Energy saving technology for data centers. HVDC(High Voltage Direct Current) + 12V Server rack system

Size: px
Start display at page:

Download "Energy saving technology for data centers. HVDC(High Voltage Direct Current) + 12V Server rack system"

Transcription

1 Energy saving technology for data centers HVDC(High Voltage Direct Current) + 12V Server rack system Green Solution Business Unit Environmental Technology Division NTT DATA INTELLILINK Corporation Copyright 2013 NTT DATA INTELLILINK Corporation

2 Copyright 2013 NTT DATA INTELLILINK Corporation 2 Case study Service In! / Sakura Internet Ishikari DC System: Type HVDC Power Supply System (Product: FRESH HVDC and XECHNO Power) Location: Ishikari DC of Sakura Internet Range: 19Racks 140kW

3 Configuration: XECHNO-Power and central power supply unit Backside of server rack Mount frame Central power supply unit Monitoring device for central PS UNIT Central Power power Supply supply Unit unit Shelf(TJ1727) PS Unit (TJ1715) Parallel running with N+1 redundant 6 Unit Max hot-pluggable SNMP Pass-through box ITE V ITE PS Unit TJ1715 (HVDC DC/DC Converter) Minus cable Plus cable Laminated bus bar Central PS (DC/DC Converter) Flexible bus bar Server Rack System (20-25 Racks / 1System) Copyright 2013 NTT DATA INTELLILINK Corporation Flexible bus bar Connected bus bar 3

4 Copyright 2013 NTT DATA INTELLILINK Corporation 4 What HVDC type can do for You Benefit1 HVDC can help you succeed in the future with greater productivity and lower costs. Benefit2 Total Efficiency higher than 90% with reducing the number of conversion! High efficiency with real loading factor, unlike UPS Intensive PS system with central power supply unit in server rack Reduction of electricity charge Non-stop maintenance and expansion through n+1 redundancy! Seamless connection to battery during power outage! Less conversion! Eliminating PS form ITE, long-lasting, highly-reliable! Fanless, liquid-capacitor less! Energy-saving effect High reliability Solving high voltage-current problems! Arc suppression circuit Middle point ground Benefit3 Safety The future technology Solar power LED Illumination Fuel cell Cooling system with outside air Superconductors etc Benefit4

5 Copyright 2013 NTT DATA INTELLILINK Corporation 5 Energy-saving effect: Energy reduction HVDC Power Supply System reduces /DC conversions between commercial power and ITE. Power loss is reduced by approximately 10-20%. CPU/MEMORY/HDD CPU/MEMORY/HDD

6 Copyright 2013 NTT DATA INTELLILINK Corporation 6 Safety ~ Multiple safety guard! PS rack DC340V DC HVDC PDU DC340V HVDC Server rack DC Server() Mother board CPU Memory HDD Key technology : Middle point ground The current is limited within safety current for human through high resistors of 47KΩ. Central Redundant Power Supply Key technology : Bus bar Dangerousness by the high voltage had been pointed out. But,,, Key technology : Arc suppression circuit W/O Suppression Circuit W/ Suppression Circuit Resolved the arc discharge issue at the time of switch-on/off and disconnection.

7 Copyright 2013 NTT DATA INTELLILINK Corporation 7 The difference UPS to HVDC- DC380V SERVER ~ UPS DC/ Power supply PDU Switching Power supply (Isolation /DC) Switching Power supply (Isolation /DC) Mother Board ~ UPS DC/ Power supply PDU η=80~92% Conventional ~ ~ Diode Rectifier (Non-Isolation) (Non-Switching) n+1 redundant η=98~99% Non-stable power supply DC V DC200~400V PDU PDU Switching Power supply (Isolation DC/DC) n+1 redundant η=93~95% η=99.5% Pass-Through (W/Protection) SERVER Mother Board n+1 redundant

8 Copyright 2012NTT DATA Corporation 8 Energy-saving effect: Total efficiency of HVDC Eff[%] 効 率 comparative chart 効 of 率 efficiency 比 較 95.0 % 20.0 % 90.0 % 9.0% 8.4% 18.0 % 16.0 % 85.0 % 18.0% 14.0 % 80.0 % 12.0 % 10.0 % 75.0 % 8.0 % 70.0 % 6.0 % 4.0 % 65.0 % 2.0 % 60.0 % 0.0 % 12.5% 25.0% 37.5% 50.0% 62.5% 75.0% 87.5% 100.0% Load Factor[%] 負 荷 率 ( % ) difference 差 異 XECHNO+Fresh 総 合 効 率 XECHNO+Fresh Total Efficiency 方 式 総 合 効 率 Type Total Efficiency XECHNO+Fresh 総 合 効 率 Difference(%) 方 式 総 合 効 率 XECHNO+Fresh Total Efficiency 差 異 ( % ) XECHNO+Fresh Type Total Efficiency Difference(%) 方 式 総 合 効 率 差 異 ( % )

9 Copyright 2013 NTT DATA INTELLILINK Corporation 9 Solar Power + HVDC Drive The Future Communication with Sunlight! Solar battery generates DC that s the same as HVDC! Doesn t need Power Conditioner Local Generation for Local Consumption Reasonable Investment...Say goodbye to Power Conditioners. Existing Solar Power Generation Power Company Power Conditioner Power Selling Power Purchase DC What percent of Solar power will be fed? Data Center HVDC Plus! Solar Simple & Direct Power Loss Reduction : 5 % - 10% DC Power Company HVDC DC Data Center

10 International standardization activity for DCEM-WG has officially started as a member of Green University of Tokyo Project DCEM-WG(Data Center Energy Management Working Group) SWG1 DCIM(Data Center Infrastructure Management) SWG2 HVDC system(high Voltage Direct Current System) to be standardized internationally (ITU etc.) to be standardized internationally (ISO/IEEE etc.) Step 3 ASP SaaS Cloud Consortium Ministry of Internal Affairs and Communications Green University of Tokyo Project Copyright 2012NTT DATA Corporation Step 2 Technical Spec Step 3 Japan Data Center Council(JDCC) Ministry of Economy, Trade and Industry DCEM-WG Step 1 DPPE Datacenter Performance Per Energy To make the Technical SPEC for HVDC/12V PS with DCIM, After one year, via demonstration experiments, we will set the standard for 10

11 Copyright 2012NTT DATA Corporation 11 High Voltage Direct Current Open Compute Project 3φ 480V UPS DC 3φ 480V/1φ 277V Open Compute project Open Rack Hardware v1.0 V2 Power shelf DC SERVER RK DC SERVER RK MOTHER BOARD -SERVER MOTHER BOARD -SERVER in in in Server /DC /DC /DC 21inch RK Open Compute Project HVDC HVDC Open Compute project DC340V /380V HVDC DC SERVER RK MOTHER BOARD -SERVER HVDCin HVDCin HVDCin DC/DC DC/DC DC/DC 21inch RK HVDC Open Compute Project

12 Copyright 2012NTT DATA Corporation 12

DATA CENTER. Enhancing the Energy Efficiency and Use of Green Energy in Data Centers

DATA CENTER. Enhancing the Energy Efficiency and Use of Green Energy in Data Centers DATA CENTER Enhancing the Energy Efficiency and Use of Green Energy in Data Centers Datacenter Performance Per Energy (DPPE) Enhances Energy Efficiency and Use of Green Energy in Data Centers This booklet

More information

DC powered data centers in the world

DC powered data centers in the world DC powered data centers in the world Keiichi Hirose, Ph.D. Senior Research Engineer R&D Headquarters NTT Facilities, Inc. Tokyo Japan LVDC Workshop SMB Strategic Group 4 on LVDC distribution systems up

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Infrastructure as a Service

Infrastructure as a Service Infrastructure as a Service Next Generation Data Center & Cloud Paul Chen paul.chen@cskytech.com 2013 Csky Information All rights reserved. Changing More Users More Devices More Data >1 Billion More Netizen

More information

Power Supply, Cooling and Mechanical Technologies for Green IT

Power Supply, Cooling and Mechanical Technologies for Green IT Power Supply, Cooling and Mechanical Technologies for Green IT Yoshinori Uzuka Kazuhiko Itakura Nobuyoshi Yamaoka Tomoyoshi Kitamura There is an emerging trend for green IT on servers. This trend includes

More information

Mixing Sodium and Lead Battery Technologies in Telecom Applications

Mixing Sodium and Lead Battery Technologies in Telecom Applications Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,

More information

Power to the adaptable data center

Power to the adaptable data center Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.

More information

New Data Center Energy Efficiency Evaluation Index DPPE (Datacenter Performance per Energy) Measurement Guidelines (Ver 2.05)

New Data Center Energy Efficiency Evaluation Index DPPE (Datacenter Performance per Energy) Measurement Guidelines (Ver 2.05) New Data Center Energy Efficiency Evaluation Index DPPE (Datacenter Performance per Energy) Measurement Guidelines (Ver 2.05) March 3, 2012 Green IT Promotion Council 1/70 Table of Contents 1. Basic Concepts

More information

CenterMind P+ Solution for efficient power management

CenterMind P+ Solution for efficient power management CenterMind P+ Solution for efficient power management Overview Over last decade DC become significant power consuming facilities Information Technology Equipment (ITE) continue to increase computing capabilities

More information

Fuel Cell Powered Data Centers: In-Rack DC Generation

Fuel Cell Powered Data Centers: In-Rack DC Generation Fuel Cell Powered Data Centers: In-Rack DC Generation Li Zhao, Jack Brouwer National Fuel Cell Research Center University of California, Irvine Sean James, Eric Peterson, Jie Liu, Di Wang Microsoft 1/18

More information

Photovoltaic Power Systems Business and Data Center Facility Business. Kiyoshi Tsutsui, President and CEO, NTT Facilities, Inc.

Photovoltaic Power Systems Business and Data Center Facility Business. Kiyoshi Tsutsui, President and CEO, NTT Facilities, Inc. Photovoltaic Power Systems Business and Data Center Facility Business Kiyoshi Tsutsui, President and CEO, NTT Facilities, Inc. September 26, 2014 The forward-looking statements and projected figures concerning

More information

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations

More information

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR

More information

UPS Applications and VRLA Battery Sizing

UPS Applications and VRLA Battery Sizing TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the

More information

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade

More information

How To Understand The Infrastructure Of A Data Center

How To Understand The Infrastructure Of A Data Center 6 Data center defined The infrastructure behind a digital world MIETEK GLINKOWSKI Today s mobile society means that people are consuming and creating data at unprecedented levels the Internet, search engines,

More information

Datacenter Hosting and Cloud Computing Services

Datacenter Hosting and Cloud Computing Services Datacenter Hosting and Cloud Computing Services Overview Background Founded in 1995, Lore Systems operates an international datacenter network which today includes full service 3+ datacenter facilities

More information

Improving Data Centers Energy Reliability & Efficiency. December 2015

Improving Data Centers Energy Reliability & Efficiency. December 2015 Improving Data Centers Energy Reliability & Efficiency December 2015 Background The challenges Alternative solutions SATEC approach Advantages Cases Summary Data Centers Energy Challenges Worldwide Data

More information

400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications

400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications WHITE PAPER 400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications Presented at 1. Objective This live demonstration of a 400V DC powered eco-system, validates the feasibility of

More information

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant uae-sj@panduit.com PANDUIT You Can t Manage What You Don t Measure:

More information

DC Electronic Loads 8500 series

DC Electronic Loads 8500 series Data Sheet DC Electronic Loads 8500 series 2400W 600 W - 1200 W 300 W Versatile & Economical DC Electronic Loads The 8500 series Programmable DC Electronic Loads can be used for testing and evaluating

More information

HOW TO USE MULTIMETER. COMPILE BY: Dzulautotech

HOW TO USE MULTIMETER. COMPILE BY: Dzulautotech HOW TO USE MULTIMETER COMPILE BY: Dzulautotech 1. GENERAL Electricity is absolutely necessary for an automobile. It is indispensable when the engine is started, the air fuel mixture is ignited and exploded,

More information

NTT Com Asia deploys NEC's Express 5800/ECO CENTER to become more competitive.

NTT Com Asia deploys NEC's Express 5800/ECO CENTER to become more competitive. Mr. Taylor Man Vice President NTT Com Asia "With our hosting solutions, such as Virtualization as a Service, we need innovative products and solutions to help us to face business challenges." Background

More information

Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary

Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary What: Duke Energy and EPRI Sponsored DC Powered Data Center Demonstration Using 380V DC Power When: 2010-2011 Where: Duke Energy

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

Green IT Promotion Council, Japan

Green IT Promotion Council, Japan Concept of New Metrics for Data Center Energy Efficiency Introduction of Datacenter Performance per Energy [ DPPE ] Green IT Promotion Council, Japan February2010 Abstract Power Usage Effectiveness (PUE)

More information

Mobile Device Power Monitor Battery Connection Quick Start Guide

Mobile Device Power Monitor Battery Connection Quick Start Guide Mobile Device Power Monitor Battery Connection Quick Start Guide Distributed By: Monsoon Solutions, Inc. www.msoon.com Introduction The Power Tool software and the Mobile Device Power Monitor hardware

More information

OPERATIONS MANUAL DATA CENTER COLOCATION

OPERATIONS MANUAL DATA CENTER COLOCATION Section I: Introduction and Service Description. OPERATIONS MANUAL DATA CENTER COLOCATION Company means MCI Communications Services, Inc., d/b/a Verizon Business Services, or any affiliated entity designated

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.

DC Power Solutions Overview. DC Power Solutions for EVERY Network Application. DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International

More information

Open Rack Charter. Authors: Gio Coglitore, Pierluigi Sarti, John Kenevey, Pete Bratach

Open Rack Charter. Authors: Gio Coglitore, Pierluigi Sarti, John Kenevey, Pete Bratach Open Rack Charter Authors: Gio Coglitore, Pierluigi Sarti, John Kenevey, Pete Bratach Contents Contents... 2 Mission Statement... 3 Summary... 3 Overview... 4 License... 4 Design Approach... 5 Physical

More information

Midas XCI Immersion Cooling. The High Efficiency, High Density, High Performance Data Center Cooling Solution

Midas XCI Immersion Cooling. The High Efficiency, High Density, High Performance Data Center Cooling Solution Midas XCI Immersion Cooling The High Efficiency, High Density, High Performance Data Center Cooling Solution Midas XCI Immersion cooling technology allows you to maximize server density and power efficiency

More information

Optimization of IT Load and Facility Energy in Data Centers

Optimization of IT Load and Facility Energy in Data Centers Optimization of IT Load and Facility Energy in Data Centers Kunio Fukumoto Nobuyuki Tamura Hideki Ishibashi While the convenience of data centers is attracting attention and demand for them is increasing,

More information

PowerChain Management solutions. PowerChain Management Solutions for Data Centers

PowerChain Management solutions. PowerChain Management Solutions for Data Centers PowerChain Management solutions PowerChain Management Solutions for Data Centers PowerChain Management keeps your data center open for business Your data center and the network that supports it form the

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International

More information

Solution Analysis White Paper CHOOSING THE RIGHT UPS FOR SMALL AND MIDSIZE DATA CENTERS: A COST AND RELIABILITY COMPARISON

Solution Analysis White Paper CHOOSING THE RIGHT UPS FOR SMALL AND MIDSIZE DATA CENTERS: A COST AND RELIABILITY COMPARISON Solution Analysis White Paper CHOOSING THE RIGHT UPS FOR SMALL AND MIDSIZE DATA CENTERS: A COST AND RELIABILITY COMPARISON Introduction A dependable uninterruptible power supply (UPS) system is essential

More information

Evaluating the Opportunity for DC Power in the Data Center

Evaluating the Opportunity for DC Power in the Data Center A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center

More information

Infinity C DC to DC Power System

Infinity C DC to DC Power System PRODUCT OVERVIEW Infinity C DC to DC Power System Models 663-664 Negative (663) or Positive (664) Output Large plant features in a small plant package Battery management including discharge test Industry

More information

Microsoft Private Cloud Fast Track Reference Architecture

Microsoft Private Cloud Fast Track Reference Architecture Microsoft Private Cloud Fast Track Reference Architecture Microsoft Private Cloud Fast Track is a reference architecture designed to help build private clouds by combining Microsoft software with NEC s

More information

Power Management of Cell Sites

Power Management of Cell Sites International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar

More information

Electricity and Power Supplies Chapter #4

Electricity and Power Supplies Chapter #4 Electricity and Power Supplies Chapter #4 Amy Hissom Key Terms Active backplane A type of backplane system in which there is some circuitry, including bus connectors, buffers, and driver circuits, on the

More information

(EMR) system in resource-constrained settings. The use of the EMR at point-of-care (POC)

(EMR) system in resource-constrained settings. The use of the EMR at point-of-care (POC) Centralized Power Backup System and Low-Power Computing A reliable power source is a core requirement for using an electronic medical record (EMR) system in resource-constrained settings. The use of the

More information

NEC Micro Modular Server Introduction. NEC November 18,2014

NEC Micro Modular Server Introduction. NEC November 18,2014 NEC Micro Modular Server Introduction NEC November 18,2014 Market Trend Cloud Computing Public cloud service market is growing. It is expected over 20% of annual growth. Cloud services used in companies

More information

Five Nines and Infrared (IR) Testing at Data Centers

Five Nines and Infrared (IR) Testing at Data Centers Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.

FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store. Text and design: Creuna/Mikla. Photo: Shutterstock, Getty Images. Document no: MMP10.0002.BR3 WWW.ELTEK.COM FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.

More information

Achievements and Issues in Promoting Diagnosis on Energy Saving in Southeast Asia and Surrounding Regions

Achievements and Issues in Promoting Diagnosis on Energy Saving in Southeast Asia and Surrounding Regions Achievements and Issues in Promoting Diagnosis on Energy Saving in Southeast Asia and Surrounding Regions Noriyuki Nakayama, Chairman, Asia Green IT Committee Environmental Management Promotion Dept.,

More information

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,

More information

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate: Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency

More information

Alternative data center power

Alternative data center power Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Combi B Alarm box. Mounting instructions

Combi B Alarm box. Mounting instructions Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power

More information

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Last time. Data Center as a Computer. Today. Data Center Construction (and management)

Last time. Data Center as a Computer. Today. Data Center Construction (and management) Last time Data Center Construction (and management) Johan Tordsson Department of Computing Science 1. Common (Web) application architectures N-tier applications Load Balancers Application Servers Databases

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill

More information

Improve competiveness of IDC and enterprise data centers with DCIM

Improve competiveness of IDC and enterprise data centers with DCIM Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM

More information

DPPE: Holistic Framework for Data Center Energy. Efficiency. - KPIs for Infrastructure, IT Equipment, Operation (and Renewable Energy) -

DPPE: Holistic Framework for Data Center Energy. Efficiency. - KPIs for Infrastructure, IT Equipment, Operation (and Renewable Energy) - DPPE: Holistic Framework for Data Center Energy Efficiency - KPIs for Infrastructure, IT Equipment, Operation (and Renewable Energy) - August 2012 Japan National Body /Green IT Promotion Council 1. Introduction

More information

Application. Key Features. Benefits. Contact us. Solution for GSM-R coverage. AIR Repeater RF/RF GSM-R 900. To ensure GSM-R coverage everywhere

Application. Key Features. Benefits. Contact us. Solution for GSM-R coverage. AIR Repeater RF/RF GSM-R 900. To ensure GSM-R coverage everywhere Application GSM-R 900 coverage enhancement Outdoor : Cell extension Indoor : Tunnels and confined areas Key Features Medium & High Power Band- & Channel- Selective Digital Smart Filter Outdoor IP65 cabinet

More information

Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure

Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Scale-Out Smart for HPC and Cloud Computing with enhanced energy efficiency The PRIMERGY CX400 Cloud extension servers are Fujitsu

More information

SL Series AC and DC Electronic Loads

SL Series AC and DC Electronic Loads SL Series AC and DC Electronic Loads Applications AC & DC Power Supply Testing Rechargeable batteries and chargers Fuel cell test - cells and stacks PFC circuit test Pulsed LED Test and Burn-in Laser Diode

More information

Magnet field- and Radiation Tolerant New Power Supply System MARATON - Technical Overview. 22-Sep-03 1

Magnet field- and Radiation Tolerant New Power Supply System MARATON - Technical Overview. 22-Sep-03 1 Magnet field- and Radiation Tolerant New Power Supply System MARATON - Technical Overview 22-Sep-03 1 Modular Power Supply System MARATON 2 Versions: To power crates (UEP6..) or generic electronics (PL5..)

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change

Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change DATA CENTRE LOCATIONS Forum Kouvola, Finland Hitachi in Europe September 2011 By Ian Blond Head of Data Centre

More information

Green and Smart Data Center -- Energy Saving --

Green and Smart Data Center -- Energy Saving -- Green and Smart Data Center -- Energy Saving -- September 15, 2015 Fuji Electric Co., Ltd. Fuji Electric Co., Ltd. All rights reserved. 1 Why does Fuji Electric undertake IDC business? Annual power consumption

More information

France Telecom Energy consumption, HVDC, cooling improvement

France Telecom Energy consumption, HVDC, cooling improvement France Telecom Energy consumption, HVDC, cooling improvement Didier Marquet (FT R&D and ETSI EE2 chairman), Marc Aubrée (FT R&D) Datacenter Code of Conduct meeting in IEA 2nd July 2007 A bit of history

More information

WHOLESALE DIRECT INC. 5620 WEST 65TH STREET

WHOLESALE DIRECT INC. 5620 WEST 65TH STREET Auto Pump V 200 100 0 100 Max Rating Vehicle mount compressor ensures truck air brake system is properly pressurized for immediate dispatch from station Pressure switch regulated operation automatically

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to

More information

Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites

Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites Power topic #NAPT-5516-EN Technical information from Cummins Power Generation Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites A system-level

More information

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 IT Power Solutions CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications

More information

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical

More information

Capacity Planning in the Modern Datacenter

Capacity Planning in the Modern Datacenter in the Modern Datacenter SERVER TECHNOLOGY - INDUSTRY BRIEF -001 July 2015 Executive Overview Today s datacenter managers oversee more infrastructure than ever, with an exponential increase in complexity

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Server Platform Optimized for Data Centers

Server Platform Optimized for Data Centers Platform Optimized for Data Centers Franz-Josef Bathe Toshio Sugimoto Hideaki Maeda Teruhisa Taji Fujitsu began developing its industry-standard server series in the early 1990s under the name FM server

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE

RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive

More information

FLEXIBILITY THROUGH STABILITY

FLEXIBILITY THROUGH STABILITY DATACENTER FLEXIBILITY THROUGH STABILITY Your ICT environment, and your organization with it, hinges on your datacenter. Your MER, SER or datacenter not only has to guarantee the storage of huge amounts

More information

YSmart Technology Co.,Ltd

YSmart Technology Co.,Ltd YSmart Technology Co.,Ltd GWV Series Grid Tie Microinverter User Manual The copyright of this user manual belong to YSmart TechnologyCompany Limited. Without the written permission of the copyright holder,

More information

Softstart. Changing of Printed Circuit Board PS S18-300. General...2 Please note!... 2

Softstart. Changing of Printed Circuit Board PS S18-300. General...2 Please note!... 2 Softstart Changing of Printed Circuit Board PS S18-300 5309 704-1 Rev E Juli-06 General...2 Please note!... 2 Identify the Printed Circuit Board that is going to be replaced...2 Replacing an older PCB

More information

High-Efficiency AC Power Distribution for Data Centers

High-Efficiency AC Power Distribution for Data Centers High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. The Top 10 things every data center manager should know about power White Paper STI-100-014 2012-April Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United

More information

Understanding the Alternator

Understanding the Alternator http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED

More information

Case study: End-to-end data centre infrastructure management

Case study: End-to-end data centre infrastructure management Case study: End-to-end data centre infrastructure management Situation: A leading public sector organisation suspected that their air conditioning units were not cooling the data centre efficiently. Consequently,

More information

TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SM1000RM1UTAA Description Tripp Lite SM1000RM1UTAA 1000VA / 1kVA / 800 watt line

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

Automation's Modular Containerized Datacenter Solutions

Automation's Modular Containerized Datacenter Solutions SAFE Automation's Modular Containerized Datacenter Solutions Automation's SAFE (Secure, Autonomous, Flexible, Efficient) Modular Containerized Datacenter offers a fast, flexible and efficient solution

More information

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen

More information

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG

More information

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity

More information

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS,

More information

DATA CENTER PHYSICAL INFRASTRUCTURE

DATA CENTER PHYSICAL INFRASTRUCTURE Is your datacenter running with maximum performance? Datacenter managers have been challenged to maintain or increase availability, maximize efficiency, and optimize the use of existing capacity. However,

More information