France Telecom Energy consumption, HVDC, cooling improvement
|
|
|
- Julianna Briggs
- 9 years ago
- Views:
Transcription
1 France Telecom Energy consumption, HVDC, cooling improvement Didier Marquet (FT R&D and ETSI EE2 chairman), Marc Aubrée (FT R&D) Datacenter Code of Conduct meeting in IEA 2nd July 2007
2 A bit of history of HVDC (1) 1880's: Edison-Tesla, initial HVDC electricity network, then AC France Telecom GEODE PROJECT high voltage DC cabinet was imagined but modular decentralized 48V was developed 1988 IEEE/INTELEC HVDC paper by Fujitsu Several Intelec DC workshops (Yokohama, Berlin, ): concern for IP powering with Deutsch Telecom, NTT, Bells France Telecom Presentation of ETSI EN by Wilfried Schulz DT EE2 chairman in Yokohama at ETSI It seemed HVDC could be better solution titre du document/date/confidentiel/auteur 2 Groupe France Télécom
3 A bit of history of HVDC (2) VDC option presented at IEEE/INTELEC by France Telecom and Alcatel 1999 INTELEC, HVDC paper from NTT-f 2000 Alcatel 312 VDC - 30 kw power station for ATM and servers systems presented in ETSI meeting (2000) and IEEE/intelec, NTT paper on 270 Vdc cabinet 2006 DC workshop N 1 WashingtonDC: Intel, Sun, EPRI, BerkeleyLBNL, NTT, ETSI, UPN, ETNO demonstration by Intel R&D NTT-f Sendaï project : 1 MW site with PV and HVDC 2007 USA DCworkshop N 2 titre du document/date/confidentiel/auteur 3 Groupe France Télécom
4 Power consumption? FTgroup -ORANGE 2006 : 3,5 TWh for the group about 2 TWh in France, (0,4% of national consumption) 2006 very rough estimations GWh kwh/client/year Possible evolution FT fix network (phone, DSL, FTTH) to 30 VoIP with standby FT mobile network to 20 Radio efficiency, Standby FT datacenters Better server use, passive cooling, HVDC FT terminals 300? 0 to 100 Standby PC+TV? 100 to 1000? World servers (without storage) I2C data (Koomey thesis)? How to master power consumption? Code of Conduct + standards to define measurement methods (ETSI, ) titre du document/date/confidentiel/auteur 4 Groupe France Télécom
5 ETSI EN (2003) 400 V HVDC option A common power supply interface Interworking of different types for telecommunications and data communication equipment Very high power efficiency Facilitate the installation, operation and maintenance in the same network of equipment from different origins (servers, NGN, ). Simple and reliable titre du document/date/confidentiel/auteur 5 Groupe France Télécom
6 Power architecture and efficiency comparaison a) centralised 48 V (R+B with a1: thyristor mode and a2: HF switched mode) 1a 3 phases Transformer 2a Short ACdistribution 3 ph 3 ou 3a Rectifiers 3 ph /48V 4a Long 48V Distribution 81 to 85 % b) Decentralised 48 V (R+B cabinet) 2b Long AC Distribution 3 ph 1b Transfo 3ph or single ph Neutral change 3b Rectifiers Single phase/48v 4b Short 48V Distribution 83 to 87 % c) HVDC (direct use or decentralised 48 V production) 97 % 2a Short AC Distribution 1a Transfo tri TNS 3c Redresseurs Tri/300Vdc 4c Distribution Longue 300Vdc 5 Conversion 300/48 90 to 93 % For Comparaison : on line UPS = 85 to 92 % off lineups = 97 % titre du document/date/confidentiel/auteur 6 Groupe France Télécom
7 HVDC Architecture : AC UPS replaced by DC UPS + DC BUS Back-up Fuel cell reducing battery size Solar PV Grid kwh saving Converters 48V telecom AC 350 HVDC Inverters 230AC users HVDC servers (intel R&D 2006) Motor with HF speed controler to save energy New fluo ou LED Not secured AC titre du document/date/confidentiel/auteur 7 Groupe France Télécom
8 France Telecom first feeling about HVDC cost < 230 V UPS and 48 V DC compared to 48V: 30 time less cupper 6 time more compact rectifiers battery centralization compared to decentralized 48V: - cooler area for battery, lifetime gain - no pb of weight compared to UPS: supressing UPS inverter stage simpler for engineering and operation more reliable offline UPS is also an efficient solution one disturbance filter is lost titre du document/date/confidentiel/auteur 8 Groupe France Télécom
9 ETSI EN Suite of ETSI standards defining thermal environment: - Large temperature range is accepted by telecom equipement (5-40 C on site) - That allows very important savings in telecom rooms till 100 kw using outside fresh-air + passive building inertia - It can be partially proposed for servers, because : + 1 C saves about 10% power consumption, servers can work till 30 to 35 C BUT 20 C is used to give time to repair cooling system (today we observe + 1 C per mn, ie 15 mn till first servers failures) So, some points under study : - Better air management in the room (e.g. ETSI TMG Thermal Management group documents) - Manufacturers are thinking to better heat management inside servers cabinets - Passive inertia can be enhanced at the level of servers titre du document/date/confidentiel/auteur 9 Groupe France Télécom
10 Further steps Improving datacenter power consumption understanding HVDC: experimentation standardisation (Cenelec, IEC) : Plug and protections site engineering impact : Datacenter and new generation telecom migration from AC to DC : cabling, HVDC Acceptability investigation - Deeper comparative economical study Cooling ingeneering and system improvement titre du document/date/confidentiel/auteur 10 Groupe France Télécom
Power Management of Cell Sites
International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar
DC powered data centers in the world
DC powered data centers in the world Keiichi Hirose, Ph.D. Senior Research Engineer R&D Headquarters NTT Facilities, Inc. Tokyo Japan LVDC Workshop SMB Strategic Group 4 on LVDC distribution systems up
380VDC Data Center At Duke Energy
380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA From
HYBRID POWER SYSTEMS for TELECOM applications
HYBRID POWER SYSTEMS HYBRID POWER SYSTEMS HYBRID POWER SYSTEM WITH AC GENSET PRAMAC has developed a new solution that allow coupling a traditional AC constant speed diesel genset with an energy storage
400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications
WHITE PAPER 400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications Presented at 1. Objective This live demonstration of a 400V DC powered eco-system, validates the feasibility of
DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.
DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Residential & Commercial Use Of DC Power
Residential & Commercial Use Of DC Power Dennis P. Symanski Senior Project Manager NEMA, UL & NFPA Low Voltage Direct Current Workshop 08APR2011 Arlington, VA From Dept of Energy Secretary Steven Chu As
Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet'
Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet' We ve prepared this information sheet to help you to minimise energy consumption and energy costs while maximising thermal comfort at home.
SRS2025. Home & small Business. Energy Storage Solution
SRS2025 Home & small Business Energy Storage Solution Leclanché Lithium-ion complete system The ideal energy storage system for Home & Small Business Lithium-ion battery storage systems Home & Small Business
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks White Paper Anil K. Trehan, Vice President, Energy Solutions CommScope, Inc. May 28, 2013 Contents
Energy Efficiency and Green Data Centers. Overview of Recommendations ITU-T L.1300 and ITU-T L.1310
Energy Efficiency and Green Data Centers Overview of Recommendations ITU-T L.1300 and ITU-T L.1310 Paolo Gemma Chairman of Working Party 3 of ITU-T Study Group 5 International Telecommunication Union Agenda
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER. www.ep2000.com 800.500.
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER Introduction Heat in the System The modern facility has been revolutionized by advancements
ABB central inverters PVS800 100 to 1000 kw
Solar inverters ABB central inverters PVS800 100 to 1000 kw ABB central inverters raise reliability, efficiency and ease of installation to new levels. The inverters are aimed at system integrators and
We develop the technology for a blue sky...
We develop the technology for a blue sky... MAVİSİS TECHNOLOGY Mavisis Technology A.Ş. is a leader technology company in power electronics area in renewable energy. Mavisis Technology, as a brand, states
(EMR) system in resource-constrained settings. The use of the EMR at point-of-care (POC)
Centralized Power Backup System and Low-Power Computing A reliable power source is a core requirement for using an electronic medical record (EMR) system in resource-constrained settings. The use of the
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS October 22, 2010 Authored by: Kevin Binnie, Senior Product Portfolio Manager ALPHA TECHNOLOGIES LTD. Executive Summary
De energievoorziening in 2040;
De energievoorziening in 2040; decentraal, duurzaam en intelligent! Prof. Dr. Ad van Wijk 25-6-2012 20-06-2012 Delft University of Technology Challenge the future There is no energy crisis Energy efficiency
Ringing at the Door. Boiling an egg. Moving by car. Flows of solar energy. There is no energy crisis. How to boil an egg?
Delft University of Technology There is no energy crisis How to boil an egg? Prof. Dr. Ad van Wijk 20-10-2011 Energy efficiency world wide is about 2% The sun gives us in one hour more energy than the
Data Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
SOLAR MICRO INVERTER 260 COMMUNICATION GATEWAY. Apparent Power Control (APC) unique micro inverter with
SOLAR MICRO INVERTER 260 COMMUNICATI GATEWAY Apparent Power Control (APC) P Q unique micro inverter with REAL & REACTIVE POWER CTROL 2 Micro Inverters unique micro inverter with real & reactive power control
Evaluating the Opportunity for DC Power in the Data Center
A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center
FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.
Text and design: Creuna/Mikla. Photo: Shutterstock, Getty Images. Document no: MMP10.0002.BR3 WWW.ELTEK.COM FREE iphone APP Get our FREE OPEX SAVER CALCULATOR iphone App scan code to go direct to App Store.
ESS industry day Introduction to Imtech Power Conversion
ESS industry day Introduction to March 12 th, 2014 Erwin Lenten Royal Imtech N.V. is a technical services provider in Europe in electrical services, ICT and mechanical services Turnover 5.4 billion, 29,000
47000 SERIES - ELECTRONIC TRANSFORMERS
7000 SERIES - ELECTRONIC TRANSFORMERS MYRRA encapsulated electronic transformers are Switched Mode Power Supplies based on Flyback topology. They constitute an interesting alternative to the traditional
ITU-T Broadband forums
ITU-T Broadband forums Energy Efficiency and Future Data Centres Amsterdam, October 22 nd Guillaume GERARD, Senior DataCenter Expert, Orange Orange group: the DataCenter big picture No less than 78 DataCenters
Hybrid-Cable-System with an Advanced Data and Power Architecture Product Brief
Hybrid-Cable-System with an Advanced Data and Power Architecture Product Brief Brugg Cables and PowiDian 11-11-2015 What is PowiDian? PowiDian is a Smart-Energy-Systems-Integrator and is covering: Production
Green Wireline Networks home networks sensors networks
GRUPPO TELECOM ITALIA Green Wireline Networks home networks sensors networks Flavio CUCCHIETTI Telecom Italia Innovation Telecom Italia numbers 17M NB users 8 Data Centres 4 Service Centr. 49.ooo battery
Photovoltaic Solar Energy Unit EESFB
Technical Teaching Equipment Photovoltaic Solar Energy Unit EESFB Products Products range Units 5.-Energy Electronic console PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION Worlddidac Member ISO 9000: Quality
World s Greenest High Performance Data Center
World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms
POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery
POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the
Energy Logic for Telecommunications
A White Paper from the Experts in Business-Critical Continuity Energy Logic for Telecommunications by Steve Roy, Global Marketing Worldwide demand for broadband and wireless services is growing at double-digit
Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery
Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the
RELAYS Solar Energy Systems
RELAYS Solar Energy Systems FUJITSU COMPONENTS CONTENTS Fujitsu relays for solar applications DC voltage versions - AC voltage versions - Latching versions RELAY PRODUCT LINE UP - SOLAR ENERGY SYSTEMS
The UCSD/Calit2 GreenLight Instrument Tom DeFanti, PI
The UCSD/Calit2 GreenLight Instrument Tom DeFanti, PI California Institute for Telecommunications and Information Technology: Calit2 Over 1000 Researchers in Two Buildings Linked via Dedicated Optical
Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions
Selecting a UPS Topology for your Data Center by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions Uninterruptible Power Supplies (UPS) are both reaching into new markets and expanding in new ways
A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW
WE BRING GREEN SOLUTIONS TO YOU A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW Provided by A COOLER PLANET A Cooler Planet 1 The Complete Solar Guide WHY GO SOLAR? TOP FIVE FACTORS TO CONSIDER FOR ADDING
Energy efficiency in TLC Networks: the Operator and the User perspective
GTTI - Parma June, 23-2009 Energy efficiency in TLC Networks: the Operator and the User perspective Telecom Italia Technology & Energy: Where are we going? 2010 2020 Gbps Interc. F. 100s Gbps Interc. F.
DC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
Wind-Diesel Hybrid System Options for Alaska. Steve Drouilhet National Renewable Energy Laboratory Golden, CO
Wind-Diesel Hybrid System Options for Alaska Steve Drouilhet National Renewable Energy Laboratory Golden, CO Wind-Diesel Hybrid Power Systems Basic Concept A wind-diesel hybrid system combines wind turbine(s)
Siemens presents new DC grid connection for offshore wind farms Siemens AG 2015 All rights reserved. siemens.com/grid-access-solutions
Higher cost efficiency in Wind Power Transmission Siemens presents new DC grid connection for offshore wind farms siemens.com/grid-access-solutions is leading in offshore grid access To date Siemens has
Summary of Electric Power Research Institute (EPRI) Report on Residential Off-Grid System Economics
Summary of Electric Power Research Institute (EPRI) Report on Residential Off-Grid System Economics September 11, 2014 0 Forward-Looking Statements Leading the Way in Electricity SM Statements contained
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure for Business-Critical Continuity Are you deploying a remote site faster than you can
Guideline for Energy Efficient Electrical systems for building. Presentation by TERI
Guideline for Energy Efficient Electrical systems for building Presentation by TERI Objective of study The study highlights how BBMP can implement energy efficiency measures in building in co-ordination
POWER TRANSMISSION FROM OFFSHORE WIND FARMS
POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred
Hybrid GenSet HYBRID POWER UNIT. Hybrid GenSet. POWER RANGE 7-35 kw. APPLICATIONS Outdoor Indoor Telecom Site. www.ascotinternational.
EN POWER RANGE 7-35 kw APPLICATIONS Outdoor Indoor Telecom Site 1 Desert Border Control (Middle East) Remote Off Grid Indoor TLC Site (Africa) Remote Off Grid OutdoorTLC Site (Asia) Remote Off Grid Indoor
Opportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
High-Megawatt Converter Technology Workshop for Coal-Gas Based Fuel Cell Power Plants January 24, 2007 at NIST
Session 4a Enjeti 1 High-Megawatt Converter Technology Workshop for Coal-Gas Based Fuel Cell Power Plants January 24, 2007 at NIST Dr. Prasad Enjeti TI TI Professor Power Electronics Laboratory College
48V eco-hybrid Systems
48V eco-hybrid Systems Jean-Luc MATE Vice President Continental Engineering Services France President Automotech cluster www.continental-corporation.com Division Naming European Conference on Nanoelectronics
ABB micro inverters MICRO-0.25/0.3-I-OUTD, CDD and accessories 250 to 300 W
Solar inverters ABB micro inverters MICRO-0.25/0.3-I-OUTD, CDD and accessories 250 to 300 W MICRO The ABB MICRO inverter system is the perfect solution suitable for photovoltaic applications when flexibility
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase.
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL
Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor
International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 11 No. 2 Nov. 2014, pp. 445-449 2014 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/
Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary
Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary What: Duke Energy and EPRI Sponsored DC Powered Data Center Demonstration Using 380V DC Power When: 2010-2011 Where: Duke Energy
Topics. HVDC Fundamentals
Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission
EssPro Energy Storage Grid Substation The power to control energy
EssPro Energy Storage Grid Substation The power to control energy EssPro Grid gives you the power to control energy helping to keep smart grids in balance Maximizing the value and performance of energy
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
Additional Solar System Information and Resources
Additional Solar System Information and Resources Background information a. Roughly 400 schools in NJ already have solar systems, producing more than 91 MW, out of approximately 2500 K- 12 schools in NJ.
Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites
Power topic #NAPT-5516-EN Technical information from Cummins Power Generation Definition of effective metrics for evaluating the efficiency of hybrid power systems at telecom cell sites A system-level
Solar and Wind Energy for Greenhouses. A.J. Both 1 and Tom Manning 2
Solar and Wind Energy for Greenhouses A.J. Both 1 and Tom Manning 2 1 Associate Extension Specialist 2 Project Engineer NJ Agricultural Experiment Station Rutgers University 20 Ag Extension Way New Brunswick,
Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery
Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery Content Exact determination of the state of charge is
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
Half the cost Half the carbon
Half the cost Half the carbon the world s most efficient micro-chp What is BlueGEN? The most efficient small-scale electricity generator BlueGEN uses natural gas from the grid to generate electricity within
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
4.0 UPS dedicated to ICT for unmatched energy savings
4.0 UPS dedicated to ICT for unmatched energy savings Introducing UPSaver by Borri, a new modular UPS series for the ICT industry, totally configurable, quickly scalable, with high efficiency and low TCO.
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
ABB Inc. April 19, 2011 Slide 1
ABB Automation & Power World: April 18-21, 2011 Allen Austin - Solar Segment Manager North America, Low Voltage Products WLP-123-1-CEU Solar applications for low voltage products ABB Inc. April 19, 2011
ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw
Solar inverters ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw PV energy, combined with energy storage systems, can help increase self-consumption and energy selfsufficiency*. One of the biggest challenges
NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM
NetSure DC Power Solutions with esure High-Efficiency Technology DC Power for Business-Critical Continuity TM NetSure solutions with esure high-efficiency technology Our Efficiency Without Compromise promise
Energy saving technology for data centers. HVDC(High Voltage Direct Current) + 12V Server rack system
Energy saving technology for data centers HVDC(High Voltage Direct Current) + 12V Server rack system Green Solution Business Unit Environmental Technology Division NTT DATA INTELLILINK Corporation Copyright
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS Executive Summary IT managers who are used to implementing power protection for IT network or data
2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams 3000. Sunteams 4000 Sunteams 5000
Photovoltaic Inverter Specification Version 2.06 1500 2000 3000 4000 5000 Kinglong New Energy Technology Co.Ltd. Kinglong New Energy Technology Co.Ltd. specification 1.1. Introduction... 3 1.1.1. Environment...
Storage Battery System Using Lithium ion Batteries
Offices and schools Utilities / Renewable energy Storage Battery System Using Lithium ion Batteries Worldwide Expansion of Storage Battery System s Commercial Buildings Residential The Smart Energy System
When Do Solar Electric & Utility Back-Up Systems Make Sense?
When Do Solar Electric & Utility Back-Up Systems Make Sense? Oil & Gas Industry Presentation Proprietary Information 2010 SunWize Technologies When Do Solar Electric and Utility Back-Up Systems Make Sense?
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
Understand Hybrid Generator Battery Systems
Understand Hybrid Generator Battery Systems For off-grid applications powered by diesel generators, move to cyclic operation to save costs Telecommunications operators in Africa, India and other developing
Solar Energy. Airports Going Green Aimee Fenlon
Solar Energy Airports Going Green Aimee Fenlon 1 Renewable vs. Non-Renewable Electrical Generation Renewables: Source Advantages Disadvantages Solar PV No CO2; Needs no Fuel Intermittent no power at night,
for Energy Storage System, New & Renewable Energy
PCS Total Solution for Energy Storage System, New & Renewable Energy The product competitiveness of our customers will be more upgraded with PLASPO s power conversion technology The perfect power conversion
Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)
Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS) Josep Pou Antoni Arias Page 1 Outline 1. Renewable Energy Perspectives 2. Solar Photovoltaic (PV) 3. Wind Generation
Your own power station: For continuous power
Mass Combi Ultra Your own power station: For continuous power Compact and lightweight inverter/battery charger Seamless switching between generator and grid Separate second charger Integrated MPPT solar
Coslight Hybrid Power System with Solar
Coslight Hybrid Power System with Solar (Technical Manual Draft V1.0) Harbin Coslight Power Co., Ltd. Contents I. Overview... 2 Characteristics of System with Solar 2 II. Composition of System with Solar......
Prospects and Problems GPON Technology over Ethernet Technology
Prospects and Problems GPON Technology over Ethernet Technology Md. Hayder Ali [email protected] SANOG 23 Conference Thimpu, Bhutam Bangladesh : Name: People's Republic of Bangladesh Population: 164.4
Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM
ENERGY SOLUTIONS RESIDENTIAL STORAGE BATTERY SYSTEM MAKING SMART TOWNS, BUILDING SMART COMMUNITIES WHY PANASONIC? RESIDENTIAL STORAGE BATTERY SYSTEM The next evolution in solar energy solutions. Panasonic
A Solar Powered Cellular Base Station
Technical Whitepaper SolarConnect Energy management solution for Base Stations A Solar Powered Cellular Base Station Many people in emerging markets like India live in rural areas with limited access to
October 14 th, 2010 Global Business Dialogue on e Society Shinsuke Ito Infrastructure and Advanced Systems Promotion Office Manufacturing Industries
October 14 th, 2010 Global Business Dialogue on e Society Shinsuke Ito Infrastructure and Advanced Systems Promotion Office Manufacturing Industries Bureau Ministry of Economy, Trade and Industry -1- Smart
DC Microgrids. Christine Chan CSE 291 5/29/2013
DC Microgrids Christine Chan CSE 291 5/29/2013 1 Introduction What constitutes a DC microgrid? Power generation PV, wind, fuel cells Electrical storage batteries, super capacitors Distribution wiring and
CUTES Solar Power System
Solar Power System Solar power systems provide a continuous, reliable power solution that's easily deployed, cost-effective and requires little maintenance. Solar Power Systems are complete, fully integrated
MAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
PV And Storage: Solutions with Potential
EN PV And Storage: Solutions with Potential Energy on demand with the Sunny Central Storage Large-scale storages... support the growth of renewable energies complete diesel and solar diesel hybrid systems
WVC300 Micro-inverter solar grid system (Power line communications)
WVC300 Micro-inverter solar grid system (Power line communications) WVC300 Using IP65 waterproof streamline design, Can effectively prevent rainwater on the surface erosion, Built-in high-performance Maximum