INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Similar documents
Transmission Protection Overview

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

VOLTAGE REGULATOR AND PARALLEL OPERATION

Specifying a Variable Frequency Drive s

Motor Fundamentals. DC Motor

Shunt Capacitor Bank Fundamentals and Protection

Protection of Phase Angle Regulating Transformers

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Typical Data Requirements Data Required for Power System Evaluation

Step Voltage Regulators

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Line Reactors and AC Drives

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

The following table shows approximate percentage wise the

SYNCHRONOUS MACHINES

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Application of Overreaching Distance Relays

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.

15LINE PROTECTION WITH PILOT RELAYS

Transmission Line Protection Principles

HV Substation Design: Applications and Considerations

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

ABB PSPS Erich Steinmann; Generator control-2013

SPECIFICATION COG-2007

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

Current Transformers Ratio / Polarity / Types

Test & Data Management Software

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Type SA-1 Generator Differential Relay

ECE 586b Course Project Report. Auto-Reclosing

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

T Substation Maintenance and Commissioning Test Equipment

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

NATIONAL CERTIFICATE (VOCATIONAL)

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Unit 33 Three-Phase Motors

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Treasure Valley Electric Plan - Community Advisory Committee

Motor Protection Voltage Unbalance and Single-Phasing

Properties of electrical signals

Percentage Restrained Differential, Percentage of What?

DIRECT CURRENT GENERATORS

The full wave rectifier consists of two diodes and a resister as shown in Figure

Principles of Adjustable Frequency Drives

Lab 8: DC generators: shunt, series, and compounded.

TDMS Test & Data Management Software

Local Back-up Protection for an Electric Power System

Permissible ambient temperature Operation Storage, transport

Lab 14: 3-phase alternator.

Offshore Platform Powered With New Electrical Motor Drive System

Instrument Transformers Application Guide

Generator Differential Relay Electrical Apparatus

Power Quality Paper #3

Underground vs. Overhead Transmission and Distribution

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

Power Plant Electrical Distribution Systems

GLOLAB Two Wire Stepper Motor Positioner

GenTech Practice Questions

January 23, Minimum Design Standards Task Force

Section B: Electricity

How To Understand And Understand The Electrical Power System

Eaton s E-Series protective relay family

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

WIND TURBINE TECHNOLOGY

Transformers. Special transformers Reactors products

When power interruptions happen.

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know?

Voltage Unbalance and Motors

Michelin North America

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

13 ELECTRIC MOTORS Basic Relations

CAPACITOR BANK TESTING SWP

ELECTRICAL CIRCUITS. Electrical Circuits

Diodes have an arrow showing the direction of the flow.

MAS.836 HOW TO BIAS AN OP-AMP

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Hyperlinks are Inactive

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Transformer protection

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

Transcription:

INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012

CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably in the past 20 years. Many learning and growth opportunities will come your way in the future.

What is System Protection? System protection is the art and science of detecting problems with power system components and isolating these components. Problems on the power system include: 1. Short circuits 2. Abnormal conditions 3. Equipment failures NERC defines the protection system as: Current Approved Definition: Protective relays, associated communication systems, voltage and current sensing devices, station batteries and DC control circuitry.

Purpose of System Protection Protect the public Improve system stability Minimize damage to equipment Protect against overloads Employ relay techs and engineers

What Components (Equipment) Do We Protect?

What Components (Equipment) Do We Protect? Generators Transformers, Reactors Lines Buses Capacitors

What Components (Equipment) Do We Protect?

Some Basics Protective relays monitor the current and/or voltage of the power system to detect problems with the power system. Currents and voltages to relays are supplied via CT s and PT s.

Some Basics Current Transformer (CT) A device which transforms the current on the power system from large primary values to safe secondary values. The secondary current will be proportional (as per the ratio) to the primary current.

Some Basics Potential Transformer (PT) A device which transforms the voltage on the power system from primary values to safe secondary values, in a ratio proportional to the primary value.

What Components (Equipment) Do We Protect?

I. Generator Protection A. Construction & Theory of Operation

Three Gorges Dam in China Largest in the world (22,000MW, 26 Generators)

I. Generator Protection What can go wrong? A. Stator Winding Problems 1. Winding-winding short 2. Stator ground

I. Generator Protection What can go wrong? A. Stator Winding Problems

Generator Protection How Do We Protect the Stator? A. Differential Protection (what goes in must come out) 1. Detects phase-phase faults B. Stator Ground Protection 1. 59N (95% of Stator) 2. Third Harmonic Voltage Method (100% of Stator) 3. Signal Injection (100% of Stator)

Generator Protection What can go wrong? B. Rotor Problems 1. Loss of field 2. Field ground a. First ground b. Second ground =TROUBLE

Generator Protection Rotor

Generator Protection How Do We Protect the Rotor? 1. Loss of Field a. Impedance

Generator Protection How Do We Protect the Rotor? 2. Field ground a. DC voltage relay (64F) The field ground relay is connected from the negative side of the field to DC ground. Detects voltage from the field to ground.

Generator Protection What else can go wrong? C. Abnormal Conditions 1. Over/Under Frequency 2. Over Excitation 3. Reverse Power 4. Out of Step 5. Unbalance Current

Generator Protection

Transformer Protection

XFMR PROTECTION Power transformers are expensive, and are a long lead-time item (1 year or longer) so protection must be effective

Transformer Protection Construction

Transformer Protection Construction

Transformer Protection Construction

Transformer Protection Transformer size and rating MVA: the capacity of the transformer in terms of million volt-amps. Size can range from less than 1 MVA to 500 MVA and higher. Transformer rating (MVA) is determined in part by the amount of cooling employed. MVA rating increases with more cooling. OA, FOA (stage 1), FOA (stage 2)

Transformer Protection What can go wrong? Winding-to-winding faults Winding-to-ground faults Bushing faults

Transformer Protection

Transformer Protection Protection Methods Fuse Overcurrent Differential

Transformer Protection High Side Fuse

Transformer Protection Transformer Damage Curve

Transformer Protection Overcurrent Relays

Transformer Protection Differential Protection: What goes in must come out.. P-in = P-out

Transformer Protection Microprocessor Relays 187T1-T Wraps transformer 187T1-B Wraps transformer and bus

Transformer Protection 187 T1-T Zone of Protection

Transformer Protection 187 T1-B Zone of Protection

Transformer Protection Some terms you will be learning about this week: Restraint Operate Slope Inrush 2 nd Harmonic

LINE PROTECTION

Transmission Line Protection Transmission lines can vary in length from several hundred feet to several hundred miles, and in voltage (line-to-line) from 46KV to 750KV. Construction can be simple, such as a single wood pole with insulators atop a crossarm, with little spacing between the conductors and from the conductors to ground. At the other end of the scale are metal lattice structures with bundled conductors (2 or more conductors per phase) with large spacing between conductors and between conductors and ground.

Transmission Line Protection

Transmission Line Protection

Transmission Line Protection Ice Storm What Can Go Wrong? FAULTS (Short Circuits) Some causes of faults: Trees Lightning Animals (birds, squirrels, snakes) Weather (wind, snow, ice) Natural Disasters (earthquakes, floods) Faulty equipment (switches, insulators, clamps, etc.)

Transmission Line Protection

Transmission Line Protection

Transmission Line Protection Faults Faults come uninvited and seldom go away voluntarily. Fault Types: Single line-to-ground Line-to-line Three Phase Line-to-line-to-ground

Transmission Line Protection How Do We Protect Transmission Lines? A. Overcurrent B. Directional Overcurrent C. Distance (Impedance) D. Pilot 1. DCB (Directional Comparison Blocking 2. POTT (Permissive Overreaching Transfer Trip) E. Line Current Differential

Transmission Line Protection Overcurrent Protection Non-Directional Relay responds to overcurrent condition Instantaneous (IOC) device #50 No intentional time delay Time Overcurrent (TOC) device #51 Various curve types, including inverse, very inverse, extremely inverse

Transmission Line Protection Overcurrent Line Protection

Transmission Line Protection AC Schematic

Transmission Line Protection Time Overcurrent Curves

Transmission Line Protection Directional Overcurrent Protection Relay responds to overcurrent condition in the forward direction only (device #67, 67N, 67NT) Will not respond to reverse faults Compares the current in the line versus a known reference that will always be the same (such as a voltage or polarizing current source)

Transmission Line Protection

Transmission Line Protection Directional Overcurrent Example

Transmission Line Protection Distance Protection A distance relay measures the impedance of a line using the voltage applied to the relay and the current applied to the relay. When a fault occurs on a line, the current rises significantly and the voltage collapses significantly. The distance relay (also known as impedance relay) determines the impedance by Z = V/I. If the impedance is within the reach setting of the relay, it will operate.

Transmission Line Protection Distance Protection Electromechanical distance relays use torque to restrain or operate KD, GCY, etc. Device #21 Microprocessor distance relays use equations to restrain or operate SEL, ABB, GE, Areva, etc. Device #11

Transmission Line Protection Distance Relay CT and PT Connections

Transmission Line Protection

Transmission Line Protection Distance Protection Typical zone reach settings

Transmission Line Protection Distance Protection When a fault occurs on a transmission line, the current increases and the angle of the current with respect to the voltage changes to a lagging angle, usually between 60 to 85 degrees.

Transmission Line Protection Distance Protection The most common characteristic (or protection shape) of distance relays is the mho characteristic, a circular type reach characteristic. Distance relays have a settable maximum torque angle (mta), which is the angle of the current compared to the angle of the voltage at which the relay is most sensitive. In the drawing on the right, the mta is approximately 75 degrees.

Introduction to System Protection Terminology Dependability: the certainty that a protection system will operate when it is supposed to Security: the certainty that a protection system will not operate when it is not supposed to Reliability = Dependability + Security

Transmission Line Protection Pilot Relaying Scheme A protection scheme which employs communications to send a signal from one station to another to allow high speed tripping (permission) or to prevent high speed tripping (blocking). Pilot protection allows over-reaching zones of protection to ensure full protection of the line as well as high speed tripping.

Transmission Line Protection Pilot Relaying Scheme Directional Comparison Blocking (DCB) A communications based protection scheme where high speed over-reaching tripping is allowed unless a block signal is received.

Transmission Line Protection Pilot Relaying Scheme Permissive over-reaching transfer trip (POTT) A communications based protection scheme where high speed over-reaching tripping is allowed only if a permissive signal is received

BLOCKING Transmission SCHEME Line Protection OPERATING PRINCIPLE BLOCKING SCHEME OPERATING PRINCIPLE STATION A Relay STATION B Relay

BLOCKING SCHEME OPERATING PRINCIPLE Relay

Transmission Line Protection BLOCKING SCHEME OPERATING PRINCIPLE DO NOT TRIP!!! External Fault Relay

Transmission Line Protection BLOCKING SCHEME OPERATING PRINCIPLE Internal Fault No block signal is sent Relay

PERMISSIVE Transmission SCHEME Line Protection OPERATING PRINCIPLE Permissive Scheme STATION A Relay STATION B Relay

Transmission Line Protection Permissive scheme internal fault Relay Relay STATION A STATION B

Transmission Line Protection Permissive scheme internal fault Relay Relay STATION A STATION B

Transmission Line Protection Permissive scheme internal fault You Can Go Ahead and Trip If You Want To! You Can Go Ahead and Trip If You Want To! Relay Relay STATION A STATION B High Speed Tripping Takes Place at Station A and B

Transmission Line Protection Permissive scheme external fault Relay Relay STATION A STATION B

Transmission Line Protection Permissive scheme external fault Relay Relay STATION A STATION B

Transmission Line Protection Permissive scheme external fault You Can Go Ahead and Trip If You Want To! Relay Relay STATION A STATION B No High Speed Tripping Takes Place Because the Fault Is Reverse to the Relay at Station B.

Transmission Line Protection BLOCKING VS. PERMISSIVE Blocking Increased dependability because if the carrier fails, the protection will trip anyway. Decreased security because if the carrier fails, the protection will trip for an out of section fault. Permissive Increased security because if the communication fails, the protection will not trip high speed. Decreased dependability because if the comm fails, the protection will not trip high speed for an in section fault.

Transmission Line Protection LINE DIFFERENTIAL No fault or external fault, current at each end is balanced The current going into the line is going out at other end

Transmission Line Protection Line differential Internal fault, relay trip is processed

Bus Protection Bus Differential: Current into bus must equal current out of bus

Bus Protection Bus Fault

Bus Protection Single bus with XFMR

Bus Protection Double bus, breaker-and-ahalf

Bus Protection Double bus, double breaker

Capacitor Protection Purpose of capacitors: Shunt capacitors raise the voltage on a bus or line to a higher level, thus helping keep the voltage at desired level Series capacitors cancel out the inductive reactance of a line, thus making the line appear shorter increasing load flow on the line.

Capacitor Protection Capacitors connected in parallel add

Capacitor Protection Capacitors connected in series sum like they are in parallel

Capacitor Protection Capacitors are connected in series and parallel combination to obtain the desired total capacitance for the bank

Capacitor Protection

Capacitor Protection Voltage across cap bank is determined by current flow and impedance (capacitive reactance) of bank. If a capacitor fuse blows or if a capacitor shorts, the voltage drop across the bank changes due to a change in capacitive reactance of the bank. A voltage relay detects the higher voltage and trips the breaker

Capacitor Protection

Introduction to System Protection????? QUESTIONS????? If you are still awake, nudge your sleeping neighbor and tell him/her that the lecture is over and it is almost time for the next lecture, which may actually prove to be an interesting and informative lecture (unlike this one). If you are not awake, may you dream that you are on a Hawaiian beach And then wake up in Pullman!