1 PQ TechWatch A product of the EPRI Power Quality Knowledge program Power Quality in Internet Data Centers November 2007 CONTENTS Background of Internet Data Centers Shared-Facility Centers Stand-Alone Centers Modular Centers Pre-Built Centers Mobile Data Centers IDC Facility Wiring Systems Automatic Transfer Systems Secondary Switchgear AC Power Systems Ideal Characteristics and Requirements....4 Reliability and Availability Power Quality Considerations Importance of Grounding Further Reading Notes Brian Fortenbery, EPRI SUMMARY The building of Internet data centers (IDCs) is a growing industry that is pushing the limits of electric power and reliability requirements. As utilities must decide whether it is worth the cost to build new infrastructure to keep up with the present demand, facility operators are looking at power distribution designs that will improve efficiency and allow them to continue to expand their operations. To meet customer expectations of five nines or % availability, IDC designers must improve power quality, reliability, and efficiency. In this quest, redundancy in the system becomes absolutely necessary, but also important are power quality issues such as mitigation of voltage fluctuations and harmonics and good techniques for grounding. This PQ TechWatch provides information about the types of data centers being built and their design, along with new standards and certification processes that are being developed. Detailed descriptions are provided of power quality considerations and possible solutions. Grounding is given its own section, where electrical standards for safe and effective grounding are discussed and examples provided.
2 About the EPRI Power Quality Knowledge Program The EPRI Power Quality Knowledge Program provides a wealth of resources in well-designed, readable, and accessible formats. Paramount among these resources are documents covering a wide range of PQ topics, written not only for use by busy PQ professionals, but also to be shared with important end-use customers and internal utility managers. The program s website, is the most comprehensive electronic PQ resource available, providing 24-7 access to proven expertise via the PQ Hotline, hundreds of PQ case studies, over 200 PQ technical documents, PQ standards references, indexes, conference presentations, and a wealth of other resources. For more information, please visit Copyright 2007, EPRI ( All rights reserved. Distribution of PQ TechWatch is subject to a license agreement with EPRI. No portion of this report may be reproduced or redistributed in any form, including electronic copies, without prior written consent from EPRI. Distribution outside the licensed organization is expressly forbidden. Product and company names mentioned in this document may be trademarks of their respective companies. Mention of third-party products is for informational purposes only and constitutes neither a recommendation nor an endorsement. EPRI and the EPRI logo are trademarks of EPRI. ii Power Quality in Internet Data Centers
3 BACKGROUND Internet data centers (IDCs) are buildings that house servers and all the associated Internet equipment for Web hosting and data-storage functions. IDC companies provide space, electric power, security, fire suppression, and connectivity for their customers. The connectivity requirement usually prompts IDC companies to locate their buildings near fiber backbones. The electric power requirement, which can be remarkably large for the building size, has traditionally been treated almost as an afterthought. For electric utilities, these power requirements can pose extremely serious problems. For example, when an IDC company approaches a utility and requests 100 MW in an urban downtown area, the request usually can not be honored without a significant investment in infrastructure. Utilities are generally skeptical about investing in this infrastructure and rightfully so. The IDCs represent a young industry without a long track record, which leaves utilities unsure about how much power might actually be used or even how long the IDC may stay in business. The data center industry enjoyed phenomenal growth in its early years. Until the spring of 2001, it seemed that there would be no end to the growth of this market segment. However, a market downturn in the spring resulted in a slowing of this growth rate. Instead of building new facilities as fast as possible, IDC companies operated for a few years in a wait-and-see mode. In 2001, it was estimated that only 45% of the colocation space in the United States was occupied. Today, the market has rebounded and data centers all over the world are filling up, with new construction proceeding in many areas. In today s market, the power density of servers has increased to the point that the main concern of facility operators is how to remove enough heat to allow installation of more servers. Many data centers have literally reached their limit in terms of cooling capacity. There are several types of data centers, to choose from depending on the needs and intent of the designers. Shared-Facility Centers Shared-facility IDCs are most likely the oldest type of IDC in existence. Indeed, they have their roots in and before the 1980s when large computer rooms inside office buildings or warehouses were the norm. Banks, universities, and the payroll departments of large companies were all likely candidates for owning such a facility. Of course, these early computer rooms were full of equipment that seems antique by today s standards, but the principle behind them was much the same. By definition, a shared-facility IDC is an IDC where at least part of the building that houses the facility is devoted to other purposes. For instance, one example is a tall office building with a few floors devoted to the IDC and the rest of the building devoted to offices and other spaces. The advantage to this type of facility lies in general cost efficiency. Existing building space can often be converted into an IDC for much less than the cost of building a new facility. Stand-Alone Centers Stand-alone IDCs were probably the second type of data center to evolve. By natural extension, the stand-alone IDC eliminates many of the drawbacks to shared facilities by removing the relative unknown factors associated with having general-use space attached to the sensitive data-center space. In a stand-alone building, the data-center company has complete control over security, fire control systems, ventilation systems, and power systems, which allows for a greater degree of security and system stability. 1 Power Quality in Internet Data Centers
4 Building a data center is a major undertaking, because the standards in materials and construction are higher out of necessity to provide the most stable, secure environment possible for clients. This type of facility is somewhat newer than the shared data center because only recently has raised-floor space (the area inside the data center that holds computer and telecommunications equipment) been in such high demand. Obviously, the greatest drawback to this type of facility is cost. Building a data center is a major undertaking, because the standards in materials and construction are higher out of necessity to provide the most stable, secure environment possible for clients. Modular Centers Modular IDCs offer some of the advantages of stand-alone facilities while not having the disadvantage of being tied to a single location. In fact, such facilities do not actually have buildings at all. Instead, computer and telecommunications hardware is housed inside a trailer or other easily transportable housing with all the requisite environmental controls. Generally, facilities of this type are not designed for long-term use, instead being designed to provide additional raised-floor space in areas where a sudden and temporary increase in demand is expected. When they are needed, the modular facilities are transported to the site where their use is required, and they are supplied with fiber optic and power connections. Pre-Built Centers Along the same thread as modular IDCs are pre-built IDCs. Simply put, a company builds a data center from the ground up and then rents, leases, or sells the facility to another company that wishes to run an IDC in it. The biggest advantage of this type of facility is that little or no lead-time is required in acquiring one and the initial outlay of capital is much less if the facility is not being purchased on a permanent basis. In general, everything the IDC needs to run except for the telecommunications and computer gear is included in the pre-built facility. These features range from generation equipment, which often has a high lead-time of its own, to heavy-duty construction materials that would have to be added to an existing building if it were to be renovated into an IDC. Mobile Data Centers Mobile data centers (MDCs) can be applied to a variety of potential applications: Internet Start-Ups. When a point of presence in a city or remote location is needed, an MDC may be used. Four hours after arriving on-site, information technology and gateway equipment can be installed and operational. Media. When a big event for broadcast over the Web is needed, an MDC may be used. In addition, when a network operations center for a news-gathering operation is needed on the scene, an MDC can be used to solve the problem. Fiber optics are connected or a satellite-dish base station is added and the Internet system is up and running within hours of arrival on-site. Disaster Recovery. When a place to house Internet equipment is needed after a disaster such as the World Trade Center attack, an MDC helps meet traditional demand but with a unique solution. Other types of applications include military and healthcare. The MDC can be delivered by heavy air transport anywhere in the 50- Hz world. A 60-Hz design is available for the United States, Japan, and other countries using 60 Hz. 2 Power Quality in Internet Data Centers
5 IDC FACILITY WIRING SYSTEMS A one-line diagram for a typical stand-alone IDC facility is shown in the figure below. To increase reliability and availability, redundancy must be built into the power system. One-Line Diagram of Data Center Power Distribution Secondary Switchgear The circuit breakers above and below the ATS are rated the same as the ATS. The ones above are in the main switchgear panel and the feeders to the ATS are three 500 MCM with a #4/0 ground. The ones downstream of the ATSs are located in the main switchboards, SBA and SBB, and control the input to those switchboards. The same size conductors are carried through from the ATSs to these switchboards. AC Power Systems From a facility manager s point of view, the main problems associated with power that affect how the IDC is operated are interruptions, power quality, and expandability. Great care and expense was taken to ensure that the interruptions and power quality at this site were addressed. The electrical arrangements to do so are described below. As for expandability, the utility has provided all the capacity requested at this site, so that should not be an issue here. Redundancy is built into power distribution designs to increase reliability. Automatic Transfer Systems Two automatic transfer systems (ATSs) are in place at the 480-V level at the plant. One is designed to take the critical loads from the utility to the backup generator upon loss of power. The other is for a second backup generator that may be used in the future. At present the loading in the plant is such that a single generator is sufficient. However, if the occupancy ramps up to greater than half load, then a second generator will be necessary. The ATSs are rated 1600 A with a 65-kA interrupting rating. Switchboards SBA and SBB have various circuit breakers feeding loads. Among those are two 45-kVA transformers for office loads and lighting. One of these has a 120/208V secondary and the other has 480/277V. A third circuit is for HVAC units, one from each switchboard. The next loads are the uninterruptible power supply (UPS) systems. A dedicated feed goes from each switchboard to a UPS. A feeder also goes from each bus to one of two units in a dual UPS used for redundancy. This system is discussed in more detail in the UPS section. Downstream from the UPSs are the critical load distribution panels, which feed the power distribution units (PDUs). Two of these panels are fed by two of the UPSs. A third panel, fed by the third (dual) UPS provides an alternate source of power for the PDUs. This redundancy will ensure very high reliability of power in this plant. 3 Power Quality in Internet Data Centers
6 Since the revitalization of the data-center industry, some much-needed formalization of the requirements and criteria for reliability and availability has occurred. IDEAL CHARACTERISTICS AND REQUIREMENTS The ideal characteristics and requirements for IDC facilities are based on contributions from industry experts. Each of the following are addressed in data-center design: Structure Power usage, availability, and reliability Ventilation and air-conditioning Floor space Telecommunications Networking Security Lighting Fire suppression Siting For the purposes of this power quality document, the most important of these items will be reliability and availability, which will be explored in more detail. In the early years, criteria for these were market driven time to market was the most important, with reliability and availability probably secondary. Today, a more formal set of guidelines is available. Reliability and Availability Since the revitalization of the data-center industry, some much-needed formalization of the requirements and criteria for the reliability and availability outlined above has occurred. Entities such as the 7X24 Exchange, AFCOM, and the Uptime Institute have played major roles in this endeavor. In particular, the Uptime Institute has taken on a lot of this effort, and although not a standards body, they are well-known and widely respected. Customer expectations have grown over the years to the point that they now expect availability of five nines, or %. This typically requires a substantial investment in hardware and infrastructure, which leads to a need for a common benchmarking standard to help define the level of availability and what is required to achieve it. The Uptime Institute has developed a tiered classification approach for this purpose. This system includes actual measured availability figures ranging from 99.67% to more than 99.99%. Recent surveys show that the Uptime Institute s tier classification system is used by the majority of respondents. One major concept in the tier levels is that of dual-powered technology, which requires at least two completely independent electrical systems. The last point of electrical redundancy is moved from the UPS system downstream to a point within the computer hardware itself. One description of this type of design is system plus system, or S+S. A site that can sustain at least one unplanned worst-case infrastructure failure with no critical load impact is considered fault tolerant. A site that is able to perform planned site infrastructure activity without shutting down critical load is considered concurrently maintainable (fault tolerance level may be reduced during concurrent maintenance). It should be noted that a typical data center is composed of at least 20 major mechanical, electrical, fire protection, security, and other systems, each of which has additional subsystems and components. All of these must be concurrently maintainable and/or fault tolerant to meet the requirements. In some cases, sites might be built with S+S electrical concepts but might not incorporate those into the mechanical systems. In such cases, the site may achieve Tier IV electrically, but only Tier II or III mechanically. 1 4 Power Quality in Internet Data Centers
7 The following is a description of these tiers, as revised in The figures below illustrate these tiers and the typical powerdistribution topologies required. Tier II Tier II is composed of a single path for power and cooling distribution with redundant components, providing 99.74% availability. Tier I Tier I is composed of a single path for power and cooling distribution, without redundant components, providing 99.67% availability. Description of Uptime Institute Tiers I and II Tier III Tier III is composed of multiple active power and cooling distribution paths (but with only one path active), has redundant components, and is concurrently maintainable, providing 99.98% availability. Tier IV Tier IV is composed of multiple active power and cooling distribution paths, has redundant components, and is fault tolerant providing % availability. As the cost of downtime increases, systems must become more reliable by adding redundancy and increasing fault tolerance. Description of Uptime Institute Tiers III and IV At Tier IV, Uptime Institute adds specifications for required hardware performance. The main addition for Tier IV is that all computer hardware must have dual power inputs. The Uptime Institute has a specification for that also, which includes thirteen points describing the required equipment performance. The requirements include two power sources to the equipment, wherein the loss of either will not affect operation. Return of lost power will not require any intervention. The other source may fail 10 seconds after return of the lost source with no impact on operation. Specifications regarding frequency, phase angle, and phase rotation are included, as well as internal terminations without transfer switches. Neutral-to-ground bonds inside the equipment are not allowed, to prevent circulating ground currents between the two sources. Other requirements include load sharing within 10% of average for multiple power sources, and internal ridethrough designs are only allowable for safe orderly shutdown. Annunciation is to be provided for fault indication within 60 seconds, and the manufacturer supplies a written certification of compliance with the specification. The Uptime Institute tests 5 Power Quality in Internet Data Centers
8 In data centers, large expenditures are made to ensure that power quality issues do not affect the operation of the business. products to independently verify and certify compliance with this specification. A listing of certified products is maintained on its website. 2 Power Quality Considerations Power quality issues are important in data centers, but in a different way than most types of operations. In data centers, large expenditures are made to ensure that power quality issues do not affect the operation of the business. PQ issues that should be considered in the data center industry include: Voltage sags Momentary interruptions Voltage swells Voltage transients (surges) Harmonics Grounding Voltage Sags and Momentary Interruptions By virtue of the nature of the power distribution system in data centers, sags and interruptions are not usually a cause of downtime. In fact, these events have been all but removed from consideration by the upstream power conditioning, using UPS and backup generators. Even a Tier I site will use UPS and generator sets, so sags and interruptions can only cause a problem if there is an equipment failure. This is why the tier definitions are so important-the power quality problem has become an infrastructure design and maintenance problem, so that the probability of downtime is significantly reduced. In fact, the most common cause of downtime in the data center industry is human error, quite often accidental activation of the emergency off switch. Other human errors can occur, which can be minimized through training and, often, installation and maintenance of the redundant systems. Ride-Through Curves for Servers Most servers can ride through sags and interruptions that last from 30 to 300 ms. In addition to the above discussion, previous testing by EPRI has shown that most servers can ride through sags and interruptions for durations that vary from 30 to 300 ms. While there may be many sag events longer than 30 ms, few are longer than 300 ms, and so devices that survive 300 ms sags are far less likely to be affected by voltage sags in general. The plot to the left shows test data for a variety of servers tested at 230 V. It should be noted that the curves represent voltage tolerance envelopes, or ride-through curves. The horizontal axis is time in cycles, while the vertical axis is the value of the remaining voltage as a percentage of nominal. Each curve shows that if sags occur that fall under the curve, the server may trip offline. If the sags are above the curve, the server will continue to operate without interruption. 6 Power Quality in Internet Data Centers
9 Voltage Swells Many UPSs on the market do not protect loads from voltage swells, but there is not much evidence of damage or equipment misoperation as a result of swells. The IEEE definition states that swells may be up to 1.8 per unit (PU) for as long as 2 minutes. EPRI testing programs for temporary overvoltage up to 3.0 per unit have determined that most end-use equipment can sustain damage under these conditions. The tests performed for temporary overvoltage are outlined below. Test Parameters for Temporary Overvoltage Test Number Simulated Condition Magnitude Duration However, based on EPRI survey data, these are not very common events. In fact, such events can be estimated to occur as seldom as once every six years in the United States. The chart on the lower left shows some of the data from the survey. Voltage Transients (Surges) Lightning is a well-known phenomenon that can cause equipment damage. Surge protection devices are widely used in commercial, industrial, and residential settings, and the data center is no exception. Most UPS manufacturers will offer surge protection for the critical loads, and in addition, the servers themselves will typically be supplied with surge protection. 1 Poor voltage regulation 2 During a fault 3 Loss of secondary neutral 1.15 PU (138 V) 1.3 PU (156 V) 1.5 PU (180 V) 6 hours 2 seconds 4 hours When studying the power supply, the transient damage can affect the following: Diode rectifier bridge Filter capacitor 4 Ferroresonance 5 Contact to high voltage circuits Swell Rates from EPRI Survey 2.0 PU (240 V) 3.0 PU (360 V) 1 minute 1 second Fuses Switching transistor The figure below shows the points where surges are likely to enter the equipment. Swell Rate Magnitude Histogram All Sites, One-Minute Aggregate Window Surge Entry Points for Equipment Swells per Site per 30 Days Swell Rate Cumulative Frequency 100% 110 to to to to to to to to % 80% 70% 60% 50% 40% 30% 20% 10% 0% Cumulative Frequency RMS Voltage Magnitude (%) Surges can enter electrical equipment and numerous connection points. Voltage swells are infrequent and rarely cause damage. 7 Power Quality in Internet Data Centers
10 The three common elements used in surge protection are Gas tubes Silicon avalanche diodes Metal oxide varistors Various vendors supply devices based on these technologies, which can be applied inside the appliance, or at the plug outside the appliance. Surge arrestors can also be applied at the panel level, or the switchgear at the service entrance to the building. Utilities sometimes apply lightning arresters outside the building, as well. Secondary surge protection devices may also be installed on the PDU transformer primary and secondary windings. Protecting both primary and secondary is the ideal arrangement for protection at the transformer level. Surge Protectors in PDU The figure below shows an example in which the primary surge protection device is installed at the switchgear on the incoming bus from the transformers. An example of a surge protector installation for a power distribution unit. Surge Protector on Switchboard Also, as seen in the figure above, with this type of device the lead length issue cannot easily be addressed. Lead length should be kept as short as possible for optimum performance, but it is unclear how this installation could be improved. This installation method may affect the peak clamping performance by about 100 to 800 volts depending on the type of transient. Another issue may be coordination of the protectors and the main switchgear surge protector. Depending upon the location of the impinging transient, the primary protector may allow a majority of the surge into the facility, which is undesirable. Caption: Surge protection is often installed along with other protected equipment in the same panel. 8 Power Quality in Internet Data Centers
11 Data lines must also be protected from surges, and plenty of devices are available to provide that protection. It may be true that harmonics levels are better because of the use of power factor correction, but that does not necessarily preclude the possibility of harmonics in the building. Data lines must also be protected, and plenty of devices are available to provide that protection. Lightning transients tend to cause currents to flow on ground conductors, which can induce voltages on data lines. These voltages can easily exceed the withstand levels for silicon devices in data ports. Exposure levels in data centers, however, will be lower because the lines never leave the building. In addition, most computing devices will have protection built in. Harmonics Many servers today are available with power factor-corrected (PFC) power supplies. IEC addresses specific harmonic limits for end-use devices, which often will require the PFC circuitry to be included. In addition, the UPSs serving those critical loads are often power factor corrected. Because of this, many people believe that data centers do not suffer from harmonics like industrial or typical commercial settings. It may be true that the levels are better because of the PFC, but that does not necessarily preclude the possibility of harmonics in the building. Some offending loads in data centers are as follows: UPSs Auxiliary electronic loads (non-pfc) Rectifiers Fluorescent lights Transformer inrush (short duration) Drives (HVAC) Soft starters (short duration) Battery chargers Some or all of these may exist and play a role in the harmonic content in the datacenter wiring. In particular, when transferring to and from generator, due to the higher source impedance, harmonic currents can cause voltage distortion at the main bus, affecting operation of other connected equipment. For example, motors and capacitors can be affected by this voltage. Harmonic currents can cause heating in transformers and cables, including neutrals. Other issues may include misoperation of fuses and breakers. When power factor correction capacitors are added to the system, resonant conditions can occur. This happens when the magnitude of the capacitive reactance is close to the magnitude of the inductive reactance of the system, usually dominated by the source impedance. Specific problems include: Heating effects in phase conductors as well as neutrals Heating in three-phase dry-type transformers Harmonic voltage-related heating in other equipment, such as motors Harmonic voltage stress on system capacitors and equipment capacitors Resonance with power factor correction capacitors Voltage distortion at the point of common coupling (PCC) Solutions are discussed in the table on the following page. Filters can be placed at various locations, including at bus or panel level or at loads filters at bus or panel level can be arranged as series-connected neutral current filters, parallel-connected zigzag filters, or parallel-connected active power filters. 9 Power Quality in Internet Data Centers
12 Harmonic Solutions Built-in filters at loads can be series inductors or can boost converter power factor correction. Branch circuit or cord connection filters can be applied as parallel-connected resonant filters, series-connected resonant filters, neutral current filters, zigzag filters, Importance of Grounding Grounding is required for safety foremost, and in the United States, sites should meet the National Electric Code (NEC) as a minimum to ensure proper safety. The secondary reason for grounding is for performance (noise control). Most equipment manufacturers will provide details on grounding of their equipment. The practice of installing separate grounding systems should be avoided and one should always look for special grounds that the manufacturer may want to install or has installed as they may violate safety codes. The NEC practices allow for safe and effective signal grounding; however, single point and star grounding may not be suitable for high frequencies. Article 645 Information Technology Equipment of the NEC provides guidance for the minimum wiring and grounding of such facilities. The practices described in IEEE Standard provide guidance for noise control without violating the NEC. IEC also addresses earthing connections. active filters, choke upstream of motor drives, or passive three-phase filters upstream of motor drives. Generic Power System Grounding Power System Grounding Grounding of the power system ties all equipment together and ensures that the equipment is at the same potential as the earth. This is accomplished by bonding the equipment to the grounding electrode system so that everything may be referenced to earth potential. This is critical during fault conditions to ensure that overcurrent protective devices operate in a timely manner to reduce or prevent equipment damage. Resistor One important goal of a grounding system is to have all equipment at the same, low voltage potential. The figure to the left illustrates an example of a power grounding system including the PDU. As can be seen, the entire distribution system on the primary side of the PDU transformers provides a high impedance return path at any point during a line-toground fault condition. This limits fault 10 Power Quality in Internet Data Centers
13 current to a level that allows continuous operation. The grounding issues on the secondary side of these transformers are addressed in a later section. European practices use various connections, including the TT system, the TN system, and the TI system. High Impedance Grounding Resistor Ground Current Set Point The TT system is designed for personnel protection, with the exposed conductive parts earthed and residual current devices used. The neutral is not bonded to the earth downstream of the transformer. This allows the first fault to occur without interrupting the service. Grounding Resistors To keep information technology equipment noise-free, the ground is often removed; however, a better practice is the use of computer signal reference grids. The TN system is more closely related to the U.S. system, with interconnection and earthing of exposed conductive devices and the neutral required. This necessitates protection through circuit-interrupting devices such as fuses and circuit breakers. This allows the first fault to interrupt the service. The TI system is similar to the TT system, with indication of the first fault through the use of an insulation monitoring device. The second fault is interrupted using fuses and breakers. Some practices in the United States are described below. High Impedance Grounding High impedance grounding usually is used in circuits rated at 1000 V or higher and is covered by Article Impedance Grounded Neutral Systems of the NEC. However, as may be seen in the figure on top right, high impedance grounding is located within the facility for 480-V operations and is supported by NEC Article Alternating-Current Circuits and Systems To Be Grounded, exception number 5. High-impedance ground resistors for a rotary UPS system. The impedance ground-current set points were found to be set at reasonable levels, less than a 5 V drop across the grounding resistor. Computer Signal Reference Ground In an attempt to keep the information technology equipment noise-free, the ground is often removed in attempts to provide isolation and a separate grounding system is provided. However, a better practice, which does not violate the NEC, is the use of computer signal reference grids, which in turn are bonded to the grounding electrode system. One such system is described in the IEEE Standard and is illustrated on the following page. 11 Power Quality in Internet Data Centers
14 Raised-Floor Grounding System Ground Grid Bonds Under Floor A compression grounding bond. Caption: IEEE provided guidance for the grounding of raised-floor grounding systems. Source: IEEE Standard 1100 However, the methods outlined in the IEEE 1100 standard or FIPS Publication 94 may not be practical or cost-effective in all cases. An alternative method is bonding of pedestal supports using a crisscrossing serpentine arrangement of cable, instead of flat ribbons, connected at every other pedestal, which results in a grid with 1.2-m squares as opposed to less than one-third of a meter. At each crisscrossing, the grounding conductors must be connected in grid fashion. The figure at top right illustrates the proper bonding method of the crisscrossing conductors. As technology is improved and density increased, and with the onslaught of lower logic voltage levels of 3.3 V and less, noise-tosignal ratios may become a problem, and the signal ground reference grids may have to be improved. The figure below illustrates a central ground plate commonly used for such improved systems. The central ground plate is designed for high frequencies. Not only is the serpentine crisscrossing and bonding of the pedestals used, but 4-inch-wide copper straps are also necessary to form ground grids of areas smaller than 0.6 m square to ensure reduction of signal noise in some information technology equipment rooms. Central Ground Plate Example The signal reference grid follows this practice of bonding to establish a low impedance signal reference grid. However, these practices only cover frequencies up to about 3 MHz and provide a reduction in noise level by a factor of 10. A central ground plate can serve as the common bonding point for many grounds. 12 Power Quality in Internet Data Centers
15 Raceways should be bonded by direct connections, which improve the ground return loops of stray EMI currents. However, the improvements may only increase the frequency range to 10 MHz. Problems associated with frequencies above 30 MHz may have to be handled differently (for example, use of a shielded enclosure). Equipment Rack and Metallic Raceway Bonding Raceways should be bonded by direct connections. These connections improve the ground return loops of stray EMI currents. Also, the mutual inductance can provide up to 75% reduction of the initial loop current by cancellation. This reduces the susceptibility and emissions problems related to common mode voltage in large sites. Any discontinuities will reduce the benefit of using metallic raceways for common mode noise reduction. Wiring Practices Connections in panels should be tight, and panels should be inspected once a year using thermal imaging as a minimum preventive maintenance action. Bonding In general, proper bonding in accordance with NEC article 250 part G should be carried out throughout the facility. The figure below illustrates one such required bond for flexible conduit joints, thereby establishing acontinuous and permanent ground requirement as stipulated by the NEC. Telecom Grounding A typical telecom system design uses a three ground rod system bonded to the main signal grounding grid and an additional grounding electrode bonded at the service entrance. The NEC allows for this additional electrode as it becomes part of the overall grounding electrode system. This will prevent the telecom system from surgeinduced overvoltages by allowing it to rise to the same potential as the building grounding system during a fault or surge current condition. Ground Currents A reasonable amount of ground current may be expected to be flowing at ground plates throughout the facility. However, NEC Article Objectionable Current Over the Grounding Connections states that measures should be taken to reduce the currents to levels satisfactory to the authority having jurisdiction. Ground currents should not be present on the grounding electrode conductors or the counterpoise grounding electrodes. These currents are associated with induction and are contained within the feeder conduits and circuit loops between the interconnected equipment and their associated grounds. A typical finding for a data center is shown below. Grounding of Conduit Flex Joint and Transformer Grounding Plate in Data Center Ground Bonding Jumper 4.3 Amps 1.5 Amps 1.5 Amps 3.2 Amps 1 Amp 4.2 Amps Flexible conduit often requires special accommodations for maintaining good ground continuity. Grounding plates provide a common bonding point for different grounds 13 Power Quality in Internet Data Centers
16 Parallel paths created by the insulated ground conductor and the conduit grounding provide paths for circulating ground current. Unbalanced spacing between phase conductors and the equipment-grounding conductor along the feeder path allows current to be induced in the grounded conductor, as seen in the top figure below. When several parallel feeders are involved and the conduits and conductors are bonded at both ends, as is the case at the service entrance and the bus, sizable currents may be introduced. This does not necessarily constitute a problem, but if problems do occur, such as noise from ground loops, the situation should be addressed. Below, at bottom, is an example of induced currents in a typical communication/computer equipment facility. If some sizable ground currents exist on the conductors at a site, it would be prudent to document and explain them. Specifically, the system documentation should describe the cause, effect, and appropriate levels of these leakage currents. Also updating of all site drawings to show the as-built condition of the grounding systems is suggested. This would be helpful later if ground loops created enough noise to require some mitigation. The PDU Grounding System Isolation Transformer The PDUs are basically step-down transformers and provide a localized source for each colocation remote power panel. The figures below show the details of a PDU, including the grounding arrangement. Arrangement of Conductors PDU Front View B A G C A B C G Optimum Conductor Arrangement Random Conductor Arrangement Induced ground currents come from asymmetry distribution of conductors within a conduit. This can be exacerbated by long cable runs. The interior view of a power distribution unit. Induced Currents in an Information Technology Facility PDU Grounding Detail Sizable ground currents should be documented in case they require mitigation later. A robust PDU grounding lug. 14 Power Quality in Internet Data Centers
17 Article Grounding Separately Derived Alternating-Current Systems in the NEC covers the requirements for the PDU. Article 250 is met satisfactorily when the PDU s neutral ground bond is grounded to the signal reference grid, which in turn is bonded to the electrode grounding system. DC-Powered Data Centers There has been a significant amount of research in recent years on the AC Power Distribution possibility of powering data centers with direct current instead of alternating current. Several publications have come from Asia, Europe, and the United States on this AC/ DC DC/ AC UPS PDU AC/ DC PSU DC/ DC 12 V 12 V 5 V 3.3 V Loads using Legacy Voltages issue. Some data centers in Japan are operating with power distribution throughout the building at 300 VDC. In Europe, Cenelec and other groups have explored the possibilities for Server 1.2 V 1.8 V 0.8 V Loads using Silicon Voltages several years. In the United States, a project was undertaken by Lawrence Berkeley National Laboratory to DC Power Distribution demonstrate the implementation of 380-VDC power distribution in a data center. This involved supplying the servers directly with 380 VDC, instead of an AC supply. 480 VAC Bulk Power Supply DC UPS or Rectifier AC/ DC Flywheel 380 VDC PSU DC/ DC 12 V 12 V 5 V 3.3 V Loads using Legacy Voltages The reason for this interest is that the system may achieve higher reliability, as evidenced by the telecom industry, as well as the possibility of higher operating efficiency. The efficiency gains come about as a result of the removal of the UPS and the transformer that usually accompanies it, as well as a higher efficiency in the server power supply due to the removal of the rectifier and power factor-corrected circuit at the input. With the DC concept, the only components necessary are a main rectifier and some kind of energy storage (flywheel, battery, etc.). The transformer and the rectifier section in the front end of the UPS, and their respective losses, are removed, as shown in the figures at right. Server 1.2 V 1.8 V 0.8 V Loads using Silicon Voltages Losses from the UPS transformer and the power supply unit (PSU) rectifier are eliminated in a DC system. = voltage regulator module continued on following page 15 Power Quality in Internet Data Centers
18 DC-Powered Data Centers (continued) The system was compared with two AC systems using two different UPS manufacturers, A and B. It should be noted that the DC system output load is less due to the improvement in the power supply efficiency. The basic results from this experiment are shown in the table to the right. Test Results from DC Data Center Demonstration Efficiency Measured with UPS A Efficiency Measured with UPS B Efficiency Measured with DC System UPS Transformer Power supply Total Efficiency 89.6% 98.0% 90.0% 79.0% 89.9% 98.0% 90.0% 79.3% 94.2% 100.0% 92.0% 86.7% Typical Efficiency 85.0% 98.0% 73.0% 60.8% Output Load (kwh) Input Load (kwh) Energy Measured with UPS A Energy Measured with UPS B Energy Measured with DC System Energy Improvement over UPS A Energy Improvement over UPS B 7.3% 7.0% Hardware Used in DC Data Center Demonstration Representatives from Ecos Consulting, the California Energy Commission, EPRI, and the Lawrence Berkeley National Laboratory are shown in front of the DC power system at Sun Microsystems. 16 Power Quality in Internet Data Centers
19 FURTHER READING European practices can be easily found in the following sources: Schneider Electric, Cahier Techniques, available from Merlin Gerin, Electrical Installation Guide According to IEC 60364, available from British Standards Institution, BS 7671:2001, Requirements for Electrical Installations, IEE Wiring Regulations, 16th Edition. J. F. Whitfield, The Electrician s Guide to the 16th Edition of the IEE Wiring Regulations, BS7671 and Part P of the Building Regulations (EPA Press, 2005). And several Leonardo Power Quality Institute documents (available from A Systems Approach to Earthing Fundamentals of Electromagnetic Compatibility Earthing Systems Fundamentals of Calculation and Design Earthing Systems Basic Constructional Aspects NOTES 1. The Uptime Institute, Industry Standard Tier Classifications Define Site Infrastructure Performance, White Paper (Santa Fe: The Uptime Institute, 2000). 2. The Uptime Institute, Fault Tolerant Power Compliance Specification Version 2.0 (2002), available from 17 Power Quality in Internet Data Centers
Power Quality for Information Technology System
Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
Power Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Power Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
Qualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power
App Notes ~ Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Coordination of Telecommunications Surge Protective Devices in Countries with Unstable
> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.
The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
Common Power Problems & Power Protection Solutions
W H I T E P A P E R Common Power Problems & Power Protection Solutions Executive Summary All systems, from home theaters and office desktops to enterprise IT equipment in data centers, are prone to downtime,
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
Switchgear Application Issues for Mission Critical Power Systems, Part One
Switchgear pplication Issues for Mission Critical Power Systems, Part One BSTRCT With the advent of high reliability data centers and telecommunication facilities, designers of commercial power face new
Power surges can also be generated by equipment in your facility such as:
Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement
Developing a Utility/Customer Partnership To Improve Power Quality and Performance
Developing a Utility/Customer Partnership To Improve Power Quality and Performance Mark McGranaghan Electrotek Concepts Knoxville, TN Abstract Many industrial and commercial electric customers now require
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
Increasing safety, reliability and efficiency for today s data centers
Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides
ELECTRONIC POWER SYSTEMS
ELECTRONIC POWER SYSTEMS TRADEOFFS BETWEEN SINGLE-PHASE & THREE-PHASE POWER WHITE PAPER: TW0057 1 Executive Summary Modern Electronic Systems are quite often powered from a three-phase power source. While
A Comparison of AC and DC Power Distribution in the Data Center Transcript
A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com [email protected] Page 2 THE BASIC
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure for Business-Critical Continuity Are you deploying a remote site faster than you can
Bourns Resistive Products
Bourns Resistive Products Diverse Requirements Drive Innovations to Pulse Resistors Introduction Countless circuits depend on the protection provided by one of the most fundamental types of passive components:
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
CPS 100 480Y S K CPS 100 480Y S C
Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
Specification guide no. 9 Active harmonic conditioner from 20 to 480 A
Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable
Design of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13
Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified
Data center power dynamics within the settings of regional power grid
Data center power dynamics within the settings of regional power grid Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical and Space Engineering Lulea
Tough Decision: On-Line or Line-Interactive UPS?
W H I T E P A P E R Tough Decision: On-Line or Line-Interactive UPS? How to Choose the Right Protection for Your Network Executive Summary In today s data-driven, technology-dependent world, no organization
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
Telecommunication Line Protectors
TN CR 0025 Telecommunication Line s 1.1 The nature of telecom surges The telecom services considered in this report are transported on twisted pair. Each service has two wires, or lines, sometimes called
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
SURGELOGIC TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage
TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage Internal and External Mounted TVSS Retrofit or New Construction Low Let-through Levels High Surge Capacities Internal
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS October 22, 2010 Authored by: Kevin Binnie, Senior Product Portfolio Manager ALPHA TECHNOLOGIES LTD. Executive Summary
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Technical Article MS-2443
. MS-2443 Safeguard Your RS-485 Communication Networks from Harmful EMC Events by James Scanlon, Senior Evaluation Engineer, Analog Devices, Inc., and Koenraad Rutgers, Senior Field Applications Engineer,
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
Voltage Tolerance Boundary
Pacific Gas and Electric Company Voltage Tolerance Boundary The only national standard for utilization voltage regulation is ANSI C84.1. Its title is American National Standard for Electric Power Systems
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
ETAP 11 The Future of Power Systems Engineering & Operation - Today
ETAP 11 The Future of Power Systems Engineering & Operation - Today Innovation Automation Collaboration Multi-Dimension Database Lock & unlock element properties 10 States to track equipment conditions
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
Opportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional
How To Understand The Electrical Power Supply Of A Power Supply System
17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
ENERGY EFFICIENT DATACENTERS ELECTRICAL DESIGN
ENERGY EFFICIENT DATACENTERS ELECTRICAL DESIGN Michael Ryan, Brett Rucker, Dean Nelson, Petr Vlasaty, Ramesh KV, Serena DeVito, and Brian Day Sun Global Lab & Datacenter Design Services Sun BluePrints
POWER EQUIPMENT AND DATA CENTER DESIGN
WHITE PAPER #51 POWER EQUIPMENT AND DATA CENTER DESIGN EDITORS: David Loucks, Eaton Stephen McCluer, Schneider Electric CONTRIBUTORS: Lynn Simmons, Dell John Collins, Eaton George Navarro, Eaton Dusty
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Data Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
White Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
Calculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
Designed for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
COMPARATIVE ANALYSIS OF DATACENTER ELECTRICAL DISTRIBUTION ARCHITECTURES. Emmanuel J. Taylor
COMPARATIVE ANALYSIS OF DATACENTER ELECTRICAL DISTRIBUTION ARCHITECTURES by Emmanuel J. Taylor Bachelor of Science in Electrical Engineering, University of Pittsburgh, 2010 Submitted to the Graduate Faculty
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
POWER QUALITY IN YOUR HOME
POWER QUALITY IN YOUR HOME How to ensure the life and reliable operation of your home electronics Electricity provides the power you need to run your home electronic equipment. Sometimes, interference
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
TERMS AND CONDITIONS
Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering
LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering