BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
|
|
|
- Emma Kennedy
- 10 years ago
- Views:
Transcription
1 DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE 1. The areas in the building that are designated as the licensed space are required by the licensing agency to meet the Building Code in effect when an application for licensure is submitted to the regulating agency. Does the building listed above, to the extent observable, meet the current North Carolina Building Code? Yes No 2. If no, list question numbers which do not comply, explain the violation and whether equivalent protection for the safety of the children is provided: 1) 2) 3) 4) 3 Are any of the above violations of a life safety concern? Yes No If yes, please list question numbers 4. In your opinion based on the violations listed above, do you recommend that the Division of Child Development issue a provisional license to allow time for correction of the violations? Yes No If yes, how long ( days) and for which violations? (Note: All violations must be corrected before a license can be issued unless a provisional time period is recommended or equivalent protection is documented.) 5. Number of rooms approved for occupancy by children? (Attach sketch of building with rooms identified) 6. Specify any local zoning restriction: Signature of Inspector /Date Jurisdiction /Phone: The Inspectors Certificate and Building Inspection Form is required to be completed in its entirety before the Division of Child Development (DCD) can consider the document complete. All questions must be answered; any NO answers must have a written explanation. This form was developed through the cooperation of the Division of Child Development and the Engineering Division of the Department of Insurance. Please note that the inspection forms do not cover all areas of the Code, but are intended to be used as a guide for the local inspector. If additional Code items which are not addressed on these forms are found to be in violation of the Code, please document them on the back of this form. Prepare in quadruplicate: Original & copy to DCD, 1 copy kept by inspector, 1 copy kept by operator.
2 Identification # County Date of Inspection CHILD CARE BUILDING INSPECTION FORM SECTION A: The following general questions should be answered for BOTH Educational and Institutional type occupancies. LIGHT & VENTILATION 1. Is the total area of all windows in the child care room equal to or greater than 8% of the floor area or is artificial light provided? Yes No 2.a Does the room have natural ventilation from a minimum amount of operable window or door area to the outside that would allow a clear opening that is equal to or greater than 4% or more of the floor area? (If NO, go to question 2b). Yes No b Is space mechanically ventilated as required by North Carolina Mechanical Code? (N/A if an existing building) N/A Yes No FIRE 3. Does this building have a manually operated fire alarm system (electrically installed system with pull box stations)? Yes No EXITS 4. Are there at least 2 exits (doors, stairs, smoke proof towers, ramps, or horizontal exits) remote from each other on each floor or fire section of the building? Yes No 5. Is the exit capacity adequate? Yes No 6. Are all means of egress adequately illuminated at all times that the building is occupied? Yes No 7. Are the means of egress identified by readily visible exit signs when the exit or way to reach it is not immediately obvious to the occupants? Yes No 8. Is emergency power provided for centers with more than 300 occupants or for centers providing night care as required by the Building Code? N/A Yes No CORRIDORS AND ACCESS TO EXITS 9. Are all means of egress unobstructed without passing through a closet, storage area, kitchen, restroom, or other hazardous space? Yes No 10. Are all exit corridors a minimum 1-hour fire resistance? N/A Yes No (If yes, go to Question 12) (N/A applies only if there are no corridors) 11. If corridors are not 1 hour fire rated, do all child care rooms, spaces, and areas have a direct level of discharge exit to the outside? Yes No 12. a. Do all corridors, ramps, and passageways have a minimum 6 feet clear width in all areas serving as means of egress for capacity of 100 or more? (N/A if capacity is less than 100) N/A Yes No b. Are all corridors, ramps, and passageways not less than 44 clear width in all areas serving as means of egress for capacity of less than 100? (N/A if capacity is more than 100) N/A Yes No 13. Are all dead-end corridors no more than 20 feet in length? N/A Yes No (N/A applies only if no dead-end occurs) Page 2 of 5
3 14. Do all doors have a minimum clear opening width of 32 (min. door width of 36 ) in the following locations: a. between occupied rooms and required exits? Yes No b. exit doors leading to the exterior? Yes No 15. Are all doors in the line of exit travel a swinging door (side hinged)? Yes No 16. Do doors to rooms that accommodate more than 50 people swing in the direction of travel? N/A Yes No (N/A applies if room accommodates less than 50 people) 17.a Do all required egress and exit doors have single motion, self-unlocking type handle, lever, push pad, or panic hardware? Yes No b. If room accomdates 100 or more people, do all required egress and exit doors have push pads or panic hardware? N/A Yes No STAIRS (NOTE: If no stairs, interior or exterior, check N/A and go to Question 22. If applicable, all questions must be answered) 18.a Are all stairs serving 50 or more occupants at least 44 inches in width? N/A Yes No b Are all stairs serving less than 50 occupants, at least 36 in width? N/A Yes No 19. Are all stairs with four or more steps provided with proper handrails and guardrails? Yes No 20. Are all interior stairs enclosed with 1-hour rated walls and 1-hour rated "B" labeled doors that are at least 36" wide? Yes No 21. Are the stair enclosure doors self-closing? Yes No WALLS AND CEILINGS 22. a. Are all wall and ceiling coverings throughout building non-combustible? (Use of untreated combustible fiber boards, wood, and other combustible fiber boards, wood and other combustible finishes is prohibited). Yes No b. Do interior wall and ceiling finish materials meet the flame spread ratings as required by the Minimum Interior Finish Classification Table, NCBC Yes No 23. Do ceilings in habitable rooms have a minimum of 7'-6" clear height? Yes No HEATING SYSTEMS/MECHANICAL 24. Is the building free of unvented fuel burning or portable electric space heaters? Yes No 25. Have air conditioning, ventilation, heating, cooking, and other service equipment been inspected and approved by the appropriate inspectors? Yes No Date Inspected 26. a. Is combustion and ventilation air for boiler or heater rooms taken directly from and discharged to the outside of the building? N/A Yes No (N/A if electric heat is installed) b. If inside air is used for fuel-burning appliance does it meet the requirements of Chapter 7 of the North Carolina Mechanical Code. N/A Yes No (N/A if inside air is not used) PLUMBING 27. Does the number of waterclosets and lavatories comply with the Plumbing Code as determined by the appropriate inspector? Yes No (1 watercloset per 15 children, 1 lavatory per 25 children) Maximum # of persons allowed by plumbing facilities? Date Inspected Page 3 of 5
4 ELECTRICAL 28. Do the visible and accessible portions of the electrical system comply with applicable sections of the Electrical Code as determined by the appropriate inspector? Yes No Date Inspected MIXED AND MULTI-USE OCCUPANCIES 29. Are all child care areas separated from adjacent occupancies in accordance with the requirement of mixed occupancies and the Occupancy Separation Requirements Table? (N/A if no mixed occupancies) N/A Yes No 30. Do all multi-use areas comply with the most restrictive applicable sections of the State Building Code for each intended use? N/A Yes No (N/A if no multi-use areas) (Multi-use is defined as an area which will be used for different functions at different times and not concurrent. Example: child care to fellowship hall.) ACCESSIBILITY CODES 31. Does this building comply with applicable State Building Codes for access/use by persons with disabilities? Yes No SECTION B: The following questions should be answered only for educational occupancy in addition to the questions answered in Section A above. 32. Does the building comply with the Allowable Heights and Building Areas Table for Educational Occupancy? (If NO, go to Section C). Yes No 33. a. Are all rooms, approved for use by children below grade 2, on the level of exit discharge? (If NO go to Section C) Yes No b. Are rooms used by children in grades 2 and higher no more than one story above the level of exit discharge? Yes No 34. a. Do rooms used by children who are less than 2 ½ years have a direct exit to the outside? (N/A applies only if center does not serve children under 2 ½ yrs) N/A Yes No b. Do rooms used by children under 2 ½ years qualify as alcoves to adjacent spaces with direct exit to the outside? Yes No c. If the square footage of the child care area is >20,000 square feet, do all rooms for all children have direct exits? (N/A if sq. footage is < 20,000) N/A Yes No (If NO to both a and b or c, go to Section C) 35. Are all rooms approved for use by children provided with an operable window which complies with Special Exit Requirements for Educational Occupancy? N/A Yes (N/A if direct exit to outside) No 36. Is the most remote point in every room occupied by children, including dining room, not more than 200 feet from the nearest exterior exit? (non-sprinklered building) Yes No 37. Are smoke detectors provided in the corridors in accordance with Automatic Fire Detection and NFPA72 for child care use? Yes No SECTION C: The following questions should be answered only for institutional occupancy in addition to the questions answered in Section A above. 38. Does the building comply with the Allowable Heights and Building Areas Table for Institutional Occupancy? Yes No Page 4 of 5
5 SECTION C cont.: 39. Are smoke detectors provided in the corridors in accordance with Automatic Fire Detection and NFPA72? Yes No 40. Does the building provide protection from hazardous areas as required by Special Institutional Occupancies, Group I Unrestrained Occupancies, Protection from Hazardous Areas? Yes No 41. Does the building have an approved automatic sprinkler system in accordance with Special Institutional Occupancies Group I Unrestrained Occupancies? Yes No 42. Is the most remote point in every room occupied by children, including the dining room, not more than 200 feet from the nearest exterior exit? Yes No Page 5 of 5
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
CHILD CARE CENTER INFORMATION SHEET
CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Single Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.
NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
FIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT SINCERE KNIT GARMENTS LTD UNIT-1 EAST ISDAIR, CHANDMARI, FATULLAH OTHER FACTORIES: FAKIR KNIT LTD. July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,
New York City Department of Buildings
The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST
DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1
Property Maintenance Check List
Property Maintenance Check List Scope These minimum conditions and responsibilities of persons for maintenance of structures, equipment and exterior property shall govern. Responsibility. Owners shall
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) HQS INSPECTIONS Part II Site Inspections 24 CFR 982.401 & 405 1si Rev. 4-20-06 General Conditions All doors and windows accessible to the outside, must have a workable lock.
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Applications for building permits will not be reviewed until all of the required information has been submitted.
NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
Healthcare Engineering. Code Summary Report
American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
FIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT SURAVEE GARMENTS LIMITED 2/C DARUS SALAM ROAD, MIRPUR OTHER FACTORIES: BABYLON CASUALWEAR LTD & ABONI FASHION March 29, 2014 Page 2 SUMMARY was surveyed for fire safety on
Classroom Door Security & Locking Hardware
Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES
MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms
FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid
DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 1. (A) PROVER NUMBER K1 K2 PART I Life Safety Code, New and Existing
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
TOWN OF DAVIE BUSINESS TAX RECEIPT 6591 ORANGE DRIVE DAVIE, FLORIDA 33314-3399 PHONE: 954.797.1212 FAX: 954.797.1086 WWW.DAVIE-FL.
BUSINESS TAX RECEIPT BUSINESS TAX RECEIPT CHECKLIST FOR SUBMITTALS COMMERCIAL/INDUSTRIAL The following information is required in order for your application to be submitted for review. Items A-E are required
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services
MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
New York City Department of Buildings
The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright
NFPA 101 2012 SELECT SIGNIFICANT CHANGES
NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com [email protected] Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is
City of Elk River BASEMENT Office Use Only
City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single
TENT AND STAGE CUSTOMER ASSISTANCE GUIDE
TENT AND STAGE CUSTOMER ASSISTANCE GUIDE Charles County Government Department of Planning & Growth Management P.O. Box 2150 La Plata, MD 20646 (301) 645 0692 / (301) 870 3935 Fax: (301) 645 0575 Web Site:
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
Underwriting Guidelines for Condominium Pac and Condominium Pac Plus
UNDERWRITING GUIDELINES FOR CONDOMINIUMS SEGMENT Local exceptions to these underwriting guidelines may apply. Please consult with your underwriter or sales executive for details and to discuss risks which
Department of Licenses and Inspections PARTNERS FOR GOOD HOUSING
City of Philadelphia Department of Licenses and Inspections PARTNERS FOR GOOD HOUSING Revised - April 2004 Produced by the Commissioner s Office PARTNERS FOR GOOD HOUSING The City of Philadelphia, on behalf
2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination
2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal [email protected] Andrew M. Schneider, P.E. Senior Fire Protection Engineer [email protected] Questions Submit
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
LOS ANGELES CITY FIRE DEPARTMENT
LOS ANGELES CITY FIRE DEPARTMENT Division 5 Permit LOCATION INFORMATION FD USE ONLY Date of Use: Date Granted PERMIT # Date Expires Name Phone#: City: Los Angeles State: California Zip: 90089 CONTRACTOR
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire
Indiana Building Rehabilitation Standard
Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
The Fire Safety Manager at 312 791 6079 (FAX 312 791 6013) can answer any questions or provide a set of fire code information.
FIRE SAFETY REGULATIONS Fire Prevention reserve the right to make any final decisions regarding the outlined requirements, according to Section 2 36 220 of the Municipal Code of Chicago on Fire Prevention.
FIRE AND LIFE SAFETY TRAINING
FIRE AND LIFE SAFETY TRAINING 1 Objectives General Information Emergency Evacuation Plans / Regulatory Requirements Notification Systems Emergency Exits and Fire Doors Electrical Safety Fire Prevention
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
WINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building
GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)
GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft
HOMEOWNER S PERMIT GUIDE
HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District
FIRE AND SAFETY REGULATIONS
FIRE AND SAFETY REGULATIONS Fire Prevention reserves the right to make any final decisions regarding the outlined requirements, according to Section 2-36-220 of the Municipal Code of Chicago on Fire Prevention.
FIRE SAFETY REQUIREMENTS
FIRE SAFETY REQUIREMENTS 156.200 GENERALLY. A. Scope. The provisions of this chapter shall govern the minimum conditions and standards for fire safety relating to structures and exterior premises, including
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
The New Life Safety Chapter What It Applies to and How Organizations Can Comply with It
The New Life Safety Chapter What It Applies to and How Organizations Can Comply with It The Joint Commission requires health care organizations to comply with the Life Safety Code * to help ensure fire
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
Instructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance
Princeton Department of Emergency & Safety Services Instructions for Obtaining a Certificate of, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance 1. Obtain an application Download from /forms
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
New Ambulatory Health Care Occupancies
NFPA 101 Substantiation: The changes proposed to NFPA 101 Chapter 20, New Ambulatory Health Care Occupancies, make the chapter a stand-alone set of requirements that do not reference the use of the provisions
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
PROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)
APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL FIRE RESTORATION PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility: