2 PN/DP and assign it and IP address...17 3.7 7. Step: Commissioning the CPU 317-2 PN/DP...20 4 Further Information... 21 Getting Started, 08/2011, A5E00268410-04 3

Table of contents 4 Getting Started, 08/2011, A5E00268410-04

Introduction 1 Introduction In the following steps we will show you the basics of configuring the PROFINET interface, using the CPU 317-2 PN/DP as an example. The PROFINET interface for the CPU 314C-2 PN/DP, 315-2 PN/DP and 319-3 PN/DP is configured in the same way as for the CPU 317-2 PN/DP. This process will take one to two hours, depending on your experience. Getting Started, 08/2011, A5E00268410-04 5

Introduction 6 Getting Started, 08/2011, A5E00268410-04

Preparation 2 Scope CPU SIMATIC Micro Memory Card required for operation? 314C-2 PN/DP yes V3.3 315-2 PN/DP yes V3.2 317-2 PN/DP yes V3.2 319-3 PN/DP yes V3.2 As of firmware version The order number can be found in the manuals, e.g. the operating instructions CPU 31xC and CPU 31x: Installation (http://support.automation.siemens.com/ww/view/en/13008499). Requirements Basic knowledge of electronic and electrical systems engineering. Knowledge in the area of network engineering would be of advantage. You have already worked with the STEP 7 programming software. You are familiar with the Microsoft Windows operating system. WARNING Operation of an S7-300 as part of plants or systems is subject to special rules and regulations, which depend on its field of application. Please make sure that you adhere to the applicable safety and accident prevention regulations, for example IEC 204 (emergency stop systems). You risk severe injury, or damage to machines and equipment if you ignore these regulations. Getting Started, 08/2011, A5E00268410-04 7

Preparation Material and tools required Quantity Item Order number (Siemens) 1 Mounting rail e.g. 6ES7390-1AE80-0AA0 1 Power supply (PS) module e.g. 6ES7307-1EA01-0AA0 1 CPU 314C-2 PN/DP or CPU 315-2 PN/DP or CPU 317-2 PN/DP or CPU 319-3 PN/DP e.g. 6ES7314-6EH04-0AB0 e.g. 6ES7315-2EH14-0AB0 e.g. 6ES7317-2EK14-0AB0 e.g. 6ES7318-3EL01-0AB0 1 SIMATIC Micro Memory Card e.g. 6ES7953-8LL20-0AA0 1 Programming device (PG) or PC with Ethernet network card, 100 Mbps, full duplex depending on the configuration Installed software STEP 7, as of V5.5 1 Switch, e.g. SCALANCE X208 e.g. 6GK5208-0BA00-2AA3 1 Industrial Ethernet twisted pair cable (Cat5) with RJ45 connectors (patch cable TP Cord RJ45/RJ45, length = 6 m) e.g. 6XV1850-2GH60 various M6 screws and nuts (lengths depend on place of commonly available installation) and matching wrench / screwdriver 1 Screwdriver with 3.5 mm blade commonly available 1 Screwdriver with 4.5 mm blade commonly available 1 Side cutter and cable stripper commonly available 1 Crimp tool for wire ferrules commonly available 0.5 m 1-wire flexible cable, conductor cross-section 1 mm 2 with commonly available wire-end ferrules, for connecting the power supply and CPU X m Cable for grounding the mounting rail with 10 mm 2 commonly available cross-section and cable lug to fit M6, length appropriate for local requirements. X m 3-wire flexible power cable (230/120 V AC) with "Schuko" plug; length to suit local requirements with suitable wire-end ferrules with shrouded contacts. commonly available 8 Getting Started, 08/2011, A5E00268410-04

Preparation Configuring the PROFINET interface 1 2 3 4 5 6 7 8 Status and error displays Bay for SIMATIC Micro Memory Card Mode selector Industrial Ethernet twisted pair cable for connecting to additional PROFINET devices Industrial Ethernet Twisted Pair cable for interconnecting PN interface X2 Programming device (PG) with STEP 7 software Mounting rail Power supply ON/OFF Figure 2-1 Configuration with CPU 317-2 PN/DP Getting Started, 08/2011, A5E00268410-04 9

Preparation 1 2 3 4 5 6 7 10 9 8 1 2 Power supply (PS) module CPU 317-2 PN/DP 3 PROFINET Port 1 The port 1 status is signaled using a two-colored LED (green/yellow): LED lights up green: LINK to a partner is active LED changes to yellow: Active data traffic (RX/TX) R: Ring port for setting up a ring topology with media redundancy 4 PROFINET Port 2 The port 2 status is signaled using a two-colored LED (green/yellow): 5 6 7 8 9 10 Figure 2-2 LED lights up green: LINK to a partner is active LED changes to yellow: Active data traffic (RX/TX) R: Ring port for setting up a ring topology with media redundancy MAC address and 2D bar code 2. Interface X2 (PN), with dual-port switch 1. Interface X1 (MPI/DP) Power supply connection Connecting cables between PS and CPU Strain relief Wiring the power supply and CPU 10 Getting Started, 08/2011, A5E00268410-04

Learning units 3 3.1 1. Step: Mount mounting rails and modules Installation sequence From left to right: Power supply PS 307 - CPU 317-2 PN/DP. The configuration diagram gives you an overview of the overall configuration. Installing and grounding the mounting rail 1. Screw on the mounting rail (screw size: M6). Make sure to maintain a minimum clearance of 40 mm above and below the mounting rail. When mounting it on a grounded metal panel or on a grounded equipment mounting panel, make sure you have a low-impedance connection between the mounting rail and the mounting surface. 2. Connect the rail to the protective conductor. An M6 protective conductor screw is provided on the mounting rail for this purpose. Stipulated cross-section of the cable connection to the protective conductor: at least 10 mm 2. Getting Started, 08/2011, A5E00268410-04 11

Learning units 3.1 1. Step: Mount mounting rails and modules Installing modules on the mounting rail 1. First of all, insert the power supply module. Slide it to the left as far as the grounding screw of the mounting rail. Fasten the power supply module. 2. To connect further modules, insert a bus connector into the CPU. 3. Hang in the CPU (1). 4. Slide it up to the left module (2). 5. You can then swing it down (3). 6. Tighten the modules with a torque of 0.8 to 1.1 Nm. 7. Insert a SIMATIC Micro Memory Card into the CPU (4). Delete the content of a SIMATIC Micro Memory Card with unknown content before you use it in the programming device. 8. You also need to install one digital input and one digital output module to the right of the CPU. To do this, repeat steps 2 to 6 as applicable. 12 Getting Started, 08/2011, A5E00268410-04

Learning units 3.2 2. Step: Wiring the power supply and CPU 3.2 2. Step: Wiring the power supply and CPU WARNING Ensure the S7-300 is completely disconnected before wiring! You may come into contact with live wires if the S7-300 is connected to the power supply. Procedure 1. Open the front panels of the power supply and the CPU. 2. Detach the strain relief clip from the power supply. 3. Strip the flexible power cable. 4. Correctly crimp on wire-end ferrules. 5. Connect the CPU to the power supply (blue to terminal M, black to terminal L1, protective conductor to terminal PE). 6. Screw the strain relief clamp in place. 7. Next, wire the power supply to the CPU. Use flexible cable with a conductor cross-section of 1 mm 2. Strip the ends to a length of approx. 6 mm. 8. Crimp wire-end ferrules to the ends. 9. Connect power supply terminals L+ and M to the terminals on the CPU. Getting Started, 08/2011, A5E00268410-04 13

Learning units 3.3 3. Step: Commissioning the hardware 3.3 3. Step: Commissioning the hardware Procedure 1. Connect your CPU (e.g. port 1 of PN interface X2) to the PG/PC. Use the twisted pair cables with RJ45 connectors. Result: The PG/PC is interconnected with the CPU. 2. Connect the PROFINET I/O device (e.g. ET 200S) to your CPU (e.g. port 2 of PN interface X2). Use the twisted pair cable with RJ45 connectors. Result: The I/O device is connected to the CPU. 3. Verify that the SIMATIC Memory Card is inserted in the CPU slot. 4. Close the front panel cover of the CPU, then set the mode selector switch on the CPU to STOP. 5. Connect the power supply cable to the mains, then switch on the power supply module. Result: The power supply 24V DCLED lights up. All LEDs on the CPU light up briefly. The SFLED and the 5V DC LED remain on. The STOP LED then flashes and the CPU automatically carries out a memory reset. After completion, the STOP LED is lit. 6. Start your PG/PC, then run SIMATIC Manager from your Windows desktop. Result: A window opens with SIMATIC Manager. 14 Getting Started, 08/2011, A5E00268410-04

Learning units 3.4 4. Step: Set up the PG/PC interface 3.4 4. Step: Set up the PG/PC interface Procedure 1. Select "Start > SIMATIC > STEP 7 > Customize PG/PC interface". Result: The dialog box for setting the PG/PC opens. 2. Select the access path. Then set the TCP/IP protocol for the network card used. Click "Properties". Select the "Assign project-specific IP address" option in the "Properties" dialog box. Confirm twice with "OK". Result: Your PG/PC settings are applied. Getting Started, 08/2011, A5E00268410-04 15

Learning units 3.5 5. Step: Configuring hardware in HW-Configuration of STEP 7 3.5 5. Step: Configuring hardware in HW-Configuration of STEP 7 Create a new project in STEP 7 1. Select the menu command "File > New...". 2. Enter a name for your project and click on OK to confirm. Result: A new project is created. Add a new S7-300 station Select "Insert > Station > SIMATIC 300 Station". Result: The SIMATIC 300 (1) icon in the right-hand part of the window is highlighted. Add a rail 1. In the right-hand part of the window, double-click first on the SIMATIC 300(1) icon and then on the Hardware icon. Result: The hardware configuration editor (HW Config) opens. 2. Insert your hardware components from the hardware catalog in the left-hand section of the window. If no catalog is displayed, use the menu command View > Catalog to activate it. In the hardware catalog, select SIMATIC 300 and then Rack 300. Drag-and-drop the mounting rail to the top section of the HW Config window. Result: This pastes the mounting rail into the upper section of the HW Config window. Add the power supply In the hardware catalog, navigate to PS 300. Drag-and-drop your power supply into slot 1 in the mounting rail. Result: The power supply module is inserted into slot 1. Note You can click the power supply module to view its order number. The order number then appears in the box beneath the catalog. 16 Getting Started, 08/2011, A5E00268410-04

Learning units 3.6 6. Step: To insert CPU 317-2 PN/DP and assign it and IP address 3.6 6. Step: To insert CPU 317-2 PN/DP and assign it and IP address Introduction Each Ethernet node is identified by a internationally unique address. This "MAC address" is preset by the manufacturer and cannot be changed. In the following steps you will assign an IP address in the the Ethernet to this physical address. Procedure 1. Navigate to CPU 300 in the hardware catalog. Drag-and-drop the CPU 317-2 PN/DP into slot 2 of the mounting rail. The CPU 317-2 PN/DP is inserted in slot 2. The properties window of the PROFINET interface X2 is displayed. The IP address for products as of V3.x can be activated by selecting the "Use different method to assign IP address" checkbox. 2. Enter the IP address and the subnet mask. When working on a corporate network, contact your network administrator for information about this address. 3. If you setup a connection via router, you must also enter the address of the router. When working on a corporate network, contact your network administrator for information about this address. 4. Click "New", then assign a name for a new Industrial Ethernet subnet. Confirm your entries with "OK". Result: You created a new Industrial Ethernet subnet. Getting Started, 08/2011, A5E00268410-04 17

Learning units 3.6 6. Step: To insert CPU 317-2 PN/DP and assign it and IP address 5. Click on the "OK" button. Result: The properties window of the PROFINET interface X2 for CPU 317-2 PN/DP closes. 6. In HW Config you can also set the options for the PROFINET interface: In HW Config, double-click on PROFINET interface X2 or on the required port for the CPU 317-2 PN/DP. If you have selected port 1 or port 2, switch to the "Options" tab. You can customize the network settings on this tab if need be. Default is "Automatic Settings", which is usually sufficient for error-free communication. Communication problems may be caused by faulty network settings or by the automatic network settings. Problems can include failure to establish connections and frequent network errors. Select a network configuration that matches your network settings. Result: Customize the network settings in HW Config. Save and compile your configuration 1. Select the menu command "Station > Save and compile". Result: The hardware configuration is compiled and saved. 2. Select the menu command "PLC > Download to module". Result: The dialog box for the selection of the target group is displayed. CPU 317-2 PN/DP is already selected as the target module. 18 Getting Started, 08/2011, A5E00268410-04

Learning units 3.6 6. Step: To insert CPU 317-2 PN/DP and assign it and IP address 3. Confirm the dialog with "OK". Result: The dialog box for the selection of the station address is displayed. The CPU is not yet displayed in "stations reached". 4. Click "View". Result: The programming device reads the MAC address and displays it in the dialog box. 5. Select the line with the MAC address of the CPU. Confirm with "OK". Result: The message window opens. Getting Started, 08/2011, A5E00268410-04 19

Learning units 3.7 7. Step: Commissioning the CPU 317-2 PN/DP 6. Confirm the message with "Yes". Result: IP address is assigned to the CPU and the configuration is loaded. 7. Close HW Config with the menu command "Station > Close". Answer the save prompt with "Yes". Result: HW Config is closed. The CPU now appears in the station in SIMATIC Manager. 3.7 7. Step: Commissioning the CPU 317-2 PN/DP Procedure Set the mode switch of the CPU to "RUN". Result: The STOP LED is off. The RUN LED starts to flash and then assumes a continuous signal. The LINK LED (green) indicates a physical Ethernet connection. The RX/TX LED (yellow) is lit or flashes when data are being transmitted/received via Ethernet. Note Note: The LINK LED and the RX/TX LED may also be combined in a two-colored LED. Result You have completed the STEP 7 configuration of the PROFINET interface X2 of your CPU 317-2 PN/DP. Other nodes can now access the CPU on the Ethernet subnet. The new functions now allow you to configure your project, or to reconfigure it, via the integrated PROFINET interface of the CPU. All PG/OP functions and other communication functions of the CPU 317-2 PN/DP are now available via the integrated PROFINET interface. 20 Getting Started, 08/2011, A5E00268410-04

Further Information 4 Reference For detailed information on address assignment for the PROFINET interface, please refer to the STEP 7 online help. Diagnostics/Correction of Errors Wrong operation, faulty wiring or a faulty hardware configuration may cause errors which the CPU indicates with the SF group error LED after a CPU memory reset. For information on how to diagnose such errors and alarms, please refer to the operating instructions, CPU 31xC and CPU 31x: Installation (http://support.automation.siemens.com/ww/view/en/13008499). Manuals containing further information Getting Started: Getting started and exercises with STEP 7 (http://support.automation.siemens.com/ww/view/en/45531551) Manual: SIMATIC NET: Twisted Pair and Fiber Optic Networks (http://support.automation.siemens.com/ww/view/en/8763736) Manual: SIMATIC communication (http://support.automation.siemens.com/ww/view/en/1254686) PROFINET System Description (http://support.automation.siemens.com/ww/view/en/19292127) Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet (http://www.siemens.com/automation/service&support). There you can find: A newsletter containing the latest information on your Siemens products. The documents you need using the search engine in Service & Support. The bulletin board, a worldwide knowledge exchange for users and experts. Your local contact for Automation & Drives in our contact database. Information about on-site services, repairs and spare parts. You will find much more under "Services". Getting Started, 08/2011, A5E00268410-04 21

Further Information 22 Getting Started, 08/2011, A5E00268410-04