1 N O W A V A I L A B L E 5 0, S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina S P E C I F I C A T I O N S Contact Doug Hollidge for more information [email protected] Phone: Company Profile:
2 1 / 11 Catawba County Powered Shell Data Center II Sample Design Criteria Upfit The following inset provides a detailed look at a conceptual infrastructure layout: SPECIFICATIONS BUILDING SHELL PERFORMANCE CRITERIA CRITICAL ELECTRICAL SYSTEMS CRITICAL COOLING SYSTEMS FIRE DETECTION/PROTECTION NETWORK ACCESS & INFRASTRUCTURE STRUCTURED CABLING For more detailed information, please contact Doug Hollidge: [email protected]
3 2 / 11 SAMPLE DESIGN SPECIFICATIONS SITE 50,000 SF powered shell building in Catawba County, North Carolina PROPOSED FLOOR PLAN (DAY 1 READINESS) Day One 10,000 SF Data Hall 16 Cold aisle pitch Approximately x 48 cabinets CRAC units and PDUs located in galleries along perimeter of data hall 24,000+/- SF infrastructure support, CRAC galleries, staging/storage, and circulation areas 1,000+/- SF office area Shell expansion space for a future Day 2 10,000 SF data hall, for a total of 20,000 SF usable IT white space (excluding galleries) Site provides future building expansion pad of up to 100,000 SF+ DAY 1 FLOORPLAN (SQUARE FOOTAGE BREAKDOWN) Data Hall: 10,000 SF Galleries: 2,670 SF Office: 1,000 SF Corridors: 1,700 SF Telecom: 400 SF Support: 9,200 SF TOTAL: 24,970 SF (Measured per BOMA Standards) NATURAL THREAT RESISTANCE No major seismic issue Sufficiently inland to minimize coastal hurricane threats Located outside of the FEMA 500 Year Flood Plain Minimal tornado probability
4 3 / 11 SAMPLE DESIGN SPECIFICATIONS ACCIDENTAL THREAT RESISTANCE Sufficient distance from major highways, military bases, and aircraft takeoff and landing paths. No rail line immediately adjacent to property INTENTIONAL THREAT RESISTANCE Secure exterior equipment yard which obscures direct view and access to exterior mechanical/electrical equipment Earthen Berm along street frontage Perimeter fencing and access controlled gates UTILITY - POWER Total power capacity is available to support Day 1 and future Day 2 loads plus future building expansion N utility, with utility bus sized for Day 2 Two 100/12.5kV physically distinct power company substations in close proximity to the site On-site feeders sized for ultimate total building load Existing 100kV power line to site UTILITY - WATER Sufficient capacity for ultimate load (existing shell footprint + expansion area). 1M gal/day available to the site Water service from public main in Penny Road adjacent to site Secondary service available from Kelly Blvd. adjacent to site
5 4 / 11 SAMPLE DESIGN SPECIFICATIONS UTILITY - SEWER Sufficient capacity for ultimate build-out of shell and expansion area 180,000 gal/day+ available to the site Drainage capacity to absorb tropical rain events and unusual local conditions (i.e.: water main rupture or collapse) NETWORK PROVIDERS AND FIBER Fiber of sufficient capacity and numbers AT&T and DukeNet can provide multiple (10G-40G) waves. AT&T and DukeNet have indicated they can provide whatever bandwidth a client would desire Separate fiber providers Two separate and distinct paths onto the site and into the building available STRUCTURAL SHELL Tilt-wall concrete and structural steel frame Minimum clear height 24 throughout Able to resist 90+ mph winds Bay configuration (column grid) 48 x 40 average throughout FLOOR SYSTEM Planned 6 slab on grade Structural footings provide design rating for 90 mph wind speeds
6 5 / 11 SAMPLE DESIGN SPECIFICATIONS EXTERIOR WALLS Tilt-wall concrete Exterior screening around equipment yard ROOF SYSTEM Design rated for minimum 90 mph wind speeds No interior drains or rooftop equipment Master label lightning protection system Mechanically fastened roof system INTRUSION DETECTION Exterior door monitoring and motion detection CCTV video surveillance system covering building perimeter and main entrances at all critical equipment areas Direct line to local police department SECURITY ENTRANCE AND ACCESS CONTROL Man-trap at main building entry to control facility access Card-entry access control with electronic door locks at main facility entrance and data hall entrances Access management system to control access of employees, partners, vendors, and visitors Access to server rooms only on need to access basis
7 6 / 11 SAMPLE DESIGN SPECIFICATIONS SECURITY MANAGEMENT & VIDEO SYSTEM Capability to view intrusion and record/control event at critical locations throughout the facility Motion detectors to protect critical access areas Graphical view and control on all detectors OFFICE SPACE Anticipate five (5) to eight (8) on-site staff Minimal office area requirement WALL FINISHES Fully demised cell walls on painted sheetrock Painted finish on exposed overhead structure in data floor areas SAMPLE PERFORMANCE CRITERIA TIER LEVEL Tier III concurrent maintainability for electrical infrastructure Tier II mechanical infrastructure Client-specific requirements can be accommodated during the design process
