Data Center Due Diligence List
|
|
|
- Theodore Jenkins
- 10 years ago
- Views:
Transcription
1 Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West Site: Parcel: Site size (in acres) Street Map Size of available adjacent property for expansion? Topography Aerial photograph Grounds: Landscaping Condition Sprinkler system (Y/N) Drainage/flooding problems (potential) Fenced (Y/N) Gates (Y/N) Easements/covenants/restrictions Outside storage Right of ways Occupancy: Zoning use Zoning authority (name, address, contact number(s) Current uses Permitted uses Future zoning plans Prior occupancy
2 If change in existing occupancy Fire restrictive separation required Required zoning Separate employee entrance Building Analysis: External Images: Roof, all directions and items on roof Windows Doors Fences/gates Parking and drainage Other structures Internal Images: All flooring Carpets Configuration Lighting Walls Ceilings Windows Square footage of building: Number of floors Elevators Freight elevator Sq. ft each floor Interior ceiling height Column spacing Window line View Approximate area of each use type: Lunch/Break room Copy room Equipment room Mailroom Mezzanine area Office Reception area Restrooms Ladies Showers Lockers Restrooms Men s Showers Lockers Storage Telephone equipment room Warehouse Floor load Door height from warehouse Other types of space Floor to floor (roof) heights Parking Requirements: Egress to main road stop light or stop signal Truck parking/maneuverability
3 Parking Requirements Continued Total number of spaces: Covered/open Employee Customer/visitor Handicap requirements Parking lot lighting Min/max foot-candles Parking lot lighting Min/max average foot-candles Loading Docks (present/needed): Location Number and size of doors Dock height Grade level Truck height Exterior loading area depth Interior loading area Covered/non-covered Electric/manual openers Condition Equipment Other requirements Data Center Construction Analysis: Construction: Contact Person: Roof: Type Condition/defects Roof rating for wind and fire Insulation Interior Walls: Condition/Defects
4 Exterior Walls/Curtain Wall: Condition/Design Defects Door Hardware: Make, condition Floor: Condition/Design Defects Structural: Contact Person: Condition: Design defects Design criteria: Live floor loads Seismic Wind Structural Calculations Structural Specifications Construction Documents Seismic Issues Mechanical: Contact Person: Heating/cooling: Type Total capacity BTU/HR BTU/HR per 1,000sf Capacity sufficient for proposed needs Mechanical Continued Maintenance Outside air available California Energy Code compliant? Exhaust Systems Type Total capacity Capacity sufficient for proposed needs Maintenance Outside air available Plumbing: Name of the local provider (contact name and telephone number) Water meter capacity Capacity sufficient for proposed needs Maintenance Drainage:
5 Industrial waste, containment, or other special needs Electrical: Name of the local provider (contact name and telephone number) Distance in miles from the site to the nearest adequate power sources Capacity of nearest utility substation Location and capacity of nearest point of connection What power is the available on the property? Main electrical watts per 1,000sf Capacity available to intended use Are there any power upgrades scheduled for the immediate area Main building service capacity (KVA) Transformer feeding building service size (KVA), primary/secondary voltage Cable size feeding transformer Voltages available in the building A copy of a current utility bill if available Number of electrical rooms and size Type of distribution system typical (conduct and wire, cable tray, mc cable, etc.) One-line diagram and electrical floor plans if available Generator or UPS power available in building. Problems siting a generator? Any local electrical code requirements that significantly differ from US standards NEC compliant distribution system(s): Does the electrical distribution system meet present National? Electrical code, building code, and factory manual requirements Maintenance/inspections/testing up to date: Is the electrical equipment in satisfactory condition? Has the electrical equipment been installed with good workmanship? Lightening Protection Lighting Levels: Average foot-candles reading for every room Adequate for intended use? Mechanical Continued Communications: Name of the local provider (contact name and telephone number) Telephone number of an existing tenant Distance to the nearest phone/data connections Number and type (copper/fiber) of lines provided to building Adequate conduit to U.S. West (4 ) Space for punch blocks (8 x 8 ) How many: phones, faxes, modems, (pc s, fire alarm, security, control systems) Cable distribution type for phone (copper category 3?) Cable distribution type to desk top for network (copper-category 5 or 3 cable, fiber). Raceway distribution (cable tray, conduit, free air, etc.) Network equipment available? What type Ethernet, token ring Local area network Wide area network Number of nodes pc s, printers, servers, controllers, and misc. equipment
6 Natural Gas: Name of the local provider (contact name and telephone number) Distance from the site to the nearest high pressure (50 psig or greater) distribution line Population within 45 mile radius of proposed complex Water Supply: Gallons per day of ground water available Are there ground water rights currently with the property? If yes, how many gallons per day are allowed to be pumped? Are there any restrictions on pumping this water? If yes, please explain restrictions Are there any known contaminants in the water on the property that would restrict it from being drinking water quality without pretreatment? Are there surface water rights with the property? Are there any restrictions on use of this water? Sewer: Name of the local provider (contact name and telephone number) Industrial waste capacity: Line size and discharge capacity available at point of connection Proposed industrial waste updates Are there any restrictions on the discharge? If yes, please explain Storm drainage capacity: Line size and discharge capacity available at point of connection Proposed storm drainage upgrades Flood exposure and history Are there any restrictions on the discharge? If yes, please explain Sanitary sewer capacity: If yes, what distance to the closest point of connection Line size and discharge capacity available at point of connection Proposed sanitary sewer upgrades Are there any restrictions on the discharge? If yes, please explain Industrial waste, containment, or other special needs Is there existing sewer treatment of 800-1,000 GPM currently available If yes, what distance to the closest point of connection Elevator: Contact Person: Type: Capacity: Platform size: Maintenance condition/history: Freight elevator Security: Contact Person: Statistical crime report for area Days/hours of use by personnel Cameras Door monitoring How many of each kind, roll-up, standard, etc.
7 Door locks Controlled access Personnel Vehicles Integrity of doors Integrity of windows Alarm Contacts: doors (Y or N) windows (Y or N) motion detectors other Other Alarm Equipment Central station monitored: By whom Location Outside Lighting Adequate lighting Adjacent property and street outside lighting Watch service rounds (Y or N) Frequently Inside or outside Police Department response time (minutes) Fire Department response time (minutes) Other employee late night security/access issues? Is sensitive material or equipment planned for this facility? Exposure from adjacent tenants (Y or N explain) Environmental: Contact Person: Have any previous Phase One and/or Phase Two reviews been done Permits Are there any current previous permits for this property? Are there wetlands on this property? Soil samples Endangered species Archeological sites Wildlife migration
8 Agency having jurisdiction Code Issues: Contact Person Agency having code jurisdiction Average permitting time for: Tenant improvement Site improvement Building expansion Agency history of property (problems) Adopted code at time of construction? Permit history of site (according to City records) Building permits Fire permits Public Works permits Planning and Zoning permits Copy of Certificate of Occupancy Year last permit pulled/closed Were modifications made without permits? Separation yards (from adjacent structures) Building area calculations based on an expected B/F1 occupancy Fire department access (to code?) Code Issues Continued Major construction revisions: (date and type) Fire resistive construction (to code?) Fire resistive separations (to code?) Egress (to code?) Access (to code?) ADA requirements Handicap Access (to code?) Building permit plan set
9 Remodel permit plan set Fire Protection: Contact Person Fire alarm: Meets code requirements (including ADA) Central monitoring Control i.e. smoke migration, fire suppression Meets users requirements Sprinklers (Y or N) Water company (contact and phone number) Number of systems Sprinkler placard design information Fire flow (from water company) Static pressure Residual pressure Residual pressure flow rate Last tested date Type: wet/dry/temperature rating Maintenance (condition) Closest hydrants Extinguishers Alarms (Y or N) Monitored (Y or N) By whom Maintenance (condition) Fire Pump (Y or N) Rating: PSI) Maintenance (condition) Fire Protection Continued Water Supply Double check valve to sprinkler system (Y or N) Recent test results: Static pressure Residual pressure/flow Number of ports flowed Pivot readings Conducted by whom Date Fire Department response time (minutes) Fire resistive occupancy/tenant separation construction provided: Rating Maintenance
10 Condition/rating of doors Condition/rating of Fire Stops Storage: Rack storage (Y or N) Rack storage height Rack configuration (single row, double row, and multiple rows) Seismic anchors/bracing? Rack sprinklers? Commodities planned for storage Solid pile storage (Y or N) Storage height Commodities planned for storage Overall Commodity Mix (commodity classification) Does the adjacent tenant, to the client facility, provide occupancy and hazard potential? Values: What is the estimated value of client occupancy? Is any plant downtime expected if client property is lost Purchasing/Lease: Lease Cost per square foot Rent Increases Security Deposit Tenants operating expenses (estimated) Janitorial cost Parking cost Taxes Utilities (estimated) Other Tenant Costs Purchasing/Lease Continued Purchase Cost per acre/ square foot Property Taxes Utilities (estimated) Off site parking (if required) Lease with option to purchase Miscellaneous: Flood exposure and history
11 Recommended upgrades Site visible defects in equipment LP gas storage Fuel storage area housekeeping Maintenance records Interruption curtailment history Hold-harmless agreements General housekeeping Complete set of plans available (digital) Flight pattern Comments:
How To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
9770 CULVER BOULEVARD CULVER CITY, CA 90232-0507 www.culvercity.org. Incidental improvements: improvements that do not qualify as minor or
9770 CULVER BOULEVARD CULVER CITY, CA 90232-0507 www.culvercity.org Construction Permitting Guidelines for Businesses Moving into Existing Buildings in Culver City If your business is moving into an existing
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the
Building Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST
CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
Design and Construction Design Phase Deliverables
Design and Construction Design Phase Deliverables Notes: 1. The Architect or Engineer of record shall submit this document along with the deliverables for the project at the end of each design phase for
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ)
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15
Middleborough Police Electronic Security Narrative
Middleborough Police Electronic Security Narrative 1. PURPOSE The purpose of this document is to define specific security, access control and surveillance requirements for the exterior and interior of
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
Appendix G. Security management plan
Appendix G Security management plan Security Management Plan Prepared by: Kann Finch Group Project Energy Australia Belmore Park Zone 1- Sub-station component General Design Requirements The perimeter
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
LogisticsCentre IV Distribution Center
KCI Intermodal BusinessCentre LogisticsCentre IV LogisticsCentre IV Distribution Center Modern Warehouse/Distribution Space Ranging From 108,000± SF to 432,000± SF 10221 NW Transcon Drive 112th Street
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
Office Space for Lease 1523 11th St, DeWitt
Office Space for Lease 1523 11th St, DeWitt Suite A $1150.00 per month 1200 sq ft, large open office area, break room, bathroom, storage and separate utilities. Additional office space available. Suite
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to
Application for Builders Risk & Wrap-Up Liability Coverage
Application for Builders Risk & Wrap-Up Liability Coverage GENERAL INFORMATION 1. Name of Applicant: 2. Address of Applicant: 3. Name of Project: Postal Code: 4. Address/Location of Project: 5. Description
1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following:
Secondary Containment, Spill Control and Drainage Guidelines for Hazardous Materials per 2010 CFC PURPOSE The intent of this guideline is to provide the requirements for the design and construction of
July 29, 2014. Revise Section 1.1 (BACKGROUND AND CONTEXT) to the following:
ADDENDUM NO. 2 TO REQUEST FOR QUALIFICATIONS FOR NEW DEVELOPMENT OF OAKLAND UNIFIED SCHOOL DISTRICT PROPERTIES, INCLUDING THE PARCELS HOUSING THE PAUL ROBESON ADMINISTRATION BUILDING AND DEWEY HIGH SCHOOL
APEC CAPABILITIES PROJECT MANAGEMENT / SUPPORT
PROJECT MANAGEMENT / SUPPORT Capital Cost Savings Construction Monitoring and Assistance In-Plant Production Assistance In-Plant Maintenance Assistance Procurement Assistance Project Cost Estimating o
9,940 SF Office Building
204 East Rhapsody Drive, San Antonio, Texas 78216 BUILDING SIZE 9,940 Sq. Ft. (According to Bexar Appraisal District) LAND SIZE 0.6862 Acre or 29,890 Sq. Ft. (According to Bexar Appraisal District) BUILDING
BUILDERS RISK / WRAP-UP LIABILITY APPLICATION
BUILDERS RISK / WRAP-UP LIABILITY APPLICATION Please complete the General Information section for All Projects and specific sections for Wrap-Up Liability and Builders Risk for each coverage as required.
Clear Creek Business Center 187,865 Sq. Ft. OFFICE/FLEX/INDUSTRIAL
Clear Creek Business Center 187,865 Sq. Ft. OFFICE/FLEX/INDUSTRIAL 6800-6880 N. Broadway, Denver CO 80221 Lease rates & terms 6870 AVAILABLE 6860 6850 3.1 Acre Build-To-Suit Site 8 High-quality buildings
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
N O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina Contact Doug Hollidge for more information Email: [email protected]
164,491 SF Food Production Facility Situated on 10 Acres Available in
164,491 SF Food Production Facility Situated on 10 Acres Available in Buffalo, New York CONSTRUCTION Acid resistant brick and coated floors in the production area with drains; clear ceiling heights from
Number Northern Arizona University Facility Services Section Page. Effective April 1, 2011
Facility Services Section Page Recharge Services, Maintenance and Construction PURPOSE 1 of 6 The purpose of this policy is to set forth standards for chargeable services for maintenance and construction
The City of Basehor, Kansas
The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The
MEASURE G-2010 EXHIBIT B FULL TEXT BALLOT PROPOSITION OF THE SAN JOSE EVERGREEN COMMUNITY COLLEGE DISTRICT BOND MEASURE ELECTION NOVEMBER 2, 2010
MEASURE G-2010 EXHIBIT B FULL TEXT BALLOT PROPOSITION OF THE SAN JOSE EVERGREEN COMMUNITY COLLEGE DISTRICT BOND MEASURE ELECTION NOVEMBER 2, 2010 To better prepare San Jose City College/ Evergreen Valley
PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
A&E PRACTICE BUSINESS OFFICE PACKAGE APPLICATION
A&E PRACTICE BUSINESS OFFICE PACKAGE APPLICATION Section 1. General Information 1. a. Applicant: b. Federal ID #: c. Primary Mailing Address: Address City State Zip d. Pho #: e. # Offices: # f. Founded:
Subject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
AVAILABLE WORLD CLASS AIRCRAFT MANUFACTURING & MAINTENANCE COMPLEX. 46,000 + to 1,200,000 + SF Available
exclusively marketed by AVAILABLE WORLD CLASS AIRCRAFT MANUFACTURING & MAINTENANCE COMPLEX 46,000 + to 1,200,000 + SF Available Aircraft Hangar, Maintenance Facilities and Support Office on USAF Base Tarmac
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
SOLD. Lot 1. 1 Mile: Population: 10,200 Median HH Income: $33,100. 3 Mile: Population: 80,200 Median HH Income: $34,900
Walmart Outparcels For Sale College Station, TX Store # 1150 1815 Brothers Blvd FM 2818 W SOLD Texas Ave S/ Hwy 6 Longmire Dr Brothers Blvd Lot 1 For more information about this site, contact: Lot 1: ±2.41
WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive
WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive Warranties Time Limits for Reporting Manufacturer s
Please Refer to Attached Sample Form
Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 32104-E Cancelling Revised Cal. P.U.C. Sheet No. 28312-E Electric Sample Form No. 62-0685 Application for Service
AVAILABLE FOR SALE. 1800 Golden Trail Court, Carrollton, TX ± 63,746 SF
AVAILABLE FOR SALE 1800 Golden Trail Court, Carrollton, TX ± 63,746 SF 1800 Golden Trail Court CONTACT INFORMATION Nathan Denton, Principal Direct: 972-934-4015 [email protected] LOCATION DATA:
Datacenter Site Selection Checklist
Checklist Use this checklist to aid in the process of selecting a new site for the data center. When visiting potential building sites, print the checklist off and take it along to record impressions and
ORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.3 Cabinets, Equipment 1.1.4 Portables 1.2 Fire / Life Safety 1.2.1 Corridor, Separation
I. Project Initiation Sheet (if any information changed since Concept Plan submittal)
Development Services 201 W. Colfax Avenue, Dept. 203 Denver, CO 80202 P: 720-865-2982 www.denvergov.org/developmentservices Formal Site Development Plan Submittal Checklist General Submittal Requirements
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
REAL ESTATE DUE DILIGENCE CHECKLIST
REAL ESTATE DUE DILIGENCE CHECKLIST October 2010 P.O. Box 2228 Baton Rouge, LA 70821 225.387.8605 www.charterschooltools.org [email protected] Copyright 2010, Charter School Tools. All rights
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:
ORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.2 Water damage in many classrooms. Replace tiles. 1.1.3 Cabinets, Equipment 1.1.4 Portables
COMMON FOR ARCHITECTS AND ENGINEERS Excerpts from HB 2284, 82 nd R
Legislation passed by the 82 nd legislature has modified the Texas Engineering Practice Act and the Texas Architect Practice Act. In order to give the public a clearer understanding of these changes, the
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Open House and Home Tour Checklist
1 The House Address: Number of floors: Listing price: Basement? Property tax: Outdoor space? Eugh closet space? Style: Eugh storage space? Square footage: Room for expansion? Number of bedrooms: What appliances
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
New River Valley Commerce Park Virtual Shell Building
1. Regional Overview 2. Site Information Table of Contents 3. Building Information 4. Building Schedule 5. Construction Budget Information 6. Contact Information Overview A : is a shovel-ready alternative
RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE
RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE Residential Course of Construction policies, also known as Builder s Risk, are designed to cover the property owner for potential loss while the property
Residential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Suffolk County Department of Health Services. Division of Environmental Quality
Suffolk County Department of Health Services Division of Environmental Quality Guidelines For the Construction of Storage Areas for Portable Containers ~~~~ Clare B. Bradley, M.D., M.P.H. Suffolk County
NEW JERSEY CENTER OF EXCELLENCE
Overview NEW JERSEY Page 1 The Plant (CUP) provides electricity via a cogeneration system, chilled water for environmental cooling, steam for heating, and compressed air primarily for HVAC control Serves
Does Wall Township require an inspection by the building department on resale of a home?
Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,
Disaster Prevention and Protection Checklist
Preservation Services Leaflet 1438 West Peachtree Street, Suite 200/Atlanta, GA 30309 Phone: 404-892-0943/Fax: 404-892-7879 Website: Disaster Prevention and Protection Checklist The inspection
Arizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST
It is essential to perform a Basic Damage Assessment (BDA) following an adverse event to help ensure the safety of building occupants as well as prevent additional losses from occurring. This checklist
EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST
DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1
SECTION XI OPINION OF PROBABLE COST
SECTION XI OPINION OF PROBABLE COST OPINION OF PROPABLE COSTS HARBOR ISLAND THE PAVILION 1) Provide a sprinkler system for the entire building. 8000 SF X $15/SF $120,000 2) Remove and replace existing
Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals
Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals Les Butler Associate Commissioner for Business and Regional
PLAN SUBMITTAL INFORMATION
PLAN SUBMITTAL INFORMATION APPLICATION FOR A BUILDING PERMIT Prior to drafting construction drawings, please check with the North Miami Beach Community Development Department concerning the following:
N O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina S P E C I F I C A T I O N S Contact Doug Hollidge for more information
Applies to: All Employees within the Facilities Management Department (FMD)
Building Area Measurement Guidelines Applies to: All Employees within the Facilities Management Department (FMD) GUIDELINES: Issued: December 17, 2013 Author: FMD Physical Planning Team PURPOSE: To establish
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District
RULES AND REGULATIONS CONTRACTOR WORK
RULES AND REGULATIONS CONTRACTOR WORK CARILLON 227 West Trade Street Suite 330 Charlotte, NC 28202 The following Rules and Regulations shall govern the operation of contractor work in the Building. For
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport
Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
2.4 Hardcopy submittals shall be provided at adequate size so that all notes are readable.
DESIGN EQUIEMENTS POJECT DELIVEABLES CHECKLISTS GENEAL INFOMATION 1.1 The following is a checklist to be used as a guide for the required deliverables for the Schematic Design phase. 1.2 Schematic Design
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
VILLAGE OF BETHALTO COMMERCIAL BUILDING PERMIT APPLICATION
VILLAGE OF BETHALTO COMMERCIAL BUILDING PERMIT APPLICATION VILLAGE OF BETHALTO COMMERICAL BUILDING PERMIT INFORMATION / REQUIRMENTS I. APPLICATION REQUIREMENTS 1. GENERAL APPLICATION REQUIREMENTS A building
CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.
Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications
VIRGINIASCAN OFFICE BUILDING DATA SHEET
VIRGINIASCAN OFFICE BUILDING DATA SHEET To be included on VirginiaScan, the building must have at least 10,000 sq. ft. available and all the fields in blue must be provided. A sale/lease price or price