EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES



Similar documents
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: Purpose

USER GUIDE Easier, Safer, Betta! WATERPROOFING

Bituminous Sheet Flat Roofs: Their repair and maintenance

What you need to know about concrete block basement construction.

Issue of the Guidelines on Prevention of Water Seepage in New Buildings

Melbourne balcony Assessments

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

WATERPROOFING FOR CONCRETE STRUCTURES

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

METHOD STATEMENT 006 TORCH APPLIED MEMBRANE TO BASEMENT WALLS

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems

Leaky Homes Financial Assistance Package (FAP) Repair plan example

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

WATERPROOFING OF WET ROOMS

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

Window Installation Instructions

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Comment Form on Proposed Gut Rehabilitation Alternatives

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

State of Connecticut Department of Public Health RADON PROGRAM

SikaProof A Technology

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

USER GUIDE Easier, Safer, Betta! gripsetbetta.com WATERPROOFING

DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H

BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES

High Performance PSA in Sheet Membrane in Water Protection

Water Damage & Repair

How To Repair A Boat Landing Deck With A Boat Bed

RECOATING AND RENEWING SPF ROOFING SYSTEMS

Inspecting to a higher standard.

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

The formation of roof waterproofing details calls for

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

DELTA Premium Moisture Management Systems for Foundations.

Waterproofing Problems: A Simple Explanation, A Simple Solution

INSTALLATION GUIDE. americanwick.com WICK (9425)

Renovating Your Basement

WATERPROOFING BASEMENTS

Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

What Causes Foundation Leaking?

Wecryl Waterproofing System under surfacing supplied by others

BLACK JACK ALL WEATHER ROOF COATING

Exterior Elevated Elements Inspection Guidelines

DENSO WATERPROOFING SYSTEMS

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

Ubiflex. Non-lead flashing system

Design and Construction of Cantilevered Reinforced Concrete Structures

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

Basement Moisture Problems

Superform Products Ltd.

Site Inspection Report

WATERPROOFING SikaProof -A TECHNOLOGY

Tested to BS 6375: Part 1: 1989 and achieved a weathertightness classification of 2000 Pa (Special)

Vision Home Inspection

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

Triflex system: Triflex ProDetail. Solution type: Roof detail and repair waterproofing. Application: Overlay of existing substrate

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

Energy Company Obligation (ECO): Technical Monitoring Questions

Ver. 2. Guide to. Inspecting Residential Brick Veneer

WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri

LAYING BLOCK AND BRICK

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

Finegan Inspection Services, Inc.

Including. Rubershield-Pro. Breather Membrane

ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.

SECTION STANDING SEAM METAL ROOFING

School Construction Authority Architecture & Engineering

ITEM THERMOPLASTIC MEMBRANE ROOFING

Asphalt Shingle Application Requirements

PB301 July Lightweight Building Solutions. Bushfire Protection.

Commercial Roof Inspection Form

Roof Inspection. Summary Report

Crescent Valley High School Roof Investigation

Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM

Site Grading and Drainage to Achieve High-Performance Basements

The WANZ Guide to Window Installation

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE

INSTALLATION OF A BAY WINDOW

Residential Inspection Guidelines

Your guide to home maintenance. Flat Roofs

COMMONLY USED RESIDENTIAL BUILDING CODES

Avoiding Air Barrier Pitfalls

How-To-build guide timber windows

R E S I D E N T I A L H O U S I N G

PETERSONS WATERFRONT CONDOMINIUMS

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R Lecturer: Jim Cahill

WATERPROOFING PRODUCTS

Excerpts from the Canadian National Building Code (NBC)

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

FIRESTOPPING & SMOKE SEALS

Transcription:

Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES

FAILING WATERPROOFING SYSTEMS Increasingly, BSA is receiving complaints about failed and leaking basements, retaining walls, balconies and planter boxes. The Building Code of Australia (BCA) requires constructions to safeguard occupants from illness or injury and protect a building from damage caused by surface water, external moisture entering a building, and internal moisture accumlating in a building. Concerns raised about roof, deck and balcony s, by building industry contractors and professionals nationally, has prompted Standards Australia to begin producing two new standards, where previously no contemporary and comprehensive standard existed. These are: 1. AS 4654.1 Waterproofing systems for exterior use, and 2. AS 4654.2 Waterproofing systems for exterior use above ground level. These standards are currently being drafted. The aim of the completed standards is to produce a consistent and reliable approach to the materials used in the design and installation of external waterproofing. Industry research and experience has found that the design of roofs, decks, balconies and planter boxes contributes to many of the failures of waterproofing systems. By setting an industry standard for materials, design and installation, the failure rate of external s is expected to dramatically reduce. Roof, Podium Slabs and Concrete Balcony Slabs A number of significantly defective roof and podium slabs have been brought to BSA s attention. These include: delamination of tiles from the to which they were adhered; dissolution of the which results in water penetration; breaks or tears in s and/or tiles caused by thermal or footing movement; and inadvertent penetration of the after it has been applied (e.g. by the fixing of balustrade posts). To avoid these types of defects occurring BSA recommends contractors consider the following best practice guidelines prior to undertaking external work. Design Slabs should be laid with falls to drainage points. A minimum fall of between 1:80 and 1:100 is recommended for slabs in sheltered locations and falls of between 1:60 and 1:80 for slabs in exposed locations. This may vary however, dependant upon: the exposure conditions of the slab; the catchment area of the podium, balcony or roof falling to each drainage point; and the type of being used. Contractors should avoid penetrating slabs wherever possible, but where penetrations are essential they must be properly sleeved and waterproofed with flanged sleeves and collars. Balustrade posts should be fixed to the face of the wall if possible. Where penetrations for balustrades are unavoidable, posts should be cored into the slab and the turned up the post to at least 25mm above the surface level of any finishes. The turned up can then be concealed and protected from UV rays and mechanical damage by cover plates.

It is, however, often impractical to face fix or core balustrades into the slab and a baseplate system of fixing is required. In these instances an initial layer of should be applied under the area of the baseplate and a second layer of should later be installed over the baseplate and turned up the post to at least 25mm above the surface level of any finishes. The turned up can then be sealed with a cover plate. When the is laid over a baseplate, any fixings should be countersunk. post support rebate or reglet and be appropriately sealed and capped to prevent moisture penetrating behind the. Membranes should extend fully over any perimeter hob and be dressed down its external face, fixed into a rebate or reglet, and finished with a sealed finishing strip. Detailing at external wall and floor junctions and under door sills are common areas where leaks occur. Although specific detailing will be influenced by the type of to be installed, there are some key design concepts that should be incorporated irrespective of the type of used. In addition to considering these best practice concepts it is important to follow the manufacturer s instructions specific to the system being installed. solid vertical member top fixing not permitted metal capping gasket 150mm lap min. mechanically fixed to substrate Ballustrade post support detail sealant around edges of base plate finished floor level upstand weatherproof external wall Another aspect of design that is critical to the end performance of the waterproofing system is the detailing of the at its perimeter, e.g. the detailing at its junction with any parapet wall, hob, building envelope and under any door and window sills. The detailing of to parapet wall junctions can be successfully achieved in a number of ways. Commonly they are capped by metal flashings. Best practice procedures dictate that these cappings should be sloped or fall to shed water and should be side fixed rather than fixed through the top of the flashing. It is also important that the is turned up the wall and preferably terminated behind the flashing. For higher parapet walls, the and capping may not overlap, however, in these situations the should terminate in a corner fillet Upstand/parapet protection It is recommended, and will be mandatory if the new standard is called up by the Building Code, that an external finished floor level is at least 100mm lower than the turned up top edge of the. This means that the will need to be turned up and terminated 100mm above the finished floor level on adjacent external walls and that the turn up at door sills will also need to terminate 100mm above the finished floor level. Greater turn ups may be required in more exposed locations or in higher wind areas, e.g. at greater heights or in cyclonic regions. In any system sharp angles and

junctions are points of weakness. Corner fillets and bond breakers are commonly required and must be installed strictly in accordance with manufacturer s instructions. weatherproof wall sealant overlap flashing and attach mechanical fixing at 300 cts max. over flashing 10mm max. vertical gap between the bottom of the flashing and the corner fillet External wall/floor junction door sill 100mm min. finished floor level 100mm minimum require very specific steps to be followed to ensure the tiles adhere firmly to the. Irrespective of which type of is used, it is essential that the manufacturer s installation instructions are stringently followed. A number of manufacturers have worked with tile adhesive manufacturers to develop complete waterproofing and tile installation systems. When selecting a it is essential to consider a number of relevant factors including: whether the will be exposed to weather or protected by subsequently applied floor finishes the type of floor finishes and adhesives that will be applied the exposure conditions of the (e.g. coastal or other aggressive environments) anticipated substrate movement ambient weather conditions (some s must be applied within specific temperature and humidity ranges) the durability of the ongoing maintenance requirements availability of specialist contractors to apply certain systems ease of application re-coating time and time before subsequent finishes can be applied the moisture content of the substrate cost. fixing bracket for wide openings where sill requires horizontal fixing Installation finished floor level External door sill protection Membrane Selection A large number of proprietary acrylic, bituminous and rubber-based waterproofing s are available for use on both trafficable and non-trafficable roof and podium slabs. Their ability to accept directly adhered floor tiles varies. Some modified bitumen and acrylic s are manufactured to accept tiling. Others Prior to installing any system it is essential that the substrate to which it is being applied is appropriately prepared. Concrete must be appropriately cured for the type of being applied and any debris, curing compound, oil, grease, dust and loose material should be removed. Waterproof s rely on a complete system to ensure that the waterproofing of the roof or podium slab is not compromised. It is essential that the manufacturer s instructions are meticulously followed and that: any joints or cracks are filled and sealed as required

any required reinforcing tape or bond breaker is applied to joints and cracks any necessary primer is applied specified coverage thickness is maintained re-coating times are adhered to the application of screeds or finishes is not undertaken until the has sufficiently cured s are appropriately protected from damage until floor finishes are installed. Timber AND METAL FRAMED Balconies The best practice procedures associated with podium and roof slabs also apply to concrete balcony slabs, but timber or metal framed balconies have some additional and specific requirements that must be recognised and accommodated. Timber or metal framed balcony decks must be appropriately designed to ensure the integrity of any waterproofing system is not compromised. The framing structure must be capable of withstanding the live and dead loads likely to be applied to the deck. This includes limiting flexibility to accommodate the installation of brittle floor finishes such as ceramic tiles. Wherever it is likely to be exposed to the weather, framing must be of sufficient durability to perform without degradation. Common problems occur when the underside of a balcony is not lined and the framing is not sufficiently durable. In such circumstances timber bearers and joists will often begin to rot around the perimeter of the deck where the members are most exposed to the weather. The substrate sheeting should be water resistant and the deck must have adequate fall to the drainage points. Prior design consideration should be given to any penetrations or fixings that may penetrate the, e.g. fixings for balcony and handrail posts. Due to the ease of penetrating timber and fibre cement decks, it is essential that adequate supervision is exercised to ensure subsequent trades, such as contractors installing balustrades and handrails, do not inadvertently penetrate the. The two most common problem areas associated with timber and metal framed decks are inadequate fall to the perimeter, and poor design and/or installation at the perimeter of the, e.g. turn-up at the wall and downward termination at the external edge. This photograph shows the result of a poorly constructed system that, amongst other things, had inadequate turn up and protection at the junction with external walls and under the door sill. The draft standard provides typical recommended details for these locations, and typical wall/floor and floor/door sill junction details were provided in previous sections of this information booklet. These photographs show a timber bearer of inadequate durability and an inadequate perimeter detail Treatment at the perimeter can be achieved a number of ways depending upon both the type of framing system and substrate and the type of being used. Some suitable methods of treatment include turning the back under the substrate and dressing it into a drip groove, turning the

down the facing board of the deck and sealing it with an over flashing, or dressing the into a gutter. substrate Balcony edge details sealant downturn to extend a minimum of 100mm sealed fixing over flashing Basements and Retaining Walls Rectification of basement leaks is a particularly difficult and expensive task. The leak may be well underground, access around the building may not be possible, the perimeter of the building may be surrounded with pavements and landscaping and the basement may be fitted out for offices or other tenancies. Proper thought, good design, good installation practices and stringent supervision of the installation of waterproof systems is essential to avoid these problems. The primary components of any basement or retaining wall system include: the structural wall the waterproof protection of the drainage behind the wall, and drainage at or near ground level. In order to avoid some common causes of basement leaks it is recommended contractors pay particular attention to the following: Ensure that a continuous system is installed under the slab and on the walls. If a different is used under the slab and on the walls it is essential that a durable waterproof joint is provided at the junction of the two systems and that the two s are compatible. Ensure that the external wall to floor junction is appropriately designed, constructed and waterproofed. Ensure selection is appropriate and that coverage is complete and of the required thickness. Use a vapour proof as well as a moisture proof where the basement is used as a habitable space or for storage of sensitive equipment etc. Use a that is able to resist aggressive chemicals or salts that may be present in the soil and is able to resist anticipated hydrostatic pressure. Follow manufacturer s instructions exactly, including issues like re-coating times. Adequately prepare the substrate prior to application of the, including ensuring any concrete is appropriately cured. Apply the with the specified coverage and thickness. Ensure that joints and penetrations are adequately sealed. Ensure the is able to resist anticipated thermal movement, soil movement or building settlement. Install appropriate sub-soil and surface drainage systems. Avoid difficult joints and awkward shapes in basement design that complicate the application of the and have the potential to introduce weak points in

the system. Adequately protect the to prevent it from being damaged by construction activities or backfilling. surface water channel base course continuous damp-proof to walls and under floors protection granular drainage metal geotextile fabric slotted drain to fall to suitable outfall drain ground to fall away from building, preferably with concrete path concrete or concrete masonry wall 50mm rebate concrete fl oor slab and foundation blinding slab (if required) damp-proof with aggressive root systems that may damage the or clog the drainage system should be avoided. Trees or shrubs that grow overly large can become potentially unstable and cause damage to the planter if they are blown over. Finally, planter boxes require regular inspection and maintenance, perhaps more than any other system. Building owners or their maintenance contractors need to regularly inspect and identify any damage or degradation caused by people, birds and other wildlife, pests, plant roots or general wear and tear. Prompt repair and maintenance should be undertaken based upon these inspections. Basement wall detail Planter Boxes Many of the principles discussed earlier also apply to planter boxes. However, planter boxes do have some additional specific requirements. wall where there is a wall adjacent to a planter box the overflashing shall be built in or sealed to the wall proprietry or fibre cement protection board or similar soil fill level waterproofing to continue over edge of planter box screw cap for clearing access bead of sealant capping to protect top of The most significant of these is the necessity for adequate drainage. Planter boxes must have a graded base to the drainage outlet and the drainage system must prevent the water level from rising above the overflow level of the. A filtered drainage riser must also be provided to relieve hydrostatic pressure, to provide access for cleaning, and as an emergency overflow in the case of excessive rain. The must be extended up the sides of the planter box to a minimum height of 100mm above the soil level and must be protected with a drainage cell wrapped in geo-textile fabric or a similar suitable material. The top edge of the must be appropriately sealed and protected with either a flashing or capping tile or similar. Care must be taken when selecting the type of plants to be grown in planter boxes. Those fillet drainage cell wrapped in geo-filter fabric the finished base of the planter box shall be graded with falls to the drainage outlet turn up geo filter fabric pipe slotted for vertical drainage openings waterproof shall terminate into drainage outlet drained to stormwater system Planter box detail

www.bsa.qld.gov.au 1300 272 272 www.beconstructive.com.au 1800 798 488