Standard Comms Rooms Specification
|
|
- Cathleen Gibbs
- 8 years ago
- Views:
Transcription
1 Standard Comms Rooms Specification Room Configuration Electrical General Distribution Boards Small Power Lighting Containment Fire Detection General To be defined in the project brief but should meet requirements as per layout configurations below For new refurbishment projects requiring new Comms rooms, a dedicated distribution board (see separate DB spec) fed from a main load panel. DB should be located outside of the comms rooms. Each distribution board must have dedicated circuits for the following: Circuit to each rack; Circuit for small power; Circuit for lighting; Circuit for ventilation Each circuit to be individually protected to avoid a problem of one affecting another Minimum 1 double socket outlet per cabinet, equally spaced around the room. Each cabinet is to be hard wired into individually switched fused spurs. In comms rooms where there are 3 or more cabinets, 1 x 16amp commando socket is required this is project specific and must be approved by CUL ISIO Dept. Lighting must be off centre to ensure even illumination around cabinets. Lux level must reach a minimum of 400 lux to 1m on horizontal plane. Trays or baskets will be project specific. Cable entry from above into the comms room is preferred. CUL has an L1 system, refer to separate Fire Alarm specification. Temperatures within comms rooms should not exceed 24 o C, 24/7, therefore the design calculations should establish whether additional cooling is required. 1
2 Mechanical Cooling Cooling is required and must meet N+1; wall mounted split units should be installed; where possible system should connect into existing chilled water system; Drip and leak detection should be Incorporated into the design. Flooring Flooring should be anti-static vinyl, colour is project dependent. Walls See separate paint specification. Ceilings Should be exposed soffit, see separate paint specification for finishes. Fabric Security Dedicated comms room to be provided, standard ISIO core should be used, where this does not apply CUL to advise and ISO to approve. Data point allowance Cabinet Sizes [This information should also be specified elsewhere for project designers.] The following data points should be allowed for: Individual offices 4 data points per person (3 x data, 1 x telephone) Open Plan offices 3 data points per person (2 x data, 1 x telephone) Preferred standard for cabinets: 42U full size cabinet: Can accommodate approximately 360 data points approximately 90 desks. NB. These figures do not include wireless demand, door controllers, cctv, etc, this is project specific and should be confirmed with ISIO. In situations where full- height racks cannot be used, ISIO should be consulted regarding an alternative smaller rack. Alternatives to be agreed with ISO: Half-height cabinet: Can accommodate approximately 80 data points approximately 25 desks. 15U Wall mounted cabinets Can accommodate no more than 72 data points. Can accommodate no more than 2 network switches 2
3 Switches The Project Manager should allow a budget for switches within the project development costs. One switch accommodates 40 data points (Approximate cost 4.5k per switch, excl VAT). Number required can be confirmed by ISIO Technical Information Cabling New buildings will also require 2 building distributions switches, a budgetary cost of 15k+VAT should be set aside for this. Adding comms rooms to existing buildings need a survey to ensure that enough switch ports are available at the Building Distribution switches, if no spare capacity an extra cost of up to 15k+VAT will need to be added to the budget. Cabinet rooms should be sited approximately for the areas whose data points they feed, the length of cable run must be no more than 80m to a data point. Cabling must comply with Cat5e standards. There should be a convenient route to run fibre back to the building distribution location. 8 core OM3 multi-mode fibre for 1-2 cabinets, 16 core MO3 multi-mode fibre for 3-4 cabinets, and fibre with SC termination. In the case of new buildings the project must take into account the requirement for a Network and Telecoms link back to the main building, this will be either achieved by using Dark Fibre or a Managed WAN Service provided by external companies, quotes for these works must be obtained by Information Services. UPS requirements A UPS must be provided in each cabinet: - Wall mounted cabinets should only have a maximum of 2 switches and will require an APC Smart-UPS 750VA:SMT750RMI2U, budgetary cost 450+VAT - Floor standing cabinet with up to 6 switches, will require an APC Smart-UPS 1000VA:SMT1000RMI2U, budgetary cost 500+VAT - Floor standing cabinet with up to 8 switches, will require an APC Smart-UPS 1500VA:SMT1500RMI2U, budgetary cost 600+VAT Applicable SKA Good Practice Measure E22 IT and Comms Room Energy Consumption -Dedicated IT and communication rooms have a calculated DCIE (data centre infrastructure efficiency) of 70% or greater. 3
4 Important note: This standard sets out the basic functional requirements for a typical new or refurbished teaching room. The actual work required for a particular project will be determined in a separate SCOPE OF WORKS DOCUMENT - some elements may not be present or require replacement. The racks for comms equipment should not be used for any other type of equipment, such as servers. Please note any value engineering relating to Comms Room must be approved by ISIO to ensure the integrity of the equipment is not compromised AVERAGE ROOM BREAKDOWN: Number of Ports Per 30 Users: Network Port 60 Telephone 30 Wireless Port 1 MFD & Fax 2 Display Screen 1 Number of Ports Per "block" calculated at 6 users per block: Network Port 12 Telephone Port 6 Wireless Port 1 per 5 blocks MFD & Fax 2 Display Screen 1 Classrooms/PC Labs/Meeting room: Pod 8 Wireless port seats = 1AP AP mounted on ceiling seats = 2AP APs mounted on ceiling seats = 3AP APs mounted on ceiling seats = 4AP APs mounted on ceiling 180+ must liaise with APs mounted on ceiling Information Services Budget per AP should be 500+VAT (extra equipment might be required if current infrastructure at full capacity, liaise with Information Services to determine capacity and also for costs) Student machine 2 Camera 1 high level Note: Wireless Access point positioning requires a survey to be carried out by a contractor in order to determine the correct positioning of the ceiling level data points, these surveys incur an additional cost. Liaise with Information services prior to the start of the cabling project. If work is carried out without the input from Information Services the ceiling level data points might have to be moved or new points installed at extra cost. 4
5 Room Size and Cabinet specifications: Wall mounted cabinet should be 600mm deep, if smaller please liaise with ISO before ordering. These can only be used with specific authorisation from Information Services Floor standing cabinets should be 800mm wide and deep, if smaller please liaise with ISO 5
6 before ordering. New 2 cabi net comms room. No new LIM lm Total width 2.8m mm x mm lm l T (: :l lm I Total length of room 2.6m I New 2 cabi net comms room. New LIM installed 1.2m Total width of room 2.8m 1.2m lr mmx, 800mm 1 T 1.2m Total length of room 2.8m 6
7
8
Portable Energy Efficient Data Centre Solution
Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com
More informationNUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
More informationData Centre Solutions energy efficient by design
Data Centre Solutions energy efficient by design Mobile & Modular Data Centre Solutions Agile, Scalable, High Performance Mobile and Modular DC solutions Flexible, scalable high performance mobile & modular
More informationGeorgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure
Georgia Tech Aerospace Server French building Server Room Server Room Policy Handbook: Scope, Processes and Procedure Version History Version/Status Release Date Comments 1.1/Draft 1.2 1.3 1.4 1.5 1.6
More informationMinimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
More informationMARULENG LOCAL MUNICIPALITY
MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details
More informationData Centre. Design and Project Management. from concept to completion
C O N S U L T I N G Data Centre Design and Project Management from concept to completion Computer rooms are the heart of most businesses today. Yet I see so many that have been patched together, are in
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationRESOURCES. Telehealth. Provincial Health Services Authority. Telehealth & General Meeting Room Design Requirements
RESOURCES Telehealth Provincial Health Services Authority Telehealth & General Meeting Room Design Requirements Prepared by IMITS, LMC Telehealth and C&W Media Services December, 2013 Revised, August 2014
More informationInformation & Communications Technology Network Infrastructure Group. Network Infrastructure Standards July 2013
Information & Communications Technology Group Standards July 2013 Appendix B - Examples Version 1.3 Appendix B - Examples Note: All these calculations are for budgeting and estimations only as each case
More informationelectrics P OW E R E N T RY B A S I C S P OW E R & C O M M U N I C AT I O N S B A S I C S P OW E R D I S T R I B U T I O N B A S I C S
P RO D U C T M A P / TA B L E O F C O N T E N T S..................6 8 6 E L E C T R I C S & C O M M U N I C AT I O N S O V E RV I E W.............6 8 9 P OW E R E N T RY B A S I C S PA N E L - M O U N
More informationREVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL CONTROL POLICY
LI_M_POPO PROVINCIAL GOVERNMENT :;:ED.JBl-C ()F SO"';-H AFR;IC. ':.,. DEPARTMENT OF CO-OPERATIVE GOVERNANCE, HUMAN SETTLEMENTS & TRADITIONAL AFFAIRS REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL
More informationAssuming you currently have a SWGfL solution, is the selected location for the new solution the same as the location of the existing solution?
SWGfL Trust Site Survey Guide Page 1 of 5 1 Site Survey Guide 2 Blank Site Survey Guide 2.1 Background This Guide provides explanations and details to assist in responding to the Site Survey. 2.2 Location
More informationANNEX C - DESIGN BRIEF
ANNEX C - DESIGN BRIEF SCOPE OF WORKS 1.0 OBJECTIVE The Contractor undertakes the fit-out works in the area outlined in the layout plan, 2 nd Floor and new extension space on the 11 th Floor, at the EBRD
More informationTCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
More informationSECTION 13: COMMUNICATIONS CONTENTS
SECTION 13: COMMUNICATIONS CONTENTS 13.1 INTRODUCTION 2 13.2 INFRASTRUCTURE FOR VOICE AND DATA NETWORKS 3 13.2.1 Building Communications Room 3 13.2.2 Floor Communications Rooms 3 13.3 DATA NETWORKS 3
More informationBELLE VUE MANCHESTER DATA CENTRE
www.iracknet.com 0843 557 5712 bellevue@iracknet.com www.iracknet.com BELLE VUE MANCHESTER DATA CENTRE 02 BELLE VUE MANCHESTER HIGHLY ADVANCED DATA CENTRE PURPOSE BUILT TO DELIVER UNRIVALLED FLEXIBILITY
More informationColocation. Introduction. Structure of the service. Service Description
Introduction IP-Only provides colocation services for customers with very high reliability and availability requirements. In combination with its transmission and IP services, IP-Only offers space in high-security
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationISS Data Centre Server Hosting. Service Description
ISS Data Centre Server Hosting Service Description March 9, 2011 Information Solutions and Services Page 1 TABLE OF CONTENTS INTRODUCTION...3 ISS SERVER HOSTING SERVICE OVERVIEW...3 WHAT IS THE ISS DATA
More informationTAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means
More informationCat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.
Cat 5, 6 or 7? A University Standard for Structured Wiring. Background isolutions recently formed Incorporates all IT service providers within the University. Focus on all ICT needs of the user and the
More informationDESIGN GUIDELINES. Local Area Network
DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA
More informationElectrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
More informationBROWACOM PRODUCTS. Our web-pages can be found from: http://www.browacom.fi
BROWACOM PRODUCTS manufactures and sells telecom solutions for professional users. Products include CityCabinet-product family, as a service Browacom offers subcontracting services in electromechanical
More informationIT Services Converged Network Installation Specification:
IT Services Converged Network Installation Specification: Author: Phil Gregory Status: Published Last Modified: 21 August 2015 Last Modified by: Phil Gregory Updates: Version Date (Initial) Comments 1.1401
More informationInstallation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk
Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network
More informationEXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
More informationOnsite Support: 24/7/365 onsite team. Security: 24/7/365 onsite manned security and CCTV. Monitoring: 24/7/365 Environmental monitoring and management
Zen DC1 Our Services: Colocation Cloud Solutions Managed Hosting Dedicated Servers Zen DC1 - Key Facts Size: 10,000 sq ft Capacity: 150 rack capacity Ownership: 100% independently owned, operated and managed
More informationFITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223
FITNESS FACILITY WIRING SPECIFICATIONS NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 CONTENTS: - Scope of work Summary - Equipment list - Technical specifications - Map of data
More informationData Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc jew@j-and-m.com J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationManaged Colocation Service Definition. SD008 v1.5 Issue Date 20 July 11
Managed Colocation Service Definition SD008 v1.5 Issue Date 20 July 11 10 Service Overview InTechnology offers secure data centre environments for your business critical systems, applications and data
More informationDATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football
More informationCalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
More informationTAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means
More informationTurnkey Projects, Conversions, Restorations & Property Management. Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE
Turnkey Projects, Conversions, Restorations & Property Management Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE Reg. Office: Karlu Galea Street, Victoria, Gozo Malta. T. 2155 6600 M. 9943 4391
More informationUniversity of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS
ANNEX K 49ER CARD SYSTEMS UNC CHARLOTTE 49ER CARD SYSTEM INSTALLATION AND CONTRACTOR REQUIREMENT SCOPE OF WORK: The following information pertains to the installation and contractor requirements to install
More informationNoteLocker 8 NoteLocker 8 as a Floor-standing Solution
NoteLocker NoteLocker 8 NoteLocker 8 as a Floor-standing Solution NoteLocker 8 is a modular storage and charging cabinet with 8 separate storage compartments. In each compartment a laptop, mobile phone,
More informationhong kong//china data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Hong Kong, China. We can colocate standard rack-mountable servers or
More informationHow To Set Up A Minipatch System For A Small Office Or Home Use
Issue : 4 Wood Communications Networking Products Catalogue Small Office & Home Solution Small Office / Home Solution Min LAN Comms Cabinets - Multimedia Panel - Soho Ethernet Switches - Multiroom Audio/Video,
More informationnr 28 nr 68 nr 4 nr 1
SEEB INTERNATIONAL BILL OF QUANTITIES AIRPORT ELECTRICAL WORKS NEW TERMINAL PIER ITEM ITEM DESCRIPTION UNIT QUANTITY BILL PART SECTION No. VOLUME 3 4 UNIT RATE (R.O.) (in words) (in figures) SECTION R:
More informationA/V and Video Conference Standards for Teaching and Learning Rooms.
A/V and Video Conference Standards for Teaching and Learning Rooms. Prepared by David Stormonth Division of Information Technology Phone 02 69334369 Mob 0439 644 946 E-mail dstormonth@csu.edu.au Overview
More informationDesign Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)
More informationHealthcareBookings.com Security Set Up
HealthcareBookings.com Security Set Up Introduction... 2 Overview of the process for using HealthcareBookings.com... 2 Professionals... 2 Patients... 3 Passwords... 4 Hosting Security... 4 Overview of
More informationSECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
More informationACCOMMODATION FOR THE ICT SERVER ROOM. (Report by the ICT Services Manager and the Projects and Assets Manager)
CABINET ACCOMMODATION FOR THE ICT SERVER ROOM (Report by the ICT Services Manager and the Projects and Assets Manager) 1. PURPOSE 1.1 To recommend that the ICT server room on the 2 nd floor of Pathfinder
More informationIT Services stakeholder roles & responsibilities in Capital Projects
IT Services/Facilities Management Directorate IT Services stakeholder roles & responsibilities in Capital Projects University of Reading 2011 Page 1 of 10 Document Approval Originator Approved for Issue
More informationJSP 315 SCALE 45 1 OFFICES
SCALE 45 OFFICES JSP 315 1 This scale is to be read in conjunction with Scale 1 and 47. Reference should also be made to Scale 9 (Civilian Staff Catering Facilities), and Scale 17 (Car Parking). It applies
More informationWireless Networks and Power Quality
Will installing wireless networking change my back-up power requirements? What data do I need to know in order to determine my wireless network back-up power requirements? What other issues should I consider
More informationEMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE
Fire Safety Technical Guide EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE Reference: A. British Standard 5266-1 Emergency Lighting - Code of Practice for the emergency lighting of premises; B. BS 5266-7
More informationSite Preparation/Renovation
Securities and Exchange Commission Request for Proposal For Site Preparation/Renovation of IT SERVER ROOM Page 1 of 12 Information Systems and Technology Division 1. Description of Work 4 2. Scope of Work
More informationColocation Service Definition. SD008 v1.3 Issue Date 19 Feb 09
Colocation Service Definition SD008 v1.3 Issue Date 19 Feb 09 Colocation Service Definition Service Overview InTechnology offers secure data centre environments for your business critical systems, applications
More informationAutomating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011
Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work
More informationContainment Solutions
Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA
More informationCo-location Service Definition. SD008 v1.2 Issue Date 18 Nov 08
Co-location Service Definition SD008 v1.2 Issue Date 18 Nov 08 Co-location Service Definition Service Overview InTechnology provides the Customer with a highly secure computing environment with 24 hour
More informationPowerful Dedicated Servers
Powerful Dedicated Servers Our dedicated servers offer outstanding performance for even the most demanding of websites with the latest Intel & Dell technology combining unparalleled server specification,
More informationQuantec Wiring Instructions
Approved Document No. DNUQ777 Rev Quantec Wiring Instructions GENERAL Quantec can be compared to a very sophisticated analogue addressable fire alarm system where the integrity of the wiring is of paramount
More informationAppendix 3H A/V and Video Conferencing Standard
Appendix 3H A/V and Standard 1. Introduction The Authority uses meeting and conference rooms for a variety of purposes. All new construction will have a mix of each type of room type as identified below.
More informationNational Aluminium Co. Ltd.
National Aluminium Co. Ltd. [NALCO] EXPRESSION OF INTEREST FOR DATA CENTRE CO-LOCATION SERVICES Address for Communication The Project Manager ERP P/1, NALCO BHAWAN NAYAPALLI, BHUBANESWAR 751061 E mail:
More informationDATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
More informationFacilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE NBN Co Limited Overview of the NBN Co Facilities Access Service April 2012 Copyright This document is subject to copyright and
More informationBest Practices for Wire-free Environmental Monitoring in the Data Center
White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning
More informationEnable Networks UFB Services Agreement Service Description for Central Office and POI Co-location Service
Enable Networks UFB Services Agreement Service Description for Central Office and POI Co-location Service 1 Interpretation 1.1 The Central Office and POI Co-location Service described in this Service Description
More informationSTRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011
STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationVisualizing Data Center Capacity with Visio
Visualizing Data Center Capacity with Visio 1. Data Center Floor Views using Visio 2007 2. Creating the floor plan 3. Deciding on rack data / attribute fields 4. Rack views text only 5. Rack views colour
More informationInformation and Communication Technology Network Cabling Infrastructure Standard
Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and
More informationCabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
More informationProposed A&A work at E-Commerce Air-Hub at SATS Airfreight Terminal 1 (AFT1)
1. ADDITION & ALTERATION TO THE MAIN WAREHOUSE 1.1 ELECTRICAL WORKS 1.1.1 The Contractor shall provide into the AFT1 building with 2 x 1000Amp power supply to be terminated with a main isolator. The power
More informationout of this world guide to: POWERFUL DEDICATED SERVERS
out of this world guide to: POWERFUL DEDICATED SERVERS Our dedicated servers offer outstanding performance for even the most demanding of websites with the latest Intel & Dell technology combining unparalleled
More informationOCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds
More informationMISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
More informationSERVER ROOM CABINET INSTALLATION CONCEPTS
SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationFire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
More informationCB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
More information19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.
19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile
More information112 Linton House 164-180 Union Street London SE1 0LH T: 020 7960 5111 F: 020 7960 5100
112 Linton House 164-180 Union Street London SE1 0LH T: 020 7960 5111 F: 020 7960 5100 Our dedicated servers offer outstanding performance for even the most demanding of websites with the low monthly fee.
More informationVideoconferencing Room Guide
Videoconferencing Room Guide IVN RoomGuide.doc Page 1 Introduction This guide will serve as a tool to plan the design and implementation of a videoconference room. The information in this guide should
More informationInstallation Guide for Hive Active Heating
Installation Guide for Hive Active Heating Important note: Installation should only ever be carried out by a qualified engineer. Technical Support If you need to contact Hive s Technical Support team during
More informationEnable Networks UFB Services Agreement Service Description for Central Office and POI Co-location Service
Enable Networks UFB s Agreement Description for Central Office and POI Co-location 1 Interpretation 1.1 The Central Office and POI Co-location described in this Description will be available from the date
More informationPrint Shop/Mail Room
Chapter XVIII Print Shop/Mail Room Page 110 CHAPTER XVIII Print Shop/Mail Room ARCHITECTURAL/STRUCTURAL A. BUILDING EXTERIOR 1.0 EXTERIOR WALLS The exterior walls are comprised of stone veneer. There were
More informationARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534
DATE: August 25, 2015 TO: All Plan Holders ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534 FROM: Jim Vernon, Architectural Partners PROJECT NAME: Nelson
More informationREQUIREMENT 5. Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations
Chapter Five: REQUIREMENT 5 Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations 5...covered multifamily dwellings with a building entrance on an accessible
More informationData Center Visualization Using Visio
Data Center Visualization Using Visio 1. Data Centers and Visualisation 2. Linking Visio to data center management systems 3. Embedding data and hyperlinks into Visio shapes 4. Data Center Space - Floor
More informationApplication Briefs: Remote Office Environment
Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small
More informationBLADE S-MAX Cabinet for Blade Server
Cabinet for Blade Server 1 2 Overview Material specification Corner verticals: 1.5 mm steel End frames: 1.5 mm steel Panel mounts: 2.0 mm steel Panel mount supports: 1.5 mm steel Side panels, door and
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationTechnical requirements
Technical requirements of site preparation for TF-T1 Module Project Manager / / Head of technical department /K. Nikitin/ St.-Petersburg 2009 Contents 1. Technical specification of TF-T1 module 2. Appearance
More informationASX Australian Liquidity Centre. ASXCoLo
ASX Australian Liquidity Centre ASXCoLo Australian Liquidity Centre Location The ASX Australian Liquidity Centre is located at: Gore Hill Business Park 219-247 Pacific Highway Artarmon. NSW, 2064 The location
More information16/32 Channel 1U Rack Mount CCTV Power Supply
16/32 Channel 1U Rack Mount CCTV Power Supply Manual PH-A3224-GUQ Shown 16-Channel 32-Channel PTC PH-A1612-PUQ PH-A3224-PUQ Glass Fuse PH-A1612-GUQ PH-A3224-GUQ Industrial design 12 Amp 3 Amps per channel
More informationIT&T Infrastructure Standards
Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...
More informationknow-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
More informationANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers
More information38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM
38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM 38.1 GENERAL Scope Modification and extension of the existing CDU Cardax security system and CCTV System including: Cardax (FT 3000 series) Access control
More informationDELTA3-1. Delta 3 Data Centre Rack Solution
DELTA3-1 Delta 3 Data Centre Rack Solution Contents Building on more than 50 years of British design and innovation, Cooper B-Line introduces Delta 3 ( Delta cubed ). Designed to offer M.O.R.E. to customers
More informationLDeX Group. Colocation Solutions for High Expectations
LDeX Group Colocation Solutions for High Expectations LDeX1 Units 8 10 The Oxgate Centre, Oxgate Lane, London, NW2 7JA +44 (0)845 370 3510 sales@ldexgroup.co.uk www.ldexgroup.co.uk 5 M VA LDeX1 delivers
More informationin other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
More informationBuilding Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24
1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition
More information