400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications



Similar documents
High-voltage DC distribution is key to increased system efficiency and renewable-energy opportunities

Qualitative Analysis of Power Distribution Configurations for Data Centers

Residential & Commercial Use Of DC Power

High-Efficiency AC Power Distribution for Data Centers

White Paper: Pervasive Power: Integrated Energy Storage for POL Delivery

Server Technology, Inc.

France Telecom Energy consumption, HVDC, cooling improvement

Motherboard- based Servers versus ATCA- based Servers

From 48 V direct to Intel VR12.0: Saving Big Data $500,000 per data center, per year

DC powered data centers in the world

Calculating power requirements for HP ProLiant rack-mounted systems

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Evaluating the Opportunity for DC Power in the Data Center

VICOR WHITE PAPER. The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications

Power Feeding Equipment for Optical Submarine Cable Systems

Server Technology Inc.

Phase Modular Finally the benefits of Modular ups are for all

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

UPS Applications and VRLA Battery Sizing

Three-Phase Electric Power Distribution for Computer Data Centers

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

When the Power Fails: Designing for a Smart Meter s Last Gasp

User Manual for CH-PFC76810

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs

Energy saving technology for data centers. HVDC(High Voltage Direct Current) + 12V Server rack system

Power Electronic Circuits

Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:

Alternative data center power

Mini Effect Gizmo. User s Manual. RJM Music Technology, Inc.

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

Power Distribution Considerations for Data Center Racks

Electrical Systems. <Presenter>

Charging what can be more simple? SAE J1772

Reducing Data Center Energy Consumption

HYBRID POWER SYSTEMS for TELECOM applications

Public Overview of the EMerge Alliance Data/Telecom Center Standard Version 1.0

Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz

Welcome to this presentation on Driving LEDs AC-DC Power Supplies, part of OSRAM Opto Semiconductors LED Fundamentals series. In this presentation we

AC versus DC Power Distribution in the Data Center

NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM

Secondary Unit Substations

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Cisco Nexus 7000 Series Power Supply Modules

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell

Welcome to this presentation on Switch Mode Drivers, part of OSRAM Opto Semiconductors LED Fundamentals series. In this presentation we will look at:

MAJORSINE Power Inverter

415V DISTRIBUTION FOR GREEN DATA CENTERS

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

UNRIVALED EMERGENCY SOLUTIONS FOR LEDs CLASS 2 OUTPUT COMPLIANCE WITH AUTO-SENSE FORWARD VOLTAGE

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

Version Date Author Description Jpo First version Jpo FET output descriptions made clearer

Fundamentals of Power

Power Supplies. Overview. Measuring Electricity. Understanding Electricity. Two Types of Current. Powering the PC

3 U CompactPCI Backplane with 4 Slots

USB I/O CONTROL BOX 8 relays, 8 digital I/O lines and 8 HV inputs

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

8 coil stator 11 coil stator

Intel architecture. Platform Basics. White Paper Todd Langley Systems Engineer/ Architect Intel Corporation. September 2010

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Creating a Usable Power Supply from a Solar Panel

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

SYSTEM 4C. C R H Electronics Design

ISPS2014 Workshop Energy to Smart Grids Presenting results of ENIAC project: E2SG (Energy to Smart Grid)

Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime

415V DISTRIBUTION FOR GREEN DATA CENTERS

High voltage tester HA 1800 Table-top device

How To Convert A Power Grid To A Direct Current (Dc) Power System

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER

R&D Access Touch 3.1 User Manual Version 1.00 Public 1 (13) User Manual. Access Touch 3.1

Mobile Device Power Monitor Battery Connection Quick Start Guide

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

SL Series AC and DC Electronic Loads

THE INPUT/OUTPUT SYSTEM. Key Points

SYSTEM 45. C R H Electronics Design

NetSure DC Power Solutions with esure High-Efficiency Technology

************* OWNER'S MANUAL BAMF800/2 BAMF1250/2 BAMF1800/2 BAMF2200/2 BAMF2600/2 BAMF1200/4 BAMF1600/4 BAMF2000/1D BAMF4000/1D BAMF5500/1D

Is an energy-wasting data center draining your bottom line?

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, W Compact and T5c fluorescent lamps

AC-115 Compact Networked Single Door Controller. Installation and User Manual

Edison s Data Center: 380Vdc brings Reliability and Efficiency to Sustainable Data Centers

Panduit Infrastructure Management Software for Data Centers and Enterprises

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

LOXONE 12 Channel Amplifier

LANTANA LUMINAIRE HI-LUME 1% ECOSYSTEM LED DRIVER L3DA4U1UMN-XXXXX

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Programming Logic controllers

Transcription:

WHITE PAPER 400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications Presented at 1. Objective This live demonstration of a 400V DC powered eco-system, validates the feasibility of what has been previously discussed in concept. The demo operates at 380V DC and makes use of existing technologies and components provided by several major vendors. The solution shown features high end-to-end efficiency and can result in significant savings in the site wiring costs versus 48V DC. This tabletop demo was put together by using standard, off-the-shelf components. Figures 1 and 2 offer an overview of the demo installation. Goal minimize TCO from AC to the point of load Rectifier Cabinet 380VDC Distribution Equipment Rack Powered Equipment AC Input 380VDC High Voltage Bus Converter + 380VDC _ GND ZVS Buck- Boost Regulator Current Multiplier 1.xV Battery ZVS Buck Regulator 2V 16V Ground Figure 1: 380V DC power system configuration for telecom applications ANDERSON Connectors A 380V-400V DC LED Lighting fixtures 380V Load FUJITSU 400V DC power strip A HV IBC 1:8 Equalizer ZVS-BB ZVS B-B 20-55V WLAN Switch 1U Server SAC 0.7-1.2V Intel VR12 CPU / memory Un-regulated 48V Load Regulated 48V Load VICOR Un-regulated 48V Load 120V, 15A wall outlet AC / DC Converter 380V-400V EMERSON NETWORK POWER VICOR HV IBC 1:32 Industrial PC 24' LED monitor Standard 12V Load Standard 12V Load Figure 2: Block diagram of the 380V DC table-top demonstration 1

2. System Aspects By using Vicor s Equalizer concept in the powered equipment power supply, there is no efficiency penalty in supporting the ETSI EN 300 132-3-1 normal service voltage range of 260V - 400V DC. The Equalizer block enables the use of a high-voltage bus converter as equipment front-end element, with minimal impact on conversion efficiency. During normal operation with source voltage greater than 350V DC the equalizer is bypassed and does not impose any losses in the power transfer. The equalizer is activated only when the source voltage drops below the 350V DC level (typically during battery discharge). Figure 3: Vicor equalizer concept to address different DC system voltages Safety concerns for 400V DC distribution have been systematically addressed with a high resistance mid-point ground (HRMG) implementation: a. On the bulk power source by midpoint resistive grounding with fault detection b. On the distribution system by using ±190V instead of 0V-380V c. On the equipment front end conversion, with fully isolated, safety extra low voltage (SELV)-output high voltage bus converters Midpoint resistive grounding with fault monitor provides for a safe and reliable distribution line; fully isolated, SELV output high voltage bus converters used as equipment front-end provide for an extra layer of safety for the operators. Figure 4: 380V DC power grid IT mid-point resistive grounding 2

2.1 Transition path from existing 12V or 48V to 400V DC powered equipment Existing 48V DC loads can be transitioned to 400V DC distribution by implementing simple, minimally invasive adapters. Figure 5: Transition path from 48V DC to 400V DC grid systems (Source: Didier Marquet, France Telecom - Orange Labs) 3

2.2 Proposed power system architectures Figure 6: External adapters can easily interface existing 48V powered equipment Figure 7: Existing equipment can be retrofitted with 400V bus converters that feed intermediate 12V buses 4

Figure 8: New rack equipment can be natively designed to accept 400V DC, by implementing Factorized Power Architecture. 5

3. Vendor Contributions 3.1 Emerson Network Power: AC to DC Power Conversion The NetSure 4015 is the latest AC to DC power system from Emerson Network Power designed for telecom and datacom facilities operating up to 400V DC, with a 3-phase AC input. The foundation of the system is our patented, next generation 15kW esure rectifier, featuring high frequency switching technology in a compact package at 97% efficiency. It is designed for easy deployment in lab evaluation or field installations, all three major components of this system fit into standard 19" racks. For the purposes of this portable demonstration, Emerson has provided a modified single phase rectifier to provide the 380V DC supply. For more information, please visit: http://www.emerson Network Power.com/400VDC 3.2 Vicor: 400V DC to Point-of-Load Conversion Vicor enables customers to efficiently convert and manage power from DC distribution to point-of-load. We address the entire power chain with a comprehensive portfolio of high efficiency, high-density, power architectures aimed at performance-critical applications. Vicor s holistic approach gives power system architects the flexibility to choose from modular, plug-and-play components ranging from bricks to semiconductor-centric solutions. For the purposes of this portable system, Vicor has provided two demonstration boards: a. Interface card featuring 400V DC bus converters, with ratios of 1:8 and 1:32 in order to power 48V and 12V loads respectively, as well as energy storage and Zero Voltage Switching Buck-boost converters in equalizer configuration in order to provide compliance to ETSI EN 300 132-3-1 standard. b. 48V reference design compliant to Intel VR12 server processors For more information, please visit: http://www.vicorpower.com/promotions/2012/compliance/vr12/dc.php or http://www.vicorpower.com 3.3 Anderson Power Products: 400V DC Connectors Anderson Power Products (APP) is the world s leading developer of DC power connectors with sixty years of experience producing connectors from 10 to 700 Amperes and from 12 to 1,000 Volts. APP is a leader in the development of DC product safety standards working within EMerge, IEC, NEMA, and in cooperation with UL. In January 2009, APP introduced the UL recognized Saf-D-Grid connector, developed for 400V DC IT equipment up to 8KW. 3.4 Fujitsu Components: 400V DC Rack PDU Fujitsu Component Limited and NTT Facilities co-developed a safe, user friendly arc extinguishing 10A, 400V DC power connector that insures user safety and equipment safety when installing or disconnecting a high voltage (10A, 400V DC) power port. The interconnect system was considered a key element in providing safe and reliable usage or ability to implement high current DC. Development started in 2007, to support 380V DC power grids in the data center applications. Fujitsu has adopted the power connector design into our Power Distribution Units (5 port and 10 port), and is currently installed in several data centers, both in Japan and in North America/Europe. Fujitsu Component also developed a key relay with arc extinguishing characteristics, to support the circuit protection requirements of the power supply manufacturers, supporting 450V DC (Fujitsu s FTR-J2 series), which is UL/CSA/VDE approved to support 450V DC (along with 277V AC). For product information, contact FCAI via telephone at 1-800-380-0059 or by email at components@us.fujitsu.com For more information, please visit: http://us.fujitsu.com/components 6

3.5 GVA Lighting: 400V DC LED Lighting GVA Lighting is a Canadian design and manufacturing company specializing in architectural and special application lighting. As a pioneer of LED lighting with 12 years of experience in large scale and high reliability projects, GVA Lighting thrives on solving great engineering challenges. GVA is the first company to offer a 380VDC lighting solution by using proprietary INFINITY technology. GVA Lighting provides unique and cost effective solutions for long lighting circuits including delineation of bridges, skyscrapers or illumination of data centers. For more information, please contact us: support@gvalighting.com 3.6 Philips: 400V DC LED Lighting Philips Green Flagship LED luminary LuxSpace Compact High Efficacy offers 2490 Lumen light output with an outstanding efficacy of 90 Lumen/Watt. This efficacy number includes LED driver with 400V DC input, the Philips Fortimo LED light engine and the reflector of the LuxSpace luminary. For the purposes of this portable demonstration, Philips Research has realized LED luminaires with 400V DC supply. For information on commercial available products of the LuxSpace Compact High Efficacy luminaire, please visit http://www.ecat.lighting.philips.com/l/indoor-luminaires/downlights/luxspace-compact-high-efficacy/52878/cat/#. 7