8 7 / 11 SAMPLE PERFORMANCE CRITERIA ENERGY MONITORING Electrical Power Monitoring System (EPMS) to provide real-time monitoring of electrical data EPMS monitoring includes interval and event history storage and reporting Monitoring includes MV switchgear, all main and feeder breakers, and UPS switchgears All monitoring functions available on each feeder breaker by web browser at assigned IP addresses FIRE CELLS OR DATA HALLS Capable of providing 2 data halls of 10,000 SF each (only one initially) Designed as fire cells with 1-hour firewall separation CRITICAL IT LOAD CAPACITY Day 1 critical power density of 150 watts/sf on 10,000 SF of white space Total capacity of 1.5 MW Expansion available for Day 2 via a second 10,000 SF data hall Day 2 shell area is adjacent to Day 1 white space CRITICAL MEP SYSTEMS Mechanical and electrical systems separated from critical primary systems to minimize risk of system disruptions RAISED FLOOR 30 Concrete-filled raised access flooring with 2,000 lb rating Rigid bolted stringer understructure assembly, under-floor grounding, and access ramps with safety rails Uniform floor load capacity of 550 lbs/sf
9 8 / 11 SAMPLE CRITICAL ELECTRICAL SYSTEMS INCOMING POWER DISTRIBUTION & DESIGN N utility (utility bus sized for Day 2) 2N distribution utilizing independent transformer Eight (8) 500kVA PDUs provided (4 per side) pole, 30 amp breakers providers (400 per side) Automatic transfer switches (ATS) provided at each chiller (typical 3) ATS also provided at other major mechanical equipment within the equipment yard Elements of Day 2 infrastructure are included in Day 1 scope such that facility shutdown is not required for Day 2 build-out Exterior grounding ring, bonded to the facility principal ground busses UPS 1500 kw static UPS systems in N+1 configuration Four (4) modules at 500kW each with flooded vented cell 15 minute lead acid storage batteries 15 minutes of capacity at full load UPS DISTRIBUTION UPS system outputs to Day 1 data hall via critical distribution switchgear and PDUs and RPPs on the floor
10 9 / 11 SAMPLE CRITICAL COOLING SYSTEMS DESIGN AND CONFIGURATION N+1 configuration of air-cooled chillers N+20% CRAC unit distribution for Day 1 white space N+1 CRAC unit configuration for electrical room Raise floor plenum for under-floor air distribution All chilled water equipment shall be installed in equipment yard and protected by NEMA 4X enclosures CHILLERS N+1 air-cooled chillers, 3 chillers at 275 tons each N+1 chilled water pumps, 3 at 475 GPM/20HP each CRACS Twelve (12) 50-ton CRAC units in mechanical/electrical galleries along the perimeter of IT space 62F discharge, plug fans, no heat and no humidification Two (2) 35-ton CRAC units serving electrical room SAMPLE CRITICAL BACKUP SYSTEMS DIESEL GENERATORS Three (3) 1.5MW medium voltage primary duty diesel engine generators Capable of supporting Day 1 total building load in an N+1 configuration Configured to expand to Day 2 total load in an N+1 configuration No provisions for EPA Tier 4 emissions requirements
11 10 / 11 SAMPLE CRITICAL BACKUP SYSTEMS DIESEL FUEL Generators will be equipped with 3,000 gallon sub-base or belly tanks to provide 72-hour run time LOAD BANKS Electrical load bank for testing and associated switchgear to test UPS and engine generators SAMPLE FIRE DETECTION / PROTECTION DAY 1 IT AREA Pre-action dry pipe fire sprinklers VESDA smoke detection VESDA smoke detectors installed below and above raised floor Capability to detect all fire events and extinguish the event Direct line to local fire department INFRASTRUCTURE & OFFICE SUPPORT AREAS Wet-pipe systems in office and office support areas A pre-action system will protect the electrical infrastructure and interior mechanical areas
12 11 / 11 SAMPLE NETWORK ACCESS & INFRASTRUCTURE REGIONAL LANDSCAPE Internet and Private Line Multiple Tier 1 telecom providers (minimum 2) within the area/city Full redundant and diverse fiber infrastructure/central offices No single point of failure and no shared components DC FACILITY - NETWORK INFRASTRUCTURE Internet, Private Line, and LEC Multiple Tier 1 telecom providers (minimum 2) into the facility Fully redundant and diverse fiber facility infrastructure with no single point of failure Capability to expand to more telecom providers with additional alternate paths DC FACILITY - INTERNAL NETWORK INFRASTRUCTURE Carrier Entrance Two (2) independent, fully diverse and dedicated telecom interconnected rooms located outside the computer room Rooms are located at opposite ends of the building SAMPLE STRUCTURED CABLING STRUCTURED CABLING Backbone cabling to horizontal distribution areas Zone distribution to rack aisles / equipment areas
13 N O W A V A I L A B L E 5 0, S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina W E B S I T E : F O R M O R E I N F O R M A T I O N : Doug Hollidge: [email protected]
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.
How To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ)
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15
LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.
LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT. THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT Designed and equipped to meet
Data Center:Build-to-Suit
Data Center:Build-to-Suit A fortified 100,000 SqFt mission critical build-to-suit constructed on a secured 5 acre parcel at Innovation Park Charlotte, NC On-Site 120MW Substation Sourced from Two Independent
NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW
VAZATA 9651 Hornbaker Road Manassas, VA 20109 VAZATA.COM VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from the ground up to deliver highly reliable and
19 Site Location, Design and Attributes. Site Location, Design and Attributes
1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile
Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport
Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
N O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina Contact Doug Hollidge for more information Email: [email protected]
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Wholesale Data Center Suites Available Now
Wholesale Data Center Suites Available Now FROM 2,500 to 100,000 Sq Ft A secure, fortified Mission Critical data center facility located in Innovation Park, Charlotte, NC Scalable data center suites available
Assessment of Existing Data Centers for Critical Facilities Round Table Group
Assessment of Existing Data Centers for Critical Facilities Round Table Group Chuck Shalley, P.E. Consulting Electrical Engineers BACKGROUND INFORMATION ASSIGNMENT Data Center Criteria Type Raised Floor
COMMODITIZING THE DATA CENTER MARKET
COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.
Subject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers
CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.
Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected]. 2011 IBM Corporation
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected] Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power
Data Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
Experience Matters...
Experience Matters... Travelport Data Center offers confidence and space to meet your demanding IT needs Transwestern presents the Travelport Data Center in Denver, Colorado totaling 267,000 SF with 121,600
Data Center CH1. Elk Grove Village, IL
Data Center CH1 Elk Grove Village, IL powerful/ efficient /reliable solutions > Data Center CH1 ABOUT DUPONT FABROS TECHOLOGY (DFT) DFT is a leading owner, developer, operator and manager of wholesale
NY2 21 CRITICAL MEGAWATTS 280,000 SQUARE FEET WWW.CORESITE.COM
CLOUD-ENABLED DATA CENTER 21 CRITICAL MEGAWATTS 280,000 SQUARE FEET WWW.CORESITE.COM NEW YORK CAMPUS The optimal location to propel your business SYMS WAY EMERSON LN EQ SECAUCUS HARTZ WAY SECAUCUS RD AMERICAN
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
X-tier Data Facility. Prepared by X-tier SAE Corporation
X-tier Data Facility Company Profile X-tier Corporation X-tier is based in Leawood, Kansas. X-tier provides business agnostic, security hardened, custom and turnkey Cloudbased software systems, services,
House your data in a building constructed for only one express purpose protect the information inside. Twin Cities East Data
Protection is Central. Twin Cities East Data Center House your data in a building constructed for only one express purpose protect the information inside. Twin Cities East Data Center is nothing less than
ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION
ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION Your business needs a robust infrastructure that is secure, cost effective and reliable in order to remain competitive in today s market. ISOMEDIA s colocation
Data Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
NeuStar Ultra Services Physical Security Overview
NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its
DATA CENTERS. VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM
DATA CENTERS VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM OVERVIEW VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from
Data Centre Barrie, Ontario
COGECO DATA SERVICES DATA CENTRE Data Centre Barrie, Ontario Cogeco Data Services offers flexible, secure, connected and fully managed ICT solutions at its Flagship Data Centre in Barrie, Ontario Data
Data Center Due Diligence List
Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West
Chicago 1 (CHI-1) Data Center
215 W. Ohio St. 5th Floor Chicago, IL 60564 Call Us Toll-Free 1 (866) 817-2811 Follow Us @SingleHop Like Us facebook.com/singlehop Chicago 1 (CHI-1) Data Center Enterprise-Class, Downtown Chicago Facility
How To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net
Our Hosting Infrastructure An introduction to our Platform, Data Centres and Data Security www.in-tuition.net UK Infrastructure Infrastructure Overview Intuition Networks has provided managed Internet
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
Establishment of State s Second Data Center. Business Continuity and Disaster Recovery. North Carolina. Office of Information Technology Services
Establishment of State s Second Data Center North Carolina Office of Information Technology Services National Association of State Chief Information Officers 2008 Recognition Awards Nomination June 2,
DATACENTER COLOCATION. Flexible, Secure and Connected
DATACENTER COLOCATION Flexible, Secure and Connected Flexible Solutions for Your Requirements Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 10 Good Reasons 12 Our
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
World s Greenest High Performance Data Center
World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms
Data Center Checklist
Data Center Checklist The use of colocation and services has continued to increase, rapidly becoming the solution of choice for organizations requiring an efficient, secure, cost-effective way to manage
Contents Error! Bookmark not defined. Error! Bookmark not defined. Error! Bookmark not defined.
We Do It Better. Contents Introduction...3 Service and Support...3 Data Center Details...4 Security...4 Location...4 Power...4 Humidification...5 AC...5 Cooling...6 Datacenter Features...6 SAS 70...6 PCI
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
LEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
Scalable. Affordable. Flexible. Fast.
Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations
Occupancy: Assembly (A-3) and Business -Includes offices, seminar rooms, classrooms, and café facility. Duke University Medical School
Introduction Background The Duke School of Nursing building offers a new three-story state of the art facility that has helped strengthen the quality and integrity of the School of Nursing at Duke. The
Strategic Data Centre Site Profiles. Data Centre Co-Location London East
Strategic Data Centre Site Profiles Data Centre Co-Location London East Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 5 Contents 1. LONDON EAST...3 1.1 LOCATION...3 1.2 TECHNICAL
F O R L E A S E F O R S A L E
F O R L E A S E F O R S A L E N C W E S T P O W E R E D S H E L L D A T A C E N T E R Cherokee County, North Carolina Contact Doug Hollidge for more information Email: [email protected] Phone: 704.651.2210
CyrusOne Global Data Center Solutions
CyrusOne Global Data Center Solutions 1649 W Frankford Road, Carrollton, TX 75007 + Leader in Global Data Center Colocation Built for tomorrow. Ready today. CyrusOne has quickly emerged as a global leader
F O R L E A S E F O R S A L E
F O R L E A S E F O R S A L E N C W E S T P O W E R E D S H E L L D A T A C E N T E R Cherokee County, North Carolina Contact Doug Hollidge for more information Email: [email protected] Phone: 704.651.2210
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
Data Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime
South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,
Data Center Overview Document
Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.
Product description NCC Data Center
Product description NCC Data Center Concept General As one of the largest actors in the Nordic construction industry, NCC Construction plays a leading role in shaping the future of our society. After building
DATA CENTERS. VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM
DATA CENTERS VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM DAL II MARSH LANE CARROLLTON TX OVERVIEW VAZATA s Dallas Data Center II (Dal II) is located at 2440 Marsh Lane
Global Data Center & Colocation Facilities
Global Data Center & Colocation Facilities Managed Hosting & Storage Services Managed Servers Virtualization services Database Management Managed Storage and Back up Services Managed Load Balancing SaaS/IaaS
Previder Datacenters it starts here
Previder Datacenters it starts here Previder Datacenters Introduction Previder has two sustainable, energy efficient and carrier-neutral datacenters in the Netherlands. Both datacenters have a number of
Strategic Data Centre Site Profiles Data Centre Co-Location London North
Strategic Data Centre Site Profiles Data Centre Co-Location London North Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 6 Contents 1. LONDON NORTH...3 1.1 LOCATION...3 1.2 TECHNICAL
Data Centre Basiglio, Milan Flexible, advanced and efficient by design.
Data Centre Basiglio, Milan Flexible, advanced and efficient by design. TelecityGroup Via Francesco Sforza 13 Milano 3 City 20080 Basiglio MI Italy Tel: +39 02 36679500 [email protected] www.telecitygroup.it
NY-1 DATACENTER AT A GLANCE. NY-1 is a Tier III-rated, SAS SSAE16 and HIPAA-certified data center
NY-1 1.866.WEBAIR.1 WWW.NY1.WEBAIR.COM NY-1 LONG ISLAND S MOST SECURE, FULLY-REDUNDANT DATA CENTER ENTERPRISE COLOCATION, PRIVATE AND HYBRID CLOUD SOLUTIONS, AND MANAGED SERVICES. DATACENTER Enjoy the
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
SYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013
SYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013 TABLE OF CONTENTS SECTION I: INDEPENDENT PRACTITIONERS TRUST SERVICES
POWERING A CONNECTED ASIA. Pacnet Hong Kong CloudSpace1 Technical Specifications. Asia s Pioneering Facility with Direct Subsea Cable Access
POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace1 Technical Specifications Asia s Pioneering Facility with Direct Subsea Cable Access Our purpose-built, 300 m 2 Pacnet Hong Kong CloudSpace1 (HKCS1)
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
Pacnet Hong Kong CloudSpace2 Technical Specifications. Upholding the Principles of Efficiency and Sustainability in Data Center Design
POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace2 Technical Specifications Upholding the Principles of Efficiency and Sustainability in Data Center Design Our purpose-built, 5,000 m 2 Pacnet Hong
T5 CHARLOTTE REGION WEST DATA CENTER PARK
Additional!Sites Up to 120+ MW available to site from Duke Energy Low cost reliable power - 3.9-4.6 /kilowatt hour Dual Circuit 100 KV Grid Connector Low natural disaster risk Multiple l fiber carriers
LEVEL 3 DATA CENTER SERVICES IN SAN FRANCISCO HOUSE POWER-INTENSIVE APPLICATIONS AND SUPPORT BUSINESS CONTINUITY
LEVEL 3 DATA CENTER SERVICES IN SAN FRANCISCO HOUSE POWER-INTENSIVE APPLICATIONS AND SUPPORT BUSINESS CONTINUITY THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT THE SCALE TO SUPPORT FLEXIBLE ENTERPRISE IT It
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 [email protected] www.telecitygroup.se
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
Datacentre Capability March 2015
Callaghan Engineering Consul-ng Engineers Project Managers Datacentre Capability March 2015 Callaghan Engineering Multi-discipline engineering & project management company Established in 1990 Offices in
Why Choose Go4Hosting Data Center?
Why Choose Go4Hosting Data Center? Security When it comes to web hosting we understand the level of technical sophistication and server security involved. At Go4Hosting Data Center we focus on Security,
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Second Place: Industrial Facilities or Processes, New
Second Place: Industrial Facilities or Processes, New Photo: Paul Howell Texas Medical Center in Houston is the largest medical center in North America. It has a chilled water system of 160,000 tons. Big
LDeX Group. Colocation Solutions for High Expectations
LDeX Group Colocation Solutions for High Expectations LDeX1 Units 8 10 The Oxgate Centre, Oxgate Lane, London, NW2 7JA +44 (0)845 370 3510 [email protected] www.ldexgroup.co.uk 5 M VA LDeX1 delivers
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
EVALUATING DATA CENTER AND COLOCATION HIGH-AVAILABILITY SERVICE DELIVERY. A FORTRUST White Paper. March, 2013. www.fortrustdatacenter.
EVALUATING DATA CENTER AND COLOCATION HIGH-AVAILABILITY SERVICE DELIVERY A FORTRUST White Paper March, 2013 When companies evaluate potential data centers and colocation service providers, they normally
HealthcareBookings.com Security Set Up
HealthcareBookings.com Security Set Up Introduction... 2 Overview of the process for using HealthcareBookings.com... 2 Professionals... 2 Patients... 3 Passwords... 4 Hosting Security... 4 Overview of
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
Technical specifications. Containerized data centre NTR CDC 40f+
Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white