1 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric Appliances Hu Huang Gree Electric Appliances Yingjiang Ma Gree Electric Appliances Rong Zhuang Gree Electric Appliances Follow this and additional works at: Liu, Fei; Huang, Hu; Ma, Yingjiang; and Zhuang, Rong, "Research on the Air Conditioning Water Heater System" (28). International Refrigeration and Air Conditioning Conference. Paper This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at Herrick/Events/orderlit.html
2 221, Page 1 Research on the Air Conditioning Water Heater System Fei Liu, Hui Huang, Yingjiang Ma, Rong Zhuang Refrigeration Institute of Gree Electric Appliances, Inc. of Zhuhai, Zhuhai, Guangdong, China Phone: , Fax: , [email protected] ABSTRACT The working principles and the basic features of air conditioning water heater (ACWH) system are introduced in this paper. The air conditioning water heater system can operate in five modes: water-heating only, space-cooling and water-heating, space-heating and water-heating, space-cooling, space-heating. Comparatively, the system can provide much better energy performance and higher equipment utilization throughout a year, and cause less thermal pollution than heat pump water heater and common air conditioner. A prototype with five modes was assembled and tested at the ambient temperature from -7 to 43, especially when frosting. When it works in the water-heating mode, it can supply hot water within two minutes, and the condensing pressure is just same with common air conditioner. When some modes switch, the temperature of the outlet hot water is constant. Theoretical analysis and experimental study were done to the ACWH in this thesis: 1. The prototype was tested in the air-conditioner laboratory of GREE. The testing data indicate that the prototype accords well with the national standards of air conditioner and heat pump water heater. 2. Based on the experimental results, analysis was done on the ACWH in main operating modes and some important conclusions were given. The results indicate that the new system can save energy through multi-duties, and it can work stably in five work modes with high efficiency. Compared with other models, the new system also includes air-conditioning unit and water heater unit, but with fewer components and higher reliability. Based on common air conditioner, this system can offer a practicable solution coupling air conditioner and water heater. It must be changing the markets of both air conditioner and water heater. 1. INTRODUCTION The heat pump water heater (HPWH) has been used since 19s, mainly for household applications. It absorbs heat energy from the ambient air to acquire hot water. In the last 2 years, the study intends to design heat pump water heater with high reliability and practicability, and many manufacturers turn to offer this production based on environmental protection and energy saving. In South Africa, HPWH has penetrated 16 percent of the market share for commercial water heaters. Because of the highly primary cost, it is difficult to become the alternative to the common water heater. However, if we can offer an air conditioner coupled with HPWH system, which can act as air conditioner and water heater with the main components such as heat exchangers, compressor, four-way valve, and capillary tube, the primary cost will be reduced and it can realize multifunction easily. In summer, with the recovery of the waste heat of condensation, it can offer free hot water, and also can improve the coefficient of performance (COP) of the air conditioner. When air conditioner is not required in spring and autumn, it can operate in HPWH mode. As the enhancement of the yearround utilization, it can be more efficient and is expected to become a strategy solving the air conditioning and hot water applications. Here we demonstrate an air conditioning water heater (ACWH) system, and the performance analysis is described in this article.
3 221, Page 2 2. THE PRINCIPLE OF ACWH The schematic diagram of air conditioning water heater system is shown in Figure 1. The system can offer the following five operating modes. Mode 1 is only for heating water; mode 2 can act as space-cooling and waterheating; mode 3 can realize both space-heating and water-heating; the other two modes are the same with the common air-conditioning circles. The switching among all these modes is by means of on-off controls of the solenoid valves and four-way valve. Each mode will be demonstrated as follows. Water valve One-way valve Water tank Compressor Water-refrigerant heat exchanger Four-way valve Inlet valve Valve 1 Pump Water inlet Separator Throttle valve Air-cooled condenser Valve 2 One-way valve Capillary 1 Evaporator Capillary 2 Figure 1: The schematic diagram of air conditioning water heater system 2.1 Water Heating Mode The system can operate in two heating modes. The one is direct heating water; the other is heating water with water recycle in the adiabatic water tank. The controller can adjust the operating mode according to the water level sensors in the tank. A water valve is placed at the hot water outlet which can be adjusted to control the water flow and keep the condensing pressure constant. When the tap water goes into the water-refrigerant heat exchanger (WRHE), it will be heated to - directly within two minutes. If needed, the outlet water temperature can be set by adjusting the water valve. As shown in Figure 1, when the power is on, the compressor sucks low-pressure refrigerant gas and then discharges high-pressure gas into water-refrigerant heat exchanger (WRHE), where refrigerant is condensed and water is heated directly. After heat exchanges, the liquid refrigerant flows across four-way valve, then it is throttled to lowtemperature and low-pressure liquid and gas by an electronic expansion valve. Refrigerant flows into outdoor aircooled condenser where it is evaporated and becomes low-pressure gas. When the low-pressure gas returns to the compressor, the circle begins again. In this mode, valve 1 is closed and valve 2 is open. When heating water, the outdoor air-cooled unit acts as evaporator, and the indoor fan doesn t run. The COP w is presented as a function of power Q w and the electric power W as shown in Equation (1). COP w =Q w / W=MC T (1) Where M is the mass flow of water; C is the specific heat of water; T is the water temperature difference between outlet and inlet of the water-refrigerant heat exchanger (WRHE).
4 221, Page Space-cooling and Water-heating (SCWH) Mode In summer, with the recovery of condensing heat, the indoor air is cooled down at the same time. Compared with water-heating mode, the high-temperature refrigerant is also condensed in the WRHE directly, and then goes through the air-cooled condenser to be super-cooled where the outdoor fan doesn t run. It is throttled by capillary 1 to low-temperature liquid and gas, and the indoor air exchanges heat with returned refrigerant. In this mode, valve 1 is open and valve 2 is closed. This mode can act as space cooling and water heating at the same time. However, it is not necessary to recover the entire condensing heat which can be released in the air-cooled condenser. The total capacity is the sum of cooling capacity Q c and heating capacity Q w, and then total COP cw can be shown as the Equation (2). COP cw =(Q c Q w )/W (2) 2.3 Space-heating and Water-heating Mode Refrigerant flows across WRHE, evaporator, capillary 2, capillary1, and air-cooled condenser in turn. Space-heating and Water-heating can realize in theory. This mode sometimes may not meet customers expectations, so that it must operate combined with the water-heating mode and spacing-heating mode. If needed, an electric heater is available. 2.4 Space-cooling Mode and Space-heating Mode In these two modes, refrigerant doesn t flow across WRHE or the water pump and inlet valve are closed, and the condensing heat is completely released by the outdoor or indoor heat exchanger. In fact, it is the same with a normal air conditioner, and is not described any more as above. In summer, space-cooling mode can be replaced by the SCWH mode, which can use the water-cooled and air-cooled heat exchangers at the same time. The performance of the system will be improved significantly with the enhancement of heat transfer. 3. EXPERIMENTS Experimental research was performed at an air-enthalpy test laboratory which can also supply water with required temperature and mass flow. The laboratory includes outdoor chamber, indoor chamber and control room. It consists of insulated walls, air-handling equipments, temperature and humidity collection system, air volume testing equipment, electric control system and computer handling unit. The cooling and heating capacity can be tested by air-enthalpy test. Air handling equipments are provided in both test chambers to control the dry bulb and wet bulb temperatures, as well as humidity. The indoor unit of air conditioning was placed in one chamber; the outdoor unit and adiabatic storage tank were placed in another chamber. T-type thermocouples were placed at each temperature test point and pressures were tested by the pressure sensors. All the testing data can be collected and displayed by the computer handling system. Table 1: Experimental test conditions in this study Outdoor chamber, Indoor chamber, Inlet/outlet water Operating Modes Dry/wet bulb Dry/wet bulb temperature, temperature temperature Mode 1 Water-heating only -7~43/- 2/1 9~3/ Mode 2 Space-cooling and water-heating 3/24 27/19 1/ Mode 3 Space-heating and water heating 7/6 2/1 9/ Mode 4 Space-cooling 3/24 27/19 - Mode Space-heating 7/6 2/1-3.1 Prototype Design The prototype includes outdoor unit, indoor unit, and an adiabatic storage tank. Based on a common air conditioner, the system adds a water-refrigerant heater exchanger, a storage tank, several solenoid valves, and water pump. The
