1

2 Table of Contents SECTION INTRODUCTION... 5 SECTION DEFINITIONS... 7 COMPANY... 7 CUSTOMER... 7 OVERHEAD SERVICE DROP... 7 UNDERGROUND SERVICE DROP... 7 SERVICE ENTRANCE... 7 SERVICE EQUIPMENT... 9 SERVICE HEAD... 9 READILY ACCESSIBLE... 9 RECREATIONAL VEHICLE... 9 MANUFACTURED HOME... 9 SECTION GENERAL INFORMATION APPLICATION FOR SERVICE CONTACT OF COMPANY REPRESENTATIVES DEPOSITS, CHARGES AND/OR CONTRACTUAL REQUIREMENTS TEMPORARY SERVICE RECREATIONAL VECHICLE PARK AND MANUFACTURED HOME SERVICES INSPECTION METERING TAMPERING NUMBER OF SERVICES AND METERS REPLACEMENT OF SERVICES CONNECTIONS SECTION SERVICE AVAILABLE GENERAL RESIDENTIAL AND FARM SERVICE COMMERCIAL AND INDUSTRIAL SERVICE SECONDARY VOLTAGE SERVICE PRIMARY VOLTAGE SERVICE SECTION OVERHEAD SERVICE GENERAL POINT OF ATTACHMENT SERVICE DROP CONDUCTOR CLEARANCES TABLE 5-1 CLEARANCES CLEARANCE FROM EXISTING COMPANY FACILITIES ATTACHMENT POINT CLEARANCE AUXILIARY DEVICES CUSTOMER S METER POLE

3 SECTION UNDERGROUND SERVICES UNDERGROUND RESIDENTIAL SERVICES UNDERGROUND COMMERCIAL/INDUSTRIAL SERVICES LOCATION OF METERING EQUIPMENT ROUTING OF UNDERGROUND SERVICES INSTALLATION OF UNDERGROUND SERVICES UNDERGROUND SERVICE IN THE DOWNTOWN EVANSVILLE BUSINESS DISTRICT UNDERGROUND PRIMARY SERVICE SECTION SERVICES TO RECREATIONAL VEHICLE PARKS AND MANUFACTURED HOME COMMUNITIES GENERAL RECREATIONAL VEHICLE PARKS MANUFACTURED HOME COMMUNITIES OVERHEAD SERVICES MANUFACTURED HOME COMMUNITIES UNDERGROUND SERVICE INDIVIDUAL MANUFACTURED HOMES SECTION SERVICE ENTRANCE WIRING GENERAL OVERHEAD SERVICES UNDERGROUND SERVICES EMERGENCY GENERATORS SECTION METERING GENERAL SECONDARY METERING EQUIPMENT PRIMARY METERING EQUIPMENT SECTION CUSTOMERS UTILIZATION EQUIPMENT PROTECTION OF SERVICE FLUCTUATING OR INTERMITTENT LOADS SIGNAL SYSTEMS LOAD BALANCE SINGLE PHASE SERVICE MOTORS PROTECTION MOTOR SINGLE PHASE MOTORS THREE PHASE MOTORS ILLUSTRATION INDEX Figure Figure

4 Figure 3 (Removed) Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure

5 Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure

6 SECTION 1 INTRODUCTION 1.01 This document is issued by Vectren Energy Delivery of Indiana, Inc. as a reference and guide to Customers, Contractors, Electricians, Engineers, Architects, and others planning electrical installations for residential or small commercial and industrial properties to be supplied with electricity from the lines of the Company This manual is a supplement to, and is not intended to replace, the GENERAL TERMS AND CONDITIONS APPLICABLE TO ELECTRIC SERVICE as published by the Company, in it s tariff, and approved by the Indiana Utility Regulatory Commission The recommendations and rules set forth herein are generally sufficient to answer questions concerning a majority of the installations within its scope. When questions arise which are not covered by this booklet, the Company will be pleased to furnish information on them or any matter pertaining to its service When planning electrical installations for larger commercial or industrial establishments, it will be necessary to contact the Company for detailed information on service requirements All electrical installations shall be made in accordance with the specifications herein, which meet or exceed the requirements of the National Electrical Code (NEC) and the National Electrical Safety Code (NESC). Any State, county, or municipal laws and regulations that may be in effect in the area in which the installations are made must be followed The Company reserves the right to disconnect, or the right to refuse to connect any service that does not comply with any rules or regulations applicable to the Company s service or which it deems to be hazardous to persons or property. 5

7 1.07 The Company will not be responsible for the adequacy, safety, or satisfactory performance of the equipment and facilities installed by the Customer. 6

8 SECTION 2 DEFINITIONS COMPANY 2.01 The word Company as used throughout this booklet refers to Vectren Energy Delivery of Indiana, Inc. CUSTOMER 2.02 The word Customer means either a present or prospective user (or his representative) of the Company s electric service. OVERHEAD SERVICE DROP 2.03 The portion of the service installation consisting of the overhead supply conductors between the Company s last pole or other aerial support and the first point of attachment to the Customer s structure or support. UNDERGROUND SERVICE DROP 2.04 That portion of the Company s service installation from the point of last connection to the Company s transformer or secondary vault or pedestal to the meter socket consisting of supply conductors buried under the Customer s premises. SERVICE ENTRANCE 2.05 The conductors and other equipment in that portion of the service installation between the point that the Company s overhead or underground service drop is attached to the Customer s structure or support and the service equipment. All 7

9 wire, cable, service raceways, meter mounting devices, fittings, etc. shall be considered as a part of the service entrance. 8

10 SERVICE EQUIPMENT 2.06 An approved service switch (or switches) or other approved protective and disconnecting devices, located near the point of entrance of the supply conductors to a building, constituting the main control and means of disconnecting the supply to that building. SERVICE HEAD 2.07 A device attached to conduit, other raceways or service entrance cable near the point that the service entrance conductors are attached to the service drop. The device is sometimes referred to as a Weather Head or Entrance Cap. READILY ACCESSIBLE 2.08 Capable of being reached quickly and safely for operating, renewal, or inspections, without the necessity of climbing over or removing obstacles or resorting to portable ladders, chairs, etc. RECREATIONAL VEHICLE 2.09 A vehicle for recreational use and not designed for year-round occupancy. Normally, special equipment is not required for towing. MANUFACTURED HOME 2.10 A home manufactured at a factory and then moved to a permanent home site. Generally, special equipment is required for towing. 9

