Crescent Valley High School Roof Investigation

Size: px
Start display at page:

Download "Crescent Valley High School Roof Investigation"

Transcription

1 Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko GENERAL INFORMATION The Corvallis School District (CSD) has asked Rowell Brokaw Architects (RBA) to assess the condition of the roofs at Crescent Valley High School (CVHS), which have developed increasing amounts of leaks over the last few years. CDS would like to know if it is possible to extend the life of the existing roof until the next bond cycle, which is several years away, or if funds will be needed earlier to replace the roofs. Mark Young and Chris Andrejko of RBA made an initial site visit on February 4 to meet with Greg Lecuyer and Kim Patten to understand the overall problem, and then followed up with another meeting on March 9 with Kim Patten, Tim Phillips and Doug Tiller to review existing building documents and discuss ongoing maintenance and repairs that have occurred. EXISTING CONDITIONS CVHS was built in 1969 and consists of 4 main buildings typically constructed of concrete and masonry walls, with a roof structure of solid wood decking over glulam beams and purlins. Building A has a metal roof structure and deck. The exterior walls form low parapets around low slope roofs with a shallow sawtooth profile. Slopes are approximately 1/2 per foot and drain to level valleys containing roof drains. One or two mechanical penthouses occur on each of the roofs (See Figure 1). Because mechanical equipment is in the penthouses, there is minimal rooftop equipment or penetrations at the main roof. The buildings range in size from 31,500 sf to 108,400 sf, for a total of about 250,000 sf of roof, including penthouses. The original roofs were built-up bituminous roofs with gravel topping applied over ½ rigid insulation. All of the buildings were re-roofed in 1985 with a Hypalon single ply roof membrane. The single ply roof and additional 1 1/2 fiberglass board insulation was mechanically fastened over the existing roofing. It appears that there were early failures at the valleys after the re-roofing, with records showing multiple replacements of roof membrane and wet insulation from 1983 to The hypalon roof is still the current roofing on the CVHS buildings. LEAKS AND MAINTENANCE Over the last few years, an increasing amount of leaks have occurred at most of the roofs, and various fixes have been applied. Most leaks have occurred at valleys and low points, as the roofs were designed without drainage crickets, causing water to pond (See Figure 2). In addition, pinholes have increased as the roof ages, causing additional leaks in other locations. For the past few years, CSD maintenance staff have spent

2 many hours during the school year looking for leaks and applying spot patches of sealant. Over the summers, they have cleaned and covered the valleys and large parts of roof with roof coatings in an effort to prolong the lives of the roofs. Roof A was entirely coated with Tremco SRC in 2006, and has not experienced leaks since then (See Figure 3). Roofs B and C/D/E were coated with Neogard Elasta-Gard in the valleys and other areas, and have experienced failure of the coating in submerged areas (See Figure 4). 2 of 14

3 ISSUES FOR ROOF REPAIR In RBA s assessment, the issues with the roof are as follows: Cost and Funding: With the next bond cycle in 2018, funds for re-roofing will not be available for another 7-8 years. Given the time required to assemble bidding packages and the possibility of phasing work over multiple years, it is possible that any interim solution will need to last up to 10 years. Future funding should be weighed against the ongoing and probable rising costs for finding and fixing leaks. Age of Current Roofing: The service life of the Hypalon roof system is approximately 20 years, and this roof is well past that age. The surface is chalked, and badly worn or brittle in some areas. As the roof deteriorates further, the amount of pinholes and leaks will increase. In addition, much of the roof has become brittle, making it a less desirable substrate for a coating. Design of Roof Drainage: Without drainage crickets, it is not possible to avoid standing water in the valleys. With the aging roof and uneven substrate of insulation, the problem becomes worse, as the drains no longer are the low points. Although membrane roofs and coatings can withstand periodic ponding, they are not designed or warranted for prolonged submersion. This is likely one factor in the delamination of the Neogard Elasta-Gard coating. Wet Substrate: Based on observations from CDS staff, the insulation has become wet in many locations due to leaks. It is likely that the insulation has not had the opportunity to completely dry out, and receives additional moisture as more leaks occur. Moisture trapped under a roof membrane will try to escape through the membrane as the temperature rises, creating pressure beneath the membrane. This results in bubbling of the membrane and ultimately, tears or delamination. This is also likely a factor in the Neogard Elasta-Gard failures, but any roofing or coating will have difficulties performing well over a wet substrate. Potential for Asbestos: The possibility of asbestos in one of the existing roofing layers was brought up. RBA contacted PBS Engineering + Environmental to discuss an asbestos survey performed sometime between 2002 and Sample cores were taken from the Building D and F roofs, and no asbestos was found. Since all of the roofs are similar, it is probable that there is no asbestos in any of the roofs. However, PBS and RBA recommend that CSD also take additional samples as a precaution. Roofing at Mechanical Penthouses: Based on reports from CSD facilities staff, there have been less problems with leaks at the penthouse roofs. Due to the fact that there is less risk for water damage in these enclosures, they can likely be addressed by spot patching over the next 10 years. However, they should be fully re-roofed at the same time the main roofs are fully re-roofed. Walkway Roofs: Open exterior walkways provide covered connections between the 3 of 14

4 buildings. These still have the original built-up roofing, which have been patched over the years. Because they are exterior space and easy to patch, there are currently no major concerns about the roofs, except for their overall age. It is possible to maintain these roofs with asphalt patching for the next 10 years, but they should be re-roofed as part of any full re-roofing project. 4 of 14

5 OPTIONS The scope of work, cost and schedule presented below are broadly defined, and meant to give a general idea of timing and budget to assist BSD to decide on a direction to take. Once an option (or variation of option) is selected, more detailed design, cost analysis and scheduling will need to be examined. OPTION 1: APPLY COATING OVER THE EXISTING ROOF: This option is an attempt to extend the life of the existing roof by applying the Tremco SRC coating over all main roofs except Bldg A, which has the coating. It has the least first cost, can be implemented quickly, and is the least invasive. However, since it does not address the inherent roof design and moisture problems, it poses the most risk of failure, and beyond a warranty for defects in sealant material, no warranty is offered. Tremco has told us this product only has a life of a few years, so it would likely need to be re-applied for it to last 10 years. RBA has little confidence that this coating option will be worry-free, given the history of roof failures with this roof design. Scope of Work: Prepare specifications and diagrams for bidding (if work to be executed by Contractor). Building A and Penthouse roofs could be optional depending on year of reroofing and upkeep of maintenance cycle. Walkway roofs not included. Clean roof surface and prepare surface according to coating manufacturers surface preparation instructions (Pressure wash by CSD). Replace any damaged or deteriorated roof drains. Apply Tremco Vulkem SRC coating over Bldgs B, C/D/E and F initially. Re-coat all Buildings in five years, unless coating fails earlier. During the life of the coating, inspect roofs on a regular basis (bi-weekly, at minimum). Clean out drains and accumulated debris, and direct ponding water to drains. If all roofs cannot be completed in one season, an option is to coat the valleys of all roofs, along with known problem areas, during the first season, leaving the remainder of the roofs for the following season. Approximate Installation Cost (B,C/D/E,F Year 1; A,B,C/D/E,F Year 5): By Contractor (Pressure wash by CSD): $4/SF x 356,100 SF = $1,424,400 Add 16,700SF for Small Penthouses Year 5: $66,800 Add 9,300 SF for Walkways Year 5: $37,200 By CSD: $1.70/SF material cost x 356,100 SF = $605,370 + $192,000 (CSD Labor Cost) = $797,370 Total Maintenance Cost: Inspect and clean debris: 3 full FTE days/month = $11,520/year. Attend to possible leaks and failures: (50% current time spent on leaks) 5 of 14

6 $15,000/year. Summer patching: (possible in spots, particularly later years) $15,000/year. Possible Schedule of Work: Install by CSD: Documents, procurement: 1 month (?). Install by Contractor: Bid documents, bidding, permit, contract: 2 months min. Install by CSD: 3-4 summers, beginning 2011 (1 building per summer) Install by Contractor: 1 summer and fall, or 2 summers, possible beginning 2011 Pros: Possible for CSD to self-perform work with manufacturer s approval. Slight possibility of bidding work for this summer with minimal documents. Least initial cost. Roofs are not exposed, so possible to continue work during the school year. Wait to re-coat Bldg. A, Penthouses, Walkways. Cons: Extreme uncertainty whether the installation will remain trouble free. At least two cycles of coating will be required to extend roof life 10 years. No warranty possible for 10 years. Moisture in insulation substrate will still be present and may cause future problems. Valleys will still create ponding, which may shorten the life of the coating, and could cause other unforeseen problems. Interim solution will require re-roof in 10 or less years. 6 of 14

7 OPTION 2: NEW DRAINAGE CRICKETS AT VALLEYS / APPLY COATING This option cuts out the existing level valleys and adds drainage crickets to mitigate the main design problem with the roof. With proper drainage, a less expensive roof coating could be used over the remaining existing roof. The recommended coating would be the Tremco SRC coating that was used on Building A, since it has generally worked on that roof. The less expensive Neogard Elasta-Gard coating is not recommended because of previous failures. While wet insulation will be removed from the valleys, there will probably be moisture under the remaining roof, which may cause problems in the future. Although this approach decreases the risk of failure, existing problems with the rest of the substrate may still cause leaks, so the prospect of the roof remaining trouble-free is uncertain. Like Option 1, the coating will need to be re-applied every few years. It is still an interim solution, and all buildings will need to be re-roofed within 10 years or less. Scope of Work: Prepare specifications and drawings for bidding. For roofs not completed the first season, the Tremco SRC coating should be applied over known trouble spots, and roofs should be inspected and cleaned more thoroughly on a regular basis until patched. Building A and Penthouse roofs could be optional depending on year of reroofing and upkeep of maintenance cycle. Walkway roofs not included Clean roof surface and prepare surface according to coating manufacturer s surface preparation instructions. Remove approximately 20 ft wide strip of top membrane, wet/damaged insulation, and deteriorated roof drains. Install tapered insulation crickets with cover board that blend to the existing roof and direct drainage towards roof drains. Install hypalon-compatible membrane (hypalon is no longer manufactured) and weld to existing roofing and roof drains. Apply roof coating over the remainder of roof, overlapping new membrane. During the life of the repair and coating, inspect roofs on a regular basis (biweekly, at minimum). Clean out drains and accumulated debris. Re-coat all roofs in five years, unless coating fails earlier. Approximate Installation Cost (not including mechanical penthouses): It is difficult to get an accurate cost for this hybrid approach of patching and coating, but removal of valleys alone will result in 20%-40% new roofing. Add coating over the remainder of main roofs and recoating at 5 years, and the cost over 10 years is well over the cost of Option 1. It possibly approaches or exceeds the cost of a full re-roof. Maintenance Cost: Inspect and clean debris: 2 full FTE days/month $7,680/year. Attend to possible leaks and failures: (25% of current time spent of leaks) $7,500/year. 7 of 14

8 Summer patching: (possible in spots, particularly in later years) $10,000/year. Interim Tremco SRC patching at problem areas while waiting to be re-coated or patched (1-2 years similar to current FTE spent of roof maintenance) $15,000. Possible Schedule of Work: Bid documents, bidding, permit, contract: 3 months. By Contractor: 1-2 summers, beginning 2012 Pros: Addresses major roof design flaw of level valleys and minimizes ponding. Without ponding, allows less expensive coating over the remainder of the roof. Probable less first cost than full re-roof. Wait to re-roof Bldg. A, Penthouses, Walkways. Cons: Leak detection, patching and maintenance will be required for existing roofs until they are patched and coated. Since hypalon is no longer manufactured, it may be difficult to find a compatible roof membrane. Difficult to patch new membrane onto deteriorated existing roofing with new membrane, and may not be possible to obtain warranty. Hybrid approach - uncertainty whether the installation will remain trouble free for 10 years. Although removes some of wet insulation, moisture probably will remain in other areas and may cause future problems. Will require ongoing inspection and possible future maintenance for leaks. Interim solution will require re-roof in 10 or less years. 8 of 14

9 OPTION 3: FULL ROOF REPLACEMENT This option replaces all of the roofs with a properly designed roof system that will last at least 30 years. All of the existing roofing will be removed so that moisture can be more predictably controlled with the new system. Tapered crickets will allow positive slopes to all drains, correcting the main roof design problem. In the roof system, insulation meeting or exceeding the current energy code will be installed, potentially saving energy costs for the future. In order to correctly install the roof at the edges and around penthouses, new flashing is also assumed. In addition, it makes sense to re-roof Bldg. A, Penthouses and Walkways at this time, since they will likely need to be re-roofed within 10 years. Scope of Work: Prepare specifications and drawings for bidding For roofs not completed the first season, the Tremco SRC coating should be applied over known trouble spots, and roofs should be inspected and cleaned more thoroughly on a regular basis until replaced. Remove existing and original roof to expose the roof deck. Remove sheet metal flashing and replace roof drains. Install 3 rigid insulation with tapered insulation crickets and cover board, directing drainage towards roof drains. Install roof membrane and new sheet metal flashing. Install walkpads from mechanical penthouses to roof drains and other maintenance areas. Approximate Installation Cost (includes mechanical penthouse roofs) Fully Adhered 80 Mil TPO or PVC (30 year roof): 251,300 SF - $2,235,000 Recommended 10% contingency for possible dry rot, etc. - $223,500 Deduct for mechanically attached ($150,000) Deduct for 60 mil (20 year) roof ($135,000) 20 year warranty (most common): $0.10/SF - $25, year warranty (available for 80 Mil): $0.15/SF - $38,0000 Maintenance Cost: Inspect and clean debris: 0.5 full FTE days/month $1,920/year. Interim Tremco SRC coating at problem areas while waiting for re-roof. ((1-2 years similar to current FTE spent of roof maintenance) $15,000. Possible Schedule of Work: Bid documents, bidding, permit, contract: 3 months. By Contractor: 1-2 summers, beginning 2012 Pros: Least risk of short and long term failure. 9 of 14

10 Long life of years, with warranties available to 30 years. Roof slope design issues will be fixed, allowing easier future re-roofing.. Substrate moisture problems will be fixed. Added insulation will increase the buildings energy efficiency Least cost over next 30 years - interim options will need similar re-roofing within 10 years. Ongoing inspection and maintenance minimized. Periodic cleaning of drains and debris. Leaks covered by warranty. Cons: Most expensive first cost. All roofs replaced, and requires replacement of metal flashing. Leak detection, patching and maintenance will be required on existing roofs until they are coated at least for another year. 10 of 14

11 FIGURE 1 Roof Diagram 11 of 14

12 FIGURE 2 Ponding in Valleys 12 of 14

13 FIGURE 3 Unit A Roof with Tremco SRC Coating 13 of 14

14 FIGURE 4 Failed Neogard Elasta-Gard Coating 14 of 14

RECOATING AND RENEWING SPF ROOFING SYSTEMS

RECOATING AND RENEWING SPF ROOFING SYSTEMS RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.

Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00. Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado

Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July

More information

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance

More information

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015 Clear Fork Valley Local School District Roofing Repairs Spring/Summer 2015 Instructions to Bidders: Public Notice To Bidders (ORC 3313.46) Notice is hereby given that sealed bids will be received at the

More information

The existing roof angle change terminations and flashings when sound and intact can be reused.

The existing roof angle change terminations and flashings when sound and intact can be reused. January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing

More information

SchoolRoof Repair - Cost For Replacement of a Student Roof, Part 2

SchoolRoof Repair - Cost For Replacement of a Student Roof, Part 2 ROOF REPAIR UPDATE For the November school newsletter, I wrote an article in which I explained the condition of the school roof, the estimated cost of replacing the three flat sections from the 1996 building

More information

Solicitation DTFACN-11-R-00079 Attachment #9

Solicitation DTFACN-11-R-00079 Attachment #9 These specs are only a general overview of the typical VOR Roof construction. These are for reference only. Each individual project will have its own specifications. 1 VOR Roof Projects IDIQ Solicitation

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)

More information

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System

More information

Roofing Repairs 07511-1

Roofing Repairs 07511-1 SECTION 07511 ROOF AND FLASHING RESTORATION WITH TITLE 24 / COOL ROOF SURFACING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

Low-slope reroofing guidelines

Low-slope reroofing guidelines Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August

More information

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings

More information

INDIAN HEAD ELEMENTARY SCHOOL

INDIAN HEAD ELEMENTARY SCHOOL ROOF ASSESSMENT REPORT INDIAN HEAD ELEMENTARY SCHOOL NOVEMBER 08, 2010 PREPARED FOR: FACILITIES DEPARTMENT WHITMAN HANSON REGIONAL SCHOOL DISTRICT 1. Purpose This Roofing Assessment Report provides a summary

More information

Building Owners Guide to a Duro-Last System!

Building Owners Guide to a Duro-Last System! Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER

More information

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof! Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing

More information

REQUEST FOR PROPOSALS

REQUEST FOR PROPOSALS Page 1 of 6 REQUEST FOR PROPOSALS Issue Date: 2/19/2013 RFP# WHS-2013-001 Title: Services for roofing improvements and annual roof assessments, Windsor School Complex, State Street, Windsor, Vermont Issuer

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:

More information

Getting The Most Out of Your Roof Asset. Program #099 PM

Getting The Most Out of Your Roof Asset. Program #099 PM Getting The Most Out of Your Roof Asset Program #099 PM Garland 12 Steps: Specifications, Inspections, Details, Field Support Budget vs. Desired Life Expectancy Reduction of Liability Resource Staying

More information

ROOF INSPECTION & MAINTENANCE

ROOF INSPECTION & MAINTENANCE Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long

More information

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO

More information

ADDENDUM NO. 2. DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015

ADDENDUM NO. 2. DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015 ADDENDUM NO. 2 DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015 RECEIPT DATE: September 30, 2015 (CHANGED) OPENING DATE: October

More information

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

CHICAGO ROOFING CONTRACTORS ASSOCIATION

CHICAGO ROOFING CONTRACTORS ASSOCIATION CHICAGO ROOFING CONTRACTORS ASSOCIATION JANUARY 22, 2016 Roofing Claims & Lawsuits Stephen M. Phillips Hendrick, Phillips, Salzman & Flatt, P.C. 230 Peachtree Street, Suite 2500 Atlanta, GA 30303 (404)

More information

ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY

ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY BEAM A Premiere Roof Asset Management Program WITH BEAM WE CAN HELP YOU MAINTAIN AND PROTECT THE ROOF THAT PROTECTS YOU. A FRAGILE BARRIER Consider

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

How to repair your existing low slope flat roof.

How to repair your existing low slope flat roof. How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

Specifying SPF Roofing Systems

Specifying SPF Roofing Systems Specifying SPF Roofing Systems Spray polyurethane foam (SPF) roofing systems have been marketed for years primarily on their documented energy saving characteristics. Consequently much of the SPF roofing

More information

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck. SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

CARLISLE OWNER S MANUAL

CARLISLE OWNER S MANUAL Investing in Solutions for Over 45 Years For over 45 years Carlisle Construction Materials Incorporated (CCM) has been creating solutions for the construction industry. Beginning with single-ply roofing

More information

Roof Systems Overview

Roof Systems Overview Roof Systems Overview Cold Applied Built-Up Roofing Systems BURmastic Tremco s line of cold applied built-up roofing systems. BURmastic 200 Combines Tremco s expertise in asphalt blending technology with

More information

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Department of Advanced Education and Skills Apprenticeship and Trades Certification Division Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Note to Apprenticeship Applicants

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING

SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

TARRANT COUNTY DETAIL STANDARDS

TARRANT COUNTY DETAIL STANDARDS TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout

More information

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Maintenance & Inspection Guide

Maintenance & Inspection Guide ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

NEOGARD. Preventive Maintenance Manual

NEOGARD. Preventive Maintenance Manual NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide

More information

SECTION 07 54 23 PVC SINGLE PLY ROOFING

SECTION 07 54 23 PVC SINGLE PLY ROOFING SECTION 07 54 23 PVC SINGLE PLY ROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Attached GENERAL CONDITIONS, GENERAL NOTES, INSTRUCTIONS TO BIDDERS, AND BID FORM are components of this section. B. Section

More information

THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING

THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING DIVISION 7 THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING 07110. MEMBRANE WATERPROOFING: The following are minimum requirements to assure adequately designed waterproofed floors for machine and equipment

More information

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

Roof Condition Analysis

Roof Condition Analysis Roof Condition Analysis Prepared for: J.W. Nelson John Evans Middle School - Gym Dome 2900 15th Avenue Greeley, Colorado Prepared by: Gregory Ham Coastal Specified Products 5252 Sherman Street Denver,

More information

Please read the entire document before purchasing and installing any of these products

Please read the entire document before purchasing and installing any of these products Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection

More information

2011 Dodson Publications, Inc. Page 1 of 6 September 16, 2011 8:19 AM

2011 Dodson Publications, Inc. Page 1 of 6 September 16, 2011 8:19 AM Contractor Makes Quick Work of Colossal Recover Maintenance Contract Helps Land Contractor Huge Reroofing Job in Colorado by Andrew Romano, senior product manager, GAF It s the closest most crews get to

More information

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION 07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling

More information

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings. SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.

More information

Hartsfield-Jackson Atlanta International Airport s

Hartsfield-Jackson Atlanta International Airport s Hartsfield-Jackson Atlanta International Airport s 2008-09 Closed Projects (Posted 1/6/2009) FC-3007000038C: MISCELLANEOUS BUILT-UP ROOF AND SINGLE PLY ROOF REPAIRS AT H-JAIA Furnish all labor, equipment,

More information

Your guide to home maintenance. Flat Roofs

Your guide to home maintenance. Flat Roofs Your guide to home maintenance Flat Roofs Your guide to home maintenance is a series of information leaflets that gives you all the information you need to keep your home in tiptop condition. Flat Roofs

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

Thank You! Owner Aaron Perry! Email info@exteriorproinc.com! 2936 Clifty Drive! Madison IN 47250! (855) 274-0444! (812) 274-0444!

Thank You! Owner Aaron Perry! Email info@exteriorproinc.com! 2936 Clifty Drive! Madison IN 47250! (855) 274-0444! (812) 274-0444! A properly installed and maintained flat roof can be one of a building s biggest assets while a leaking or failing roof can quickly become a building s biggest expense. We ve put this simple guide together

More information

Roofing 101 - Signs that Your Roof Needs Repair/Replacement

Roofing 101 - Signs that Your Roof Needs Repair/Replacement By: Cherie Martel Roofing 101 - Signs that Your Roof Needs Repair/Replacement 1. Tell us a little bit about your company and its foundation. In 1963, Samuel T. Martel began a small family run roofing company,

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing

More information

Winterizing Your Building

Winterizing Your Building Winterizing Your Building DEC Author: Steven J. Susca This article was originally published in the Hoffmann Architects Journal in Issue 3, 2009. As spring thaws uncover the ravages winter weather has wreaked

More information

Aerial Infrared Roof Moisture Surveys

Aerial Infrared Roof Moisture Surveys Aerial Infrared Roof Moisture Surveys INTRODUCTION IR P/PM (infrared predictive/preventive maintenance) is not limited to annual infrared surveys of electrical switchgear. For instance, infrared thermography

More information

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

A. This Section includes rubberized asphalt sheet membrane waterproofing systems. SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practice Roof Design: Sustainable Energy Efficient Reroofing Presented by Edis Oliver, PE Principal 9511 Lake Creek Parkway Austin,

More information

Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities

Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities Roof Restoration System For building owners, property management firms and facility managers seamless possibilities Extending your roof life Think of your existing older roof custom fit with a seamless,

More information

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing

More information

Roofing & Waterproofing Forensics for the 21 st Century. Peter Brooks, President

Roofing & Waterproofing Forensics for the 21 st Century. Peter Brooks, President Roofing & Waterproofing Forensics for the 21 st Century Peter Brooks, President March 20, 2013 ICRI Spring Convention Selecting the Appropriate Non-Destructive Testing Technology What is the Goal? Methodologies:

More information

The Perfect Fit For Metal Retrofit

The Perfect Fit For Metal Retrofit D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are

More information

Commercial Roof Inspection Form

Commercial Roof Inspection Form Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

Reroof or Restore? The right decision can save weeks of time and thousands of dollars

Reroof or Restore? The right decision can save weeks of time and thousands of dollars APOC A DIVISION OF GARDNER - GIBSON 5903 Paramount Boulevard Long Beach, California 90805 Telephone (800) 562-5669 Fax (562) 423-9597 www.apoc.com THE FOLLOWING TECHNICAL ARTICLE WAS PUBLISHED IN A MAJOR

More information

The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois

The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois Wiss, Janney, Elstner Associates, Inc. 10 South LaSalle Street, Suite 2600 Chicago, Illinois 60603 312.372.0555 tel 312.372.0873 fax www.wje.com The Building Group First Tuesdays October 2, 2012 Jason

More information

WISCONSIN HOUSING AND ECONOMIC DEVELOPMENT AUTHORITY

WISCONSIN HOUSING AND ECONOMIC DEVELOPMENT AUTHORITY WISCONSIN HOUSING AND ECONOMIC DEVELOPMENT AUTHORITY EPDM - SINGLE PLY MEMBRANE ROOFING REPLACEMENT SPECIFICATION Section 07500 - June 97 - Revised TO: Owners/Project Managers/Contractors RE: All WHEDA

More information

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36. Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth

More information

Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015

Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015 PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015 FACILITIES & MAINTENANCE By Rick Thomas Fluid-Applied Roofing for Repair and Renovation Leaking roofs are one thing which every private university facility

More information

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections

More information

FEFPA 2015 SUMMER CONFERENCE. Energy Effectiveness through Roof Coatings and Solar

FEFPA 2015 SUMMER CONFERENCE. Energy Effectiveness through Roof Coatings and Solar FEFPA 2015 SUMMER CONFERENCE Energy Effectiveness through Roof Coatings and Solar Welcome Danny G. Daniel Stokes, CSI, CDT, RCI, CPRC Vice President Advanced Roofing Inc. About Danny Stokes Vide President

More information

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's The NRCA Roofing and Waterproofing Manual apply to work of this Section. SECTION 075419 POLYVINYL CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for

More information

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

StuccoSpec Moisture Testing Inspection

StuccoSpec Moisture Testing Inspection e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012

More information

WATERPROOFING FOR CONCRETE STRUCTURES

WATERPROOFING FOR CONCRETE STRUCTURES MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck

More information

SWEPCO HEAVY DUTY POLYMASTER ROOF SYSTEM 201

SWEPCO HEAVY DUTY POLYMASTER ROOF SYSTEM 201 31 SC: 33 SWEPCO POLYMASTER ROOF SYSTEM 201 APPLICATION SPECIFICATIONS IMPORTANT -- These application specifications are provided for the use of all persons who are to apply SWEPCO Products. Please read

More information

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new

More information

Rooftop Matters. 2 0 1 2 Benchmark Report. Executive Summary

Rooftop Matters. 2 0 1 2 Benchmark Report. Executive Summary The 2012 Benchmark Report is our initial survey covering results from roof inspections and service calls over a six-month period. Our intention is to update these results annually in order to provide meaningful

More information

Detached accessory structures that contain no conditioned floor area are exempt.

Detached accessory structures that contain no conditioned floor area are exempt. RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

What to Do About Your Roof and How to Hire a Roofing Contractor

What to Do About Your Roof and How to Hire a Roofing Contractor ROOFI NG What to Do About Your Roof and How to Hire a Roofing Contractor On those rare occasions when it rains in Arizona and you have a leak, you may wonder if you need a brand new roof, especially if

More information

Nondestructive Evaluation of USCG. 2401 Hawkins Pt. Road Curtis Bay, MD 21226. Provided by: HurleyIR

Nondestructive Evaluation of USCG. 2401 Hawkins Pt. Road Curtis Bay, MD 21226. Provided by: HurleyIR Nondestructive Evaluation of USCG 2401 Hawkins Pt. Road Curtis Bay, MD 21226 Provided by: HurleyIR On Tuesday May 20 th 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers of the USCG

More information