5 221, Page 4 storage tank is an insulated cylinder and water capacity is about 8L. The prototype was designed based on the schematic diagram shown in Figure Experimental Test Conditions In mode 1, the ambient temperature was from -7 to 43, and the inflow water temperature was from 9 to 3. The outlet water temperature was set to by adjusting the water valve. The other four modes operated only in the nominal test conditions according to the national standards of air conditioner and heat pump water heater. The experimental test conditions are shown in Table RESULTS This study emphasizes on the direct heating water. Mode 1 was tested in temperature conditions, while mode 2 just operated in the standard testing condition shown in table 1. The prototype is different from a common heat pump water heater, which can offer hot water within 2 minutes by means of heat transfer of large temperature difference. The experimental results were discussed combined with the first two modes as follows. 4.1 Hot Water Output The curves of hot water output are shown in Figure 2 at different inflow water and ambient temperatures. As shown in Figure 2, the hot water output tends to rise more rapidly at higher ambient temperature or inflow water temperature. It can offer about 4L hot water each hour when the inflow water temperature is 1 and ambient temperature is 2. From this figure, we can know that the hot water output is relative to the parameters of the inflow water and ambient air. When the ambient temperature is 3 and the inflow water temperature is 4, the hot water output is about 8L, while it decreases sharply to 12L at -7 ambient temperature and inflow water temperate. The mass flow is also various in different conditions, so that the hot water output changes accordingly. Therefore, we should choose the equipment according to the largest hot water consumption in cold weather. Figure 2: Hot water output vs. inflow water and ambient temperatures 4.2 Variation of System Parameters Experimental results at variable inflow water and ambient temperatures are shown in Figure 3-6. As shown in Figure 3, the increase of inflow water temperature causes that the heating power increases a little, and the heating capacity decreases about 1~2W, so the COP w decreases. Compared with Figure 3, Figure 4 shows that as the ambient temperature rises, the heating capacity increases significantly, but the power consumption does not increase greatly. Therefore, the COP w increases. Figure shows that as inflow water temperature rises, the outlet water temperature, the discharge temperature and outlet refrigerant temperature of WRHE do not increase significantly, and the inlet refrigerant temperature keeps constant at first and then decreases obviously. As seen in Figure 6, because the outlet water temperature is constant,
6 221, Page the condensing pressure is almost stable at about 2.1 MPa, while the evaporating pressure increases with the rise of ambient temperature. Capacity,Power, kw Heating Capacity Heating Power Inflow Water Temperature, Capacity, Power, kw Heating Capacity Heating Power Ambient Temperature, Figure 3: Heating capacity, power and vs. inflow water temperature Figure 4: Heating capacity, power and vs. ambient temperature Temperature, Outlet Water Temperature Discharging Temperature Inlet Refrigerant Temperature Outlet Refrigerant Temperature Inflow water temperature, Pressure,1 Pa Evaporating Pressure Condensing Pressure Ambient Temperature, Figure : Experimental results of variable inflow water temperature Figure 6: Pressure vs. ambient temperature In mode 2, when the indoor air temperature is cooled down, and the condensing temperature is constant, the compression ratio will increase gradually even to be overloaded, especially in cold weather. For the sake of stability and safety, it is necessary to restrict the compression ratio. When the room temperature meets the limited value, the system will switch to water-heating mode, and the evaporator turns to outdoor air-cooled heat exchanger, so that the compression ratio can be controlled during the operation period in water-heating mode. Generally, when pipe temperature is below -2 in the indoor unit, the freezing protection will be effective, and the indoor fan doesn t run any more. Then the compression ratio decreases, and the evaporating pressure rises obviously. In cold weather, the compression ratio in mode 1 also increases gradually because of frosting, so it is important to defrost in time, which makes the discharging temperature and evaporating pressure under control. 4.3 Heating Water of Large Temperature Difference In Figure 7, the results of measured temperatures in the characteristic process points are presented. During operation of the system, the inlet refrigerant temperature (T r, i ) was 76 C, and the condensing temperature (T k ) was about 3 C. The outlet Refrigerant temperature of WRHE (T r, o ) was kept constant to 42 C. The degree of super-cooled was no less than 1 C. When inflow water temperature (T w, i ) is 1 C, the outlet water temperature (T w, o ) can reach C. By means of heat transfer of large temperature difference, sensible heating effect is remarkable. As the flow decreases, it is easy to realize high outlet water temperature even above the condensing temperature. For the HPWH adopting recycle heating water mode, as the inflow water temperature increases gradually, the COP w and heating capacity decrease sharply, and the system will be easy to be overloaded. However, for this direct water-heating mode, maximum discharging pressure is just about 2.1MPa, which is well within the safe compressor operating range.
7 221, Page 6 Temperature, Tr,o=42 Tw,i=1 Tk=3 Tr,i=76 Tw,o= Refrigerant Temperature Water Temperature Relative Position of Heat Exchanger Figure 7: Temperatures in the characteristic process points, 2 ambient temperature in mode Coefficient of Performance Figure 8 shows that the COP w of water-heating mode is from 1.8 to. at different ambient temperatures. As the ambient temperature rises, the COP w also increases. When the ambient temperature is -7, the water heating is about 1.8. In mode 2, total COP cw is the sum of COP w and COP c. The heating and cooling capacities are 29743W and 12198W, respectively, and the total COP cw of this system is about 6.8. The of heating water is above 4., and the COP c reaches 2.8, which is expected to be higher when the outlet hot water temperature is lower than. When the indoor air temperature drops, the total COP cw also decreases. Then it turns to the water-heating mode, and the overcharged refrigerant will be removed to operate at optimal heating water cycle. On the other hand, when the water in the tank meets the limited water level, the outdoor fan runs and the condensing heat is dispersed by the aircooled heat exchanger. All these indicate that the air conditioning water heater system can operate with high efficiency and save energy even at low ambient temperature Ambient temperature, Figure 8: Curve of water-heating mode. CONCLUSIONS According to the experimental results, the air conditioning water heater system can operate in five modes, and it can replace air conditioner and water heater. In HPWH mode, cold water can be heated to directly which is well within the safe operating range. Compared with the traditional air conditioner and water heater, the prototype can supply hot water in time, and it improves the system s all-year utilization. The highest COP w in water-heating mode is., and the nominal COP cw is 6.8 in mode 2, which is expected to be higher for this prototype based an air conditioner with higher COP. The ACWH provides an ideal strategy solving the hot-water supply and air-
8 221, Page 7 conditioning at the same time. The results indicate that the new system can save energy through multi-duties, and it can work stably in several work modes with high efficiency. NOMENCLATURE COP coefficient of performance ( ) Subscripts ACWH air conditioning water heater ( ) c cooling W power consumption (W) r refrigerant C specific heat (kj/kg. ) k condensing Q heat-flow rate (W) w water T temperature ( ) i inlet M mass flow (kg/h) o outlet REFERENCES Jie J., Gang P., Tin-tai C., Wei H., 2, Performance of Multi-functional Domestic Heat-pump System, Applied Energy, Vol.8, p Huimin J., Yang W., Uiliang M., Yang Y., 2, Experimental Research on the Dynamic Characteristics of the Energy-saving Type Air Conditioner with Domestic Hot Water Supply, China HV&AC, Vol. 3: p
9
Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 00 Measurement And Application of Performance Characteristics Of A Free Piston
Domestic air-conditioner and integrated water heater for subtropical climate
Applied Thermal Engineering 23 (23) 581 592 www.elsevier.com/locate/apthermeng Domestic air-conditioner and integrated water heater for subtropical climate Jie Ji a, Tin-tai Chow b, *, Gang Pei a, Jun
Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets
2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
Experimental Evaluation Of The Frost Formation
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Evaluation Of The Frost Formation Yusuke Tashiro Mitsubishi
Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling
for Simultaneous Heating and Cooling F. Sustainable Energy Centre, University of South Australia Mawson Lakes Boulevard, Mawson Lakes 5095 AUSTRALIA E-mail: [email protected] Abstract The high efficiency
Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under
Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering Experimental Analysis of an Automotive Air Conditioning System With Two-Phase
Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Testing methods applicable to refrigeration components and systems
Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University
Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Experimental Analysis of a Variable Capacity Heat Pump System Focusing on
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
The Development of a Frost-Less Heat Pump
The Development of a Frost-Less Heat Pump V. C. Mei, R. E. Domitrovic, and F. C. Chen, Oak Ridge National Laboratory J. K. Kilpatrick, Tennessee Valley Authority ABSTRACT There are two major concerns associated
UNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
GREE, MAKING BETTER AIR CONDITIONERS
GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI Add:Jinji RD.Qianshan Zhuhai 519070,Guangdong,China Tel: (+86-756)8614883 Fax: (+86-756)8627140 Email: [email protected] http://www.gree.com.cn Heat Pump Water Heater
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"
Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced
Heat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests
August 26, 2015 REPORT #E15-294 Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests Prepared by: Energy 350 107 SE Washington St., Suite 145 Portland, OR 97214 Northwest Energy
Schedule 3(A) Room Air Conditioners
Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
Analytical Study on the Performance Characteristics of a Liquid Injection Refrigeration Cycle.
urdue University urdue e-ubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Analytical Study on the erformance Characteristics of a Liquid Injection Refrigeration
How to choose a heat pump and use it wisely
How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by
Increasing the evaporation temperature with the help of an internal heat exchanger
Increasing the evaporation temperature with the help of an internal heat exchanger A. TAMBOVTSEV (a), H. QUACK (b) (a,b) Technische Universität Dresden, D-01062, Dresden, Germany (a) Fax: (+49351) 463-37247,
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Refrigerant Charge and Ambient Temperature Effects on the Refrigeration Cycle of a Small Capacity Food Freezer
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 24 Refrigerant Charge and Ambient Temperature Effects on the Refrigeration Cycle
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Technical Service Manual. Version One
[Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
New Trends in the Field of Automobile Air Conditioning
New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic
TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov. 2003 to Mar. 15, 2004.
Proceedings World Geothermal Congress 2005 Antalya, Turkey, 24-29 April 2005 A Case Study of Ground Source Heat Pump System in China Jun Zhao, Chuanshan Dai, Xinguo Li, Qiang Zhu and Lixin Li College of
Design of a Heat Pump Assisted Solar Thermal System
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Design of a Heat Pump Assisted Solar Thermal System Kyle G. Krockenberger Purdue
SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange
Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange ING. TOMMASO FERRARESE Thermodynamics Laboratory Engineer
High Pressure Ammonia Systems New Opportunities
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 High Pressure Ammonia Systems New Opportunities Andy Pearson Star Refrigeration
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE
DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE Md Shahid Imam, Dr.M.Shameer Basha, Dr.Md.Azizuddin, Dr. K.Vijaya Kumar Reddy 4 M.Tech HVAC II Yr, Royal Institute of Technology & Science Chevella R.R Dist
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
Hot Water. Heat pump water heaters. Residential and Commercial R410a
Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
The Second Law of Thermodynamics
The Second aw of Thermodynamics The second law of thermodynamics asserts that processes occur in a certain direction and that the energy has quality as well as quantity. The first law places no restriction
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A Jignesh K. Vaghela Assistant Professor, Mechanical Engineering Department, SVMIT, Bharuch-392001, (India) ABSTRACT
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
Basic Technology Series
Basic Technology Series Fundamentals of Car Air Conditioning 2007 Air Conditioning #003 The Rear Cooler Construction Fan Fan Filter Figure A : Trunk Figure B : Overhead Dual Air-Conditioner In This Issue
Development and testing of a multi-type air conditioner without using AC inverters
Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Condensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
P. A. Hilton Ltd REFRIGERATION & AIR CONDITIONING VAPOUR COMPRESSION HEAT PUMPS VENTILATION VOCATIONAL
REFRIGERATION & AIR CONDITIONING Refrigeration and air conditioning is an aspect of modern life that is accepted almost without thought. Food storage, the long distance transport of foodstuffs, stockpiling
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
Technical data. Danfoss DHP-A
Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs
CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank
CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS Blank SONNTAG/BORGNAKKE STUDY PROBLEM 7-1 7.1 A car engine and its fuel consumption A car engine produces 136 hp on the output shaft with a thermal efficiency
Silicagel-water adsorption cooling prototype system for mobile air conditioning
Silicagel-water adsorption cooling prototype system for mobile air conditioning R. de Boer S.F. Smeding S. Mola Paper to be presented at the Heat Powered Cycles Conference 09 Berlin, 7 to 9 September 2009
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =
POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES
POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES M. Bantle 1, I. Tolstorebrov, T. M. Eikevik 2 1 Department of Energy Efficiency, SINTEF Energy Research, Trondheim, Norway,
The Development of Heat Pump Water Heaters Using CO 2 Refrigerant
The Development of Heat Pump Heaters Using CO 2 Refrigerant Shigeharu TAIRA* * DAIKIN Industries, Ltd., 1000-2 Aza-Ohtani, Okamoto-cho, Kusatsu, Shiga 525-8526 Abstract heating consumes about one-third
Test Report issued under the responsibility of:
Test Report issued under the responsibility of: TEST REPORT EHPA-DACH Testing Regulation Supplemental requirements for granting the international quality label for heat pumps Testing of Air/Water Heat
CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
How To Calculate The Performance Of A Refrigerator And Heat Pump
THERMODYNAMICS TUTORIAL 5 HEAT PUMPS AND REFRIGERATION On completion of this tutorial you should be able to do the following. Discuss the merits of different refrigerants. Use thermodynamic tables for
Final Report by Air Conditioner Evaluation Standard Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural
Final Report by Air Conditioner Evaluation Standard Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural Resources and Energy Regarding air conditioners, the target
HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)
HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HEATER SYSTEM 1. Heater System A: GENERAL A semi-center type integrated air conditioning unit is used, where a high performance heater core and an evaporator core
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
RESEARCH HIGHLIGHT. The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption
RESEARCH HIGHLIGHT December 2014 Technical Series 14-104 The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption INTRODUCTION Heat pump water heaters are one of the most energyefficient
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers
COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
Waste Heat Recovery through Air Conditioning System
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning
8. Refrigeration. 4. Liquid. Refrigerant. 4. Liquid Refrigerant. Figure 8.1 Refrigeration system layout (single stage)
2. Vapor 8. Refrigeration 4. Liquid 3. Condenser 5. Receiver 4. Liquid 1. Compressor 6. Throttling Device 12. Electricity 2. Vapor 8. Recirculator 4. Liquid 7. Liquid/Vapor 7. Liquid/Vapor 10. Warm Air
Basic Operating Characteristics of CO2 Refrigeration Cycles With Expander-Compressor Unit
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Basic Operating Characteristics of CO2 Refrigeration Cycles With Expander-Compressor
Automobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
Cool Design for Homes and Offices
AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive, and designed to fit any space: there are Cool Design for Homes and Offices a lot of reasons why Air Blue air conditioners
SOLAR COOLING WITH ICE STORAGE
SOLAR COOLING WITH ICE STORAGE Beth Magerman Patrick Phelan Arizona State University 95 N. College Ave Tempe, Arizona, 8581 [email protected] [email protected] ABSTRACT An investigation is undertaken of a
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description
Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
HEATER, AIR CONDITIONING AND VENTILATION
55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS
WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of
UNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY