1 Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory Gaithersburg, Maryland USA Telephone: Telefax: Web Site: International Appliance Technical Conference, March 25-27, 2002, Lexington, KY, USA
2 Page 1 ABSTRACT This investigation compares performance ratings obtained when testing water-source heat pumps using the Air-Conditioning and Refrigeration Institute (ARI) Standard 320 and the International Organization for Standardization (ISO) Standard Multiple tests included a ducted 1.75 kw (0.5 ton) unit and a non-ducted 3.52 kw (1.0 ton) unit. Air external static pressure and water flow were varied at the ISO conditions to determine the correction in capacity and total power mandated by the ISO standard. ISO cooling capacity for the first and second units were 0.1 % higher and 1.1 % lower than the ARI capacity, respectively. ISO cooling energy efficiency ratio (EER) for the first and second units were 4.5 % higher and 3.9 % lower than the ARI EER, respectively. ISO heating capacity for the first and second units were 4.8 % lower and 2.9 % lower than the ARI capacity, respectively. ISO heating coefficient of performance (COP) for the first and second units were 6.2 % higher and 1.0 % lower than the ARI COP, respectively. INTRODUCTION Globalization of economies creates new marketing opportunities and increases the importance of international standards. The adoption of an international standard offers substantial economic benefits, but the transition from a national to an international standard poses a question of whether the ratings obtained by using these standards are equivalent. This study was concerned with the rating obtained for water-source heat pumps tested using two standards: the standard developed by the Air- Conditioning and Refrigeration Institute (ARI), ARI Standard 320 (1998), and the standard developed by the International Organization for Standardization (ISO), ISO Standard (1998). On January 1, 2000, the ARI adopted the ISO standard as the basis for its certification programs. The standard developed by the American Society of Heating, Refrigerating, and Air- Conditioning Engineers, ASHRAE Standard 90.1 (1999), references both the ARI standard and the ISO until October 29, 2001, with the ISO standard designated as the exclusive standard starting at this date. The goal of this study was to evaluate the differences in rated energy efficiency ratio (EER) for cooling operation and coefficient of performance (COP) for heating operation obtained when using these two test methods. The test and rating results obtained when using the ARI standard and ISO standard are expected to be somewhat different because of three inherent differences between these standards: (1) The first difference is the slightly different dry-bulb and dew-point temperatures. These different operating conditions are related to different temperature scales (Fahrenheit vs. Celsius) and do not
3 Page 2 represent a significant difference in the test operating temperatures. (2) The second difference between the ARI standard and the ISO standard is the external air static pressure applied during the test. Under the ARI standard, the unit must be tested while operating against the external air static pressure that is specified by the standard for a given system s capacity. Under the ISO standard, the unit must be tested against static pressure specified by the manufacturer. After completion of the test, a credit is given for the indoor fan power to the total energy input, and the system capacity is adjusted for the heat added by the indoor fan. (3) The third difference is the treatment of the energy input to the water pump. Under the ARI standard, this energy input is not included in the calculation of the total energy input, and the standard specifies the water flow rate that results in a 5.6 C (10.0 F) temperature change across the heat exchanger. Under the ISO standard, the test must be performed at the mass flow rate specified by the manufacturer, and the energy input to the water pump is measured and included in the total energy input. The following sections present the experimental apparatus, systems tested, and laboratory test results obtained by the ARI and ISO standards. Tests of one ducted and one non-ducted watersource heat pump provided comparison data for these two test procedures. In addition to standard testing carried out using the two standards, expanded testing was performed under ISO testing conditions with varied air external static pressure and water flow rates. These tests provided information regarding the effect on the rating of these two parameters that are specified by the manufacturer of the heat pump. Payne and Domanski (2001) presented a full report of this study. EXPERIMENTAL SETUP The main components of the experimental apparatus included the tested heat pump, the nozzle chamber, and the pull-thru fan. The water-source heat pump was supplied with distilled water at the appropriate temperature and flow rate. All measurements were collected according to ASHRAE Standard EXPERIMENTAL PROCEDURE AND TEST CONDITIONS For both cooling (Tables 1 and 2) and heating (Tables 3 and 4) tests, the refrigeration chamber was maintained within 0.3 o C (0.5 o F) of a constant drybulb temperature and dew-point temperature. In the cooling mode, the water flow rate was adjusted to give a 5.6 C (10.0 F) temperature increase for the ARI standard and as specified by the manufacturer for the ISO standard.
4 Page 3 Table 1: ARI cooling conditions Location Setpoint Tolerance Indoor Drybulb 26.7 o C (80.0 o F) Indoor Dewpoint Inlet Water Outlet Water 15.8 o C (60.4 o F) 29.4 o C (85.0 o F) 35.0 o C (95.0 o F) Table 2: ISO cooling conditions Location Setpoint Tolerance Indoor Drybulb Indoor Dewpoint Inlet Water Water Flow 27.0 o C (80.6 o F) 14.7 o C (58.5 o F) 30.0 o C (86.0 o F) Specified by the manufacturer Table 3: ARI heating conditions Location Setpoint Tolerance Indoor Dry-bulb 21.1 o C (70.0 o F) Inlet Water 21.1 o C (70.0 o F) Water Flow Same water flow as in the cooling test In the heating mode, all fan settings and water flow rates were maintained the same as the respective cooling tests. For the ISO standard, the fan power correction was added to the heating capacity and to the total power. Table 4: ISO heating conditions Location Setpoint Tolerance Indoor Dry-bulb 20.0 o C (68.0 o F) Maximum Dew Point 11.7 o C (53.1 o F) 20.0 o C Inlet Water (68.0 F) Water Flow Same as in the cooling test above UNITS TESTED, TESTS PERFORMED AND DATA REDUCTION Unit 1 was a ducted design with a nominal cooling capacity of 1.75 kw (0.5 ton). Unit 2 was a non-ducted console type design with a nominal cooling capacity of 3.52 kw (1.0 ton). Neither unit included a pump for circulating water through the water coil. For the non-ducted unit, the air static pressure at the exit of the unit was maintained at zero for all tests. Table 5 below summarizes the tests performed on each unit for the cooling and heating modes. The tests designated as Modified ISO were performed with increased and decreased air static pressure and water coil pressure drop to examine their effects upon EER and COP. For the ISO standard, a correction to the air-side capacity and total power were calculated based on the external static air pressure drop of
5 Page 4 the air coil and the water pressure drop across the water coil. This correction Table 5: Test matrix summary for cooling and heating modes External Air Static Pressure* Water Coil Pressure Drop ARI 320 Normal Normal ISO Normal Normal High Normal Modified Low Normal ISO Normal High Normal Low * The non-ducted unit was maintained at zero exit static pressure for all tests. was calculated by Equation 1 with the p being the static pressure drop of the fluid considered, air or water. The fan power correction was added to the total power consumption and subtracted from the total capacity for the cooling tests. The fan power correction was added to the total power consumption and capacity for the heating tests. Pumping power was added to the total power for all heating and cooling tests. q p Φ pa = (1) η is the pump or fan power Φ pa adjustment (watts), q is the fluid flow rate (L/s), p is the measured pressure drop (Pa), and η is as specified by ISO Standard Total power was measured by a wattmeter during the test period, which was never shorter than 30 min. The total power measurement was combined with the water coil capacity as a secondary calculation of the air-side capacity. For the ARI standard, the reported capacity is based on the airside measurements. For the ISO standard, the reported capacity is the average of the air-side and secondary method capacities. UNIT 1: COOLING TEST RESULTS Table 6 summarizes the cooling test results for Unit 1, the ducted 1.75 kw (0.5 ton) nominal cooling capacity system. For the ISO test, the table presents detailed information; the uncorrected capacity, power, and EER are presented first. The following entries are system operating parameters, ISO corrections for capacity and power, and the corrected capacities and EERs. These corrected values are the reported capacities and EERs when tests are performed using the ISO method. The last entries are the results of the ARI tests. Under the ARI cooling conditions, air-side capacity and EER were 2352 W (8024 Btu/h) and 13.21, respectively. For the ISO cooling conditions, air-side capacity and EER were 2353 W (8028 Btu/h) and Correcting the capacity and power for the fan and pump, according to Equation 1, changed the EER from (the uncorrected value in Table 6) to (an increase of 7.1 %). Variation in air static pressure has the greatest effect upon capacity and EER due to the capacity correction
6 Page 5 and fan power correction required by the ISO standard. For the low and high air static pressure tests, air-side capacity changed by 0.3 % and 3.6 %, respectively, as air volume flow changed by +30 % and 30 %. EER change due to the changes in air volume flow rate were 0.7 % and 2.2 %. As water flow was varied by 10 % and +10 %, ISO air-side capacity changed by 1.6 % and +0.1 %, respectively. EER changed by 1.4 % and +0.7 %. ARI capacity was 1.6 % higher than the ISO uncorrected capacity. ARI EER was 1.6 % higher than the ISO uncorrected EER. These differences were due to the differences in test conditions (dry bulb and dew point). ISO capacity increased by 1.6 % due to correcting for fan heat input according to Equation 1. ISO EER increased by 7.0 % due to the corrections for fan heat, fan power, and pump power. The pump power correction was 1.5 % of the total power for all tests. UNIT 1: HEATING TEST RESULTS Table 7 summarizes the heating test results for Unit 1. Under the ARI heating conditions air-side capacity and COP were 3270 W (11157 Btu/h) and 4.81, respectively. For the ISO heating conditions air-side capacity and COP were 3114 W (10624 Btu/h) and Variations in air static pressure had the greatest effect upon capacity and efficiency due to the capacity correction and fan power correction. For the low and high air static pressure tests, air-side capacity changed by 1.8 % and -1.6 %, respectively, as air volume flow changed by +30 % and - 30 %. COP change due to the changes in air volume flow rate were 1.7 % and -2.3 %. As water flow was varied by - 10 % and +10 %, ISO air-side capacity changed by -0.8 % and +0.7 %, respectively. ISO COP changed by +0.2 % and +0.0 %. ARI capacity was 1.2 % higher than the ISO uncorrected capacity. COP was 1.0 % lower than the ISO uncorrected COP. These differences were due to the differences in test conditions (dry bulb and dew point). ISO capacity decreased by 0.3 % due to correcting the tests for fan capacity. The combined effects of fan heat, fan power, and pump power increased ISO COP by 5.0 %. UNIT 2: COOLING TEST RESULTS Unit 2 was a non-ducted 3.52 kw (1.0 ton) nominal cooling capacity, console heat pump designed for wall mounting with no ductwork; therefore, air static pressure was maintained at zero for all tests to simulate free discharge to the indoor space. Table 8 summarizes the cooling test results for Unit 2. Under the ARI cooling conditions, air-side capacity and EER were 3085 W (10528 Btu/h) and 14.18, respectively. For the ISO cooling conditions, air-side capacity and EER were 3051 W (10412 Btu/h) and ARI capacity was 1.1 % higher than the ISO uncorrected capacity.
7 Page 6 EER was 2.4 % higher than the ISO uncorrected EER. These differences were due to the differences in test conditions (dry-bulb and dew-point temperatures). The pump power was less than 2.8 % of the total power for all tests. ISO EER decreased with respect to the ISO raw results by 1.6 %. Changes in water flow rate through the water coil produced a small effect upon the ISO cooling test results. As water flow was varied by 20 % and +20 %, ISO averaged capacity changed by 1.3 % and 0.3 %, respectively. EER changed by 2.8 % and +0.2 %. UNIT 2: HEATING TEST RESULTS Table 9 summarizes the heating test results for Unit 2. Table 9 does not include tests at a low water flow rate. Two tests were performed at a lowered water flow rate, but they were excluded due to unacceptable variations (pulses) in water flow rate through the water coil. ARI air-side capacity and COP were 4668 W (15927 Btu/h) and For the ISO normal airflow heating conditions air-side capacity and COP were 4534 W (15469 Btu/h) and When water flow rate was increased by 16.9 %, ISO capacity increased by 0.8 % and ISO COP decreased by 1.6 %. For the high water flow rate Percent Difference (%) ISO Percent difference with respect to ARI cooling capacity DUCTED NON-DUCTED case, the pump power correction was 3.5 % of the total power. ARI capacity was 1.2 % higher than the ISO uncorrected capacity. ARI COP was 2.6 % lower than the ISO uncorrected COP. The pump power correction was less than 2.8 % of the total power. SUMMARY The purpose of this experimental investigation was to examine differences in ratings obtained from tests according to ARI Standard 320 and ISO Standard This investigation included tests at different volumetric flow rates of air and water to examine the effect of capacity and power corrections on the rating obtained by the ISO test procedure. Figures 1 and 2 summarize results for capacity changes. ISO Percent difference with respect to ISO cooling capacity Figure 1: Cooling capacity comparison
8 Page 7 Percent Difference (%) ISO Percent difference with respect to ARI heating capacity cooling capacity for the ducted unit and non-ducted unit were 0.1 % higher and 1.1 % lower than the ARI capacity, respectively. In the heating mode, the ISO capacities were 4.8 % lower and 2.9 % lower than the ARI capacities. The range of capacity change was from 3.6 % to 1.8 %. As shown by Figure 3, the ISO cooling EERs for the ducted unit and the non-ducted unit were 4.5 % higher and 3.9 % lower than the ARI EERs, respectively. The ISO heating COPs (Figure 4) for the first and second units were 6.2 % higher and 1.0 % lower than the ARI COPs, respectively. The range of ISO EER and ISO COP changes due to DUCTED NON-DUCTED LOW NON-DUCTED NORMAL Percent difference with respect to ISO heating capacity Figure 2: Heating capacity comparison Percent Difference (%) ISO Percent difference with respect to ARI cooling EER variation of the external air static pressure and water flow rate was from 2.8 % to 1.8 %. The uncertainties for test results were calculated applying the uncertainty propagation law and considering the uncertainties of all involved temperature, pressure, and power measurements. For the 95 % confidence level, the maximum uncertainty for EER and COP was found to be 5.2 % and 5.9 %, respectively. Hence, the differences between the ISO and ARI ratings are near or within the limits of uncertainty. DUCTED NON-DUCTED LOW Percent difference with respect to ISO cooling EER Figure 3: Cooling efficiency comparison
9 7 6 ISO Payne and Domanski Page 8 5 Percent Difference (%) Percent difference with respect to ARI heating COP Percent difference with respect to ISO heating COP -1-2 DUCTED NON-DUCTED LOW NON-DUCTED NORMAL -3 Figure 4: Heating efficiency comparison REFERENCES ANSI/ASHRAE Standard Methods of testing for rating unitary air conditioning and heat pump equipment. American Society of Heating, Refrigerating and Air-Conditioning Engineers Tullie Circle NE, Atlanta, GA, USA. ARI Standard Standard for water-source heat pumps. Air- Conditioning and Refrigeration Institute North Fairfax Drive, Arlington, VA, USA. ASHRAE Standard Energy Standard for Buildings Except Low-Rise Residential Buildings. American Society of Heating, Refrigerating and Air- Conditioning Engineers Tullie Circle NE, Atlanta, GA, USA. ISO Water-source heat pumps-testing and rating for performance-part 1: Water-to-air and brine-to-air heat pumps. International Organization for Standardization. Case postale 56, CH-1211 Geneva 20, Switzerland. Payne, W.,V. and Domanski, P.A., A Comparison or Rating Water- Source Heat Pumps Using ARI Standard 320 and ISO Standard , IR 6803, National Institute of Standards and Technology, Gaithersburg, MD. ACKNOWLEDGEMENT This study was sponsored by the United States Department of Energy, Office of Building Technology, State and Community Programs under contract DE-AI01-99EE The authors thank Dr. Samuel Yana Motta of Honeywell and Mr. David Yashar of for their review and comments on the draft of this report. We also thank Mr. Anthony Downs for his assistance with the testing and analysis of data.
10 Page 9 Cooling Using ISO : Uncorrected Capacity, W Uncorrected Total Power, W Table 6: ARI and ISO cooling test results for Unit 1 External Air Static Pressure Water Coil Pressure Drop Low Normal High Low Normal High 2326 (7935) 2316 (7902) 2227 (7598) 2276 (7766) 2316 (7902) 2318 (7908) Uncorrected EER, Btu/Wh Water Flow, L/s (gpm) (2.0) (2.0) (2.0) (1.9) (2.0) (2.1) Water Temp Change, C ( F) 5.44 (9.8) 5.44 (9.8) 5.38 (9.7) 5.83 (10.5) 5.44 (9.8) 5.17 (9.3) Water Pressure Drop, Pa (psid) (2.00) (2.05) (1.97) (1.60) (2.05) (2.37) Air Flow, L/s (cfm) 155 (328) 142 (301) 127 (270) 141 (299) 142 (301) 143 (302) Air Temp Change, C ( F) (18.4) (19.1) 11.0 (19.8) (19.2) (19.1) (19.3) Air Static, Pa (in H 2 O) 69 (0.28) 78.2 (0.31) 99.4 (0.40) 82 (0.33) 78.2 (0.31) 79 (0.32) ISO Capacity Adjustment: For Fan Heat, W 36 (122) 37 (126) 42 (144) 39 (132) 37 (126) 37 (128) ISO Power Adjustment: For Fan Power, W For Pump Power, W Corrected Capacity, W 2361 (8057) 2353 (8028) 2269 (7742) 2315 (7898) 2353 (8028) 2355 (8036) Corrected EER, Btu/Wh Using ARI 320 Capacity, W 2352 (8024) 2352 (8024) Total Power, W EER, Btu/Wh
11 Page 10 Heating Using ISO : Uncorrected Capacity, W Uncorrected Total Power, W Table 7: ARI and ISO heating test results for Unit 1 External Air Static Pressure Water Coil Pressure Drop Low Normal High Low Normal High 3213 (10964) 3161 (10787) 3112 (10618) 3153 (10757) 3161 (10787) 3198 (10914) Uncorrected COP Water Flow, L/s (gpm) (1.982) (1.97) (1.987) (1.684) (1.97) (2.149) Water Coil Temp (8.5) 4.72 (8.5) Change, C ( F) (8.4) (9.8) (8.5) (7.9) Water Pressure Drop, Pa (psid) (2.046) (1.973) (2.028) 9990 (1.449) (1.973) (2.355) Air Flow, L/s (cfm) (331) 147 (311) (287) (315) (311) (315) Air Coil Temp Change, C ( F) (32.9) 19.0 (34.2) 20.0 (36.0) (34.0) 19.0 (34.2) (34.4) Air Static, Pa (in H 2 O) 82 (0.329) 98 (0.393) 106 (0.427) 91 (0.366) 98 (0.393) 90 (0.362) ISO Capacity Adjustment: For Fan Heat, W 43 (146) 48 (163) 48 (164) 45 (154) 48 (163) 45 (152) ISO Power Adjustment: For Fan Power, W For Pump Power, W Corrected Capacity, W 3170 (10818) 3114 (10624) 3064 (10454) 3107 (10603) 3114 (10624) 3154 (10761) Corrected COP Using ARI 320 Capacity, W 3270 (11157) 3270 (11157) Total Power, W EER, Btu/Wh
12 Page 11 Table 8: ARI and ISO cooling test results for Unit 2 Water Coil Pressure Drop Cooling Low Normal High Using ISO : Uncorrected Capacity, W 3010 (10272) 3051 (10412) 3043 (10382) Uncorrected Total Power, W Uncorrected EER Water Flow, L/s (gpm) (2.15) (2.694) (3.23) Water Coil Temp Change, C ( F) 6.67 (12.0) 5.33 (9.6) 4.44 (8.0) Water Pressure Drop, Pa (psid) (2.09) (3.16) (4.44) Air Flow, L/s (cfm) 158 (335) 157 (332) 157 (333) Air Coil Temp Change, C ( F) (22.3) (22.4) (22.3) Air Static, Pa (in H 2 O) 3.74 (0.015) 2.74 (0.011) 2.74 (0.011) ISO Capacity Adjustment: For Fan Heat, W ISO Power Adjustment: For Fan Power, W For Pump Power, W Corrected Capacity, W 3010 (10272) 3051 (10412) 3043 (10382) Corrected EER Using ARI 320 Capacity, W 3085 (10528) Total Power, W 742 EER 14.18
13 Page 12 Table 9: ARI and ISO normal airflow heating test results for Unit 2 Water Coil Pressure Drop Heating Normal High Using ISO : Uncorrected Capacity, W 4534 (15469) 4571 (15598) Uncorrected Total Power, W Uncorrected COP Water Flow, L/s (gpm) (3.135) (3.666) Water Coil Temp Change, C 4.28 (7.7) 3.72 (6.7) ( F) Water Pressure Drop, Pa (psid) (4.57) (6.114) Air Flow, L/s (cfm) (400) (400) Air Temp Change, C ( F) (38.5) (38.8) Air Static, Pa (in H 2 O) 1.5 (0.006) 1.5 (0.006) Pump Power Correction, W Corrected Capacity, W 4534 (15469) 4571 (15598) Corrected COP Using ARI 320 Capacity, W 4668 (15927) Total Power, W 946 COP 4.94
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Development and testing of a multi-type air conditioner without using AC inverters
Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
Energy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not
Understanding Heating Seasonal Performance Factors for Heat Pumps
Understanding Heating Seasonal Performance Factors for Heat Pumps Paul W. Francisco, University of Illinois, Building Research Council Larry Palmiter and David Baylon, Ecotope, Inc. ABSTRACT The heating
Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS
SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS
Low GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, [email protected] Abstract
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
Laboratory Performance Testing of Residential Window Mounted Air Conditioners
Laboratory Performance Testing of Residential Window Mounted Air Conditioners Jon Winkler Chuck Booten Dane Christensen Jeff Tomerlin April 29, 2012 NREL is a national laboratory of the U.S. Department
Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment
ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2 (Formerly ARI Standard 340/360-2007) 2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Strategy Guideline: HVAC Equipment Sizing
Strategy Guideline: HVAC Equipment Sizing Arlan Burdick IBACOS, Inc. February 2012 This report received minimal editorial review at NREL NOTICE This report was prepared as an account of work sponsored
ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
HAIL EFFECTS ON AIR-CONDITIONER PERFORMANCE
Proceedings of IMECE 2007 2007 ASME International Mechanical Engineering Congress and Eposition November 11-15, 2007, Seattle, Washington, United States IMECE2007-41518 HAIL EFFECTS ON AIR-CONDITIONER
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Energy Impact of Increased Server Inlet Temperature
Energy Impact of Increased Server Inlet Temperature By: David Moss, Dell, Inc. John H. Bean, Jr., APC White Paper #138 Executive Summary The quest for efficiency improvement raises questions regarding
Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE
P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering
TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
Schedule 3(A) Room Air Conditioners
Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression
Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:
Appendix C. Minimum Equipment Efficiency Standards
Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,
Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs
HVAC/R EQUIPMENT Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs As global demand for energy consumption continues to increase, the race to build more
AHRI Standard 1361 (SI) 2016 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners
AHRI Standard 1361 (SI) 2016 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Introduction To VRF: System Overview, Applications, & Savings Opportunities
Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous
Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July 2008. Prepared by
Regency TAFE, SA An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump July 2008 Prepared by Andrew Pang Andrew Pang & Associates Pty Ltd Phone: 0438 188 180 Facsimile: 9331 0898
The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings
4276 The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings Michael J. Brandemuehl, Ph.D., P.E. Member ASHRAE James E. Braun, Ph.D., P.E. Member ASHRAE ABSTRACT
ASHRAE Climatic Data Activities. Dru Crawley Didier Thevenard
ASHRAE Climatic Data Activities Dru Crawley Didier Thevenard ASHRAE American Society of Heating Refrigerating and Air- Conditioning Engineers >50,000 members Major products: Handbooks (Fundamentals, Systems
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL
AMCA International Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air
newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?
engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort
Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998
ABC FOUR CORNERS Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998 Reverse Cycle, High Wall Mounted, Non-Ducted, Single Phase, Single Split System Air Conditioner OPTICAL ACC-25V2 Report No. 30W-07-0038-TRP-221466-0
ANSI/AHRI Standard 1350 (I-P) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings
ANSI/AHRI Standard 1350 (I-P) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings Approved by ANSI on May 19, 2015 IMPORTANT SAFETY DISCLAIMER AHRI does not set
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems ASHRAE TRP-1384 Scott P. Hackel Under the supervision of Professors Greg Nellis and Sanford Klein and the University of Wisconsin
TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning
The Development of a Frost-Less Heat Pump
The Development of a Frost-Less Heat Pump V. C. Mei, R. E. Domitrovic, and F. C. Chen, Oak Ridge National Laboratory J. K. Kilpatrick, Tennessee Valley Authority ABSTRACT There are two major concerns associated
SASO 2663 :2014 ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS
SASO 2663 :2014 (SASO 2663/2012 including the modifications approved in Saudi Council Board No../2014) ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS ENERGY LABELLING
Closed-Loop Ground-Coupled Heat Pump Systems
The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
Testing methods applicable to refrigeration components and systems
Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Research on the Air Conditioning Water Heater System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08
Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.
Hot Dry Climate Air Conditioner (HDAC) Combined Field Test Report
Hot Dry Climate Air Conditioner (HDAC) Combined Field Test Report Prepared for: Southern California Edison Company Refrigeration and Thermal Test Center (RTTC) Design & Engineering Services 6060b N. Irwindale
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE
This article was published in ASHRAE Journal, September 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Public Review Draft. ASHRAE Standard
BSR/ASHRAE Addendum s to ANSI/ASHRAE Standard 62.2-2007 Public Review Draft ASHRAE Standard Proposed Addendum s to Standard 62.2-2007, Ventilation and Acceptable Indoor Air Quality in Low- First Public
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Data Center Heat Rejection
This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
HVAC FORMULAS. TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F. 288,000 BTU/24 hr. 12,000 BTU/hr.
HVAC FORMULAS TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F 288,000 BTU/24 hr. 12,000 BTU/hr. APPROXIMATELY 2 inches in Hg. (mercury) = 1 psi WORK = Force
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance