COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9
|
|
|
- Dwight Owen
- 9 years ago
- Views:
Transcription
1 COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR State Board of Building Regulations & Standards 1 Ashburton Place Room 1301 Boston, MA (617) Date of Issue July 14, 1998 On June 9, 1998, the Board of Building Regulations and Standards approved the following guidelines For use by Code Officials, Design Professionals and Contractors.
2 FIRE PROTECTION SYSTEMS NARRATIVE REPORTS The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device may be designed to initiate other life saving fire protection systems or devices, or other mechanical systems. In some circumstances different individuals or different companies may design safety systems, which are required to interact. The narrative report is intended to provide a single document, which describes the design rationale of all fire protection systems and the interface between systems. It is an invaluable tool for building officials, building owners and maintenance personnel. 780 CMR requires the submission of so called fire protection systems narrative reports as part of the construction documents, which must be filed in order to obtain a building permit (or permit in part). The following document has been developed to assist end users of the Massachusetts State Building Code in the preparation narrative reports for fire protection systems as required in 780 CMR 9 (Section ).
3 GENERAL NARRATIVE REPORTS As regulated by 780 CMR, Section Fire Protection Construction Documents: 1. a. Basis (methodology) of design for the protection of the occupancy and hazard for compliance with 780 CMR and applicable NFPA Standards, in the form of a narrative report. b. Sequence of operation of all fire protection systems and operation in the form of a narrative report. c. Testing criteria to be used for final system acceptance in the form of a narrative report. DEFINITION A Narrative Report is a written summary description of the building or structures and all applicable fire protection systems and related operational features. Explains the analogy and methodology used by the designers in the design of the systems for the protection of the building occupants and emergency response personnel for all required and non-required fire protection systems. APPLICABILITY Required fire protection system installed in new buildings or structures, required fire protection system modification or addition to an existing system, non-required fire protection systems regulated by regulatory codes other than 780 CMR or voluntarily installed require approval, permits and inspections by building and fire department officials. The enforcement provision of 780 CMR require that a narrative report be submitted as part of the plan review and prior to the issuance of building permit. Administratively depending on the project size, scope and complexity, the code official should make a reasonable decision as to require a full comprehensive or partial report. A Narrative Report for detached one and two family dwellings is not a requirement of Section , however a limited version of the narrative report identifying the type and style of household fire warning systems to be installed is recommended. PURPOSE Expedites the plan review and inspection process by building and fire officials. It is maintained on file for use at the time of final inspection and periodic reviews during future field inspections. Is referenced to insure that all future modifications, alterations, addition or deletion to the original systems are current and that the original system s protection and required system performance are not compromised or have been altered without building or fire official prior review. Building owners benefit by knowing how their building fire protection and life safety systems work and provides procedures and method for testing and maintenance. A copy of the
4 Narrative Report should be kept on the premises and be available for review prior to testing or proposed modifications to be made to any portion of the building s life safety systems. DEVELOPMENT & SUBMISSION FORMAT Prepared by a qualified, identified individual who has taken charge in the development of an entire coordinated report which includes all information regarding the design basis, sequence of operation and testing criteria associated with all required or non-required fire protection systems set forth by applicable Laws, Regulations and Standards. The report is to be submitted with plans and specifications for review and approval by code officials prior to the issuance of a building permit. The Narrative Report should be written in a clear conversational format. The installation specification is not considered a Narrative Report. The Narrative Report is a stand alone document, 8 ½ x 11 for filing and ease of use by code officials, including an administrative cover page identifying the project name, building address, name, address and phone number of the individual who has taken charge in the preparation of the Narrative Report. COMMENTARY The promulgation of the State Building Code is written in a way to require uniformity for all buildings and structures regardless of local conditions. The intent of the codes can be subjective and interpretive by both designers and code officials, uniformity is not always necessarily achieved. The Narrative Report attempts to clarify to the code official the designer s intent and his interpretation of the code. The code official may agree or disagree with the designer s interpretation. Historically the requirements for fire protection systems have become site specific and building code requirements not uniformly enforced. The size of the community, fire department staffing, fire department equipment availability and suppression tactics established by the local fire department have effected the uniformity of enforcement. Site specific requirements less than or more than the building code requires may have reasonable intent; however, this type of enforcement in some cases has proven to be controversial in the applicability of code uniformity. The Narrative Report can be a valuable instrument when accurately prepared, it will establish a line of communication between the designer and the code official resulting in what the building code mandates, uniformity and consensus in the interpretation of the code.
5 (1.a) BASIS (METHODOLOGY) OF DESIGN This portion of the narrative report should be broken down into six sections. SECTION 1 Building Description This section identifies specific features of a building that contributes to the overall understanding of the fire protection systems and features required to be identified in the Narrative Report. a) Building Use Group b) Total square footage of building c) Building height d) Number of floors above grade e) Number of floors below grade f) Square footage per floor g) Type(s) of occupancies (hazards) within the building h) Type(s) of construction i) Hazardous material usage and storage j) High storage of commodities within a building usually over 12 ft. k) Site access arrangement for emergency response vehicles SECTION 2 Applicable Laws, Regulations and Standards This section identifies regulatory codes and standards that may have an impact in the design and plan approval of the required and the non-required fire protection systems as per the requirements of 780 CMR, requiring the preparer of the Narrative report to have had conducted a comprehensive code research. a) 780 CMR code sections Fire Protection System Requirements b) NFPA Standards and Edition used for design of each specific fire protection system c) Applicability of Sections of M.G.L., Chapter 148, Fire Protection d) Applicability of Sections of 527 CMR Fire Prevention Regulations e) Applicability of approved local by-laws, or ordinances f) Applicability of specialized codes (plumbing, elevator and electrical, architectural access) g) Applicability of Federal Laws (OSHA, ADA, etc.) SECTION 3 Design Responsibility for Fire Protection Systems This section identifies the accountability for a specific fire protection system design and the accountability for the integration of the fire protection systems constituting a building life safety system. The professional engineer (PE) fully designs (complete layout and calculations) and specifies the fire protection system or systems to be installed, reviews and approves the installing contractor s shop drawings. The PE is considered the engineer of record and certifies the system installation for code compliance at completion. The professional engineer (PE) provides a partial design and specifies the design criteria to be used by the installing contractor who finalizes the system layout, provides calculations to
6 confirm the design criteria. The PE reviews and approves the installing contractor s final layout and calculations. The PE is considered the engineer of record and certifies the system installation for code compliance at completion. Design-build, the installing contractor completely designs and specifies (develops a full system layout, design criteria and calculations), installs the system and certifies system installation for code compliance at completion. There may be a professional engineer involved but not necessarily. Whichever above method is selected, the project requires an engineer of record to assume responsibility for the coordination of each specific fire protection system requiring integration, forming an entire building life safety system. SECTION 4 Fire Protection Systems to be Installed This section identifies key performance design criteria and features for each specific fire protection system. a) Water supply, fire mains and hydrants b) Automatic sprinkler systems and components c) Standpipe systems and components d) Fire alarm systems and components e) Automatic fire extinguishing systems f) Manual suppression systems g) Smoke control/management systems h) Kitchen cooking equipment and exhaust systems i) Emergency power equipment j) Hazardous material monitoring equipment k) Seismic considerations The description (specific features) for the above fire protection systems shall also indicate if the system is: Required by Regulations, Law or approved by-law or Ordinance Non- required, developer provides voluntarily A complete new system An addition or expansion to existing system A modification/repair to existing system Level of protection to be provided to be provided, 100% or partial protection or exempt by regulatory code
7 SECTION 5 Features Used in the Design Methodology This section identifies the designer s intent in the overall design and criteria development of either a required or a non-required system. a) Building occupant notification and evacuation procedures b) Emergency response personnel, site and system features c) Safeguards, fire prevention and emergency procedures during new construction and impairment plans associated with existing system modifications d) Method for future testing and maintenance of systems and documentation SECTION 6 Special Consideration and Description This section identifies the designer s intent to deviate from prescriptive requirements of regulatory codes and standards with alternative methods. a) Application of performance-base design in lieu of prescriptive code requirement b) Interpretation/clarification between designer and code officials c) Waiver or variance sought through the regulatory appeal process (1.b) SEQUENCE OF OPERATION This portion of the narrative report is a difficult section to write as it entails the specific operation of system devices and equipment and their related integration. SECTION 1 An operational description of either a system or specific devices within a system and the resulting action associated with the operation of the system or specific devices. The operational description shall include all interconnected (integrated) fire protection systems and devices required or non-required forming an entire building life safety system. All signage indicating equipment location, operational and design features and certified documents attesting to system installation integrity. This section of the narrative report can be brief as in a simple system such as a one story 15,000 sq. ft. mercantile building with only a sprinkler system and fire alarm notification devices. Or complex such as in a 25 story high-rise hotel with fire pumps, emergency generator, fire alarm and sprinkler zones, automatic standpipes, automatic voice and manual evacuation signals, smoke management system, automatic elevator recall, special extinguishing systems, remote annunciation, automatic locking devices, alarm retransmission methods and emergency response procedures. The sequence of operation of a building life safety system, particularly with complicated systems must be reviewed and understood by code officials. A team approach should be used by developers, designers, equipment suppliers, contractors including code officials to clearly
8 describe and understand the proper operation of the integrated systems. When a complex system is proposed, the initial narrative report of the sequence of operation should be viewed only as a draft. At various stages of installation modifications made be made. The designers should submit a final narrative for approval by the code officials prior to witnessing a system acceptance. Communication between the developers and code officials is an important element particularly in this phase, as the building codes and the NFPA Standards tend to be flexible and interpretative (1.c) TESTING CRITERIA This portion of the narrative report should be broken down into the following three sections. SECTION 1 Testing Criteria This section identifies the individual in charge who will coordinate the final acceptance testing and witnessed by appropriate code officials. Personnel a) Identification of professional in charge for setting up and coordinating all testing Method of verification and confirmation by professional in charge that all fire protection systems, equipment and devices have been individually tested and tested as an entire system when specific systems are integrated to form a building life safety system Method of coordination by professional in charge of all contractors, equipment distributors and code officials required to perform and witness all testing dates and times, notification to public utilities, personnel required to perform all required testing as a system or individual system component testing SECTION 2 Equipment and Tools This section will identify the necessary equipment available on site at time of witnessing the operational features of the fire protection systems, integrated building lie safety and systems that require validation from code officials to expedite the acceptance testing. a) Identification of equipment and procedures to be used to verify system performance Example: Manufacturer s instructions Specifier s special instructions Approved Narrative Report, sequence of operation section Smoke machines Smoke candles Sound meters Fire hoses, nozzles Flow measuring devices Gauges
9 Voltage meters Magnets Communication radios Fire department equipment Special tools Notification announcements SECTION 3 Approval Requirements This section identifies all the close-out documents for the code official s departmental records. a) Establish method of approval required (verbal or written) from code official if system satisfies all operational code compliance requirements b) Establish method of remedial action when a system or portion of a system fails to operate satisfactorily c) Documentation to be submitted to code officials at completion verifying that systems are in compliance with all laws, regulations and standards and pre-approved narrative reports Documentation as required by 780 CMR, Section Documentation to be submitted to code officials listing names, addresses and telephone number of personnel for emergency notification DEFINITIONS Fire Protection Systems Automatic sprinkler systems, fire detection system, fire alarm notification system, smoke control system, kitchen hood suppression systems, etc. Building Life safety System a combination of fire protection systems and other building fire protection features such as automatic door closers, emergency generators, emergency egress lighting, elevator systems, etc., interconnected or integrated with multiple fire protection systems functioning simultaneously when activated. Preparer of Narrative report An individual who has taken charge of a project and has knowledge of required and non-required fire protection systems and buildings life safety systems. The designer in charge of a specific design for a fire protection system may prepare their portion of the Narrative Report to be submitted to the individual who has taken charge. The individual who has taken charge shall compile the data from the designer of each system and prepare a single, comprehensive and coordinated final Narrative Report describing each system and when applicable a description of how each system interfaces with the building life safety system s integration and sequence of operation. The take charge individual may be the architect, engineer of record, and the designer of any of the fire protection systems or an independent qualified consultant.
Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
Inspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
Fire Code Inspector II
Class specifications are intended to present a descriptive list of the range of duties performed by employees in the class. Specifications are not intended to reflect all duties performed within the job.
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
Fire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
Sam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems
Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems usa.siemens.com/infrastructure-cities Share current and upcoming standards
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
POSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008
SOCIETY OF FIRE PROTECTION ENGINEERS (SFPE) NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS (NSPE) NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) POSITION STATEMENT THE ENGINEER AND
2012 Ontario Building Code Changes Affecting Fire Alarm Systems
2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009
FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
Fire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) Alberta Technical Seminar
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Fire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
Amendments to the 2012 INTERNATIONAL FIRE CODE
Amendments to the 2012 INTERNATIONAL FIRE CODE 2012 Edition, International Fire Code. Section 101.1 Amend to read as follows. 101.1 Title. These regulations shall be known as the Fire Code of the City
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
OVERVIEW SCOPE DEFINITIONS
Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
946 CMR: MASSACHUSETTS DEVELOPMENT FINANCE AGENCY 946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES
946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES Section 7.01: Scope and Purpose 7.02: Definitions - Fire and Police Alarms 7.03: Duties of Fire Chief 7.04: Smoke Detectors in Certain
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
Global Leaders in Fire Engineering. Company Overview. Finding simple solutions to complex problems.
Company Overview Finding simple solutions to complex problems. ON M9B 6H7 AB T2H 1Z9 339941 From our offices in,, and, we serve our national and international clients by providing cost-effective solutions
Fire Alarm Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 [email protected] Fire Alarm Submittal Requirements and Acceptance Testing To all Registered
CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR PUBLIC SCHOOLS, CHARTER SCHOOLS AND JUNIOR COLLEGES
DEPARTMENT OF PUBLIC SAFETY CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR PUBLIC SCHOOLS, CHARTER SCHOOLS AND JUNIOR COLLEGES 8 CCR 1507-30 [Editor s Notes follow the text of the rules at the end
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
City of Beacon Building Department
City of Beacon Building Department PLEASE SUBMIT THE FOLLOWING: 1. A complete application signed by the owner. 2. An application for a certificate of Occupancy/Compliance. 3. Completed application processing
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers
Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
Program No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES
MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
ALARM SYSTEM REGULATIONS. BE IT ENACTED by the County Legislature of the County of Cattaraugus as follows:
ALARM SYSTEM REGULATIONS BE IT ENACTED by the County Legislature of the County of Cattaraugus as follows: SECTION 1. Legislative Intent. 1.1. It is the intent of this Local Law to regulate and control,
Fire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM
PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM B 3 CASE STUDY RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO PARTICIPATION
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings Richard W. Bukowski, P.E., FSFPE NIST Building and Fire Research Laboratory The events of September 11, 2001 have generated
Check Off (Below) Information That Is Submitted With Permit
TOWN of BOYLSTON 221 Main St Boylston, MA. 01505 508-869-6064 / fax # 508-869-6210 COMMERCIAL BUILDING PERMIT BUILDING PERMIT INSTRUCTIONS and APPLICATION Please be advised that any incomplete and/or not
COMMISSIONING OF FIRE ALARM SYSTEMS
COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
Development Services Guidelines
Dear Customer/Developer: Balcones Heights 3300 Hillcrest San Antonio, Texas 78201 210-735-9148 ext 246 Fax: 210-735-9409 Development Services Guidelines Welcome to the City of Balcones Heights, we look
South Carolina DSS. "Records and Reports" 7-12
South Carolina DSS Child Care Services Child Care Licensing & Regulatory Fire & Life Safety Office Records and Reports Questions 7-12 For Educational Child Care Facilities 1 Presentation is designed to:
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
BUSINESS USE PERMIT APPLICATION
BUSINESS USE PERMIT APPLICATION Instructions and Information for Business Use Permits and Temporary Certificates of Occupancy are included at the end of this application. Planning and Development Services
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide It is recommended that this guide be kept at all times at the Fire Command Center. This publication is provided
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
City of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003
M E M O R A N D U M To: Partnership for Safer Buildings Date: 21 March 2003 From: Codes Assessment Subcommittee Walter Smittle III, Chairman Re: Building Code Fire Safety Concerns: NFPA 5000, Building
FIRE SAFETY INFORMATION FACT SHEET
Disclaimers: This information was believed to be correct at the date of its publication. This information is for general information purposes only and should not be relied upon for legal advice. FIRE SAFETY
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection