SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp



Similar documents
ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

Electrical Code Regulation

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Please check with your local inspection authority for any additional requirements before installation.

Description. Lugs for NEMA Stud Kits a. (2) #6-350 kcmil SUK350TA (1) #2-600 kcmil SUK600TA. (2) # kcmil SUK1000TA.

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

MOBILE HOME SERVICE REQUIREMENTS GAS

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

Equipment. Metering. Metering Equipment 1. Contents

IRRIGATION PUMPING Table of Contents - Section 900

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE

2012 Edition Redbook 11.0 GENERAL DRAWINGS AND STANDARDS

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps

Temporary Power Outlet Panels

Short Circuit Current Calculations

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

Electric Service Standards

UNDERGROUND ELECTRIC TEMPORARY SERVICE PANEL

Electrical Service Guidelines

TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. GENERAL... Page 3

Electric Service Standards

Temporary Power Outlet Panels. Selection and Application Guide.

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRIC SERVICE HANDBOOK

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE

Requirements for the installation of. Electric Services. September 8, Specifications for Electric Installations

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features

Box and Conduit Fill Calculations

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

The Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure

Customer Metering and Services Guide

Approved Meter Sockets and Cabinets

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

Electric Service Requirements & Guidelines

Hyperlinks are Inactive

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

GUE, GUB Junction Boxes

Section 5 Meters and Service Entrance Equipment

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

TABLE OF CONTENT

Mobile Home Pre-Inspection Checklist

BRANCH CIRCUIT AND FEEDER REQUIREMENTS

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

SERVICE - GENERAL Residential, Commercial, Industrial

Generator DoCKInG StatIonS

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA

Customer Purchased Meter Sockets & Metering Equipment

CITY OF LOS ANGELES CALIFORNIA

MANUFACTURER S CERTIFICATE OF COMPLIANCE

UNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT Phone: Fax:

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

Indianapolis Power & Light Company

Section 10 Electric Switchboards: 0 Through 600 Volts

Residential Electrical Inspection. Checklist

THE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

Type 1, 3, & 3R Enclosures

Residential Electric Service Handbook

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

800 Communications Circuits

8146/5 Series Breaker Panelboards

Step 1: Application Instructions

CHAPTER 2 EXAMPLES AND TABLES

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

Residential Electrical Inspection. Checklist

METERING INSTALLATION REQUIREMENTS

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Grounding & Bonding Why it is done And How to Install Properly

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

SPEEDFAX TM 2011 Load Centers & Circuit Breakers Contents

Electronic Watt-Hour Meters Catalog

Electric Service Manual

Requirements for Electrical Installations

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

18 AWG thru 8 AWG Not greater than 100/30 100/30. 6 AWG thru 1/0 AWG Not greater than 200/60 100/30

HIGHLAND VALLEY SUPPLY, INC STANDARD TERMS AND CONDITONS OF SALE

For 100 Amp Automatic Transfer Switch/Load Center Models: 10 Circuit, 12 Circuit and 16 Circuit. Installed with 7, 10, 13 and 16kW Generators.

Least Cost Cable System. Strategies to Reduce Cable and Infrastructure Costs When Transitioning to an All Conduit Systems

Issued E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

Residential Electrical Inspection Checklist

Guide for Electric Service and Meter Installations

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Electric Service Guide for Residential Construction

Power Outlet Panels. Product Guide

MCC Ratings. Voltage Rating

Electric Service and Meter Installations Manual SCANA Corporation 2013

Electric Service Guide for Residential Construction

Distribution Dry Type Transformers

Applying For New or Revised Electric Service

GENERAL ELECTRICAL REQUIREMENTS

Transcription:

SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS REVISION 10-01-14 ORIGINATED 03-94 PREVIOUS NUMBER ER 1-220-B, 07-12-93 ER 19-750, 03-21-94 ER 19-755, 03-21-94 Updated catalog numbers for single phase 4 Jaw 320/400 Amp meter sockets, general revisions to others, and added Note 7.5. REFERENCE: Indiana Electrical Code / National Electrical Code (IEC/NEC), latest revision ER 5-500, 5-550, 7-500, 13-230, latest revision UL 414, latest revision ANSI C12.7, latest revision SPECIFICATION: TYPICAL UNDERGROUND INSTALLATION

07-01-15 PAGE 2 OF 6 SERVICE ENTRANCE - UNDERGROUND 1. GENERAL: 1.1 Residential electric and gas meters should both be located on the same side of the home within the front 1/3 to aid meter reading, testing and service, and to aid emergency response in the event of a fire or some other hazardous condition. 1.2 The riser conduit shall be installed in the left-most or right-most, bottom knockout of the meter box. For close lot lines, concrete, asphalt, or sites where our trenching equipment can not access; conduit shall be installed by the customer to a clear location in which NIPSCO will be able to install the service. 1.3 The service disconnecting means shall be installed at a readily accessible location nearest the point of entrance of the service entrance conductors. 1.4 Bonding bushings and jumpers shall be used to maintain electrical continuity to service equipment enclosures when the entire concentric knockout is not removed. 1.5 For grounding, refer to ER 7-500. 1.5.1 Ground rods and ground wires shall be installed a minimum of 24" away from the riser pipe to permit the installation and maintenance of service cables. 1.6 For larger service sizes or long service runs, customer shall check with Local Operating office, for required riser conduit size, and meter box needs. For conduit lengths in excess of 10' long, or in the case of conduit systems (any including elbows and/or couplings), refer to EU 2-160, for cable pulling requirements and conduit sizes. 1.7 Conduit & Conductor Recommendations: Service Entrance Service Size Conduit (per IEC/NEC) Service Riser Entrance Run Service Entrance Conductors (See Notes below) Residential 1φ 3W 120/240V All Other Services Grounding (Cu Only) 100 Amps 2 Inch (See 1.6) 1 ½ or 2 Inch #4 Cu #3 Cu #2 Al #1 Al #8 200 Amps 2-½ Inch (See 1.6) 2 Inch 2/0 Cu 3/0 Cu 2 ½ Inch 4/0 Al 250 KCM Al #4 320/400 Amps 3 Inch (See 1.6) 3 Inch 400 KCM Cu 500 KCM Cu 3 ½ Inch 600 KCM Al 700 KCM Al 1/0 Note: Approved service entrance cable, with weather-proof fittings, may be used between socket and the general service disconnect, where permitted by local authority. All recommendations for conductor sizes assume a 75EC temperature rating. Larger conductor sizes may be necessary if lower temperature ratings exist. Refer to IEC/NEC 310-16 for proper conductor sizes, in this case. The following are the recommended insulation types, based on 75EC minimum temperature rating: RH, RHH, RHW, THHW, THW, THWN, THHN, XHHW, USE.

SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 3 OF 6 1.8 All meter sockets shall meet the following specifications, unless otherwise stated below. 1.8.1 Meter sockets shall be designed for use with standard detachable type watthour meters. 1.8.2 Sockets shall meet the requirements in AEIC, EEI, NEMA Standards for watthour meter sockets. 1.8.3 Meter sockets shall have a swing style latch, which will accept padlock or wire style seal. 1.8.4 Meter sockets shall be made of aluminum alloy or galvanized steel. 1.8.5 Meter sockets shall be of the ringless type. 1.8.6 Meter sockets shall be UL listed. 1.8.7 Meter sockets shall be provided with concentric knockouts in the back, sides and bottom. Knockouts shall be sized to accommodate the conduit recommendations in Spec 1.7. 1.8.8 Meter sockets shall be provided with a by-pass of the manual, horn or lever type, so arranged that the meter socket cannot be sealed with the by-pass on. 1.8.9 Meter sockets shall be provided with a grounding connector for a #6 conductor. 1.8.10 Meter sockets shall be plainly marked with the manufacturer s name, catalog number and electrical ratings. 1.8.11 Meter sockets shall be rated at a minimum of 200 amps. 1.8.12 Meter sockets shall be a minimum of 11 inches wide. Note: Larger sized boxes or side wire boxes will be needed for long service runs. (See Spec 1.6) 1.8.13 All sockets will have the following conductor terminations on the line side: 1.8.13.1 200 Amp - lugs to fit #2 through #4/0 (minimum) conductor Note: Lugs to fit 350 KCM will be needed in boxes used for long service runs. (See Spec 1.6) 1.8.13.2 320 Amp - d Diameter studs 1.8.14 Pedestal style meter sockets are approved for use, where noted. They shall meet all above mentioned specifications (where applicable), unless otherwise stated below. 1.8.14.1 Pedestal style meter sockets shall be a minimum of 8" wide. 1.8.14.2 Pedestal style meter sockets shall be installed with a height of 3'-5' to the top of the meter. 1.8.14.3 Pedestal style meter sockets shall be installed so 18" of the enclosure is beneath grade.

07-01-15 PAGE 4 OF 6 SERVICE ENTRANCE - UNDERGROUND 2. 4 JAW - 200 AMP: 2.1 Used for the following services: 2.1.1 120 volt, 1 phase, 2 wire 2.1.2 120/240 volt, 1 phase, 3 wire 2.2 Approved Sockets 2.2.1 Any socket, rated for 200 amps, which meets the specifications in 1.8 above, including pedestal style meter sockets (see spec 1.8.14). 2.2.2 Optional Universal All-In-One Meter Main which has a disconnect and breaker positions built in. See table below. 200 Amp U5168-XTL-200-KK 200a, 120v, 1ph, 2w 200a, 120/240v, 1ph, 3w

SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 5 OF 6 3. 4 JAW - 320/400 AMP 3.1 Used for the following services: 120/240 volt, 1 phase, 3 wire 3.2 Approved Sockets 3.2.1 Sockets shall meet all specifications in 1.8 above. 3.2.2 The right line side location of the 320 amp socket box shall be provided with a reduced jaw. 3.2.3 Meter sockets shall be supplied with a label designating "Use 320 Amp Meter Only". 3.2.4 Bypass shall be of the manual, jaw release, lever type. 3.2.5 Approved for use: Landis & Gyr 48104-82WI Type HQ-4SWT U3000-O-K3L-K2L U1748 O -WI (See Note 7.1) U5890-X-2/200-BL (See Note 7.2) U5059-X-2/200-K3L (See Note 7.2) 320/400a, 120/240v, 1ph, 3w Durham T-H4309 (See Note 7.3) 4. 5 JAW - 200 AMP: 4.1 Used for the following services: 4.1.1 240 volt, 3 phase, 3 wire (B phase grounded) 4.1.2 120/208 volt, 1 phase, 3 wire (contact Local Operating Office for information) 4.2 Approved Sockets 4.2.1 Sockets shall meet all specifications in 1.8 above. 4.2.2 Sockets shall be provided with a removable ground strap on the fifth jaw. 4.2.3 Bypass shall be of the manual, jaw release, lever type. 4.2.4 Approved for use: Landis & Gyr 40405-02QG U9551-O U9108-O (See Note 7.5) U5168-XLT-200-KK-5T (See Note 7.4) 200a, 240v, 3ph, 3w Durham UT-H5213.. (See Note 7.3)

07-01-15 PAGE 6 OF 6 SERVICE ENTRANCE - UNDERGROUND 5. 7 JAW - 200 AMP: 5.1 Used for the following services: 120/208 volt, 3 phase, 4 wire 5.2 Approved Sockets 5.2.1 Sockets shall meet all specifications in 1.8 above. 5.2.2 Sockets shall be provided with a strap to connect the neutral to the socket ground jaw. 5.2.3 Bypass shall be of the manual, jaw release, lever type. 5.2.4 Approved for use: Landis & Gyr 40407-02QG U9701-O U9107-O (See Note 7.5) Durham UT-H7213... (See Note 7.3) 200a, 120/208v, 3ph, 4w 6. 7 JAW - 320/400 AMP: 6.1 Used for the following services: 120/208 volt, 3 phase, 4 wire 6.2 Approved Sockets 6.2.1 Sockets shall meet all specifications in 1.8 above. 6.2.2 The right line side location of the 320 amp socket box shall be provided with a reduced jaw. 6.2.3 Meter sockets shall be supplied with a label designating "Use 320 Amp Meter Only". 6.2.4 Bypass shall be of the manual, jaw release, lever type. 6.2.5 Approved for use: Landis & Gyr 44707-02 U2594-X-K7 320/400a, 120/208v, 3ph, 4w 7. NOTES: 7.1 Pedestal style socket needs extension kit S1848. (See spec 1.8.14) 7.2 Optional socket for 120/240 volt, 1 phase, 3 wire, 320 Amp. Has 2-200 Amp main disconnects built in enclosure. 7.3 Provided with hub plate cover 7.4 Optional socket for 120/208 volt, 1 phase, 3 wire, 200 Amp. Has main disconnect and breaker positions built in enclosure. 7.5 Pedestal style socket needs extension kit S3488 (See spec. 1.8.14)