TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System



Similar documents
TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Development and testing of a multi-type air conditioner without using AC inverters

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

UNIT 2 REFRIGERATION CYCLE

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

Testing methods applicable to refrigeration components and systems

A/C refrigerant system, overview

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

Test Report issued under the responsibility of:

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

Research on the Air Conditioning Water Heater System

Characteristics of Evaporators

LG Electronics AE Company, Commercial Air Conditioning

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

Air Conditioners Technical Data

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

MAC-120HE-01 Air-Cooled Chiller

Todd M. Rossi, Ph.D. President

HP switch LP switch Discharge thermo Comp. Surface thermo

Heating, Ventilation & Air Conditioning Equipment

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

1116, Suenaga, Takatsu-ku, Kawasaki , Japan

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Refrigeration Basics 101. By: Eric Nelson

Heating, Ventilation & Air Conditioning Equipment

THE REPLACEMENT OF R-22

Product Data. Features/Benefits. AquaForce 30XA Air-Cooled Liquid Chillers. 80 to 500 Nominal Tons (265 to 1740 Nominal kw)

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Appendix C. Minimum Equipment Efficiency Standards

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Product Data. Split System Cooling F-EN. March 2015

Appendix - Controllers 179

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Laboratory Performance Testing of Residential Window Mounted Air Conditioners

UNDERSTANDING REFRIGERANT TABLES

How To Know If A Refrigeration System Is Efficient

york air-conditioning products Residential & VRF News 2015

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

ECOCIAT. Domestic hot water heat recovery unit

Analytical Study on the Performance Characteristics of a Liquid Injection Refrigeration Cycle.

How To Make A High Efficiency Thermostat

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

42-Volt Electric Air Conditioning System Commissioning and Control For a Class-8 Tractor

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

Engineering Specifications

HVAC and REFRIGERATION

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

catalog Single Package Vertical Air Conditioners and Heat Pumps

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Failure code manual. content

SECTION HEAT PUMPS

Increasing the evaporation temperature with the help of an internal heat exchanger

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

The Second Law of Thermodynamics

Daikin Altherma hybrid heat pump. The natural combination

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

TWE+TTA TWE+TWA T.R.

Refrigeration Compressed Air Dryer Buran Ultrapulse

Technical data. Danfoss DHP-A

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

The Development of a Frost-Less Heat Pump

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.

ON-VEHICLE INSPECTION

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

HVAC Systems: Overview

Why and How we Use Capacity Control

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps

Cooling kw Heating kw

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov to Mar. 15, 2004.

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

AIR REVERSING R744 AIR CONDITIONING SYSTEM

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE

Open Cycle Refrigeration System

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System Zhang Lei Zhu Yanting Shanghai Hitachi Electrical Appliances CO., LTD 888 Ningqiao Rd. Pudong Jinqiao Shanghai, China December 10, 2013 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

1. Introduction To support the Low-GWP AREP as well as to find an appropriate alternative for refrigerant R410A, we carried out the performance test of R32 in cooling mode as a drop-in replacement for the baseline R410A, in a pair of rooms based on the air-enthalpy test method at Shanghai Hitachi s test center. 2. Test Setup Testing was conducted with a split air conditioning system produced by GREE (Model KFR-72), which has a nominal capacity of 7350 W (nearly 2Ton), and it was designed for the baseline refrigerant R410A. Both evaporator and condenser in the system are tube-fin type heat exchangers. We employed a hermetic rotary type of compressor with constant speed. The lubricant inside compressor is a POE type oil that is suitable for both R410A and R32. On the basis of theoretical thermodynamic calculation, R32 may have a high discharge temperature which would have a negative impact on compressor s reliability. So, we added a flash-tank in the system to control the discharge temperature of R32 when necessary. In addition, two electronic valves were employed as the expansion device. The schematic diagram and measure points layout are shown in figure 1. Measuring points are including inlet and outlet temperature of heat exchangers, compressor suction temperature and pressure, compressor discharge temperature and pressure, and air flow rate of the indoor chamber side. Respecting temperature measurements, we used platinum resistance sensors with errors within -/+0.1K of the quantity measured. As to pressure measurements, we used sensors with errors within ±1% of the pressure measured. YOKOGAWA DR240 Hybrid recorder was used to record the parameters measured by sensors. Other data such as capacity and EER were calculated by the testing software. All tests here were performed in accordance with AHRI Standard 210/240. System was first run with R410A under test A condition to determine the optimized refrigerant charge. The charge increased 50g at a time to get the maximized EER. After that, test B and C were conducted with the optimized charge. Then, R410A was cleared from system, and the R32 tests were carried out in the same order. Slight adjustments were made to the orifice diameter inside EEV1 when testing the alternative R32, to seek a better system EER. 2

Figure1. Schematic Diagram of Testing System 3

3. Results Manufacturer: Shanghai Hitachi (Compressor) Manufacturer s Notation: The following information on this page remains same for all the drop-in tests. Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System R32 POE68 R410A / POE System: GREE-KFR-72; Compressor: Shanghai Hitachi -ASH280* 7350 W, RAC Other System Changes 1. A flash-tank was added in the system as figure 1 shows. 2. The diameter of orifice inside the electronic valves is adjustable in accordance with the given pulse signal. During R32 test, EEV1 was adjusted to a smaller diameter compared with R410A system, to seek a better performance. System Data Base. Alt. Ratio Degradation Coefficient Cd 0.050 0.119 2.38 Seasonal Energy Efficiency Ratio - SEER 12.88 13.06 1.014 Data Source(s) for Refrigerant Properties NIST REFPROP, Version 8.0 Additional Notes 1. During the course of drop-in test, injection was off. 2. The testing system is a room air conditioner having a fixed-speed compressor and a fix-speed indoor fan. 3. No modification was made to the heat exchangers during the test. Some parameters of the heat exchanges are listed in following form. Type Face Area (mm^2) Fin type Fins per inch Number of rows Evaporator 307800 (W*H: 405*760) Strip type 19 2 Fin-tube Condenser 303750(W*H:405*750) Wavy 16 2 4

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM-TEST A Manufacturer: Shanghai Hitachi Comparison Data Base. Alt. SI Units Base. Alt. IP UNits Ratio Mode (Heating/Cooling) Cooling Compressor Type Rotary Type Shanghai Hitachi model# ASH280* Compressor Displacement 0.0803 0.0803 M^3/min 2.836 2.836 Ft ^3min 1 Nominal Motor Size 2.5 2.5 hp 1 Motor Speed 2868 2868 rpm 1 Expansion Device Type EEV EEV Lubricant Charge 0.6 0.6 kg 1.3 1.3 lb 1 Refrigerant Charge 2.15 1.6 kg 4.74 3.53 lb 0.744 Refrigerant Mass Flow Rate 3.09 2.26 kg/min 6.81 4.98 lb/min 0.731 Composition, at compr. Inlet if applicable % wt Ambient In - db 26.7 26.7 C 80 80 F Temps. door wb 19.4 19.4 C 67 67 F Out- db 35 35 C 95 95 F door wb 23.9 23.9 C 75 75 F Total Capacity 6847 7498 W 23369 25590 Btu/hr 1.095 Sensible Capacity 5008 5278 W 17092 18014 Btu/hr 1.054 Total System Power Input 2224 2403 W 2224 2403 W 1.080 Compressor Power Input 2070 2249 W 2070 2249 W 1.086 Energy Efficiency Ratio (EER) (total 3.08 3.12 W/W 10.51 10.65 Btuh/W 1.013 Coeff. Of Performance (COP) (total Note: 1.In the above form, the designed value of motor speed is adopted, and compressor displacement as well as the refrigerant mass flow is calculated in accordance with it. 5

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM-TEST A Type of System: split RAC Alternate Refrigerant: R32 Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Air Flow Rate (gas) 18.6 18.9 m ^ 3/min 656.9 665.7 ft ^ 3/min 1.01 Inlet 26.7 26.7 C 80.0 80.1 F Outlet 13.8 13.5 C 56.8 56.2 F Condenser Heat Exchange Fluid Air Air Flow Rate (gas) N/A N/A m ^ 3/min N/A N/A ft ^ 3/min N/A Inlet N/A N/A C N/A N/A F Outlet N/A N/A C N/A N/A F Refrigerant Side Data s & Pressures Baseline Alternative Baseline Alternative T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 13.6 1037 12.7 1062 56.5 150.4 54.9 154.0 Compressor Discharge 61.8 2728 66.3 2835 143.2 395.6 151.4 411.1 Condenser Inlet 54.4 N/A 42.3 N/A 129.9 N/A 108.2 N/A Condenser Outlet 41.8 N/A 35 N/A 107.2 N/A 94.9 N/A Expansion Device Inlet 3.1 N/A 9.6 N/A 5.6 N/A 17.4 N/A Subcooling, at expan. device N/A N/A N/A N/A N/A N/A N/A N/A Evaporator Inlet N/A N/A N/A N/A N/A N/A N/A N/A Evaporator Outlet 10.8 N/A 10.4 N/A 51.4 N/A 50.7 N/A Evaporator Superheat 2.3 1.8 4.1 3.2 6

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM-TEST B Manufacturer: Shanghai Hitachi Comparison Data Base. Alt. SI Units Base. Alt. IP UNits Ratio Mode (Heating/Cooling) Cooling Compressor Type Rotary Type Shanghai Hitachi model# ASH280* Compressor Displacement 0.0803 0.0803 M^3/min 2.836 2.836 Ft ^3min 1 Nominal Motor Size 2.5 2.5 hp 1 Motor Speed 2868 2868 rpm 1 Expansion Device Type EEV EEV / Lubricant Charge 0.6 0.6 kg 1.3 1.3 lb 1 Refrigerant Charge 2.15 1.6 kg 4.74 3.53 lb 0.744 Refrigerant Mass Flow Rate N/A N/A kg/min N/A N/A lb/min N/A Composition, at compr. Inlet if applicable % wt Ambient In - db 26.7 26.7 C 80 80 F Temps. door wb 19.4 19.4 C 67 67 F Out- db 27.8 27.8 C 82 82 F door wb 18.3 18.3 C 65 65 F Total Capacity 7563 8108 W 25812 27672 Btu/hr 1.072 Sensible Capacity 5255 5525 W 17935 18857 Btu/hr 1.051 Total System Power Input 1953 1992 W 6666 6799 W 1.02 Compressor Power Input 1799 1838 W 6140 6273 W 1.022 Energy Efficiency Ratio (EER)(total) 3.87 4.07 W/W 13.21 13.89 Btuh/W 1.052 Coeff. Of Performance (COP) (total) Note: 1.In the above form, the designed value of motor speed is adopted, and compressor displacement is calculated in accordance with it. 7

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM-TEST B Type of System: split RAC Alternate Refrigerant: R32 Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Air Flow Rate (gas) 18.7 18.8 m ^ 3/min 660.4 662.2 ft ^ 3/min Inlet 26.7 26.69 C 80.0 80.0 F Outlet 13.0 12.6 C 55.4 54.6 F Condenser Heat Exchange Fluid Air Air Flow Rate (gas) N/A N/A m ^ 3/min N/A N/A ft ^ 3/min N/A Inlet N/A N/A C N/A N/A F Outlet N/A N/A C N/A N/A F Refrigerant Side Data s & Pressures Baseline Alternative Baseline Alternative T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 15.3 981 11.0 1041 59.6 142.26 51.7 150.96 Compressor Discharge 58.9 2321 58.5 2398 138.0 347.74 137.4 347.74 Condenser Inlet 50.6 N/A 49.7 N/A 123.0 N/A 121.4 N/A Condenser Outlet 33 N/A 34.6 N/A 91.4 N/A 94.2 N/A Expansion Device Inlet N/A N/A N/A N/A N/A N/A N/A N/A Subcooling, at expan. device 5.2 N/A 4.1 N/A 9.4 N/A 7.4 N/A Evaporator Inlet N/A N/A N/A N/A N/A N/A N/A N/A Evaporator Outlet 12.3 N/A 9.5 N/A 54.2 N/A 49.1 N/A Evaporator Superheat 5.7 1.6 10.2 2.8 8

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM-TEST C Manufacturer: Shanghai Hitachi Comparison Data Base. Alt. SI Units Base. Alt. IP UNits Ratio Mode (Heating/Cooling) Cooling Compressor Type Rotary Type Shanghai Hitachi model# ASH280* Compressor Displacement 0.0803 0.0803 M^3/min 2.836 2.836 Ft ^3min 1 Nominal Motor Size 2.5 2.5 hp 1 Motor Speed 2868 2868 rpm 1 Expansion Device Type EEV EEV Lubricant Charge 0.6 0.6 kg 1.3 1.3 lb 1 Refrigerant Charge 2.15 1.6 kg 4.74 3.53 lb 0.744 Refrigerant Mass Flow Rate N/A N/A kg/min N/A N/A lb/min N/A Composition, at compr. Inlet if applicable % wt Ambient In - db 26.7 26.7 C 80 80 F Temps. door wb 19.4 19.4 C 67 67 F Out- db 27.8 27.8 C 82 82 F door wb 13 13 C 55.4 55.4 F Total Capacity 6234 6619 W 21276 22590 Btu/hr 1.062 Sensible Capacity 5965 6287 W 20358 21457 Btu/hr 1.054 Total System Power Input 1924 1969 W 6567 6720 W 1.023 Compressor Power Input 1770 1815 W 6041 6195 W 1.025 Energy Efficiency Ratio (EER)(total) 3.24 3.36 W/W 11.058 11.468 Btuh/W 1.037 Coeff. Of Performance (COP) (total) Note: 1.In the above form, the designed value of motor speed is adopted, and compressor displacement is calculated in accordance with it. 9

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM-TEST C Type of System: split RAC Alternate Refrigerant: R32 Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Air Flow Rate (gas) 18.8 18.9 m ^ 3/min 662.2 666.4 ft ^ 3/min 1.006 Inlet 22.9 23.8 C 73.2 74.8 F Outlet 8.1 8 C 46.5 46.4 F Condenser Heat Exchange Fluid Air Air Flow Rate (gas) N/A N/A m ^ 3/min N/A N/A ft ^ 3/min N/A Inlet N/A N/A C N/A N/A F Outlet N/A N/A C N/A N/A F Refrigerant Side Data s & Pressures Baseline Alternative Baseline Alternative T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 7.2 881 7.2 905 45.0 127.76 45.0 131.24 Compressor Discharge 49.3 2250 55.3 2312 120.7 326.28 131.5 335.27 Condenser Inlet 43.0 N/A 46.5 N/A 109.4 N/A 115.7 N/A Condenser Outlet 34.0 N/A 33.8 N/A 93.2 N/A 92.9 N/A Expansion Device Inlet N/A N/A N/A N/A N/A N/A N/A N/A Subcooling, at expan. device 3.0 N/A 3.4 N/A 5.3 N/A 6.0 N/A Evaporator Inlet N/A N/A N/A N/A N/A N/A N/A N/A Evaporator Outlet 5.2 N/A 4.9 N/A 41.3 N/A 40.8 N/A Evaporator Superheat 2.1 1.5 3.7 2.7 10

4. Discussions Detailed parameters obtained through tests are list in the data forms above. The optimized refrigerant charge of baseline R410A system is 2150g, while the charge amount of the alternative refrigerant R32 is 25.6% less. Test A, B and C were carried out with the opt charge of each refrigerants. To directly compare the performance of baseline and alternative refrigerants, some parameters in test data forms are illustrated in the form of bar graphs as the following four figures. 9000 2500 8000 7000 2000 Total Capacity,W 6000 5000 4000 3000 Total Power Input,W 1500 1000 2000 500 1000 0 A B C R410A R32 0 A B C R410A R32 Figure 2:Capacity of R410A and R32 Figure 3:Total Power Input of R410A and R32 4.5 70 Total COP,W/W 4 3.5 3 2.5 2 1.5 1 0.5 Compressor Discharge, 60 50 40 30 20 10 0 A B C R410A R32 0 A B C R410A R32 Figure 4:COP of R410A and R32 Figure 5: Discharge of R410A and R32 Figure 2 shows that in all cooling tests conditions, R32 has a better capacity over R410A, and the increment varies from 6.2% to 9.5%. However, since the total power input of R32 system rises accordingly as shown in figure 3, the increment of COP is not so well as capacity. Figure 4 indicates that comparatively significant performance advantage over baseline system is at B condition by 5.2%, while at test A condition, R32 system has a slight 1.3% COP increment over R410A system. 11

At first, we worried the high discharge temperature of R32 would affect the compressor reliability, since it is nearly 20 higher than that of R410A according to thermodynamic calculation. Owing that capacity of both heat exchangers are big enough, the discharge temperature of R32 has been limited. As figure 5 shows, difference of measure discharge temperature between baseline R410A and alternative R32 is within 6. Submitted by: LIU CHUNHUI 12