11 SECTION 3 GENERAL INFORMATION APPLICATION FOR SERVICE 3.01 Application for service for either a new installation or additional service to an existing installation must be placed with the New Business Service Center of the Company at the earliest possible date, and before any work is started. An early application is necessary to assure that the type of service desired is available and to give the Company adequate time to determine the facilities required, to secure necessary Permits and/or Right-of-Way, and to construct the facilities required to provide the service requested by the Customer. CONTACT OF COMPANY REPRESENTATIVES 3.02 Initiation of contact with Company representatives regarding new or reworked service should be made by telephoning the Business Service Center. Followup contact should be directed to the representative assigned to handle the Customer s request. Business Service Center 20 N.W. Fourth Street Evansville, Indiana Phone: or DEPOSITS, CHARGES AND/OR CONTRACTUAL REQUIREMENTS 3.03 The Company may require that an applicant make a meter deposit, a contribution in aid of construction, or execute a contract setting forth the terms and conditions under which the service desired will be provided. In general, the 10

12 details of these matters will be explained at the time the Customer makes application for service. However, in many cases, costs to provide the service requested by the Customer will not be known at the time application is made. In this event, contract requirements will be completed later with the Customer and before service is extended. TEMPORARY SERVICE 3.04 The Company has special requirements for temporary service and must be consulted before each installation. After a period of time the service may be investigated by the Company to determine the status of its usage. The Company's structural requirements for temporary service installations to be used in conjunction with construction work (often referred to as temporary saw service ) are shown in Figure 1 for overhead service and Figure 2 for underground service. RECREATIONAL VECHICLE PARK AND MANUFACTURED HOME SERVICES 3.05 The Company has special requirements for service to recreational vehicle parks and manufactured homes, and should be consulted in each case. Before service will be supplied to this type of customer, the Customer s facilities must conform to State, County, or Municipal Codes that may be in effect. Refer to Section 7 and to Figures 11, 19, and 20 for construction details. INSPECTION 3.06 In some areas, local law requires that all new or additional wiring on the Customer s premises be inspected and approved by an authorized electrical inspector before being connected for service. It is the Customer s obligation to arrange and pay for whatever inspection is required and to ensure that the Company receives notification of inspection approval. 11

13 METERING TAMPERING 3.07 Tampering with the meters or with conductors carrying unmetered current, and the unauthorized breaking of the Company s seal is prohibited by law and will not be tolerated by the Company. Violators are subject to prosecution and statutory penalties. NUMBER OF SERVICES AND METERS 3.08 Ordinarily, the Company will install only one service drop to a building for each class of service rendered. If the building is occupied by one tenant, only one watthour meter for each class of services rendered will be installed. If occupied by several tenants, each one will become a customer of the Company and a meter will be installed for his respective class of service. In such cases all meters shall be grouped at a central location. Consult the NEC for appropriate service equipment. REPLACEMENT OF SERVICES 3.09 When a Customer desires to replace an existing service with a larger service or to relocate the attachment of the service drop on the Customer s premises, the Company shall be consulted before such work is started in order to ensure that the proposed changes shall conform to the latest editions of applicable codes or to the requirements of the Company relative to clearances, meter location, grounds, etc., as set forth in this manual. Permanent service connections shall not be made until such requirements are met. CONNECTIONS 3.10 All permanent connections between the Company s facilities and the Customer s wiring will be made by the Company, and unauthorized permanent connections will not be permitted. Temporary connections, subject to the terms 12

14 of Article 3.09, may be made by a licensed electrician to reduce the duration of service interruption to the Customer. Upon completion of the temporary connections, the Customer (or the Customer s electrician) shall ensure that the Company s Business Service Center representative handling the respective request receives notification of the completion of the temporary connections. The Company will then schedule installation of permanent connections. 13

15 SECTION 4 SERVICE AVAILABLE GENERAL 4.01 All electric service supplied by the Company is 60 Hertz alternating current. The voltage and the number of phases, which will be supplied, depend upon the location, character, and size of the Customer s load. The Customer should consult the Business Service Center regarding the type of service which will be provided before proceeding with the purchase of equipment and the installation of wiring. RESIDENTIAL AND FARM SERVICE 4.02 General, residential and farm services will be supplied single phase, three wire at a nominal 120/240 volts. Under special conditions, which must be established through consultation with Company representatives, other secondary voltage services may be supplied. COMMERCIAL AND INDUSTRIAL SERVICE 4.03 Service normally available to service commercial and industrial loads may be single phase, three-wire, or three phase, three- or four-wire. The Company should always be consulted concerning the exact characteristics of the type of service available. 14

16 SECONDARY VOLTAGE SERVICE 4.04 The following secondary voltage services are normally supplied by the Company: NOMINAL PHASE WIRES VOLTAGE SERVICE AVAILABLE FOR a.) /240 Small lighting and/or power loads. b.) /208 Small lighting and/or power loads. (Downtown Evansville Only) c.) /480 Small power loads. d.) Small and medium power loads. e.) /208 Large lighting and/or power loads. f.) /240 Small lighting and/or power loads. g.) Large power loads. h.) /480 Large lighting and/or power loads. PRIMARY VOLTAGE SERVICE 4.05 Service at primary voltage is available to customers using large amounts of energy. The Company s Business Service Center should be consulted regarding the availability of this service. 15

17 SECTION 5 OVERHEAD SERVICE GENERAL 5.01 Where overhead service is requested the Company will furnish and install an adequate overhead service drop from the Company s pole or other aerial support to the point of attachment on the Customer s structure. POINT OF ATTACHMENT 5.02 The Company shall be consulted and the point where the overhead service drop will be attached to the Customer s structure will be located by mutual agreement between the Company and the Customer. If the point of attachment is to be located on a Customer s building, then it shall be located on the building s exterior wall or on a support extending vertically above an exterior wall. The point of attachment should be located on the side of the building nearest Company facilities and shall be readily accessible to Company personnel. Where a Customer requests the connection of new service entrance conductors to an existing overhead service drop that crosses over the roof of the building, the connection will be allowed as long as the service drop meets or exceeds all NESC clearance requirements. If the existing drop does not meet or exceed NESC clearance requirements, then the Customer shall route the service riser(s) and service entrance conductors to an acceptable attachment point on an exterior wall of the building or on a supporting structure extending vertically above the exterior wall No more than one overhead service drop will be run to a building except as provided by Article of the National Electrical Code. Exceptions include fire pumps, emergency lighting, different voltages and other conditions. Where 16

18 two or more service drops are required for the delivery of different classes of service to a Customer s premises, they shall be installed at the same location unless otherwise specified by the Company The Customer shall provide a safe and adequate anchorage to support the overhead service drop. Figures 12, 13, and 14 show typical ways of providing this support The Customer shall install the necessary facilities for mounting and securing the service drop attachments. The Company normally will furnish the service drop attachment hardware for the Customer to install. SERVICE DROP CONDUCTOR CLEARANCES 5.06 The point of attachment of an overhead service drop to a structure shall be equal to or greater than the minimum height requirements specified in paragraph The minimum height at the point of attachment shall be increased as needed to provide the minimum clearances indicated in TABLE 5-1. The Company s Layout and Design representatives can provide the amount of sag in the service drop conductor to assist the Customer in determining the minimum acceptable height of attachment. The maximum height of such attachments should not exceed (30) feet unless a greater height is necessary to provide minimum clearances as listed in TABLE 5-1. NOTE: The clearances listed in TABLE 5-1 are per the latest edition of the National Electrical Safety Code (NESC). The clearances listed are a partial listing of the complete NESC that should be pertinent to most construction situations encountered. The Company shall be consulted regarding situations that are not addressed by TABLE 5-1. Footnotes recognizing significant exceptions to the basic clearances of TABLE 5-1 follow the tabular data. The Company may be consulted to identify other exceptions that might change the requirements listed and to clarify the application of the TABLE. 17

19 TABLE 5-1 CLEARANCES Nature of surface underneath overhead service drop conductors Clearances (ft) Type I Conductor Clearances (ft) Type II Conductor Railroad tracks Roads, streets, and other areas subject to truck traffic Residential driveways and other areas not subject to truck traffic Other land traversed by vehicles such as cultivated, grazing, forest, orchard, etc. Water areas not suitable for sail boating or where sail boating is prohibited Swimming Pools (1) See Figures 26&30 Clearance from the water level, edge of pool, base of diving platform, or anchored raft Clearance in any direction to the diving platform or tower 22.5(2) (2) 15.0 Clearance of supply conductors passing by but not attached to buildings and other installations Buildings (See Figures 32 and 33) Horizontal Vertical- Above or below roofs or projections not accessible to pedestrians Vertical- Above or below roofs or projections accessible to pedestrians Signs, chimneys, radio television antennas, tanks, and other installations not classified as buildings or bridges. (See Figures 32 and 33) Horizontal-Areas without catwalk Horizontal-Areas beside catwalk Vertical-Areas without catwalk Vertical-Areas over catwalk

20 Supply Conductor Type Type I - Supply cables of 0 to 750V that are insulated, nonshielded, and supported on and cabled together with an effectively grounded bare messenger. Type II - Open supply cables of 0 to 750V. Footnotes (1) This rule does not apply to a pool fully enclosed by a solid or screened permanent structure. (2) This rule does not apply when the supply conductors are 10 feet or more from the edge of the pool, diving platform, or diving tower. CLEARANCE FROM EXISTING COMPANY FACILITIES 5.07 It is the Customer s responsibility to notify the Company of any clearance conflicts between existing Company facilities and the Customer s new or planned buildings and/or other structures. Figures 26 to 34 illustrate the basic National Electrical Safety Code clearance requirements. It should be noted that the horizontal clearances listed are to conductors that could be displaced by wind. Therefore, the Customer shall notify the Company before installing buildings or other structures at a distance of less than 20 feet from Company distribution facilities or 40 feet from Company transmission facilities so that the exact clearance requirement can be determined. ATTACHMENT POINT CLEARANCE 5.08 Customers shall position the service drop attachment point such that the service drop conductors (less than 600 V) will have a clearance of not less than 3 feet in any direction from windows, doors, porches, fire escapes, or similar locations. Exceptions allowing lessor clearances as illustrated in Figure 37 involving conductors above the top level of windows or near windows designed 19

21 not to open must be approved by the Company prior to installation of the attachment point by the Customer. Figure 35 illustrates the clearance requirements for attachment of service drop conductors to through-the-roof service masts for various service voltage levels and building construction configurations. AUXILIARY DEVICES 5.09 The Customer shall not attach auxiliary devices or supplemental equipment of any kind to the Company s service drop wires. CUSTOMER S METER POLE 5.10 Where the Customer s structure to which the service drop is attached is a pole furnished and installed by the Customer, such pole shall be properly treated with a wood preservative, set at least five feet in the ground, and be of sufficient height to provide the required service drop clearance as outlined in paragraph 5.06 (See Figures 4 through 11) Any connections to the meter pole by the Customer, except the service entrance wiring and pole top disconnect switches (See Figure 7), must be made at least 12 inches below the point of attachment of the Company s service drop. 20

22 SECTION 6 UNDERGROUND SERVICES UNDERGROUND RESIDENTIAL SERVICES 6.01 Where underground service is requested for a single-unit dwelling, the Company will furnish, install, and maintain an adequate underground service drop from the Company s overhead or underground source to a meter socket mounted on the Customer s building wall (See Figure 15). For farmsteads or other similar customers where a load-center metering point is desired by the Customer, the metering equipment may be mounted on a Company approved pedestal as shown in Figures 18 and Where underground service is requested for a multi-unit dwelling with two to six units between firewalls, the Company will furnish, install, and maintain an adequate underground service drop from the Company s overhead or underground source to the bus connection point of a gang meter socket mounted on the Customer s building wall (See Figure 16) Where underground service is requested for a multi-unit dwelling with more than six units between firewalls, the Company will furnish, install, and maintain an adequate underground service drop from the Company s overhead or underground source to the Customer s main disconnect switch connected directly ahead of a gang meter socket. The switch and gang meter socket shall be installed on the Customer s building wall (See Figure 17). 21

23 UNDERGROUND COMMERCIAL/INDUSTRIAL SERVICES 6.04 Where underground service is requested for small commercial developments for which the Company determines that self-contained metering is appropriate, the Company will furnish, install, and maintain an adequate underground service drop from the Company s overhead or underground source to the Customer s meter mounting equipment (<480 V service) or service disconnect switch (480 V service) mounted on the Customer s building wall. The metering equipment shall be arranged the same as the residential requirements listed in 6.01 through 6.03 depending on the number of metered units per service drop (See Figures 15, 16, and 17) Where underground service is requested for commercial/industrial customers for which the Company determines that instrument transformer metering is appropriate, the Company will furnish, install, and maintain an adequate underground service drop from the Company s overhead or underground source to the meter mounting equipment (or to the Customer s service disconnect switch if the number of services > six) mounted on the Customer s building wall or inside the Customer s enclosed switchgear (See Figures 22 and 24). As an option for certain classes of service the Customer may extend his service entrance conductors to the Company s pad-mounted transformer located outside the Customer s building wall. In such cases, instrument transformers shall be mounted inside the secondary compartment of the transformer and the watt-hour-demand meter shall be mounted on the building wall or optional pedestal supplied and installed by the Customer (See Figure 23). The Customer shall terminate each service entrance conductor with a one or two-hole lug as directed by the Company. The Company will complete the connection by bolting the lugs to the transformer secondary terminal spades. 22

24 LOCATION OF METERING EQUIPMENT 6.06 The Company shall be consulted and the metering equipment will be located by mutual agreement between the Company and the Customer. If the metering point is attached to the Customer s building, then it should normally be located on the side of the building nearest to existing Company facilities. The metering equipment shall be situated such that it is readily accessible to Company personnel. ROUTING OF UNDERGROUND SERVICES 6.07 The Customer will be responsible for locating all known Customer-owned underground facilities in advance of route selection of the underground service drop by the Company. The Customer shall also inform the Company of any planned future activities such as building additions, landscaping, swimming pool installation, etc. that may interfere with Company service drop cables The Customer shall extend conduit (size and number specified by the Company) from the metering equipment to an underground point not covered by a permanent structure (sidewalk, patio, driveway, etc.)(see Figure 15, 16, 17, and 22). INSTALLATION OF UNDERGROUND SERVICES 6.09 The Customer will be responsible for providing a grade within six inches of the final grade along the proposed underground service drop route prior to the Company s scheduled time of installation. The Customer shall also keep the service drop route clear of any building materials or other obstructions to Company installation equipment. 23

25 UNDERGROUND SERVICE IN THE DOWNTOWN EVANSVILLE BUSINESS DISTRICT 6.10 The downtown Evansville Business District, generally bounded by Sycamore Street, Eighth Street, Locust Street, and Riverside Drive, or as may be changed by future requirements, is serviced by underground distribution. Notification of new loads or changes in existing loads in this area should be made to the Company s Business Service Center before any equipment is ordered, purchased, or installed New services and replacement services in the downtown Evansville area shall be installed underground whenever it is practicable. The Company will install the necessary raceway to the property line of the Customer. The Customer will install raceway entrances through his building wall to the property line for connection with the raceway installed by the Company. The Company will furnish and install the service conductor to the Customer s service equipment. Service entrance locations shall be established by mutual agreement of the Company and the Customer. UNDERGROUND PRIMARY SERVICE 6.12 Where primary voltage underground service is requested by large commercial/industrial customers, the Company will furnish, install, and maintain an adequate source from the Company s primary distribution facilities to the Customer s metering structure or enclosed switchgear. The primary metering arrangement for this service will be determined by mutual agreement between the Customer and the Company on an individual basis. 24

26 SECTION 7 SERVICES TO RECREATIONAL VEHICLE PARKS AND MANUFACTURED HOME COMMUNITIES GENERAL 7.01 Services to Recreational Vehicle Parks and Manufactured Home Communities are subject to negotiation between the Developer and the Company. The Company should be consulted before plans are finalized in order to determine availability, type of service, and the extent of charges necessary to supply services. It will be necessary also, before such services are supplied, to confirm that the facilities to be serviced conform to existing State, County, and Municipal Codes. Meters are normally located away from the home on a meter pole or pedestal; however, a meter may be mounted directly on a manufactured home if either of the following is true: 1. The meter socket is attached to the home at the factory and the home meets HUD specifications before it is shipped. 2. There is a letter from the manufacturer stating that a meter mounted on the home exterior is permissible, a manufacturer s representative installs the meter socket at the building site, and the home meets HUD specifications. RECREATIONAL VEHICLE PARKS 7.02 Services to Recreational Vehicle Parks shall be furnished at one or more grouped metering locations which shall be determined by mutual agreement between the Company and the Customer and subject to conditions outlined in paragraph

27 MANUFACTURED HOME COMMUNITIES OVERHEAD SERVICES 7.03 When overhead services are desired in Manufactured Home Communities the services will be installed, subject to conditions outlined in paragraph 7.01, in easements provided by the Developer and accepted by the Company. Services will be extended to meter poles also provided by the Developer. Length of service drops shall not exceed 75 feet. Refer to Figures 5, 6, and 11 for pole and clearance specifications. MANUFACTURED HOME COMMUNITIES UNDERGROUND SERVICE 7.04 When desired by the Developer (Customer) and subject to conditions outlined in paragraph 7.01, underground services will be supplied from Company facilities. Primary voltage conductor will be buried in easements provided by the Developer and services will be supplied from pad-mounted transformers, which will be installed and maintained by the Company. Underground service drop conductor will be extended to meter pedestals, which shall be placed on fiberglass ground sleeves. The conductor and meters will be furnished and installed by the Company. The pedestals and ground sleeves will be supplied and installed by the Developer. Refer to Figures 19, 20, and 21 for specifications covering pedestal and ground sleeve installations. INDIVIDUAL MANUFACTURED HOMES 7.05 Where service is requested for an individual manufactured home, the Company will furnish, install, and maintain either an adequate overhead or underground service drop to a free standing metering point. Refer to Figures 5, 6, and 11 for pole and clearance specifications for an overhead service drop to a Customer owned meter pole. Refer to Figures 19, 20, and 21 for specifications regarding pedestal and ground sleeve installations for an underground service drop to a Customer installed meter pedestal. 26

28 SECTION 8 SERVICE ENTRANCE WIRING GENERAL 8.01 The Customer should consult the Company before determining the location of service equipment for new construction or for changes in existing buildings where a relocation of service equipment is proposed. This may prevent delay and expensive reconstruction. See paragraphs 5.02 and Service entrance conductors shall consist of: (a) Approved service entrance cable; or (b) Approved conductors in galvanized rigid steel conduit, intermediate metal conduit, aluminum conduit, electrical metal tubing or other service raceway meeting approval of the Company regulations and the National Electrical Code Unmetered conductors will not be permitted in any conduit, wiring raceways, pull box, distribution cabinet or other similar device containing metered conductors Where the Customer requests a class of service that is provided from a Company secondary voltage source of supply that has a grounded neutral, the Customer is obligated to extend a grounded neutral service entrance conductor sized in accordance with the NEC from the meter mounting device (or from the weatherhead point of connection on overhead services) to the Customer s service entrance equipment with each set of service entrance conductors installed. 27

29 8.05 The Customer s service entrance equipment shall include a means of disconnect of the Customer s load from the Company s distribution system. Such service equipment may be a fused switch or circuit breaker. It must be of a type listed by the Underwriters Laboratories, Inc., as suitable for service equipment. It shall be externally operable with an interrupting capacity sufficient for the voltage employed and for the fault current, which must be interrupted. The service entrance equipment shall be readily accessible and located near the point the service conductors enter the building. When located outdoors, the disconnecting means shall be of either weatherproof construction or mounted inside a weatherproof box A service entrance shall consist of not less than three (3) No. 3 AWG copper wires or equivalent, except: (a) (b) (c) Three (3) No. 6 AWG copper wires or equivalent will be approved where services are being changed from a 30-ampere service to a 60-ampere service. Three (3) No. 8 AWG copper wires or equivalent will be approved for service entrance to telephone booths, railroad signals, traffic signals, sign boards and other similar small installations. Three (3) No. 8 AWG copper wires or equivalent will be approved for the electric water heater circuit from the meter enclosure to the Customer s service equipment Service entrance conductors for new single family residences shall have not less than 100 amperes nominal capacity. Installations having only one branch circuit shall have not less than 60 amperes nominal capacity. For individually metered multi-unit complexes, conductors serving individual units shall also meet this requirement. 28

30 8.08 All meter sockets, meter boxes, instrument transformer enclosures, service equipment boxes, metal conduits and neutral conductors shall be permanently grounded by means of a ground connection, as required by the National Electrical Code. The Customer shall not extend a grounding conductor form the meter socket to provide a communications utility bond attachment point. Such bonds may be accomplished by attachments to grounded metal conduits, the service grounding electrode, or other grounded leads attached to the grounding electrode (See Figures 38 and 39). No external ground attachment to the meter socket is allowed. OVERHEAD SERVICES 8.09 The service entrance wiring shall be furnished, installed, and maintained by the Customer. The meter mounting device or meter socket for self-contained metering installations will be furnished and installed by the Customer. For instrument transformer metering installations, the meter enclosures and instrument transformer racks will be supplied by the Company and installed by the Customer When metering equipment is installed outdoors, the service entrance run from the service head to the metering equipment shall be installed entirely on the outside surface of the building wall, except a service riser or mast may be extended vertically through a projecting roof. Where the metering equipment is installed indoors, the service entrance run must be exposed as much as possible and never installed within the hollow spaces of walls. At such locations, the service riser must be extended to a service drop attachment point located on an exterior wall or on a support extending vertically above an exterior wall. Normally, metering will be installed outdoors For individually metered multi-unit complexes, service entrance conductors between the termination of the service drop and the group metering installation 29

31 shall be sized in accordance with the National Electrical Code and any State, County or Municipal requirements that may be in force in the area where the installation is made All service entrance conductors shall be continuous and without splice or tap between the connection at the service drop and the meter mounting device, and between the meter mounting device and the service equipment, except as provided by the National Electrical Code Service entrance cable, conduit or bus duct shall be securely fastened to the building or structure with non-ferrous or malleable galvanized straps and nonferrous or galvanized screws. Expansion shield or lead anchors shall be used to fasten the screws on masonry buildings. Straps shall be spaced so as to prevent sagging of cable, but in no case at intervals greater than three (3) feet Each service entrance shall be equipped with an approved service head. The service head shall be located not more than 18 inches from the point of attachment of any service drop. Each conductor of the service entrance, therefore, must extend no less than two (2) feet beyond the service head for wires smaller than No. 1/0 and not less than three (3) feet for wires No. 1/0 and larger to provide sufficient length for connection to the service drop wires Service heads shall be located such that the service drop can meet the grade clearance requirements specified in paragraph 5.06 throughout the span. The service head should be located above the service drop attachment point The minimum clearances for service drop connections shall be maintained for the service head and the open wires from the service head to the service drop (See Figures 4 through 14). 30

32 8.17 The Customer shall make the connections of the service entrance conductors in the meter-mounting device The Company will furnish and install the permanent connectors for connecting the service entrance conductors to the service drop if the needed connectors are of standard Company sizes. Under no circumstances shall the Customer make this connection without specific permission of the Company s Electric Meter Department or the Business Service Center. UNDERGROUND SERVICES 8.19 The service entrance wiring shall be furnished, installed, and maintained by the Customer. The meter mounting device or meter socket for self-contained metering installations will be furnished and installed by the Customer. For instrument transformer metering installations, the meter, meter socket, and instrument transformer enclosures will be supplied by the Company and installed by the Customer For individually metered multi-unit complexes with more than six units metered per service drop, service entrance conductors between the Customer s main disconnect switch and the group metering installation (See Figure 15) shall be sized in accordance with the National Electrical Code and any State, County, or Municipal requirements that may be in force in the area where the installation is made All service entrance conductors shall be continuous and without splice or tap between the connection at the Customer s main disconnect switch, if required, and the meter mounting device, and between the meter mounting device and the service equipment, except as provided by the National Electrical Code. 31

33 EMERGENCY GENERATORS 8.22 The Customer shall provide and install a transfer switch connected in accordance with Figure 25 in situations where the Customer wishes to install his own emergency generator system. 32

34 SECTION 9 METERING GENERAL 9.01 The Company will furnish, install and own the meter for the registration of all electrical energy used by the Customer. The meter will be sealed to insure that its accuracy will be maintained. The seals shall not be disturbed by anyone except a duly authorized employee or representative of the Company Meter and instrument transformer enclosures or instrument transformer racks, shall be furnished by the Company. Meter mounting devices (sockets) for selfcontained metering installations shall be supplied by the Customer. This equipment shall be installed by and at the expense of the Customer on all new service installations and on all existing installations where the Customer s service entrance wiring is to be replaced, altered or relocated The Customer shall provide a suitable place on his premises for the installation of metering equipment. The equipment, where practicable, shall be installed on the outside wall of the Customer s building or structure. It shall be so located that adequate space and unobstructed access shall be provided and maintained for the Company s representatives to read, test, maintain and exchange such equipment. The Customer shall consult the Company regarding the proper location of the equipment. Metering equipment shall not be located on buildings at the edge of driveways, alleys, streets, or similar exposed places where it can be damaged by moving vehicles unless the equipment is protected by a substantial guard rail or posts. When there is no suitable location either on the interior or exterior of a Customer s building or structure, the meter shall be installed on the Customer s pole or other mutually acceptable metering structure. 33

35 9.04 All rooms or places where meters are installed shall have a minimum height of seven (7) feet. A minimum of three (3) feet of clear working space shall be provided in front of all meters and instrument transformer enclosures. They shall not be installed in places near electric motors and belts or other moving machinery, which would endanger the safety of those reading or working on the meters If any of the facilities belonging to the Company are damaged or destroyed on account of negligence or misuse by the Customer or anyone under the Customer s direction or control, then, the cost of the necessary repairs or replacement shall be paid for by the Customer. The Company shall also seek recovery from any other persons responsible for damage to or destruction of Company facilities. SECONDARY METERING EQUIPMENT 9.06 All individual meter installations with service at 240 volts or less shall be connected in a meter-switch-fuse sequence. All individual meter installations employing metering transformers mounted either adjacent to an outdoor service weatherhead or on the secondary bushings of a pad mounted transformer shall be connected in a meter-switch-fuse sequence. All individual self-contained or cabinet-mounted transformer meter installations with service at 480 volts shall be connected in a switch-meter-fuse sequence. A meter-switch-fuse sequence is an installation where the metering equipment is connected on the source or line side of the service disconnecting means installed in conjunction with the meter. A switch-meter-fuse sequence is an installation where the metering equipment is connected on the load side of the service disconnecting means in conjunction with the meter. All residential multiple occupancy building meter installations (240 volts or less) with two (2) to six (6) meters shall be connected in a meter-switch-fuse sequence. All multiple occupancy building meter 34

36 installations (240 volts or less) with more than six (6) meters shall be equipped with a main disconnect switch proceeding all other metering and service equipment (main disconnect switch-meter-fuse sequence). Installations in multiple occupancy buildings requiring more than six (6) meters for service above 240 volts must be equipped with a main disconnect switch that precedes all metering and service equipment followed by an individual disconnect switch immediately preceding each self-contained or cabinet-mounted meter set (main disconnect switch-meter disconnect switch-meter-fuse sequence). Due to the flexible size and number of tenant spaces afforded by multiple occupancy commercial buildings, all service disconnect switches (maximum of six) to the building shall be mounted externally and grouped together in one location with the metering equipment. Where the building design will allow more than six (6) individual occupancies, then a main disconnect switch should be installed ahead of the metering regardless of the number of customers occupying the building initially A building with individual occupancy above the second floor, shall normally have all service equipment grouped in a common accessible location. On such service entrances, disconnecting means shall also be installed on the load side of each meter in a location readily accessible to each occupant In exceptional cases where it is physically impracticable to make outdoor installations, as in the case of large apartment houses or where there is not a suitable outdoor location, meters may be installed indoors. However, the Customer s service entrance must be enclosed in continuous metal conduit and consist of a continuous service cable to the metering equipment or to the service equipment located near the metering equipment. Company access to the metering equipment should not require contact with building security or maintenance personnel. When there is no suitable location either on the 35

37 interior or exterior of a Customer s building or structure, the meter shall be installed on the Customer s pole or other mutually acceptable metering structure. In cases where there are several floors and several customers on each floor making it impractical to install the meters in one location, meters may, with Company approval, be grouped in an accessible public space on each floor. In such installations the service equipment and the feeder switch for the unmetered circuit to the meters on each floor must be grouped at one accessible location. In general, only one service shall be installed for each type of service delivered to the building On large installations where the Customer installs a cubicle or bus structure, it is permissible to install the Company s meter instrument transformers in the Customer s cubicle or bus structure provided advance approval is obtained from the Company. A sealable compartment with a hinged door and suitable drilled mounting facilities for the instrument transformers shall be provided in the cubicle by the Customer. The bus shall be drilled for connections to the metering transformers. A standard meter socket or meter test block cabinet, furnished by the Company shall be installed by the Customer at a convenient nearby location for the meter or meters. A one and one-fourth (1-1/4) inch galvanized steel or aluminum conduit for the metering leads shall be installed by the Customer between the instrument transformer compartment and the meter box or meter socket. The meter and transformer compartment shall have a hinged door, which shall be sealable. Dimensions for the meter and transformer compartment for these installations will be furnished by the Company The Company will, unless otherwise expressly provided for, furnish all meter and instrument transformer cabinets, meters, and metering auxiliaries required for metering installations. All meters and other facilities furnished by the Company, which may be on the Customer s premises, shall be and remain the 36

38 property of the Company and the Customer shall protect such property from loss or damage. The Customer shall supply individual or pre-wired gang meter sockets for self-contained metering installations, subject to approval by the Company. Pre-wired gang meter sockets must feature independently removable meter socket covers. Each socket cover on Customer-supplied gang units shall cover only one meter socket position In case meters are installed indoors, they shall be mounted on a rigid wall or panel, which is free from vibration. They shall be located in a clean, dry and safe place as near as practicable to the point where the service entrance enters the building. They shall not be located in such places as sheds, attics, bedrooms, living rooms, bathrooms, toilets, restaurant kitchens, stairways, ventilating shafts, closets, coal bind, coal furnace rooms, etc., or in any location where the visits of Company employees will inconvenience either the Customer or the employee. Meters shall not be located in places such as basements or in other locations, which are not accessible by permanent stairs. A ladder cannot be accepted as a substitute for stairs Where instrument transformer meter installations are required, the conduit from the instrument transformer box or instrument transformer rack to the meter socket or enclosure of the Company s instrument transformer secondary leads shall be furnished and installed by the Customer. The Company will specify the size of such conduit if it is to be larger than one and one-fourth (1-1/4) inches, and it shall contain no junction or outlet boxes The service entrance conductors shall be connected by the Customer to the meter socket or connection block on self-contained meter installations and to the instrument transformers on instrument transformer meter installations. Service entrance conductors on window type current transformer installations shall be run through the window of the current transformers. All watt-hour 37

39 meters and instrument transformer secondary wires will be installed by the Company. Metered load conductors shall not pass through adjacent meter or instrument transformer enclosures Meter sockets and meter boxes shall be mounted in a plumb and level position with the center of the meter not over five (5) feet and not less than three (3) feet above permanent ground or floor level. Sufficient space shall be provided for the installation of demand meters in all installations of meter boxes, whether or not they are installed at the time the initial installations are made Where multiple meter installations are required, the Customer shall mark each meter enclosure and associated service equipment to identify the apartment, office or store for which the equipment is installed. Such marking shall be made with metal letters or numbers supplied by the Company and located such that they cannot be inadvertently changed (relocated) When metering equipment is installed on a wood pole, the Customer shall furnish, install and maintain a treated pine or cedar pole having a minimum top circumference of fifteen (15) inches, set at least five (5) feet in the ground and of sufficient height to provide the required service drop clearances (See Figures 4 through 11 and paragraph 5.06). The Customer must guy the pole when such guying is deemed necessary by the Company. Weather-proof service equipment shall be installed on the load center pole near the metering equipment. PRIMARY METERING EQUIPMENT 9.17 The Company will provide and install all primary metering equipment. If the metering is to be mounted on the Customer s pole, then the Customer must provide the minimum pole clearances shown on Figure 40 and Figure 41. If the primary metering will not be pole mounted, the Customer must provide a 38

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property. INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,

More information

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877

More information

Electric Service and Meter Installations Manual SCANA Corporation 2013

Electric Service and Meter Installations Manual SCANA Corporation 2013 Electric Service and Meter Installations Manual SCANA Corporation 2013 Revised: June 2013 On file with South Carolina Public Service Commission Table of Contents Section 1: Introduction 1 Customer Call

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

ELECTRIC SERVICE HANDBOOK

ELECTRIC SERVICE HANDBOOK ELECTRIC SERVICE HANDBOOK Revised July 2006 Table of Contents Electric Construction Title: Electric Service Handbook Page No. TOC Rev. July-06 Section 1: Introduction...1-010 Section 2: DP&L Offices...2-010

More information

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering Requirements Clearance Requirements August 2015 A current version

More information

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations. PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.

More information

MOBILE HOME SERVICE REQUIREMENTS GAS

MOBILE HOME SERVICE REQUIREMENTS GAS ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

Electrical Service Guidelines

Electrical Service Guidelines Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps NEW SERVICE INSTALLATION STEPS Here is the step-by-step process required to fulfill your service installation request. Please take a few minutes to review the steps, become familiar with key milestones

More information

SPECIFICATIONS FOR ELECTRIC SERVICE GARLAND POWER & LIGHT

SPECIFICATIONS FOR ELECTRIC SERVICE GARLAND POWER & LIGHT FOREWORD This booklet is issued by the Electric Department of the City of Garland, herein after referred to Garland Power & Light or GP & L, to acquaint electric customers of Garland Power & Light, or

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Guide for Electric Service and Meter Installations

Guide for Electric Service and Meter Installations Guide for Electric Service and Meter Installations April 28, 2009 Preface This booklet is not intended to conflict with the National Electrical Safety Code, the National Electrical Code, or such state

More information

Electrical Code Regulation

Electrical Code Regulation Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

Questions and Answers for Heating and A/C Contractors

Questions and Answers for Heating and A/C Contractors 1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs.

Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs. Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs. REA Energy Services Sells and Installs: Heating and Air Conditioning Electrical Contracting Geothermal Heat Pumps Back-Up

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

Electric Service Guide for Commercial Construction

Electric Service Guide for Commercial Construction Electric Service Guide for Commercial Construction Contents Contacting KCP&L... 2 Voltages... 2 Temporary Service... 2 Customer-Provided Temporary Service... 2 KCP&L-Provided Temporary Service.... 2 Current

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

Wellesley Municipal Light Plant. Standard Requirements for Electric Service

Wellesley Municipal Light Plant. Standard Requirements for Electric Service Wellesley Municipal Light Plant Standard Requirements for Electric Service Index Section 1... General Information Section 2..General Requirements for Service Section 3. Types of Available Service Section

More information

Customer Metering and Services Guide

Customer Metering and Services Guide This document is an uncontrolled copy and may not be the most current copy. The most current copy is available at www.atcoelectric.com. This document is the property of ATCO Electric and may be updated

More information

208.652.7431 Report power outage after hours: 866.887.8442. 1150 N. 3400 E. Ashton, ID 83420 www.frr ec.com. Ashton, Idaho Headquarters Building

208.652.7431 Report power outage after hours: 866.887.8442. 1150 N. 3400 E. Ashton, ID 83420 www.frr ec.com. Ashton, Idaho Headquarters Building The aim of Fall River Rural Electric Cooperative, Inc. is to make electric energy available to its members at the lowest cost consistent with sound economy and good management. Ashton, Idaho Headquarters

More information

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Changes in the 10/2/2013 Revision of the CNP Service Standards Book

Changes in the 10/2/2013 Revision of the CNP Service Standards Book 0 Changes in the 10/2/2013 Revision of the CNP Service Standards Book 1. Article 303 - Three Phase (Page 19). Revised 240/120V Delta, Added Max Load to Overhead and Underground 2. Article 408 - Service

More information

Requirements for the installation of. Electric Services. September 8, 2003. Specifications for Electric Installations

Requirements for the installation of. Electric Services. September 8, 2003. Specifications for Electric Installations Requirements for the installation of Electric Services & Meters September 8, 2003 Specifications for Electric Installations TABLE OF CONTENT Section I - Introduction... 1 Section II - Definitions... 3

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016)

4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016) 0 4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016) 1. Article 422.1 Meter Pole Installations - Requirements (Page 59). Revised paragraph - Steel poles shall be truck accessible.

More information

INFORMATION REQUIREMENTS SUPERSEDES ALL PREVIOUS ISSUES EFFECTIVE DECEMBER 1, 2010

INFORMATION REQUIREMENTS SUPERSEDES ALL PREVIOUS ISSUES EFFECTIVE DECEMBER 1, 2010 ELECTRIC SERVICE AND METERING INFORMATION & REQUIREMENTS SUPERSEDES ALL PREVIOUS ISSUES EFFECTIVE DECEMBER 1, 2010 TABLE OF CONTTTABLE OF CONTENTS Page No. INDEX a SECTION I FOREWORD... 1 SECTION II SERVICE

More information

Electric Service Guide for Residential Construction

Electric Service Guide for Residential Construction Electric Service Guide for Residential Construction Table of Contents Contacting KCP&L... 2 Existing Home Remodeling or Additions... 2 Changing your electric service... 2 What you need to know before you

More information

Electric Service Requirements & Guidelines

Electric Service Requirements & Guidelines Electric Service Requirements & Guidelines Montana Service Area September 2011 NORTHWESTERN ENERGY Montana Service Area ELECTRIC SERVICE REQUIREMENTS AND GUIDELINES CONTENTS I. GENERAL INFORMATION 1.01

More information

SERVICE - GENERAL Residential, Commercial, Industrial

SERVICE - GENERAL Residential, Commercial, Industrial PAGE 1 OF 9 USE: Rules and procedures for overhead or underground services. PREVIOUS REVISION 10-01-01 ORIGINATED 03-94 PREVIOUS NUMBER ER 1-290-B, 07-15-93 LATEST REVISION: Remove details of Facility

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

OVERHEAD SERVICE. Table of Contents - Section 400

OVERHEAD SERVICE. Table of Contents - Section 400 OVERHEAD SERVICE Table of Contents - Section 400 PARAGRAPH 400.0 OVERHEAD SERVICES (0-600 VOLTS)... 1 400.1 GENERAL... 1 400.2 IDENTIFICATION OF CONDUCTORS... 1 400.3 MAXIMUM SERVICE ENTRANCE CONDUCTOR

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

Information and Requirements for Electric Service. Chapters 1, 2, 4, 6 and Appendix

Information and Requirements for Electric Service. Chapters 1, 2, 4, 6 and Appendix Organization: Manual: Section: Electric Distribution Information and Requirements for Electric Service Chapters 1, 2, 4, 6 and Appendix Tracking Number: 05-077 Date: January 6, 2006 SME: Jim Calore Contact

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

Electric Service Standards

Electric Service Standards VI - 1 of 17 VI. METERING EQUIPMENT A. Equipment Furnished and Installed by FPL FPL provides and installs, at its expense, adequate metering instruments to measure the electric service used by the Customer.

More information

SERVICE ENTRANCE REQUIREMENTS MANUAL

SERVICE ENTRANCE REQUIREMENTS MANUAL SERVICE ENTRANCE REQUIREMENTS MANUAL 7th Edition 2012 TABLE OF CONTENTS BTU General Policies and Procedures... 3 SECTION 1: Temporary Construction Meter Poles... 5 Temporary Overhead Fed Meter Pole...

More information

Electric Service Rules

Electric Service Rules 2016 Electric Service Rules GENERAL INFORMATION TEMPORARY SERVICES OVERHEAD SERVICES UNDERGROUND SERVICES DISTRIBUTED GENERATION METERING HUD MANUFACTURED HOMES FARM SERVICES UTILITY/CATV SERVICES PRIMARY

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

Carolina Power & Light Company 51 d/b/a Progress Energy Carolinas, Inc. SERVICE REGULATIONS

Carolina Power & Light Company 51 d/b/a Progress Energy Carolinas, Inc. SERVICE REGULATIONS Carolina Power & Light Company 51 d/b/a Progress Energy Carolinas, Inc. 1. SERVICE AGREEMENT SERVICE REGULATIONS (d) (e) (f) Description: The Service Agreement (hereinafter sometimes termed "Agreement")

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

Building Permits: When are they required?

Building Permits: When are they required? Building Permits: When are they required? Generally, you need to obtain a building permit from the City whenever you construct, enlarge, alter, repair, move, remove, improve, convert, or demolish a building

More information

Electric Service Standards

Electric Service Standards IV: 1 of 24 IV. SERVICE and METER CONNECTIONS A. Service Equipment 1. General The Customer should consult FPL at an early stage to verify availability of service (section II.C) and to determine the FPL

More information

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8 DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2 Kinds and Uses of Service... 2-1-1 and 2-1-2 Wye Network Area Maps Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8 Transformer Connections

More information

CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES. EFFECTIVE MARCH 1, 1995 Revised 1/01/2013

CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES. EFFECTIVE MARCH 1, 1995 Revised 1/01/2013 CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES EFFECTIVE MARCH 1, 1995 Revised 1/01/2013 CARROLL COUNTY ELECTRICAL DEPARTMENT 103 WEST PARIS ST. P. O. BOX 527 HUNTINGDON, TENNESSEE 38344 Telephone

More information

In the year Two Thousand Eleven.. Resolved by the City Council of the City of Burlington, as follows:

In the year Two Thousand Eleven.. Resolved by the City Council of the City of Burlington, as follows: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 APPROVAL OF AMENDMENTS TO BURLINGTON ELECTRIC DEPARTMENT S OPERATING GUIDELINES In the year Two Thousand Eleven.. Resolved

More information

Policy and Guidelines for Electric Service

Policy and Guidelines for Electric Service Policy and Guidelines for Electric Service FRANKLIN MUNICIPAL POWER & LIGHT 1050 Pretlow Street Franklin, VA 23851 757-562-8568 757-562-7883 Fax January 2008 Franklin Power & Light HELPFUL TELEPHONE NUMBERS

More information

How To Get A Power Line Extension

How To Get A Power Line Extension GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

County of Riverside Building and Safety Department

County of Riverside Building and Safety Department County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

Section 5 Meters and Service Entrance Equipment

Section 5 Meters and Service Entrance Equipment Table of Contents Section 5 Meters and Service Entrance Equipment A. GENERAL... 5-3 B. METER TOTALIZING... 5-4 C. SEQUENCE OF SERVICE ENTRANCE EQUIPMENT... 5-4 D. METER LOCATIONS... 5-11 E. METER ROOMS...

More information

Requirements for Electric Service and Meter Installations

Requirements for Electric Service and Meter Installations Requirements for Electric Service and Meter Installations Florida service area Revised 2012 Amended 7/2013 2014 Duke Energy Corporation 140165 01/14 Section TABLE OF CONTENTS Page Number Committee Member

More information

HOMEOWNER S PERMIT GUIDE

HOMEOWNER S PERMIT GUIDE HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448

More information

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE A. GENERAL NOTES: Service entrance line and load conductors, conduit straps, weatherhead, lock nuts, bushings, connectors, and

More information

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES 1. Acceptance of Electricity Service By establishing or requesting a POD or by continuing an

More information

CHAPTER 5 - Company Equipment on Member s Premises... 16 Sealing of Equipment... 16 Theft of Service... 16

CHAPTER 5 - Company Equipment on Member s Premises... 16 Sealing of Equipment... 16 Theft of Service... 16 Table of Contents Page CHAPTER 1 General Information... 4 Purpose of Service Rules... 4 Member Wiring - Code Compliance and Inspection... 4 Service Entrance Equipment... 5 Application for New Service...

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 OCA #230100 First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 AN ORDINANCE AMENDING SECTIONS 4.A.080, 4.1.020, 4.1.110, 4.2.010, 4.2.070, 4.2.125, 4.2.170, 4.2.175 AND 4.2.220;

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Underground Commercial Electric Service

Underground Commercial Electric Service Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT

More information

MOBILEHOME PARK INSPECTION RESIDENT INFORMATION BOOKLET

MOBILEHOME PARK INSPECTION RESIDENT INFORMATION BOOKLET State of California Business, Transportation and Housing Agency Department of Housing and Community Development Division of Codes and Standards MOBILEHOME PARK INSPECTION RESIDENT INFORMATION BOOKLET *

More information

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the

More information

Considering UNDERGROUND. tampaelectric.com

Considering UNDERGROUND. tampaelectric.com Considering UNDERGROUND Electric Service? tampaelectric.com INTRODUCTION The majority of Tampa Electric s customers receive their electric service through overhead construction, which is the standard type

More information

WHEN IS A PERMIT REQUIRED?

WHEN IS A PERMIT REQUIRED? WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,

More information

Electric Service Conversion Overhead-to-Underground. Minnesota

Electric Service Conversion Overhead-to-Underground. Minnesota Electric Service Conversion Overhead-to-Underground Xcel Energy Electric Connections Minnesota Process Please fill out these forms and complete this checklist to begin your application process: 1) Overhead-to-Underground

More information

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...

More information

Electric Service Guide for Residential Construction

Electric Service Guide for Residential Construction Electric Service Guide for Residential Construction TABLE OF CONTENTS Contacting KCP&L... 2 Existing Home Remodeling or Additions... 2 Building a New Home... 3 KCP&L Services at a Glance... 4 Current Transformers...

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Section 10 Electric Switchboards: 0 Through 600 Volts

Section 10 Electric Switchboards: 0 Through 600 Volts Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,

More information

METERING INSTALLATION REQUIREMENTS

METERING INSTALLATION REQUIREMENTS METERING INSTALLATION REQUIREMENTS Table of Contents Section 300 PARAGRAPH 300.0 METERING AND SERVICE ENTRANCE EQUIPMENT... 1 300.1 GENERAL... 1 300.2 METERED AND UNMETERED CONDUCTORS... 1 300.3 SEALING

More information

WALKING-WORKING SURFACES (SLIPS, TRIPS, AND FALLS)

WALKING-WORKING SURFACES (SLIPS, TRIPS, AND FALLS) WALKING-WORKING SURFACES (SLIPS, TRIPS, AND FALLS) Slips, trips, and falls constitute the majority of general industry accidents. They cause 15% of all accidental deaths, and are second only to motor vehicles

More information

INSPECTION GUDELINES

INSPECTION GUDELINES GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist 443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota

More information

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding A Guide for California Developers of Com m ercial Property This guide consists of

More information