TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.
|
|
- Silas Skinner
- 7 years ago
- Views:
Transcription
1 TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA + SAP C241BA SPLIT SYSTEM AIR CONDITIONER FILE NO. Indoor Model No. Product Code No. Destination SAP K161GJA S General (50/60Hz) SAP K181GJA S General (50/60Hz) SAP K181MBA S Middle East (50/60Hz) SAP K241GJA S General (50/60Hz) SAP K241MBA S Middle East (50/60Hz) Outdoor Model No. Product Code No. Destination SAP C161GA S General (50Hz) SAP C161JA S General (60Hz) SAP C181GA S General (50Hz) SAP C181JA S General (60Hz) SAP C181MA S Middle East (50Hz) SAP C181BA S Middle East (60Hz) SAP C241GA S General (50Hz) SAP C241JA S General (60Hz) SAP C241MA S Middle East (50Hz) SAP C241BA S Middle East (60Hz) Indoor Unit Outdoor Unit SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA SAP C161GA SAP C161JA SAP C181GA SAP C181JA SAP C181MA SAP C181BA SAP C241GA SAP C241JA SAP C241MA SAP C241BA REFERENCE NO. SM700456
2 Important! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. If Necessary, Get Help This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. Special Precautions WARNING WARNING CAUTION When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. When Installing In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. When Connecting Refrigerant Tubing Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leakfree connection. Check carefully for leaks before starting the test run. When Servicing Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Others CAUTION Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas. i
3 Table of Contents Page 1. OPERATING RANGE SPECIFICATIONS 2-1. Unit Specifications Major Component Specifications Other Component Specifications DIMENSIONAL DATA REFRIGERANT FLOW DIAGRAM PERFORMANCE DATA 5-1. Performance charts Air Throw Distance Chart Cooling Capacity ELECTRICAL DATA 6-1. Electrical Characteristics Electric Wiring Diagrams INSTALLATION INSTRUCTIONS 7-1. Installation Site Selection Remote Control Unit Installation Position Recommended Wire Length and Diameter FUNCTION 8-1. Room Temperature Control Dry Operation Freeze Prevention Outdoor Fan Speed Control TROUBLESHOOTING 9-1. Check before and after troubleshooting Air conditioner does not operate Some part of air conditioner does not operate Air conditioner operates, but abnormalities are observed If a sensor is defective CHECKING ELECTRICAL COMPONENTS Measurement of Insulation Resistance Checking Continuity of Fuse on PCB Ass'y Checking Motor Capacitor MAINTENANCE Changing Address of Remote Control Unit in Indoor Unit APPENDIX INSTRUCTION MANUAL ii
4 1. OPERATING RANGE 50Hz models Outdoor Unit Cooling SAP C161GA SAP C181GA SAP C241GA Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32 C D.B. / 23 C W.B. 43 C D.B. Minimum 19 C D.B. / 14 C W.B. 19 C D.B. Outdoor Unit Cooling SAP C181MA SAP C241MA Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32 C D.B. / 23 C W.B. 52 C D.B. Minimum 19 C D.B. / 14 C W.B. 19 C D.B. 60Hz models Outdoor Unit Cooling SAP C161JA SAP C181JA SAP C241JA Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32 C D.B. / 23 C W.B. 43 C D.B. Minimum 19 C D.B. / 14 C W.B. 19 C D.B. Outdoor Unit Cooling SAP C181BA SAP C241BA Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 29 C D.B. / 19 C W.B. 54 C D.B. Minimum 19 C D.B. / 14 C W.B. 19 C D.B. 1
5 2. SPECIFICATIONS 2-1. Unit Specifications Indoor Unit Outdoor Unit SAP K161GJA SAP C161GA Power Source Voltage rating V Single phase 50Hz 220/230/240 V Performance Cooling Capacity kw 4.70 / 4.70 / 4.70 BTU/h 16,000 / 16,000 / 16,000 Air circulation (High) m 3 /h 760 Moisture removal (High) Liters/h 2.3 Electrical Rating Cooling Available voltage range V 198 ~ 264 Running amperes A 7.2 / 7.2 / 7.3 Power input W 1,540 / 1,570 / 1,610 Power factor % 97 / 95 / 92 C.O.P. W/W 3.1 / 3.0 / 2.9 Compressor locked rotor amperes A 38 / 40 / 41 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo) Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,090 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo db-a 41 / 38 / 36 Outdoor : Hi db-a 53 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Dimensions & Weight Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm 1, Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. DATA SUBJECT TO CHANGE WITHOUT NOTICE. 2
6 Indoor Unit Outdoor Unit SAP K161GJA SAP C161JA Power Source Voltage rating 220V Single phase 60Hz 220 V Performance Cooling Capacity kw 4.70 BTU/h 16,000 Air circulation (High) m 3 /h 760 Moisture removal (High) Liters/h 2.3 Electrical Rating Cooling Available voltage range V 198 ~ 242 Running amperes A 8.1 Power input W 1,770 Power factor % 99 C.O.P. W/W 2.7 Compressor locked rotor amperes A 41 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo) Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,150 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo db-a 41 / 38 / 36 Outdoor : Hi db-a 51 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Dimensions & Weight Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm 1, Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. DATA SUBJECT TO CHANGE WITHOUT NOTICE. 3
7 Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181GA SAP C181MA Power Source Voltage rating V Single phase 50Hz 220/230/240 V Performance Cooling Capacity kw 5.15 / 5.15 / 5.15 BTU/h 17,600 / 17,600 / 17,600 Air circulation (High) m 3 /h 760 Moisture removal (High) Liters/h 2.7 Electrical Rating Cooling Available voltage range V 198 ~ 264 Running amperes A 9.6 / 9.5 / 9.5 Power input W 2,030 / 2,060 / 2,110 Power factor % 96 / 94 / 93 C.O.P. W/W 2.5 / 2.5 / 2.4 Compressor locked rotor amperes A 45 / 46 / 48 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo) Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,140 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo db-a 41 / 38 / 36 Outdoor : Hi db-a 53 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Dimensions & Weight Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm 1, Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. DATA SUBJECT TO CHANGE WITHOUT NOTICE. 4
8 Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181JA SAP C181BA Power Source Voltage rating 220V Single phase 60Hz 220 V Performance Cooling Capacity kw 5.15 BTU/h 17,600 Air circulation (High) m 3 /h 760 Moisture removal (High) Liters/h 2.7 Electrical Rating Cooling Available voltage range V 198 ~ 242 Running amperes A 7.8 Power input W 1,700 Power factor % 99 C.O.P. W/W 3.0 Compressor locked rotor amperes A 41 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo) Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,150 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo db-a 41 / 38 / 36 Outdoor : Hi db-a 51 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Dimensions & Weight Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm 1, Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. DATA SUBJECT TO CHANGE WITHOUT NOTICE. 5
9 Indoor Unit SAP K241GJA SAP K241GJA Outdoor Unit SAP C241GA SAP C241MA Power Source Voltage rating V Single phase 50Hz 220/230/240 V Performance Cooling Capacity kw 6.40 / 6.45 / 6.45 BTU/h 21,800 / 22,000 / 22,000 Air circulation (High) m 3 /h 830 Moisture removal (High) Liters/h 3.3 Electrical Rating Cooling Available voltage range V 198 ~ 264 Running amperes A 12.8 / 12.8 / 12.8 Power input W 2,650 / 2,680 / 2,760 Power factor % 94 / 91 / 90 C.O.P. W/W 2.4 / 2.4 / 2.3 Compressor locked rotor amperes A 67 / 70 / 73 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo) Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,785 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo db-a 43 / 41 / 39 Outdoor : Hi db-a 54 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 10 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 15.88(5/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Dimensions & Weight Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm 1, Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. DATA SUBJECT TO CHANGE WITHOUT NOTICE. 6
10 Indoor Unit SAP K241GJA SAP K241GJA Outdoor Unit SAP C241JA SAP C241BA Power Source Voltage rating 220V Single phase 60Hz 220 V Performance Cooling Capacity kw 6.40 BTU/h 21,800 Air circulation (High) m 3 /h 830 Moisture removal (High) Liters/h 3.3 Electrical Rating Cooling Available voltage range V 198 ~ 242 Running amperes A 14.5 Power input W 2,890 Power factor % 91 C.O.P. W/W 2.2 Compressor locked rotor amperes A 89 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo) Airflow direction (Indoor) Horizontal Manual Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,770 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo db-a 43 / 41 / 39 Outdoor : Hi db-a 54 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 10 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 15.88(5/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket Dimensions & Weight Indoor Unit Outdoor Unit Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm 1, Depth mm Weight Net kg Shipping kg Shipping volume m Remarks: Rating conditions are: Cooling : Indoor air temperature 27 C D.B. / 19 C W.B. Outdoor air temperature 35 C D.B. / 24 C W.B. DATA SUBJECT TO CHANGE WITHOUT NOTICE. 7
11 2-2. Major Component Specifications Indoor Unit Indoor Unit SAP K161GJA Controller PCB Part No. Controls Control circuit fuse Remote Control Unit POW-K181GJA Microprocessor 250 V 3.15 A RCS-2S2E Fan & Fan Motor Type Cross-flow Q'ty... Dia. and length mm 1... ø88 / L746 Fan motor model... Q'ty UF2-31A5P-S... 1 No. of poles... 50/60Hz rpm (High ) ,440 / 1,410 Nominal output W 30 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close Automatic reclosing Run capacitor µf 2.0 VAC 440 Flap Motor Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 25 C) Ω Each terminals (1 2, 1 3, 1 4, 1 5) : 400 ± 7% Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m DATA SUBJECT TO CHANGE WITHOUT NOTICE. 8
12 Indoor Unit SAP K181GJA SAP K181MBA Controller PCB Part No. Controls Control circuit fuse Remote Control Unit POW-K181GJA Microprocessor 250 V 3.15 A RCS-2S2E Fan & Fan Motor Type Cross-flow Q'ty... Dia. and length mm 1... ø88 / L746 Fan motor model... Q'ty UF2-31A5P-S... 1 No. of poles... 50/60Hz rpm (High) ,440 / 1,410 Nominal output W 30 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close Automatic reclosing Run capacitor µf 2.0 VAC 440 Flap Motor Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 25 C) Ω Each terminals (1 2, 1 3, 1 4, 1 5) : 400 ± 7% Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m DATA SUBJECT TO CHANGE WITHOUT NOTICE. 9
13 Indoor Unit SAP K241GJA SAP K241MBA Controller PCB Part No. Controls Control circuit fuse Remote Control Unit POW-K241GJA Microprocessor 250 V 3.15 A RCS-2S2E Fan & Fan Motor Type Cross-flow Q'ty... Dia. and length mm 1... ø88 / L746 Fan motor model... Q'ty UF2-31A5P-S... 1 No. of poles... 50/60Hz rpm (High) ,440 / 1,410 Nominal output W 30 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close Automatic reclosing Run capacitor µf 2.0 VAC 440 Flap Motor Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 25 C) Ω Each terminals (1 2, 1 3, 1 4, 1 5) : 400 ± 7% Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m DATA SUBJECT TO CHANGE WITHOUT NOTICE. 10
14 Outdoor Unit Outdoor Unit SAP C161GA Compressor Type Rotary (Hermetic) Compressor model C-R140H5W S Nominal output W 1,400 Compressor oil... Amount cc 4GSD-T or SAY-56T Coil resistance (Ambient temp. 25 C) Ω C R : C S : Safety devices Type External(OLR A) External(OLR T) Overload relay MRA TS-120N Operating temp. Open C 145±5 120±5 Close C 69±11 95±11 Operating amp.(ambient temp. 25 C) Trip in 6 to 16 sec. at 23.5A Run capacitor µf 35.0 VAC 400 Crank case heater Fan & Fan Motor Type Propeller Q'ty... Dia ø420 Fan motor model... Q'ty KFG6S-51A5P-S... 1 No. of poles... rpm (High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-YEL : YEL-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close C Automatic reclosing Run capacitor µf 4.0 VAC 440 Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 11
15 Outdoor Unit SAP C161JA Compressor Type Rotary (Hermetic) Compressor model C-R132H6D S Nominal output W 1,400 Compressor oil... Amount cc 4GSD-T or SAY-56T Coil resistance (Ambient temp. 25 C) Ω C R : C S : Safety devices Type External(OLR A) External(OLR T) Overload relay MRA TS-120N Operating temp. Open C 145±5 120±5 Close C 69±11 95±11 Operating amp.(ambient temp. 25 C) Trip in 6 to 16 sec. at 27A Run capacitor µf 35.0 VAC 400 Crank case heater Fan & Fan Motor Type Propeller Q'ty... Dia ø420 Fan motor model... Q'ty KFG6S-51A6P-S... 1 No. of poles... rpm (220 V, High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : 81.3 WHT-YEL : YEL-PNK : Safety devices Type Internal protector Operating temp. Open C 130±5 Close C Automatic reclosing Run capacitor µf 3.0 VAC 440 Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 12
16 Outdoor Unit SAP C181GA SAP C181MA Compressor Type Rotary (Hermetic) Compressor model C-2R170H5T Nominal output W 1,700 Compressor oil... Amount cc 4GSD-T or SAY-56T Coil resistance (Ambient temp. 25 C) Ω C R : C S : Safety devices Type Internal protector Overload relay Operating temp. Open C Automatic opening Close C Automatic reclosing Operating amp.(ambient temp. 25 C) Run capacitor µf 40.0 VAC 400 Crank case heater Fan & Fan Motor Type Propeller Q'ty... Dia ø420 Fan motor model... Q'ty KFG6S-51A5P-S... 1 No. of poles... rpm (230 V, High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-YEL : YEL-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close C Automatic reclosing Run capacitor µf 4.0 VAC 440 Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 13
17 Outdoor Unit SAP C181JA SAP C181BA Compressor Type Rotary (Hermetic) Compressor model C-R132H6D S Nominal output W 1,400 Compressor oil... Amount cc 4GSD-T or SAY-56T Coil resistance (Ambient temp. 25 C) Ω C R : C S : Safety devices Type External(OLR A) External(OLR T) Overload relay MRA TS-120N Operating temp. Open C 145±5 120±5 Close C 69±11 95±11 Operating amp.(ambient temp. 25 C) Trip in 6 to 16 sec. at 27A Run capacitor µf 35.0 VAC 400 Crank case heater Fan & Fan Motor Type Propeller Q'ty... Dia ø420 Fan motor model... Q'ty KFG6S-51A6P-S... 1 No. of poles... rpm (220 V, High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : 81.3 WHT-YEL : YEL-PNK : Safety devices Type Internal protector Operating temp. Open C 130±5 Close C Automatic reclosing Run capacitor µf 3.0 VAC 440 Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 14
18 Outdoor Unit SAP C241GA SAP C241MA Compressor Type Rotary (Hermetic) Compressor model C-R221H5S Nominal output W 2,200 Compressor oil... Amount cc 4GSD-T or SAY-56T... 1,350 Coil resistance (Ambient temp. 25 C) Ω C R : C S : Safety devices Type Internal protector External(OLR T) Overload relay OL-D24 Operating temp. Open C Automatic opening 150±5 Close C Automatic reclosing 63±11 Operating amp.(ambient temp. 25 C) Trip in 6 to 16 sec. at 59A Run capacitor µf 40.0 VAC 400 Crank case heater Fan & Fan Motor Type Propeller Q'ty... Dia ø420 Fan motor model... Q'ty KFG6S-51D5P-S... 1 No. of poles... rpm (230 V, High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-YEL : YEL-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close C Automatic reclosing Run capacitor µf 4.0 VAC 440 Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.2 Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 15
19 Outdoor Unit SAP C241JA SAP C241BA Compressor Type Rotary (Hermetic) Compressor model C-R191H6M Nominal output W 1,900 Compressor oil... Amount cc 4GSD-T or SAY-56T... 1,350 Coil resistance (Ambient temp. 25 C) Ω C R : C S : Safety devices Type Internal protector External(OLR T) Overload relay OL-D24 Operating temp. Open C Automatic opening 150±5 Close C Automatic reclosing 63±11 Operating amp.(ambient temp. 25 C) Trip in 6 to 16 sec. at 59A Run capacitor µf 35.0 VAC 400 Crank case heater Fan & Fan Motor Type Propeller Q'ty... Dia ø420 Fan motor model... Q'ty KFG6S-51C6P-S... 1 No. of poles... rpm (220 V, High) Nominal output W 50 Coil resistance (Ambient temp. 20 C) Ω WHT-BRN : WHT-YEL : YEL-PNK : Safety devices Type Internal protector Operating temp. Open C 130±8 Close C Automatic reclosing Run capacitor µf 3.5 VAC 440 Heat Exch. Coil Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.2 Face area m External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 16
20 2-3. Other Component Specifications Indoor Unit SAP K161GJA SAP K181GJA SAP K241GJA SAP K181MBA SAP K241MBA Transformer (TR) ATR-J105 Rating Primary AC 230V, 50/ 60 Hz Secondary 19V, 0.526A Capacity 10VA Coil resistance Ω (at 21 C) Primary (WHT WHT): 205 ± 10% Secondary (BRN BRN): 2.0 ± 10% Thermal cut-off temp. 150 C Thermistor (Coil sensor) DTN-TKS131B Resistance kω 0 C 15.0 ± 2% Thermistor (Room sensor) DTN-TKS142B Resistance kω 25 C 5.0 ± 3% Outdoor Unit SAP C161GA SAP C161JA SAP C181GA SAP C181JA SAP C181MA SAP C181BA SAP C241GA SAP C241JA SAP C241MA SAP C241BA Power Relay (PR) Coil rating G7L-2A-TUB AC V, 50/60Hz Coil resistance Ω (at 23 C) 21 ± 15% Contact rating AC 220V, 25A Thermostat (Fan Speed Control 23S) MQT5S Switching temp. C high LOW 28.5 C ± 1.5 low HIGH 31.5 C ± 2 Contact rating AC 220V, 3A 17
21 3. DIMENSIONAL DATA Indoor Unit SAP K161GJA SAP K181GJA SAP K241GJA SAP K181MBA SAP K241MBA (3) Remote control unit Center of tubing hole (2 places) Drain hose ø Narrow tube ø6.35 (1/4") Wide tube ø12.7 (1/2") Wide tube ø15.88 (5/8") K161, K181 K241 Unit : mm 18
22 Outdoor Unit SAP C161GA SAP C161JA SAP C181GA SAP C181JA SAP C181MA SAP C181BA 538 AIR INTAKE 136 AIR DISCHARGE ø12 Wide tube service valve ø12.7 (1/2") Narrow tube service valve ø6.35 (1/4") Unit : mm 19
23 Outdoor Unit SAP C241GA SAP C241JA SAP C241MA SAP C241BA Air intake Air discharge Wide tube service valve ø15.88 (5/8") Narrow tube service valve ø6.35 (1/4") Unit : mm 20
24 4. REFRIGERANT FLOW DIAGRAM Indoor Unit SAP K161GJA SAP K161GJA SAP K181GJA SAP K181MBA Indoor Unit Outdoor Unit Outdoor Unit SAP C161GA SAP C161JA SAP C181JA SAP C181BA, Wide tube Wide tube service valve Accumulator Compressor O.D. ø12.7 mm (1/2 ") Evaporator Condenser Narrow tube Narrow tube service valve Capillary tube O.D. ø6.35 mm (1/4") Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181GA SAP C181MA Indoor Unit Outdoor Unit Wide tube Wide tube service valve Accumulator Compressor O.D. ø12.7 mm (1/2 ") Capillary for liquid injection Evaporator Condenser Narrow tube Narrow tube service valve Capillary tube O.D. ø6.35 mm (1/4") 21
25 Indoor Unit SAP K241GJA SAP K241GJA SAP K241MBA SAP K241MBA Indoor Unit Outdoor Unit Outdoor Unit SAP C241GA SAP C241JA SAP C241MA SAP C241BA Wide tube Wide tube service valve Muffler Accumulator Compressor O.D. ø15.88 mm (5/8 ") Capillary for liquid injection Evaporator Condenser Narrow tube Narrow tube service valve Strainer Capillary tube O.D. ø6.35 mm (1/4") Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Thickness: Min. 8 mm Wide tube Insulation Narrow tube Thickness: Min. 8 mm 22
26 5. PERFORMANCE DATA 5-1. Performance charts Indoor Unit SAP K161GJA Outdoor Unit SAP C161GA Indoor Unit Outdoor Unit SAP K161GJA SAP C161JA Cooling Characteristics Cooling Characteristics 14 Indoor inlet air D.B. temp. ( C) 13 Outdoor fan speed 14 Indoor inlet air D.B. temp. ( C) 13 Outdoor fan speed Operating current (A) Low High Operating current (A) Low High Outdoor inlet air D.B. temp. ( C) Outdoor inlet air D.B. temp. ( C) Low pressure at wide tube service valve MPa (kgf/cm 2 G) 1.47 (14) 1.38 (13) 1.28 (12) 1.18 (11) 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 ( 6 ) 0.59 ( 5 ) 0.49 ( 4 ) 0.39 ( 3 ) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Low pressure at wide tube service valve MPa (kgf/cm 2 G) 1.47 (14) 1.38 (13) 1.28 (12) 1.18 (11) 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 ( 6 ) 0.59 ( 5 ) 0.49 ( 4 ) 0.39 ( 3 ) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High NOTE... Points of Rating condition Black dots in above charts indicate the following rating conditions. Cooling: Indoor air temperature 27 C D.B./ 19 C W.B. Outdoor air temperature 35 C D.B./24 C W.B. 23
27 Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181GA SAP C181MA Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181JA SAP K181BA Cooling Characteristics Cooling Characteristics Indoor inlet air D.B. temp. ( C) Outdoor fan speed Indoor inlet air D.B. temp. ( C) Outdoor fan speed Operating current (A) Low High Operating current (A) Low High Outdoor inlet air D.B. temp. ( C) Outdoor inlet air D.B. temp. ( C) 55 Low pressure at wide tube service valve MPa (kgf/cm 2 G) 1.47 (14) 1.38 (13) 1.28 (12) 1.18 (11) 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 ( 6 ) 0.59 ( 5 ) 0.49 ( 4 ) 0.39 ( 3 ) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Outdoor inlet air D.B. temp. ( C) Low pressure at wide tube service valve MPa (kgf/cm 2 G) 1.47 (14) 1.38 (13) 1.28 (12) 1.18 (11) 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 ( 6 ) 0.59 ( 5 ) 0.49 ( 4 ) 0.39 ( 3 ) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Outdoor inlet air D.B. temp. ( C) NOTE... Points of Rating condition Black dots in above charts indicate the following rating conditions. Cooling: Indoor air temperature 27 C D.B./ 19 C W.B. Outdoor air temperature 35 C D.B./24 C W.B. 24
28 Indoor Unit SAP K241GJA SAP K241MBA Outdoor Unit SAP C241GA SAP C241MA Indoor Unit SAP K241GJA SAP K241MBA Outdoor Unit SAP C241JA SAP K241BA Cooling Characteristics Cooling Characteristics Operating current (A) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Operating current (A) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Outdoor inlet air D.B. temp. ( C) Outdoor inlet air D.B. temp. ( C) 55 Low pressure at wide tube service valve MPa (kgf/cm 2 G) 1.47 (14) 1.38 (13) 1.28 (12) 1.18 (11) 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 ( 6 ) 0.59 ( 5 ) 0.49 ( 4 ) 0.39 ( 3 ) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Outdoor inlet air D.B. temp. ( C) Low pressure at wide tube service valve MPa (kgf/cm 2 G) 1.47 (14) 1.38 (13) 1.28 (12) 1.18 (11) 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 ( 6 ) 0.59 ( 5 ) 0.49 ( 4 ) 0.39 ( 3 ) Indoor inlet air D.B. temp. ( C) Outdoor fan speed Low High Outdoor inlet air D.B. temp. ( C) NOTE... Points of Rating condition Black dots in above charts indicate the following rating conditions. Cooling: Indoor air temperature 27 C D.B./ 19 C W.B. Outdoor air temperature 35 C D.B./24 C W.B. 25
29 5-2. Air Throw Distance Chart Indoor Unit SAP K161GJA SAP K181GJA SAP K181MBA Room air temp. : 27 C Fan speed : High Horizontal distance (m) Axis air velocity (m/s) Vertical distance (m) : Flap angle 0, : Axis air velocity 0 : Flap angle 30, : Axis air velocity 30 Heating Indoor Unit SAP K241GJA SAP K241MBA Room air temp. : 27 C Fan speed : High Horizontal distance (m) Axis air velocity (m/s) Vertical distance (m) : Flap angle 0, : Axis air velocity 0 : Flap angle 30, : Axis air velocity 30 26
30 5-3. Cooling Capacity Indoor Unit Outdoor Unit SAP K161GJA SAP C161GA 240V Single Phase 50Hz RATING CAPACITY 4.70 kw AIR FLOW RATE 760 m 3 /h EVAPORATOR CONDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC 4.94 # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 27
31 Indoor Unit Outdoor Unit SAP K161GJA SAP C161JA 220V Single Phase 60Hz RATING CAPACITY 4.70 kw AIR FLOW RATE 760 m 3 /h EVAPORATOR CONDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC 4.94 # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 28
32 Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181GA SAP C181MA 240V Single Phase 50Hz RATING CAPACITY 5.15 kw AIR FLOW RATE 760 m 3 /h EVAPORATOR CONDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC 5.41 # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 29
33 Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181JA SAP C181BA 220V Single Phase 60Hz RATING CAPACITY 5.15 kw AIR FLOW RATE 760 m 3 /h EVAPORATOR CONDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC 5.41 # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 30
34 Indoor Unit SAP K241GJA SAP K241MBA Outdoor Unit SAP C241GA SAP C241MA 240V Single Phase 50Hz RATING CAPACITY 6.45 kw AIR FLOW RATE 830 m 3 /h EVAPORATOR CONDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC 6.77 # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 31
35 Indoor Unit SAP K241GJA SAP K241MBA Outdoor Unit SAP C241JA SAP C241BA 220V Single Phase 60Hz RATING CAPACITY 6.40 kw AIR FLOW RATE 830 m 3 /h EVAPORATOR CONDENSER ENT. TEMP. C OUTDOOR AMBIENT TEMP. C W.B. D.B TC CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC SHC TC 6.72 # CM SHC SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC SHC TC CM SHC SHC SHC SHC TC : Total Cooling Capacity (kw) SHC : Sensible Heat Capacity (kw) CM : Compressor Input (kw) Rating conditions (#Mark) are Outdoor Ambient Temp. 35 C D.B. Indoor Unit Entering Air Temp. 27 C D.B. / 19 C W.B. 32
36 6. ELECTRICAL DATA 6-1. Electrical Characteristics Indoor Unit Outdoor Unit SAP K161GJA SAP C161GA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at V ~ 50Hz Rating Conditions Running Amps. A 0.37 / / / / 7.3 Power Input kw / / / / 1.61 Full Load Conditions Running Amps. A 0.37 / / / / 8.7 Power Input kw / / / / 1.97 Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. Indoor Unit Outdoor Unit SAP K161GJA SAP C161JA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220V ~ 60Hz Rating Conditions Running Amps. A Power Input kw Full Load Conditions Running Amps. A Power Input kw Rating Conditions Full Load Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 43 C D.B. 33
37 Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181GA SAP C181MA Indoor Unit SAP K181GJA SAP K181MBA Outdoor Unit SAP C181JA SAP C181BA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at V ~ 50Hz Rating Conditions Running Amps. A 0.37 / / / / 9.5 Power Input kw / / / / 2.11 Full Load Conditions Running Amps. A 0.37 / / / / 13.4 Power Input kw / / / / 3.03 Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 52 C D.B. Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220V ~ 60Hz Rating Conditions Running Amps. A Power Input kw SSA 385, 386 Running Amps Conditions Power Input Full Load Conditions Running Amps. A Power Input kw Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. SSA 385, 386 Conditions (Saudi standard) : Indoor Air Temperature 29 C D.B. / 19 C W.B. Outdoor Air Temperature 46 C D.B. / 24 C W.B. Full Load Conditions : Indoor Air Temperature 29 C D.B. / 19 C W.B. Outdoor Air Temperature 54 C D.B. 34
38 Indoor Unit SAP K241GJA SAP K241MBA Outdoor Unit SAP C241GA SAP C241MA Indoor Unit SAP K241GJA SAP K241MBA Outdoor Unit SAP C241JA SAP C241BA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at V ~ 50Hz Rating Conditions Running Amps. A 0.39 / / / / 12.8 Power Input kw / / / / 2.76 Full Load Conditions Running Amps. A 0.39 / / / / 16.8 Power Input kw / / / / 3.74 Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. Full Load Conditions : Indoor Air Temperature 32 C D.B. / 23 C W.B. Outdoor Air Temperature 52 C D.B. Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220V ~ 60Hz Rating Conditions Running Amps. A Power Input kw SSA 385, 386 Running Amps Conditions Power Input Full Load Conditions Running Amps. A Power Input kw Rating Conditions : Indoor Air Temperature 27 C D.B. / 19 C W.B. Outdoor Air Temperature 35 C D.B. SSA 385, 386 Conditions (Saudi standard) : Indoor Air Temperature 29 C D.B. / 19 C W.B. Outdoor Air Temperature 46 C D.B. / 24 C W.B. Full Load Conditions : Indoor Air Temperature 29 C D.B. / 19 C W.B. Outdoor Air Temperature 54 C D.B. 35
39 6-2. Electric Wiring Diagrams Indoor Unit SAP K161GJA SAP K181GJA SAP K241GJA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 36
40 Indoor Unit SAP K181MBA SAP K241MBA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 37
41 Outdoor Unit SAP C161GA SAP C161JA SAP C181JA SAP C181BA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 38
42 Outdoor Unit SAP C181GA SAP C181MA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 39
43 Outdoor Unit SAP C241GA SAP C241JA SAP C241MA SAP C241BA WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 40
44 7. INSTALLATION INSTRUCTIONS 7-1. Installation Site Selection, Indoor Unit 15 cm min. 15 cm 15 cm To prevent abnormal heat min. min. INDOOR UNIT WARNING generation and the possibility of fire, don t place obstacles, enclosures and grills in front Front View of or surrounding the air Fig.1 conditioner in a way that may block air flow. AVOID: direct sunlight. nearby heat sources that may affect performance of the unit. areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. DO: select an appropriate position from which every corner of the room can be uniformly air-conditioned. (High on a wall is best) select a location that will hold the weight of the unit. select a location where tubing and drain pipe have the shortest run to the outside. allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 1) install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed Table 1 and Fig. 2a. Table 1 INDOOR UNIT Elevation difference (H) CAUTION Fig. 2a Fig. 2 For stable operation of the air conditioner, do not install wall-mounted type indoor units under 1.5m from floor level. Fig. 2b Tubing length (L) OUTDOOR UNIT Indoor Unit Minimum height from floor level 1.5m Floor level Wall Model Max. Allowable Tubing Length at Shipment (m) Limit of Tubing Length (L) (m) Limit of Elevation Difference (H) (m) Required Amount of Additional Refrigerant (g/m)* C161, C C * If total tubing length becomes 7.5 to 20 m (max.) or 10 to 30 m (max.), charge additional refrigerant (R22) by 25 g/m. No additional charge of compressor oil is necessary. 41
45 Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 3) damp, humid or uneven locations. DO: choose a place as cool as possible. choose a place that is well ventilated. allow enough room around the unit for air intake/exhaust and possible maintenance. (Figs. 4a and 4a) provide a solid base (concrete block, cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig.5) use lug bolts or equal to bolt down unit, reducing vibration and noise. Hot air Outdoor unit NO Fig. 3 Fig 3 Exhaust fan Heat source Required space around the unit. Air intake Min. 5 cm Air discharge Min. 10 cm Top View Top Fig. View 4a Min. 40 cm Valve side Min. 25 cm Obstacle above Air discharge 2 m 2 m Obstacle Ground Side View Fig. 4b Fig 4 C Anchor bolts (4 pcs.) Air intake Min. 10 cm Concrete or equal About 40 cm About 10 cm Fig. 5 Fig. 5 - A 42
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97
More informationSERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86
More informationSERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
More informationSERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EHDS + SAP-CRV96EHDS SAP-KRV126EHDS + SAP-CRV126EHDS FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EHDS
More informationOperating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
More informationtechnical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL SAP-KRV9AEH + SAP-CRV9AEH SAP-KRV12AEH + SAP-CRV12AEH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV9AEH SAP-KRV12AEH Product
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV93EH + SAP-CRV93EH SAP-KRV123EH + SAP-CRV123EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No.
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationUSER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKS1NB41 & CZ18BT1U + CUKS1NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)
More informationHP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
More informationAir Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
More informationSplit-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
More informationNewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE
More informationDC INVERTER SPLIT SYSTEM AIR CONDITIONER
AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EH + SAP-CRV96EH SAP-KRV126EH + SAP-CRV126EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EH SAP-KRV126EH
More informationyork air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
More informationAIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
More informationMULTI SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL AER534QC Dual System Kit :DKR8585C (Option) MULTI SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AER534QC 387007146 Model No. Product Code No. DKR8585C 387025905 Outdoor
More informationNewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug
More informationPortable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
More informationUHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
More informationUse and Care Manual. Model CPA12KH AIR CONDITIONER
Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage
More informationREFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca
More informationSERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
More informationAppendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
More informationAir Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV
Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................
More informationSERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03
Domestic Air Conditioner SERVICE MANUAL Model HW-05LN03 Feature Anti-mold filter Mechanical control Easy clean filters Slide chassis 4-way airflow direction 2 cool settings, 2 fan settings Serial Number:
More informationAIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
More informationTECHNICAL DATA & SERVICE MANUAL
TECHNICAL DATA & SERVICE MANUAL REVE 247C (I) Cooling only model REVE 237R (I) Heat pump model 0.8180.501.1 11 / 2007 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3 2) Major Component
More informationROOM AIR CONDITIONER INSTALLATION MANUAL
ROOM AIR CONDITIONER INSTALLATION MANUAL ( Split Type) Please read this installation manual completely before installing the product When the power cord is damaged, replacement work shall be performed
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH SAP-CMRV9EH SAP-CMRV9EH SAP-CMRVEH SAP-CMRVEH FILE NO. Destination: Europe Northern Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.6k.6k
More informationSPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET
SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET (PART NO. 97474700) For authorized service personnel only. This installation instruction sheet describes how to install the outdoor unit only.
More informationCONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
More informationCS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE
Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------
More informationNew Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
More informationAir Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
More informationOperating Instructions Air Conditioner
F566272 Operating Instructions Air Conditioner CS-C18FFH CS-C28FFH CU-C18FFH CU-C28FFH ENGLISH Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
More informationCU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE
Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW
More informationSi10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationSERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2
SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-
More informationTransformer oil cooler ALFA A02
A02 Transformer oil cooler ALFA Transformer oil cooler ALFA The transformer oil cooler ALFA is used to cool power transformers by means of forced air and oil flow. The oil in the cooler is circulated using
More informationECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
More informationPortable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC
Portable Evaporative Air Cooler OWNER S MANUAL Read and save these instructions before use Model: CL30XC Power rating: 250 Watts Voltage rating: 230 Volt, 50Hz Made in P.R.C. QUICK START GUIDE Fill with
More informationAir Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315
RECORD THIS INFORMATION FOR FUTURE REFERENCE: Number Serial Number ADB Number ADB Serial Number Date Purchased USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 CANADA Dometic
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationModel: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0
Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationLG Floor Standing Type Air Conditioner INSTALLATION MANUAL
website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG Floor Standing Type Air Conditioner INSTALLATION MANUAL LG IMPORTANT Please read this installation manual completely before
More informationPortable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477
More informationSWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
More informationNEW 3-PIPE ECOi MF2 SERIES
NEW 3-PIPE ECOi MF2 SERIES SIMULTANEOUS HEATING AND COOLING VRF SYSTEM Internet Control Ready INTERNET CONTROL NEW Energy Environmentally friendly refrigerant R410A Down to -20 ºC in heating mode OUTDOOR
More informationSplit Type Room Air Conditioner. KSWM units
OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.
More informationALL IN ONE. Heat Pump Water Heater
ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit. www.airtradecentre.com CONTENTS A. IMPORTANT REMARKS ------------------------------------------------------------------------------------------------
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationSERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
More informationDESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LECA AS G09LECA AS G12LECA AS G14LECA OUTDOOR AO G07LEC AO G09LEC AO G12LEC AO G14LEC 1. INDOOR UNIT : AS G07LECA AS G09LECA AS
More informationIndoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
More informationFailure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
More informationHow To Measure Temperature On A Thermostat
Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationCS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING
Order No: PAPAMY1207094CE Indoor Unit CS-CE9NKE CS-CE12NKE Outdoor Unit CU-CE9NKE CU-CE12NKE WARNING This service information is designed for experienced repair technicians only and is not designed for
More informationhore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
More informationQuest 105, Dry155, and 205 Dual
Quest 105, Dry155, and 205 Dual Read and Save These Instructions This manual is provided to acquaint you with the dehumidifier so that installation, operation and maintenance can proceed successfully.
More informationPORTABLE AIR CONDITIONER
VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner
More information14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
More informationMulti System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split
Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate
More informationLOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
More informationREGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationSERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
More informationSHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS
SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS 2 This water heater must be installed (water and electrical installation), commissioned and serviced
More informationInstruction manual for Firstline FCS12000CH
Instruction manual for Firstline FCS12000CH Contents Introduction... 2 Safety Awareness... 3 Safety Awareness... 4 Name of Parts... 5 Name of Parts... 6 Remote Controller Preparation... 7 Operation of
More informationAIR CONDITIONER OUTDOOR UNIT
AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.
More informationCONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
More informationHeat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
More informationReverse Cycle Inverter Split System Air Conditioner
Reverse Cycle Inverter Split System Air Conditioner Model Number TAC-09CHSA/JAI5 INSTALLATION MANUAL Contents 03 Warranty Details 04 Welcome 05 General Safety Instructions 06 Product Overview 07 Selecting
More informationCARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
More informationUSER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA
USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your
More informationCEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS
CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Please read this instruction sheet completely before installing the product. When the power cord is damaged, replacement work should be
More informationService Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
More informationHAIER WINDOW TYPE AIR CONDITIONER. Service Manual. Part # AC-8888-104. HAIER TRADING COMPANY, LLC www.haieramerica.com
HAIER WINDOW TYPE AIR CONDITIONER Service Manual Part # AC-8888-104 HAIER TRADING COMPANY, LLC www.haieramerica.com 1 SERVICE MANUAL Models HWR08XC5 ESA3065 ESA3085 Features Top-Discharge Air Flow Ultra
More informationSplit System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
More informationENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...
More informationPortable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
More informationINSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
More informationNO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
More informationAquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.
AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice
More informationM SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
More informationPortable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
More information