Submit shop drawings for equipment provided under this section Shop drawings shall indicate:



Similar documents
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Sample - No Commercial Use

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE

Switchgear and Metal-Enclosed Bus

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Primary and Secondary Electrical Distribution Systems

Secondary Unit Substations

SECTION SWITCHBOARDS

This section applies to the design and installation of transformers.

Alternate Methods to Short Circuit Breaker Coordination

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

SECTION MEDIUM VOLTAGE SWITCHGEAR

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

MCC Ratings. Voltage Rating

Atlanta Chapter IEEE Industry Applications Society

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Engineers Edge, LLC PDH & Professional Training

Extend the Life of Existing Switchgear

Fusible Disconnect Switch

Short Circuit Current Calculations

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Cable/Conduit Conversion

Tmax MCCBs. Molded case circuit breakers. Tmax

Hyperlinks are Inactive

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

SECTION MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR

Unified requirements for systems with voltages above 1 kv up to 15 kv

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

LVA Take Offs in Bid Manager

CalMod Design-Build Electrification Services

IRRIGATION PUMPING Table of Contents - Section 900

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing

Sentron Series Circuit Breakers

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Requirements for Electrical Installations

SECTION ELECTRICAL ACCEPTANCE TESTS

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

How To Test A Power Switch On A Power Supply

The following components are common to most cubicles; this example is an ABB HK cubicle.

DESIGN CLARIFICATION (DC)

How To Operate A Gec Transfer Switch Open Transition Amp Power Supply

Evaluating Water-Damaged Electrical Equipment

Bolted contact switches. Pringle switches

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Customer Substation Manual 08/05/02

FAQs-Main switchboard design criteria

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

Catalog January. Heavy industrial power applications Motor contactors and starters

DOCUMENT ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, Contract Name: 13,800-Volt and 480-Volt Switchgear

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Arc Terminator Active Arc-Resistant Switchgear

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

8146/5 Series Breaker Panelboards

Mini Power-Zone Unit Substation

Diesel Engine Driven Generators Page 1 of 6

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

Evaluating Water-Damaged Electrical Equipment

Contents. Clean Control Center Harmonic Correction Unit. Selection Dimensions Specifications. Description

Evaluating Fire- and Heat-Damaged Electrical Equipment

SENTRON Switching and Protection Devices Air Circuit Breakers

Evaluating Water-Damaged Electrical Equipment

RAY-MAX Integrated Solar Power Strip

Contents. Description. Product Selection Guide

Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances

Power Management Module 2. Installation

SECTION VARIABLE FREQUENCY DRIVES

Medium Voltage Motor Control Assemblies

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

Low Voltage Switchgear

Table of Contents. Review Answers...77 Final Exam...80

SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS

GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT

Transcription:

Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions, and sections under Division 1 General Requirements. Description Contractor shall furnish and install free-standing, dead-front type low-voltage distribution switchboards, utilizing group mounted circuit protective devices. Reference Standards ANSI C37.13 IEEE Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures ANSI C37.17 Trip Devices for AC and General Purpose DC Low-Voltage Power Circuit Breakers NEMA PB2 Dead Front Distribution Switchboards NEMA KS 1 Enclosed and Miscellaneous Distribution Equipment Switches (600 Volts Maximum) UL 489 Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures UL-891 Dead Front Switchboards Submittals Shop Drawings Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Manufacture and model numbers of equipment and devices General arrangement: - Plan view indicating overall dimensions, shipping splits and weights - Front elevation indicating location of devices and instruments - Section through switchgear showing space available for conduits Seismic certification and equipment anchorage details Electrical one-line drawings Short circuit ratings of bus and interrupting rating of lowest rated device Circuit schedules showing feeder circuit identification, device description, including trip unit or fuse clip rating Schematic wiring diagram Cable lug termination device Time current characteristics curves Main breakers Feeder breakers Ground fault relaying Test data Submit power distribution acceptance test reports to Engineer for review and acceptance, prior to energization of equipment. 5 Pages App-16435-1 06/11

Instruction Manuals In addition to Section 16000 General Electrical Requirements, manual shall include the following: Wiring diagrams for all systems. Maintenance and Spare Parts Provide list of recommended spare parts Delivery, Storage, And Handling Upon completion, assembly and testing by manufacturer of equipment specified, should it be found necessary for shipping and installation purposes to disassemble equipment, match-mark parts to facilitate erection in field. Mark crates, boxes and cartons clearly to identify equipment. Show crate, box or carton identification number on shipping invoices. Store switchboard units in clean, dry environment protected from elements. Maintain factory bracing, packaging and wrapping. Handle units in accordance with manufacture s written handling instructions. Lift units only by manufacturers approved means. Part 2 - Products Materials Acceptable Manufactures: Cutler-Hammer, General Electric, Siemens Ratings Assembly shall be rated to withstand fault current as shown on drawing Nominal system voltage rating of switchboard shall be as shown on the drawings. Construction Switchboard shall consist of vertical sections bolted together. Sides and rear shall be covered with removable bolt-on covers. Provide adequate ventilation within enclosure. Switchboard sections shall be rear aligned. Protective devices shall be group mounted. Devices shall be front removable and load connections front accessible. Assembly shall be provided with adequate lifting means. Switchboard shall be suitable for use as service entrance equipment. Bus General Bus bars shall be silver-plated copper. Main horizontal bus bars shall be mounted with all three phases arranged in same vertical plane. Bus sizing shall be based on 65 C over 40 C ambient temperature outside the enclosure. Provide a full capacity neutral bus. Provide copper ground bus, sized per NEMA Standards, extending entire length of switchgear. Bus Bar Connection Bus bar connections shall be bolted. 5 Pages App-16435-2 06/11

Bus joints shall be provided with conical spring-type washers. Clamp joints shall not be used. Wiring Terminations Provide small wiring, necessary fuse blocks and terminal blocks within switchboard. Control components mounted within assembly, such as fuse blocks, relays, pushbuttons, switches, etc., shall be suitably marked for identification corresponding to appropriate designations on manufacturer s wiring diagrams. Mechanical-type terminals shall be provided for all line and load terminations suitable for copper cable rated for 75 C. Lugs shall be provided in incoming line section for connection of main grounding conductor. Control wire shall be type SIS. Control wire shall be bundled and secured with nylon ties. Insulated locking spade terminals shall be provided for all control connections, except where saddle type terminals are provided integral to a device. Current transformer secondary leads shall be connected to short-circuit terminal blocks. Groups of control wires leaving the switchboard shall be provided with terminals blocks with suitable numbering strips. Provide wire markers at each end of control wiring. Protective Devices Main Breaker Main breaker shall be fixed insulated case circuit breaker, fully electronic, LSIG/LSI. Breaker shall be listed for 100% continuous ampere rating. Main breaker shall be provided with solid-state trip units. Frame ampere ratings shall be as shown on drawings. Main breakers shall be manually operated (MO). Feeder Breakers Feeder breakers shall be fully electronic molded case circuit breakers or Power Circuit Breakers, LSI. Thermal magnetic breakers are not acceptable. Circuit breakers shall have minimum of symmetrical interrupting capacity as indicated on drawings. Circuit breakers 200-ampere through 2500-ampere shall have microprocessor-based RMS sensing trip units. Solid State Trip Units Provide breakers, with solid-state microprocessor based trip units. Unit shall consist of current sensors, solid-state trip device, flux transfer shunt trip and solid-state adjustable time/current curve shaping elements. Solid state elements shall provide: Long time current pickup settings and long time delay bands. Short time current pickup settings sand short time delay bands. Instantaneous trip settings with switchable 12t ramp. Ground fault pickup settings (where indicated on drawings). Adjustments shall be made using non-removable, discrete steps. Sealable transparent cover shall be provided over adjustments. Ground Fault (where indicated on drawings): Trip shall be provided as an integral part of breaker. Pick-up shall be adjustable with maximum setting of 1200 amps. Time delay shall be adjustable. 5 Pages App-16435-3 06/11

Trip unit shall contain means to conduct circuit breaker tests. Breaker shall be equipped with externally accessible test points to be used for field testing. Customer Metering Provide customer metering compartment with hinged door. Current transformers for each meter. Current transformers shall be wired to shorting-type terminal blocks. Potential transformers including primary and secondary fuses with disconnecting means. Meter shall be microprocessor-based as manufactured by Veris. The unit shall display the following: Phase amperes (A, B, C). Phase voltage (A-B, B-C, C-A, A-N, B-N, C-N). Enclosures NEMA 3R Gasketed Enclosure, indoors and outdoors Finish Exterior and interior of switchboard shall be ANSI-61 light gray. Indoors and sage green outdoors. Accessories Lockout Devices: Provide circuit breakers with integral, lockout/tagout devices. Shunt trip devices: Provide shunt trip bell alarms and auxiliary switches. Nameplates Nameplates shall be secured to switchboard enclosure with screws. Switchgear assembly: Switchgear shall be provided with nameplate indicating manufacturer s name and drawing number. In addition to name and drawing number, provided: - Voltage ratings (kv nominal; kv maximum design; kv BIL) - Main bus continuous rating (amperes) - Short-circuit ratings (amperes, rms symmetrical and Mva three-phase symmetrical) - Momentary and fault-closing ratings (amperes, rms asymmetrical) Control components mounted within assembly shall be marked for identification corresponding to appropriate designation on manufacture s drawings. Part 3 - Execution Inspection Visually inspect equipment and components at time of delivery. Submit report to Owner/Engineer with list of items to be corrected. Factory Testing Standard Factory Tests Shall Be Performed On Equipment Provided Under This Section. 5 Pages App-16435-4 06/11

Switchboard shall be completely assembled, wired, adjusted, and tested at factory. Manufacturer shall provide 3-certified copies of factory test reports. Installation Contractors shall install equipment per manufacturer s instructions and contract drawings. Assembly shall be provided with adequate lifting means and shall be capable of being moved into installation position and bolted directly to floor without use of floor sills provided floor is level to 1/8 inch per 3-foot distance in any direction. Necessary hardware to secure assembly in place shall be provided by Contractor. Provide 4-inch high housekeeping pad for switchboards as indicated on drawings. Pad footprint shall be size to adequately support switchboard. Bolt switchboard securely to pad. Protect equipment during installation to prevent twisting or deformation, exposure to damaging environments, and work of other trades. Maintain protection until completion of construction. Prior to energization, factory representative shall visually inspect switchgear installation to insure that switches and motor operators are operable and bus connections are complete. Field Quality Control Contractor shall perform field adjustments of protective devices as required to place equipment in final operating condition. Settings shall be in accordance with approved short-circuit study, protective device evaluation study and protective device coordination study. Necessary field settings of devices and adjustments and minor modifications to equipment to accomplish conformance with approved short circuit and protective device coordination study shall be carried out by Contractor at no additional cost to Owner. Immediately prior to final inspection, thoroughly clean equipment. Refinish damaged enclosures to original quality. Acceptance Testing Perform acceptance tests on switchboard in accordance with contract documents Power Distribution Acceptance Tests. Adjust or replace equipment as needed to comply with manufacturer s specifications. Re-test device and submit new test reports. Equipment shall have passed acceptance tests prior to energization. Certified test report of standard production tests shall be available to Engineer upon request. Switch operators shall be tested at least once after energization. Training Contractor shall provide training session for up to [XXX] Owner s Representatives for one normal workday at a jobsite location determined by Owner. Training session shall be conducted by Manufacturer s Qualified Representative. Training program shall consist of instruction on operation of assembly, circuit breakers, fused switches, and major components within assembly. End of Appendix Section 16435 5 Pages App-16435-5 06/11