1 Industrial Controls Load Feeder - Selection data for Fuseless and Fused Load Feeders Gerätehandbuch Configuration Manual Edition 01/2016 siemens.com

2

3 Introduction 1 General information 2 Industrial Controls Load feeders Configuration Manual Selection tables 400 V AC 3 Selection tables 500 V AC 4 Selection tables up to 690 V 5 Fused selection tables up to 690 V 6 Installation guidelines 7 Service and support 8 01/2016 A8E A/RS-AA/005

4 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: Trademarks WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Digital Factory Postfach NÜRNBERG GERMANY 3ZX1012-0RA21-1AC0 P 01/2016 Subject to change Copyright Siemens AG All rights reserved

5 Table of contents 1 Introduction General information Selection tables 400 V AC starter + contactor starter + contactor + thermal overload relay 3RU Circuit breaker + contactor + 3RB3 solid-state overload relay starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF starter + solid-state contactor starter + solid-state reversing contactor starter + star (wye)-delta starting + 3RU21 thermal overload relay starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF starter + 3RW30 soft starter starter + 3RW40 soft starter starter + 3RW44 soft starter Selection tables 500 V AC starter + contactor starter + contactor + thermal overload relay starter + contactor + 3RB3 solid-state overload relay starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, or 3UF starter + contactor assembly for star-delta (wye-delta) start + 3RU21 thermal overload relay starter + contactor assembly for star-delta (wye-delta) start + 3RB2. electronic overload relay, or 3UF7, 3RB starter + 3RW40 soft starter starter + 3RW44 soft starter Selection tables up to 690 V starter + contactor starter + contactor + thermal overload relay Configuration Manual, 01/2016, A8E A/RS-AA/005 5

6 Table of contents 6 Fused selection tables up to 690 V Short-circuit protection contactor type of coordination 1 and Short-circuit protection 3RU2 thermal overload relay, type of coordination 1 and Short-circuit protection: Contactor + 3RU2 thermal overload relay, type of coordination 1 and Short-circuit protection: Contactor + 3RB3 solid-state overload relay Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF Short-circuit protection: Contactor + 3RR2 monitoring relay, type of coordination 1 and Short-circuit protection: Star-delta (wye-delta) contactor Short-circuit protection: Soft starter + 3RU2 thermal overload relay Short-circuit protection: Solid-state contactor, type of coordination 1 and Short-circuit protection: feeders with 3RW3 + 3RT + 3RB30/3RB Contactor assemblies for star-delta (wye-delta) start + 3RB30/31 solid-state overload relay and 3RT20 contactor Contactor assemblies for star-delta + electronic overload relay 3RB2. or 3UF7 and contactor 3RT Installation guidelines Mounting variants under different conditions of use Minimum clearances to grounded or live parts (400 V / 500 V / 690 V AC) Service and support Siemens Industry Online Support SIRIUS Innovations system configurator Index Configuration Manual, 01/2016, A8E A/RS-AA/005

7 Introduction 1 SIRIUS the modular system family for switching, protecting and starting motors The innovations in the SIRIUS modular system family represent a totally new switchgear generation up to 37 kw. They are based on the existing SIRIUS modular system family, which has been systematically optimized and extended with many new functions. The individual switching devices, each of which is available with screw or spring-loaded terminals, can be easily assembled to form complete load feeders, either using link modules or by mounting directly. Size Main circuit Function Components S00 S0 S2 Switching and Contactors starting Semiconductor switching devices --- Soft starters Protecting starter s relays Monitoring Current monitoring relays Configuration Manual, 01/2016, A8E A/RS-AA/005 7

8 Introduction Size Function Components S00 S0 S2 Feeders Feeders Compact starters --- Control circuit Function modules for mounting on contactors Function modules for connection to the automation level 8 Configuration Manual, 01/2016, A8E A/RS-AA/005

9 Introduction Highlights Load feeders: Completely new series up to 37 kw / 400 V Comprehensive variety of starter technologies: electromechanical, semiconductors, soft starters Short-circuit breaking capacity up to 150 ka Modular design: Coordiated components ensure combinability Variants and sizes: Economical and flexible with 3 sizes and a broader performance range Accessories: Optimum variance with uniform accessories Type of construction: Space-saving design with small device width and butt-mounting type of construction up to 60 C Setup: Fast startup, short setting-up times, and simple wiring Communication: Optional connection to AS-Interface or IO-Link with function modules Maintenance: Extremely durable, low maintenance, and reliable Approvals: Global approvals and certifications, such as UL, CSA, CCC, shipbuilding... Mounting: Permanently secure mounting, screw or snap fitting Spring-loaded connection technology: Quick and secure connection, vibration-proof, and maintenance-free Environment: Environment friendly production and materials, recycling capability, low power loss Design: Clear-cut, ergonomic design (winner of the if Product Design Award) Configuration Manual, 01/2016, A8E A/RS-AA/005 9

10 Introduction 10 Configuration Manual, 01/2016, A8E A/RS-AA/005

11 General information 2 General criteria for the selection of devices The motor starter s, contactors, solid-state switching devices, soft starters and overload relays in the following tables are all specified in their basic versions with screw terminals, i.e. (in particular) without accessories. Where available, of course, versions with spring-loaded terminals or ring cable lug connections as well as accessories such as auxiliary switches, auxiliary trip units etc. can be used. The contactors listed have a rated control supply voltage Us of 230 V AC, 50 Hz. Versions with other voltages can also be used. The 3RU21 thermal overload relay and the 3RB30 / 3RB31 electronic overload relays can be directly mounted onto the contactor. The 3RB22 / 3RB23 / 3RB24 electronic overload relay and the SIMOCODE pro 3UF7 motor protection and control device are essentially used for stand-alone installation. In their basic version, these devices are specified with a rated control supply voltage of 230 V AC. Mounting the combinations When mounting the devices, specific arcing spaces must be maintained so that short-circuits can be cleared safely and reliably. The appropriate installation guidelines can be found in Section Installation guidelines (Page 139). The technical data of the individual devices must be taken into account when selecting a device. 400 V / 500 V / 690 V AC The tables below are primarily structured for the 400 V and 500 V line voltages for grounded networks (at 50 and 60 Hz) generally found in IEC regions. Tests are carried out with a test voltage which lies 10% above these values (further details can be found in the test reports). Thus, the specified combinations can also be used for other networks as long as their maximum voltage does not exceed the test voltage. This means, for instance, the combinations for 400 V can also be used for 415 V networks that have a line supply tolerance of +5%. Ambient conditions A maximum ambient temperature of 60 C applies to all electromechanical controlgear, and 40 C to soft starters and solid-state contactors. Higher temperatures are possible with derating. For details, refer to the System Manual or contact Technical Assistance. A maximum installation height of 2000 m applies to electromechanical controlgear, and 1000 m to soft starters and solid-state contactors. Higher installation altitudes are also possible with derating. For details refer to the appropriate manuals. Configuration Manual, 01/2016, A8E A/RS-AA/005 11

12 General information Trip classes CLASS 5, CLASS 10, CLASS 20, CLASS 30 and CLASS 40 Trip classes, according to IEC , define the time intervals within which the protection equipment (overload release of a motor starter or overload relay) must trip from the cold state, for a symmetrical, three-phase load with a 7.2-fold set current Ie. The tripping times are as follows: CLASS 5 and CLASS 10 between 2 s and 10 s, CLASS 20 between 4 s and 20 s, CLASS 30 between 9 s and 30 s, CLASS 40 between 30 s and 40 s. In practice, devices with trip CLASS 5 and CLASS 10 are generally used. These devices are designed for standard applications. CLASS 5 and CLASS 10 are often referred to as normal starting. Combinations for CLASS 20, CLASS 30 and CLASS 40 are available for applications where a higher starting current is required for a prolonged period. In this case, using standard devices of CLASS 5 and CLASS 10 would result in unwanted tripping. CLASS 20, CLASS 30 and CLASS 40 are also known as heavy starting devices. Large fan motors are an example of this type of application. As well as the overload protection devices, the contactors and short-circuit protection devices must also be designed for these long starting times. This is why combinations acc. to CLASS 5 and CLASS 10 are generally more cost-effective. CLASS 20, CLASS 30 and CLASS 40 are only generally used if genuinely necessitated by the application. 12 Configuration Manual, 01/2016, A8E A/RS-AA/005

13 General information Type of coordination 1 or 2 When selecting the combinations, in many cases, either coordination type 1 or 2 can be selected. According to IEC , the coordination type defines the permissible degree of damage for a device following a short-circuit. Type of coordination 1: After a short-circuit, it is permissible for the starter to be inoperative, in particular, damage to the contactor, solid-state switching devices and overload relay is permissible. Type of coordination 2: The starter is still operative. There must be no signs of damage to the devices, with the exception of slightly welded contactor contacts if these can be easily separated again without any noticeable deformation. In both cases, the short-circuit is reliably and safely cleared. Combinations of coordination type 2 are therefore of a higher quality and are rapidly available for reuse after a short-circuit. In the case of solid-state switching devices, the same applies as for type of coordination 2, that the short-circuit is cleared without any damage to the power semiconductors. Combinations of coordination type 1 are generally the more favorably priced solution. Combinations of coordination type 2 automatically fulfill the requirements of coordination type 1. Tests All of the specified combinations are tested in compliance with IEC Configuration Manual, 01/2016, A8E A/RS-AA/005 13

14 General information With or without overload relay In addition to the combinations comprising a motor starter (for motor protection) and contactor, combinations are also available with motor starter (for starter protection), contactor and overload relay. In the first case, the motor starter assumes the dual function of overload protection and short-circuit protection, while in the second case, the motor starter assumes only the short-circuit protection function and the overload relay the overload protection function. The tripping behavior of both solutions under overload and short-circuit conditions is technically comparable. For fuseless load feeders with electronic overload relays, and for higher trip classes, CLASS 20, CLASS 30 and CLASS 40 in particular, a motor starter is often used instead of an MSP for starter combinations. This is due to the following: from the point of view of thermal destruction limits, MSPs for starter combinations are generally designed for CLASS 10 motor starts. The current measurement of electronic overload relays usually moves into saturation upwards of a 10-fold rated current, so that the intrinsic protection of the motor starter is no longer guaranteed for higher trip classes. In order to ensure thermal intrinsic protection, it is advisable to use a motor starter /circuit breaker that protects itself over the overload release. The motor starter /circuit breaker is selected so that the point at which the characteristic curve of the overload relay intersects with the a-tripping characteristic of the motor starter /circuit breaker is more than 10 x the set current. This ensures that, in the case of motor faults, such as overload or blocking, the overload relay always trips and not the motor starter. In this situation, combinations with motor starter and contactor offer the most costeffective solution. However, combinations with overload relays offer distinct advantages for certain applications: 3RB30 / 3RB31 and 3RB22 / 3RB23 / 3RB24 electronic overload relays or SIMOCODE pro 3UF7 can be used to achieve not only trip CLASS 5 and CLASS 10 but also solutions for heavy starting, such as CLASS 20, CLASS 30, and CLASS 40. Using electronic overload relays offers a wide setting range of 1:4 or 1:10. This offers advantages during configuration (e.g. if the exact motor current is not known) and enables us to reduce the number of variants required. and short-circuit protection are carried out separately and can also be signaled separately. Alternatively, the 3RV2921-1M signaling block can be used for the 3RV motor starter instead of the overload relay. This also supports the separate signaling of overloads and short-circuits. Setting of the overload relay to "Automatic Reset" can also save a walk to the control cabinet in the case of overload tripping, as a manual reset in the control cabinet is not required. Alternatively, this function can also be implemented with the "3RV21 motor starter with overload relay function". These devices can be used in the motor starter + contactor tables instead of the 3RV20 motor starter. 14 Configuration Manual, 01/2016, A8E A/RS-AA/005

15 General information Star(wye)(Y)-delta function(δ) starting In order to keep the current peaks in the line supply as low as possible, contactor assembly are frequently used as star(wye)-delta starters to start three-phase motors. However, to make worthwhile use of YΔ starting, a low load torque is required during starting. Only then can the motor approximately reach its rated speed in the Y stage before switching to Δ operation. An overload relay should be used for motor overload protection. Normally, this is located directly in the motor feeder cable U1, V1, W1, as shown in the circuit diagram. Using this arrangement, the overload protection is effective in both the Y and Δ circuit. The overload relay should be set for 58% of the rated motor current. The control current wiring and switching from Y to Δ are implemented with plug-on function modules for the SIRIUS innovations. The switching time can be set between 1 and 100 s. The function modules thus perform the function of the timing relay. In the tables, circuit breakers are used for starter combinations (without overload releases). However, 3RV20 motor starter s for motor protection with the same rated current can also be used instead. In this case, the rated motor current of the motor starter must be set to the maximum value. This prevents a simultaneous tripping of the motor starter and overload relay. Configuration Manual, 01/2016, A8E A/RS-AA/005 15

16 General information Soft starting with soft starters What is the basic principle of a soft starter? Soft starters limit the starting current and starting torque. This reliably prevents mechanical stress and mains voltage dips. The motor voltage is reduced using phase control and is increased from an adjustable starting voltage up to the mains voltage within a specific ramp time. Soft starting and stopping reduces the stress on connected equipment, thus ensuring prolonged smooth and trouble-free production. 3RW30 soft starters for the soft starting of three-phase asynchronous motors for simple applications performance range: up to 55 kw at 400 V (75 hp at 460 V) 3RW40 soft starters with integrated functions; electronic motor overload and intrinsic device protection and adjustable current limiting performance range: up to 250 kw at 400 V (300 hp at 460 V) The 3RW44 solid-state soft starters offer the following: soft starting and stopping electronic motor overload and intrinsic device protection adjustable current limiting numerous functions for higher-level requirements performance range: up to 710 kw at 400 V in standard circuit up to 1200 kw at 400 V (1700 hp at 460 V) in the inside-delta circuit More information can be found on the Internet ( 16 Configuration Manual, 01/2016, A8E A/RS-AA/005

17 General information For the correct dimensioning of soft starters for motors with high starting current ratios (I/Ie >= 8), we recommend our Simulation Tool for Soft Starters (STS) : Download ( Readme ( Load feeders with soft starters Soft starters can also be used to prevent current peaks in the line supply instead of the star(wye)-delta starting combinations. Three versions of these soft starters are available: 3RW30 3RW40 3RW44 The 3RW4 soft starters come as standard with an integrated solid-state overload relay. This means that, in fuseless combinations, a motor starter is only required for shortcircuit protection. In the case of 3RW30 soft starters, the motor starter must also cover the overload protection. Configuration Manual, 01/2016, A8E A/RS-AA/005 17

18 General information 3RB22 / 23 / 24 overload relays and SIMOCODE pro The modular, electronic overload relays with external power supply type 3RB22 / 23/ 24 for high-feature applications up to 630 A have been designed for inverse-time delayed protection of loads with normal and heavy starting against excessive temperature rises due to overload, phase unbalance or phase failure. SIMOCODE pro is a flexible, modular motor management system for motors with constant speeds in the low-voltage performance range. It provides the intelligent, communicationcapable interface between the higher-level automation system and the motor feeder. A configuration with 3RB22 / 23 / 24 overload relays and with SIMOCODE pro requires in each case a basic unit, a connection cable, and a current measuring module. The article numbers of the current measuring modules are listed in the tables. Details of the basic units and connection cables are given in the following: 3RB22 / 23 / 24 Basic unit (= evaluation module) Monostable, screw: 3RB2283-4AA1 Bistable, screw: 3RB2383-4AA1 Monostable, spring-loaded: 3RB2283-4AC1 Bistable, spring-loaded: 3RB2383-4AC1 Monostable, screw: 3RB2483-4AA1 Monostable, spring-loaded: 3RB2483-4AC1 Connection cable 0.1 m (S00-S3): 3RB2987-2B 0.5 m (S00-S12): 3RB2987-2D For other accessories for 3RB22 / 23 / 24 overload relays see Catalog IC 10 Chapter Configuration Manual, 01/2016, A8E A/RS-AA/005

19 General information SIMOCODE pro SIMOCODE pro C, Basic Unit 1 PROFIBUS DP interface, 12 Mbit/s, RS485 4I / 3O freely assignable, input for thermistor connection, monostable relay outputs 24 V DC: 3UF7000-1AB V AC / DC: 3UF7000-1AU00-0 SIMOCODE pro V, Basic Unit 2 PROFIBUS DP interface, 12 Mbit/s, RS485 4I / 3O freely assignable, input for thermistor connection, monostable relay outputs, can be expanded by expansion modules 24 V DC: 3UF7010-1AB V AC / DC: 3UF7010-1AU00-0 SIMOCODE pro C PROFIBUS DP interface, 12 Mbps, RS485 4I / 3O freely assignable, input for thermistor connection, monostable relay outputs 24 V DC: 3UF7000-1AB V AC/DC: 3UF7000-1AU00-0 SIMOCODE pro S PROFIBUS DP interface, 15 Mbps, RS485 4I / 2O freely assignable, input for thermistor connection, monostable relay outputs, can be expanded by multifunction module 24 V DC: 3UF7020-1AB V AC/DC: 3UF7020-1AU01-0 SIMOCODE pro V PROFIBUS DP interface, 12 Mbps, RS485 4I / 3O freely assignable, input for thermistor connection, monostable relay outputs, can be expanded by expansion modules 24 V DC: 3UF7010-1AB V AC/DC: 3UF7010-1AU00-0 Configuration Manual, 01/2016, A8E A/RS-AA/005 19

20 General information SIMOCODE pro V PROFINET ETHERNET/PROFINET IO, OPC UA server and web server, 100 Mbps, 2 x connection to bus through RJ45, PROFINET system redundancy, media redundancy protocol, 4 I/3 O freely assignable, input for thermistor connection, monostable relay outputs, can be expanded by expansion modules, web server in German/English/Chinese/Russian 24 V DC: UF7011-1AB V AC/DC: 3UF7011-1AU00-0 SIMOCODE pro V Modbus RTU Modbus RTU interface, 57.6 Mbps, RS485 4I / 3O freely assignable, input for thermistor connection, monostable relay outputs, can be expanded by expansion modules 24 V DC: 3UF7012-1AB V AC/DC: 3UF7012-1AU00-0 Connection cable 0.1 m, flat: 3UF7931-0AA m, flat: 3UF7935-0AA m, flat: 3UF7932-0AA m, round: 3UF7932-0BA m, round: 3UF7937-0BA m, round: 3UF7933-0BA00-0 For other accessories and software for SIMOCODE pro see Catalog IC 10 Chapter 10. Note The coordination tests with SIMOCODE pro current measuring modules 3UF710 apply to the same extent for current measuring modules / voltage measuring modules 3UF711.. of the same rated current range. 20 Configuration Manual, 01/2016, A8E A/RS-AA/005

21 General information Link modules Table 2-1 Connection system Screw-type connection system Link module versions Link module version starter contactor in size S00 Article number 3RA1921-1D starter contactor in size S0 AC 3RA2921-1A starter contactor in size S0 DC starter soft starter in size S00 starter soft starter in size S0 starter solid-state contactor 3RA2921-1B starter contactor in size S2 starter soft starter in size S2 3RA2931-1A Configuration Manual, 01/2016, A8E A/RS-AA/005 21

22 General information Connection system Springloaded connection system Link module version starter contactor in size S00 Article number 3RA2911-2A starter contactor in size S0 3RA2921-2A starter soft starter in size S00 3RA2911-2G starter soft starter in size S0 3RA2921-2G 22 Configuration Manual, 01/2016, A8E A/RS-AA/005

23 General information Connection system Hybrid connection system 1) Link module version starter contactor in size S00 Article number 3RA2911-2F starter contactor in size S0 3RA2921-2F 1) The motor starter has a screw connection and the contactor has a spring-loaded connection. Configuration Manual, 01/2016, A8E A/RS-AA/005 23

24 General information 24 Configuration Manual, 01/2016, A8E A/RS-AA/005

25 Selection tables 400 V AC starter + contactor CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 150 ka three-phase motor 4-pole at 400 V AC 1) output P current I starter protection Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors Contactor 2) Size kw A A A Article No. Article No RV2011-0AA10 S00/S RV2011-0BA10 S00/S RV2011-0CA10 S00/S RV2011-0DA10 S00/S RV2011-0EA10 S00/S RV2011-0FA10 S00/S RV2011-0GA10 S00/S RV2011-0HA10 S00/S RV2011-0JA10 S00/S RV2011-0KA10 S00/S RV2011-1AA10 S00/S RV2011-1BA10 S00/S RV2011-1CA10 S00/S RV2011-1DA10 S00/S RV2011-1EA10 S00/S RV2011-1FA10 S00/S RV2011-1GA10 S00/S RV2011-1HA10 S00/S RV2011-1JA10 3RT2016- S00/S RV2011-1KA10 3RT2017- S00/S RV2011-4AA10 3RT2018- S00/S00 Configuration Manual, 01/2016, A8E A/RS-AA/005 25

26 Selection tables 400 V AC 3.1 starter + contactor three-phase motor 4-pole at 400 V AC 1) output P current I starter protection Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors Contactor 2) kw A A A Article No. Article No RV2021-4BA10 3RT2025- S0/S RV2021-4CA10 3RT2026- S0/S RV2021-4CDA10 3RT2026- Size S0/S RV2021-4NA10 3RT2027- S0/S (up to 256 A starting current) 3RV2021-4EA10 3RT2027- S0/S ) Use size S2 3RV2021-4PA10 3RT2028- S0/S ) Use size S2 3RV2021-4FA10 3RT2028- S0/S RV2032-4PA10 3RT2035- S2/S RV2032-4UA10 3RT2035- S2/S RV2032-4VA10 3RT2036- S2/S RV2032-4WA10 3RT2036- S2/S RV2032-4XA10 3RT2037- S2/S RV2032-4JA10 3RT2037- S2/S RV2032-4KA10 3RT2038- S2/S (up to 720 A starting current) 3RA2032-4RA10 3RT2038- S2/S2 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Discrete mounting only without a link module, short-circuit breaking capacity Iq = 55 ka 26 Configuration Manual, 01/2016, A8E A/RS-AA/005

27 Selection tables 400 V AC 3.1 starter + contactor CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 150 ka three-phase motor 4-pole at 400 V AC 1) output P current (guide value) I starter protection Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors Contactor 2) Size kw A A A Article No. Article No RV2011-0AA10 S00/S RV2011-0BA10 S00/S RV2011-0CA10 S00/S RV2011-0DA10 S00/S RV2011-0EA10 S00/S RV2011-0FA10 S00/S RV2011-0GA10 S00/S RV2011-0HA10 S00/S RV2011-0JA10 S00/S RV2011-0KA10 S00/S RV2011-1AA10 S00/S RV2011-1BA10 S00/S RV2011-1CA10 S00/S RV2011-1DA10 S00/S RV2011-1EA10 S00/S RV2011-1FA10 3RT2024- S00/S RV2011-1GA10 3RT2024- S00/S RV2011-1HA10 3RT2024- S00/S RV2011-1JA10 3RT2024- S00/S RV2011-1KA10 3RT2024- S00/S RV2011-4AA10 3RT2026- S00/S RV2021-4BA10 3RT2027- S0/S RV2021-4CA10 3RT2027- S0/S RV2021-4DA10 3RT2027- S0/S RV2021-4NA10 3RT2027- S0/S (up to 256 A starting current) 3RV2021-4EA10 3RT2027- S0/S0 Configuration Manual, 01/2016, A8E A/RS-AA/005 27

28 Selection tables 400 V AC 3.1 starter + contactor three-phase motor 4-pole at 400 V AC 1) output P current (guide value) I starter protection Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors Contactor 2) kw A A A Article No. Article No RV2032-4EA10 3RT2035- S2/S RV2032-4PA10 3RT2035- S2/S RV2032-4UA10 3RT2035- S2/S RV2032-4VA10 3RT2036- S2/S RV2032-4WA10 3RT2036- S2/S RV2032-4XA10 3RT2037- S2/S RV2032-4JA10 3RT2037- S2/S RV2032-4KA10 3RT2038- S2/S (up to 720 A starting current) Size 3RV2032-4RA10 3RT2038- S2/S2 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 28 Configuration Manual, 01/2016, A8E A/RS-AA/005

29 Selection tables 400 V AC 3.2 starter + contactor + thermal overload relay 3RU starter + contactor + thermal overload relay 3RU21 CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 150 ka threephase motor 4- pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size relay (thermal) 3) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A Article No. Article No. Size Article No. A A RV2311-0BC RV2311-0CC RV2311-0DC RV2311-0EC RV2311-0FC RV2311-0GC RV2311-0HC RV2311-0JC RV2311-0KC RV2311-1AC RV2311-1BC RV2311-1CC RV2311-1DC RV2311-1EC10 S00/S00/S00 3RU2116-0BB S00/S00/S00 3RU2116-0CB S00/S00/S00 3RU2116-0DB S00/S00/S00 3RU2116-0EB S00/S00/S00 3RU2116-0FB S00/S00/S00 3RU2116-0GB S00/S00/S00 3RU2116-0HB S00/S00/S00 3RU2116-0JB S00/S00/S00 3RU2116-0KB S00/S00/S00 3RU2116-1AB S00/S00/S00 3RU2116-1BB S00/S00/S00 3RU2116-1CB S00/S00/S00 3RU2116-1DB S00/S00/S00 3RU2116-1EB Configuration Manual, 01/2016, A8E A/RS-AA/005 29

30 Selection tables 400 V AC 3.2 starter + contactor + thermal overload relay 3RU21 threephase motor 4- pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size relay (thermal) 3) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A Article No. Article No. Size Article No. A A RV2311-1FC10 S00/S00/S00 3RU2116-1FB RV2311-1GC10 S00/S00/S00 3RU2116-1GB RV2311-1HC10 S00/S00/S00 3RU2116-1HB RV2311-1JC10 3RT2016- S00/S00/S00 3RU2116-1JB RV2311-1KC10 3RT2017- S00/S00/S00 3RU2116-1KB RV2311-4AC10 3RT2018- S00/S00/S00 3RU2116-4AB RV2321-4AC10 3RT2025- S0/S0/S0 3RU2126-4AB RV2321-4BC10 3RT2025- S0/S0/S0 3RU2126-4BB RV2321-4CC10 3RT2026- S0/S0/S0 3RU2126-4CB RV2321-4DC10 3RT2026- S0/S0/S0 3RU2126-4DB RV2321-4NC10 3RT2027- S0/S0/S0 3RU2126-4NB RV2321-4EC10 3RT RV2332-4EC10 3RT RV2332-4PC10 3RT RV2332-4UC10 3RT RV2332-4VC10 3RT RV2332-4WC10 3RT RV2332-4XC10 3RT RV2332-4JC10 3RT2037- S0/S0/S0 3RU2126-4EB (up to 256 A starting current) S2/S2/S2 3RU2136-4EB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4GB S2/S2/S2 3RU2136-4HB S2/S2/S2 3RU2136-4QB S2/S2/S2 3RU2136-4JB Configuration Manual, 01/2016, A8E A/RS-AA/005

31 Selection tables 400 V AC 3.2 starter + contactor + thermal overload relay 3RU21 threephase motor 4- pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size relay (thermal) 3) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A Article No. Article No. Size Article No. A A RV2332-4KC10 3RT2038- S2/S2/S2 3RU2136-4KB RV2332-4RC10 3RT2038- S2/S2/S2 3RU2136-4RB (up to 720 A) (up to 720 A starting current) Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Assembled combinations of three are not permitted. Configuration Manual, 01/2016, A8E A/RS-AA/005 31

32 Selection tables 400 V AC 3.2 starter + contactor + thermal overload relay 3RU21 CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 150 ka threephase motor 4-pole at 400 V AC 1) starter Starter protection Contactor 2) Size relay (thermal) 3) Maximum permitted setting range overload release output P current I IE1 / IE2 motors IE3 / IE4 motors kw A Article No. Article No. Article No. A A RV2311-0BC10 S00/S00/S00 3RU2116-0BB RV2311-0CC10 S00/S00/S00 3RU2116-0CB RV2311-0DC10 S00/S00/S00 3RU2116-0DB RV2311-0EC10 S00/S00/S00 3RU2116-0EB RV2311-0FC10 S00/S00/S00 3RU2116-0FB RV2311-0GC10 S00/S00/S00 3RU2116-0GB RV2311-0HC10 S00/S00/S00 3RU2116-0HB RV2311-0JC10 S00/S00/S00 3RU2116-0JB RV2311-0KC10 S00/S00/S00 3RU2116-0KB RV2311-1AC10 S00/S00/S00 3RU2116-1AB RV2311-1BC10 S00/S00/S00 3RU2116-1BB RV2311-1CC10 S00/S00/S00 3RU2116-1CB RV2311-1DC10 S00/S00/S00 3RU2116-1DB RV2311-1EC10 S00/S00/S00 3RU2116-1EB RV2311-1FC10 3RT2024- S00/S0/S00 3RU2116-1FB Configuration Manual, 01/2016, A8E A/RS-AA/005

33 Selection tables 400 V AC 3.2 starter + contactor + thermal overload relay 3RU21 threephase motor 4-pole at 400 V AC 1) starter Starter protection Contactor 2) Size relay (thermal) 3) Maximum permitted setting range overload release output P current I IE1 / IE2 motors IE3 / IE4 motors kw A Article No. Article No. Article No. A A RV2311-1GC10 3RT RV2311-1HC10 3RT RV2311-1JC10 3RT RV2311-1KC10 3RT RV2311-4AC10 3RT RV2321-4BC10 3RT RV2321-4CC10 3RT RV2321-4DC10 3RT RV2321-4NC10 3RT RV2321-4EC10 3RT RV2332-4EC10 3RT RV2332-4PC10 3RT RV2332-4UC10 3RT RV2332-4VC10 3RT RV2332-4WC10 3RT RV2332-4XC10 3RT RV2332-4JC10 3RT2037- S00/S0/S0 3RU2126-1GB0 4) S00/S0/S0 3RU2126-1HB0 4) S00/S0/S0 3RU2126-1JB0 4) S00/S0/S0 3RU2126-1KB0 4) S00/S0/S0 3RU2126-4AB0 4) S0/S0/S0 3RU2126-4BB S0/S0/S0 3RU2126-4CB S0/S0/S0 3RU2126-4DB S0/S0/S0 3RU2126-4NB S0/S0/S0 3RU2126-4EB (up to 256 A starting current) S2/S2/S2 3RU2136-4EB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4GB S2/S2/S2 3RU2136-4HB S2/S2/S2 3RU2136-4QB S2/S2/S2 3RU2136-4JB Configuration Manual, 01/2016, A8E A/RS-AA/005 33

34 Selection tables 400 V AC 3.2 starter + contactor + thermal overload relay 3RU21 threephase motor 4-pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size relay (thermal) 3) Maximum permitted setting range overload release IE1 / IE2 motors kw A Article No. Article No. Article No. A A RV2332-4KC10 3RT RV2332-4RC10 3RT2038- IE3 / IE4 motors S2/S2/S2 3RU2136-4KB S2/S2/S2 3RU2136-4RB (up to 720 A) (up to 720 A starting current) Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Assembled combinations of three are not permitted. 4) Can also be used in size S00 (3RU2116). 34 Configuration Manual, 01/2016, A8E A/RS-AA/005

35 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay Type of coordination 1, short-circuit breaking capacity I q = 150 ka/100 ka threephase motor 4-pole at 400 V AC 1) Circuit breaker Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release IE1 / IE2 motors IE3 / IE4 motors starter kw A A Article No. Article No. Article No. A A CLASS 10, short-circuit breaking capacity Iq = 150 ka None 3RV2311-0CC None 3RV2311-0DC None 3RV2311-0HC None 3RV2311-0JC None 3RV2311-0KC None 3RV2311-1AC None 3RV2311-1BC None 3RV2311-1BC None 3RV2311-1DC None 3RV2311-1EC None 3RV2311-1GC10 S00/S00/S00 3RB3016-1RB0 S00/S00/S00 3RB3016-1RB0 S00/S00/S00 3RB3016-1NB0 S00/S00/S00 3RB3016-1NB0 S00/S00/S00 3RB3016-1NB0 S00/S00/S00 3RB3016-1PB0 S00/S00/S00 3RB3016-1PB0 S00/S00/S00 3RB3016-1PB0 S00/S00/S00 3RB3016-1PB0 S00/S00/S00 3RB3016-1SB0 S00/S00/S00 3RB3016-1SB Configuration Manual, 01/2016, A8E A/RS-AA/005 35

36 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) power P current I Circuit breaker Starter protection 3) Setting range release starter Contactor 2) Size relay (electronic) Maximum permitted setting range overload release IE1 / IE2 motors kw A A Article No. Article No. Article No. A A None 3RV2311-1HC None 3RV2311-1JC None 3RV2311-4AC None 3RV2321-4BC None 3RV2321-4EC None 3RV2332-4EC None 3RV2332-4VC RV2032-4KA RV2032-4RA10 CLASS 10, short-circuit breaking capacity Iq = 100 ka None 3RV2331-4EC None 3RV2331-4VC RV2031-4VB RV2031-4WB RV2031-4JB10 S00/S00/S00 3RB3016-1SB0 3RT2016- S00/S00/S00 3RB3016-1TB0 3RT2024- S00/S0/S0 3RB3026-1QB0 3RT2025- S0/S0/S0 3RB3026-1QB0 3RT2027- S0/S0/S0 3RB3026-1VB0 3RT2035- S2/S2/S2 3RB3036-1UB0 3RT2036- S2/S2/S2 3RB3036-1UB0 3RT2038- S2/S2/S2 3RB3036-1UB0 3RT3038- S2/S2/S2 3RB3036-1UB0 3RT2035- S2/S2/S2 3RB3036-1UB0 3RT2036- S2/S2/S2 3RB3036-1UB0 3RT2036- S2/S2/S2 3RB3036-1UB0 3RT2036- S2/S2/S2 3RB3036-1WB0 3RT2037- S2/S2/S2 3RB3036-1WB0 IE3 / IE4 motors (up to 256 A starting current) Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 36 Configuration Manual, 01/2016, A8E A/RS-AA/005

37 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay Type of coordination 2, short-circuit breaking capacity I q = 150 ka/100 ka threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 5, short-circuit breaking capacity Iq = 150 ka None 3RV2311-0CC None 3RV2311-0DC None 3RV2311-0FC None 3RV2311-0HC None 3RV2311-0JC None 3RV2311-0KC None 3RV2311-1AC None 3RV2311-1BC None 3RV2311-1DC None 3RV2311-1EC None 3RV2321-1GC None 3RV2321-1HC None 3RV2321-1JC None 3RV2321-1KC10 3RT2024-3RT2024-3RT2024-3RT2024- S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 3RB3113-4RB0 3RB3113-4RB0 3RB3113-4NB0 3RB3113-4NB0 3RB3113-4NB0 3RB3113-4PB0 3RB3113-4PB0 3RB3113-4PB0 3RB3113-4PB0 3RB3113-4SB0 3RB3123-4SB0 3RB3123-4SB0 3RB3123-4QB0 3RB3123-4QB Configuration Manual, 01/2016, A8E A/RS-AA/005 37

38 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A None 3RV2321-4AC None 3RV2321-4CC None 3RV2321-4EC None 3RV2332-4EC None 3RV2332-4UC None 3RV2332-4VC RV2032-4KA10 CLASS 5, short-circuit breaking capacity Iq = 100 ka None 3RV2331-4EC None 3RV2331-4PC None 3RV2331-4JC RV2031-4JB10 3RT2026-3RT2027-3RT2027-3RT2035-3RT2035-3RT2036-3RT2038-3RT2035-3RT2035-3RT2037-3RT2037- S0/S0/S0 S0/S0/S0 S0/S0/S0 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 3RB3123-4QB0 3RB3123-4VB0 3RB3123-4VB0 3RB3133-4UB0 3RB3133-4UB0 3RB3133-4UB0 3RB3133-4WB0 3RB3133-4UB0 3RB3133-4UB0 3RB3133-4WB0 3RB3133-4WB (up to 256 A starting current) Configuration Manual, 01/2016, A8E A/RS-AA/005

39 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 10, short-circuit breaking capacity Iq = 150 ka None 3RV2311-0CC None 3RV2311-0DC None 3RV2311-0HC None 3RV2311-0JC None 3RV2311-0KC None 3RV2311-1AC None 3RV2311-1BC None 3RV2311-1BC None 3RV2311-1DC None 3RV2311-1EC None 3RV2321-1GC None 3RV2321-1HC None 3RV2321-1JC None 3RV2321-4AC None 3RV2321-4BC None 3RV2321-4EC None 3RV2332-4EC None 3RV2332-4VC10 3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2035-3RT2036- S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S2/S2/S2 S2/S2/S2 3RB3016-1RB0 3RB3016-1RB0 3RB3016-1NB0 3RB3016-1NB0 3RB3016-1NB0 3RB3016-1PB0 3RB3016-1PB0 3RB3016-1PB0 3RB3016-1PB0 3RB3016-1SB0 3RB3026-1SB0 3RB3026-1SB0 3RB3026-1QB0 3RB3026-1QB0 3RB3026-1QB0 3RB3026-1VB0 3RB3036-1UB0 3RB3036-1UB (up to 256 A starting current) Configuration Manual, 01/2016, A8E A/RS-AA/005 39

40 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A RV2032-4KA RV2032-4RA10 CLASS 10, short-circuit breaking capacity Iq = 100 ka None 3RV2331-4EC None 3RV2331-4VC RV2031-4VB RV2031-4WB RV2031-4JB10 3RT2038-3RT2038-3RT2035-3RT2036-3RT2036-3RT2036-3RT2037- S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 3RB3036-1UB0 3RB3036-1UB0 3RB3036-1UB0 3RB3036-1UB0 3RB3036-1UB0 3RB3036-1WB0 3RB3036-1WB Configuration Manual, 01/2016, A8E A/RS-AA/005

41 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 20, short-circuit breaking capacity Iq = 150 ka RV2011-0FA RV2011-0HA RV2011-0JA RV2011-1AA RV2011-1BA RV2011-1CA RV2011-1DA RV2021-1FA RV2021-1GA RV2021-1HA RV2021-1JA RV2021-4AA RV2021-4BA RV2021-4DA None 3RV2332-4XC RV2032-4XA RV2032-4RA10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2037-3RT2037-3RT2038- S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S2/S2/S2 S2/S2/S2 S2/S2/S2 3RB3016-2RB0 3RB3016-2RB0 3RB3016-2NB0 3RB3016-2NB0 3RB3016-2NB0 3RB3016-2PB0 3RB3016-2PB0 3RB3026-2PB0 3RB3026-2PB0 3RB3026-2PB0 3RB3026-2SB0 3RB3026-2QB0 3RB3026-2QB0 3RB3026-2QB0 3RB3036-2UB0 3RB3036-2UB0 3RB3036-2UB Configuration Manual, 01/2016, A8E A/RS-AA/005 41

42 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 20, short-circuit breaking capacity Iq = 100 ka RV2031-4PB RV2031-4PB RV2031-4UB RV2031-4WB RV2031-4XB10 3RT2035-3RT2035-3RT2035-3RT2036-3RT3037- S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 S2/S2/S2 3RB3036-2UB0 3RB3036-2UB0 3RB3036-2UB0 3RB3036-2UB0 3RB3036-2UB Configuration Manual, 01/2016, A8E A/RS-AA/005

43 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) starter Starter protection 3) Contactor 2) Size relay (electronic) Maximum permitted setting range overload release power P current I Setting range release starter IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 30, short-circuit breaking capacity Iq = 150 ka RV2011-0HA RV2011-0JA RV2011-1AA RV2011-1BA RV2011-1CA RV2011-1DA RV2021-1FA RV2021-1GA RV2021-1HA RV2021-1JA RV2021-4AA RV2021-4BA RV2021-4DA RV2021-4EA RV2032-4KA RV2032-4KA10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2027-3RT2038-3RT2038- S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S0/S0/S0 S2/S2/S2 S2/S2/S2 3RB3113-4RB0 3RB3113-4RB0 3RB3113-4NB0 3RB3113-4NB0 3RB3113-4NB0 3RB3113-4PB0 3RB3123-4PB0 3RB3123-4PB0 3RB3123-4PB0 3RB3123-4SB0 3RB3123-4SB0 3RB3123-4QB0 3RB3123-4QB0 3RB3123-4QB0 3RB3133-4UB0 3RB3133-4UB (up to 256 A starting current) Configuration Manual, 01/2016, A8E A/RS-AA/005 43

44 Selection tables 400 V AC 3.3 Circuit breaker + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) power P current I starter Starter protection 3) Setting range release starter Contactor 2) Size relay (electronic) Maximum permitted setting range overload release IE1 / IE2 motors kw A A Article No. Article No. Article No. A A CLASS 30, short-circuit breaking capacity Iq = 100 ka RV2031-4EB10 3RV2031-4VB10 3RV2031-4XB10 3RT2035-3RT2036-3RT2037- S2/S2/S2 S2/S2/S2 S2/S2/S2 3RB3133-4UB0 3RB3133-4UB0 3RB3133-4WB0 IE3 / IE4 motors Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 44 Configuration Manual, 01/2016, A8E A/RS-AA/005

45 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 Type of coordination 1, short-circuit breaking capacity I q = 150 ka threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS None 3RV2311-0DC None 3RV2311-0FC None 3RV2311-0HC None 3RV2311-0JC None 3RV2311-0KC None 3RV2311-1AC None 3RV2311-1BC None 3RV2311-1DC None 3RV2311-1EC None 3RV2311-1GC None 3RV2311-1HC None 3RV2311-1JC10 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x0-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF71x1-1AA00-0/ S00/S00 3UF71x1-1AA00-0/ S00/S00 3UF71x1-1AA00-0/ S00/S00 3UF71x1-1AA00-0/ 3RT2016- S00/S00 3UF71x1-1AA00-0/ Configuration Manual, 01/2016, A8E A/RS-AA/005 45

46 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors kw A A Article No. Article No. Article No. A A None 3RV2321-4AC None 3RV2321-4CC None 3RV2321-4EC None 3RV2332-4EC None 3RV2332-4VC RV2032-4XA RV2032-4RA10 3RT2024- S0/S0 3RT2026- S0/S0 3RT2027- S0/S0 3RT2035- S2/S2 3RT2036- S2/S2 3RT2037- S2/S2 3RT2038- S2/S2 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 IE3 / IE4 motors (up to 256 A starting current) Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 4) The necessary current measuring modules (x = 0) or the current measuring modules / voltage measuring modules (x = 1) are specified. The corresponding basic units 3RB22 / 3RB23 / 3RB24 and 3UF7 are additionally required. 46 Configuration Manual, 01/2016, A8E A/RS-AA/005

47 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 Type of coordination 2, short-circuit breaking capacity I q = 150 ka/100 ka threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 5, short-circuit breaking capacity Iq = 150 ka None 3RV2311-0DC None 3RV2311-0FC None 3RV2311-0HC None 3RV2311-0JC None 3RV2311-0KC None 3RV2311-1AC None 3RV2311-1BC None 3RV2311-1DC None 3RV2311-1EC None 3RV2321-1GC None 3RV2321-1HC None 3RV2321-1JC None 3RV2321-1KC None 3RV2321-4AC10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2026- S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ Configuration Manual, 01/2016, A8E A/RS-AA/005 47

48 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A None 3RV2321-4CC None 3RV2321-4EC None 3RV2332-4EC None 3RV2332-4UC None 3RV2332-4VC RV2032-4KA10 CLASS 5, short-circuit breaking capacity Iq = 100 ka None 3RV2331-4EC None 3RV2331-4UC None 3RV2331-4WC RV2031-4JB10 3RT2027-3RT2027-3RT2035-3RT2035-3RT2036-3RT2038-3RT2035-3RT2035-3RT2036-3RT2037- S0/S0 S0/S0 S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG (up to 256 A starting current) Configuration Manual, 01/2016, A8E A/RS-AA/005

49 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 10, short-circuit breaking capacity Iq = 150 ka None 3RV2311-0DC None 3RV2311-0FC None 3RV2311-0HC None 3RV2311-0JC None 3RV2311-0KC None 3RV2311-1AC None 3RV2311-1BC None 3RV2311-1DC None 3RV2311-1EC None 3RV2321-1GC None 3RV2321-1HC None 3RV2321-1JC None 3RV2321-4AC None 3RV2321-4CC None 3RV2321-4EC None 3RV2332-4EC None 3RV2332-4VC RV2032-4XA10 3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2035-3RT2036-3RT2037- S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S2/S2 S2/S2 S2/S2 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG (up to 256 A starting current) Configuration Manual, 01/2016, A8E A/RS-AA/005 49

50 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A RV2032-4RA10 CLASS 10, short-circuit breaking capacity Iq = 100 ka None 3RV2331-4EC None 3RV2031-4VC RV2031-4UB RV2031-4WB10 3RT2038-3RT2035-3RT2036-3RT2035-3RT2036- S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005

51 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 20, short-circuit breaking capacity Iq = 150 ka RV2011-0HA RV2011-0JA RV2011-1AA RV2011-1BA RV2011-1CA RV2011-1DA RV2021-1FA RV2021-1GA None 3RV2321-1GC None 3RV2321-1HC None 3RV2321-1JC RV2021-4AA RV2021-4BA RV2021-4DA None 3RV2332-4PC None 3RV2332-4XC RV2032-4XA RV2032-4RA10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2035-3RT2037-3RT2037-3RT2038- S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S2/S2 S2/S2 S2/S2 S2/S2 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005 51

52 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 20, short-circuit breaking capacity Iq = 100 ka None 3RV2331-4PC RV2031-4DB RV2031-4EB RV2031-4UB RV2031-4WB RV2031-4XB10 3RT2035-3RT2035-3RT2035-3RT2035-3RT2036-3RT2037- S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 S2/S2 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005

53 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 30, short-circuit breaking capacity Iq = 150 ka RV2011-0JA RV2011-1AA RV2011-1BA RV2011-1CA RV2011-1DA RV2021-1FA RV2021-1GA RV2021-1HA None 3RV2321-1HC RV2021-1JA RV2021-4AA RV2021-4BA RV2021-4DA RV2021-4EA RV2032-4PA RV2032-4KA RV2032-4KA10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2027-3RT2035-3RT2038-3RT2038- S00/S00 S00/S00 S00/S00 S00/S00 S00/S00 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S0/S0 S2/S2 S2/S2 S2/S2 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x0-1AA00-0/ 3RB2906-2BG1 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG (up to 256 A starting current) Configuration Manual, 01/2016, A8E A/RS-AA/005 53

54 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 30, short-circuit breaking capacity Iq = 100 ka RV2031-4PA RV2031-4EB RV2031-4VB RV2031-4JB10 3RT2035-3RT2035-3RT2036-3RT2037- S2/S2 S2/S2 S2/S2 S2/S2 3UF71x1-1AA00-0/ 3UF71x1-1AA00-0/ 3UF71x2-1AA00-0/ 3RB2906-2JG1 3UF71x2-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005

55 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors kw A A Article No. Article No. Article No. A A CLASS 40, short-circuit breaking capacity Iq = 150 ka RV2011-1AA RV2011-1AA RV2011-1BA RV2011-1DA RV2021-1FA RV2021-1FA RV2021-1GA RV2021-1JA RV2021-1JA RV2021-4AA RV2021-4AA RV2021-4DA RV2021-4EA10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2024-3RT2026-3RT2026-3RT2027-3RT2027- S00/S00 3UF71x0-1AA S00/S00 3UF71x0-1AA S00/S00 3UF71x0-1AA S00/S00 3UF71x0-1AA S0/S0 3UF71x0-1AA S0/S0 3UF71x0-1AA S0/S0 3UF71x0-1AA S0/S0 3UF71x0-1AA S0/S0 3UF71x1-1AA S0/S0 3UF71x1-1AA S0/S0 3UF71x1-1AA S0/S0 3UF71x1-1AA S0/S0 3UF71x1-1AA Configuration Manual, 01/2016, A8E A/RS-AA/005 55

56 Selection tables 400 V AC 3.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relays, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) or current measuring module 4) Maximum permitted setting range overload release IE1 / IE2 motors kw A A Article No. Article No. Article No. A A CLASS 40, short-circuit breaking capacity Iq = 100 ka RV2031-4PB RV2031-4UB RV2031-4XB RV2031-4JB10 3RT2035-3RT2035-3RT2037-3RT2037- IE3 / IE4 motors S2/S2 3UF71x1-1AA S2/S2 3UF71x1-1AA S2/S2 3UF71x2-1AA S2/S2 3UF71x2-1AA Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 4) The necessary current measuring modules (x = 0) or the current measuring modules / voltage measuring modules (x = 1) are specified. The corresponding basic units 3RB22 / 3RB23 / 3RB24 and 3UF7 are additionally required. 56 Configuration Manual, 01/2016, A8E A/RS-AA/005

57 Selection tables 400 V AC 3.5 starter + solid-state contactor 3.5 starter + solid-state contactor Restriction In accordance with the product standard DIN IEC , the solid-state switching devices are designed for motors with a maximum starting current ratio of 8 times the rated current (I/Ie 8). For dimensioning for motors with higher starting current conditions (typically I/Ie > 8), the maximum permissible rated operational current has to be reduced in accordance with the following table: Starting current ratio Maximum permissible rated operational current [A] 3RF3405-.BB.. 3RF3410-.BB.. Solid-state contactors 3RF3412-.BB.. 3RF3416-.BB.. <= 8 times times times times times Configuration Manual, 01/2016, A8E A/RS-AA/005 57

58 Selection tables 400 V AC 3.5 starter + solid-state contactor CLASS 10, type of coordination 1, short-circuit breaking capacity I q 5 ka / 50 ka three-phase motor 4-pole at 400 V AC 1) starter protection Maximum permitted setting range overload release Size Solid-state contactor 2) output P current (guide value) I IE1 / IE2 motors IE3 / IE4 motors Mounting with lateral clearance of 20 mm Butt-mounting 3) kw A A A Article No. Article No. Article No. Short-circuit breaking capacity Iq = 50 ka RV2011-0BA10 S00 3RF3405-1BB04 3RF3405-1BB RV2011-0CA10 S RV2011-0DA10 S RV2011-0EA10 S RV2011-0FA10 S RV2011-0GA10 S RV2011-0HA10 S RV2011-0JA10 S RV2011-0KA10 S RV2011-1AA10 S RV2011-1BA10 S RV2011-1CA10 S RV2011-1DA10 S RV2011-1EA10 S RV2011-1FA10 S RV2011-1GA10 S00 Short-circuit breaking capacity Iq = 20 ka RV2011-1GA10 S00 3RF3405-1BB04 3RF3410-1BB RV2011-1HA10 S00 3RF3410-1BB04 3RF3410-1BB RV2011-1JA10 S00 58 Configuration Manual, 01/2016, A8E A/RS-AA/005

59 Selection tables 400 V AC 3.5 starter + solid-state contactor three-phase motor 4-pole at 400 V AC 1) output P current (guide value) I starter protection Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors Size Solid-state contactor 2) Mounting with lateral clearance of 20 mm Butt-mounting 3) kw A A A Article No. Article No. Article No. Short-circuit breaking capacity Iq = 5 ka RV2011-1KA10 S00 3RF3412-1BB04 3RF3412-1BB RV2021-4AA10 S0 3RF3416-1BB04 3RF3416-1BB RV2021-4BA10 S0 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) The rated currents must be reduced if the solid-state contactor is butt mounted. Detailed characteristic curves can be found in the SIRIUS Innovations manual - SIRIUS 3RF34 solid-state switching devices. See also SIRIUS Innovations manual - SIRIUS 3RF34 solid-state switching devices ( Configuration Manual, 01/2016, A8E A/RS-AA/005 59

60 Selection tables 400 V AC 3.6 starter + solid-state reversing contactor 3.6 starter + solid-state reversing contactor Restriction In accordance with the product standard DIN IEC , the solid-state switching devices are designed for motors with a maximum starting current ratio of 8 times the rated current (I/Ie 8). For dimensioning for motors with higher starting current conditions (typically I/Ie > 8), the maximum permissible rated operational current has to be reduced in accordance with the following table: Starting current ratio Maximum permissible rated operational current [A] Solid-state reversing contactor 3RF BD.4 3RF BD.4 3RF BD.4 <= 8 times times times times times Configuration Manual, 01/2016, A8E A/RS-AA/005

61 Selection tables 400 V AC 3.6 starter + solid-state reversing contactor CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 10 ka / 50 ka three-phase motor 4-pole at 400 V AC 1) starter protection Maximum permitted setting range overload release Size Solid-state reversing contactor 2) output P current (guide value) I IE1 / IE2 motors IE3 / IE4 motors Mounting with lateral clearance of 20 mm Butt-mounting 3) kw A A A Article No. Article No. Article No. Short-circuit breaking capacity Iq = 50 ka RV2011-0BA10 S00 3RF3403-1BD04 3RF3403-1BD RV2011-0CA10 S RV2011-0DA10 S RV2011-0EA10 S RV2011-0FA10 S RV2011-0GA10 S RV2011-0HA10 S RV2011-0JA10 S RV2011-0KA10 S RV2011-1AA10 S RV2011-1BA10 S RV2011-1CA10 S RV2011-1DA10 S RV2011-1EA10 S00 3RF3405-1BD RV2011-1FA10 S RV2011-1GA10 S00 3RF3405-1BD04 Configuration Manual, 01/2016, A8E A/RS-AA/005 61

62 Selection tables 400 V AC 3.6 starter + solid-state reversing contactor three-phase motor 4-pole at 400 V AC 1) output P current (guide value) I starter protection Maximum permitted setting range overload release IE1 / IE2 motors IE3 / IE4 motors Size Solid-state reversing contactor 2) Mounting with lateral clearance of 20 mm Butt-mounting 3) kw A A A Article No. Article No. Article No. Short-circuit breaking capacity Iq = 10 ka RV2011-1GA10 S00 3RF3405-1BD04 3RF3410-1BD RV2011-1HA10 S00 3RF3410-1BD04 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) The rated currents must be reduced if the solid-state contactor is butt mounted. Detailed characteristic curves can be found in the SIRIUS Innovations manual - SIRIUS 3RF34 solid-state switching devices. See also SIRIUS Innovations manual - SIRIUS 3RF34 solid-state switching devices ( 62 Configuration Manual, 01/2016, A8E A/RS-AA/005

63 Selection tables 400 V AC 3.7 starter + star (wye)-delta starting + 3RU21 thermal overload relay 3.7 starter + star (wye)-delta starting + 3RU21 thermal overload relay CLASS 10, types of coordination 1 and 2, short-circuit breaking capacity I q = 150 ka threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (thermal) Line contactor + delta contactor Star contactor Setting range release relay kw A Article No. Article No. Article No. Article No. A Type of coordination RV2311-1KC RV2311-4AC10 3RT RV2321-4AC10 3RT RV2321-4AC10 3RT RV2321-4DC10 3RT RV2321-4EC10 3RT RV2332-4EC10 3RT RV2332-4PC10 3RT RV2332-4PC10 3RT RV2332-4UC10 3RT RV2332-4VC10 3RT RV2332-4VC10 3RT RV2332-4WC10 3RT2036-3RT2024-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2027-3RT2027-3RT2027-3RT2027- S00/S00/S00 3RU2116-1HB S00/S00/S00 3RU2116-1JB S0/S00/S00 3RU2116-1JB S0/S0/S0 3RU2126-1JB S0/S0/S0 3RU2126-4AB S0/S0/S0 3RU2126-4BB S2/S2/S0 3RU2136-4BB S2/S2/S0 3RU2136-4BB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4EB S2/S2/S0 3RU2136-4DB Configuration Manual, 01/2016, A8E A/RS-AA/005 63

64 Selection tables 400 V AC 3.7 starter + star (wye)-delta starting + 3RU21 thermal overload relay threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (thermal) Line contactor + delta contactor Star contactor Setting range release relay kw A Article No. Article No. Article No. Article No. A RV2332-4WC10 3RT RV2332-4XC10 3RT RV2332-4JC10 3RT RV2332-4KC10 3RT RV2332-4KC10 3RT RV2332-4RC10 3RT2038-3RT2027-3RT2035-3RT2035-3RT2035-3RT2035-3RT035- S2/S2/S0 3RU2136-4EB S2/S2/S2 3RU2136-4EB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4GB S2/S2/S2 3RU2136-4HB Configuration Manual, 01/2016, A8E A/RS-AA/005

65 Selection tables 400 V AC 3.7 starter + star (wye)-delta starting + 3RU21 thermal overload relay threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (thermal) Line contactor + delta contactor Star contactor kw A Article No. Article No. Article No. Article No. A Type of coordination RV2321-4AC10 3RT RV2321-4AC10 3RT RV2321-4DC10 3RT RV2321-4EC10 3RT RV2332-4EC10 3RT RV2332-4PC10 3RT RV2332-4PC10 3RT RV2332-4UC10 3RT RV2332-4VC10 3RT RV2332-4VC10 3RT RV2332-4WC10 3RT RV2332-4WC10 3RT RV2332-4XC10 3RT RV2332-4JC10 3RT RV2332-4KC10 3RT RV2332-4KC10 3RT RV2332-4RC10 3RT2038-3RT2024-3RT2024-3RT2026-3RT2027-3RT2027-3RT2027-3RT2027-3RT2027-3RT2027-3RT2027-3RT2035-3RT2035-3RT2035-3RT2035-3RT035- Setting range release relay S0/S0/S00 3RU2126-1HB S0/S0/S00 3RU2126-1JB S0/S0/S0 3RU2126-4AB S0/S0/S0 3RU2126-4BB S2/S2/S0 3RU2136-4BB S2/S2/S0 3RU2136-4BB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4EB S2/S2/S0 3RU2136-4DB S2/S2/S0 3RU2136-4EB S2/S2/S2 3RU2136-4EB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4FB S2/S2/S2 3RU2136-4GB S2/S2/S2 3RU2136-4HB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. Configuration Manual, 01/2016, A8E A/RS-AA/005 65

66 Selection tables 400 V AC 3.8 starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 3.8 starter + contactor assembly for star-delta (wyedelta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 CLASS 10, types of coordination 1 and 2, short-circuit breaking capacity I q = 150 ka / 100 ka threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 1 with 3RB3, short-circuit breaking capacity Iq = 150 ka RV2311-4AC RV2321-4AC RV2321-4AC RV2321-4BC RV2321-4EC RV2332-4EC RV2332-4PC10 3RT2016- S00/S00/S00 3RB3026-1QB RT2016- S0/S00/S00 3RB3026-1QB RT2024-3RT2024- S0/S0/S0 3RB3026-1QB RT2025-3RT2024- S0/S0/S0 3RB3026-1QB RT2025-3RT2024- S0/S0/S0 3RB3026-1VB RT2035-3RT2026- S2/S2/S0 3RB3036-1UB RT2035-3RT2027- S2/S2/S0 3RB3036-1UB Configuration Manual, 01/2016, A8E A/RS-AA/005

67 Selection tables 400 V AC 3.8 starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 1 with 3RB3, short-circuit breaking capacity Iq = 100 ka RV2331-3RT2035-3RT2026- S2/S2/S0 3RB3036-1UB EC RV2331-3RT2035-3RT2027- S2/S2/S0 3RB3036-1UB PC RV2031-3RT2036-3RT2027- S2/S2/S0 3RB3036-1UB VB RV2031-3RT2036-3RT2027- S2/S2/S0 3RB3036-1UB VB RV2031-3RT2036-3RT2027- S2/S2/S0 3RB3036-1UB WB RV2031-3RT2037-3RT2035- S2/S2/S2 3RB3036-1UB XB RV2031-4JB10 3RT2037-3RT2035- S2/S2/S2 3RB3036-1UB Configuration Manual, 01/2016, A8E A/RS-AA/005 67

68 Selection tables 400 V AC 3.8 starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 1 with 3RB22 / 3RB23 / 3RB24 or 3UF7, short-circuit breaking capacity Iq = 150 ka RV2311-4AC RV2321-4AC RV2321-4AC RV2321-4CC RV2321-4EC RV2332-4EC RV2332-4PC10 3RT2016- S00/S00/S00 3UF71x1-1AA00-0/ 3RT2016- S0/S00/S00 3UF71x1-1AA00-0/ 3RT2024-3RT2024- S0/S0/S0 3UF71x1-1AA00-0/ 3RT2025-3RT2024- S0/S0/S0 3UF71x1-1AA00-0/ 3RT2025-3RT2024- S0/S0/S0 3UF71x2-1AA00-0/ 3RB2906-2JG1 3RT2035-3RT2026- S2/S2/S0 3UF7101-1AA00-0 3UF7111-1AA00-0 3RT2035-3RT2027- S2/S2/S2 3UF7101-1AA00-0 3UF7111-1AA00-0 Type of coordination 1 with 3RB22 / 3RB23 / 3RB24 or 3UF7, short-circuit breaking capacity Iq = 100 ka RV2331-4EC RV2331-4PC RV2031-4VB RV2031-4VB RV2031-4WB RV2031-4XB RV2031-4JB10 3RT2035-3RT2026- S2/S2/S0 3UF7101-1AA00-0 3UF7111-1AA00-0 3RT2035-3RT2027- S2/S2/S0 3UF7101-1AA00-0 3UF7111-1AA00-0 3RT2036-3RT2027- S2/S2/S0 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2036-3RT2027- S2/S2/S0 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2036-3RT2027- S2/S2/S0 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2037-3RT2035- S2/S2/S2 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2037-3RT2035- S2/S2/S2 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA Configuration Manual, 01/2016, A8E A/RS-AA/005

69 Selection tables 400 V AC 3.8 starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 2 with 3RB3, short-circuit breaking capacity Iq = 150 ka RV2321-3RT2026- S0/S0/S00 3RB3026-1QB AC RV2321-3RT2027- S0/S0/S00 3RB3026-1QB BC RV2321-3RT2027-3RT2024- S0/S0/S0 3RB3026-1VB EC RV2332-3RT2035-3RT2026- S2/S2/S0 3RB3036-1UB EC RV2332-4PC10 3RT2035-3RT2027- S2/S2/S0 3RB3036-1UB Type of coordination 2 with 3RB3, short-circuit breaking capacity Iq = 100 ka RV2331-3RT2035-3RT2026- S2/S2/S0 3RB3036-1UB EC RV2331-3RT2035-3RT2027- S2/S2/S0 3RB3036-1UB PC RV2031-3RT2036-3RT2027- S2/S2/S0 3RB3036-1UB VB RV2031-3RT2036-3RT2027- S2/S2/S0 3RB3036-1UB VB RV2031-3RT2036-3RT2027- S2/S2/S0 3RB3036-1UB WB RV2031-3RT2037-3RT2035- S2/S2/S2 3RB3036-1UB XB RV2031-4JB10 3RT2037-3RT2035- S2/S2/S2 3RB3036-1UB Configuration Manual, 01/2016, A8E A/RS-AA/005 69

70 Selection tables 400 V AC 3.8 starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 2 with 3RB22 / 3RB23 / 3RB24 or 3UF7, short-circuit breaking capacity Iq = 150 ka RV2321-4AC RV2321-4CC RV2321-4EC RV2332-4EC RV2332-4PC10 3RT2026- S0/S0/S00 3UF71x1-1AA00-0/ 3RT2027- S0/S0/S00 3UF71x1-1AA00-0/ 3RT2027-3RT2024- S0/S0/S0 3UF71x2-1AA00-0/ 3RB2906-2JG1 3RT2035-3RT2026- S2/S2/S0 3UF7101-1AA00-0 3UF7111-1AA00-0 3RT2035-3RT2027- S2/S2/S2 3UF7101-1AA00-0 3UF7111-1AA Configuration Manual, 01/2016, A8E A/RS-AA/005

71 Selection tables 400 V AC 3.8 starter + contactor assembly for star-delta (wye-delta) start + 3RB3, 3RB2. electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (electronic) or current measuring module 3) Line contactor + delta contactor Star contactor kw A Article No. Article No. Article No. Article No. A Type of coordination 2 with 3RB22 / 3RB23 / 3RB24 or 3UF7, short-circuit breaking capacity Iq = 100 ka RV2331-4EC RV2331-4PC RV2031-4VB RV2031-4VB RV2031-4WB RV2031-4XB RV2031-4JB10 3RT2035-3RT2026- S2/S2/S0 3UF7101-1AA00-0 3UF7111-1AA00-0 3RT2035-3RT2027- S2/S2/S0 3UF7101-1AA00-0 3UF7111-1AA00-0 3RT2036-3RT2027- S2/S2/S0 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2036-3RT2027- S2/S2/S0 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2036-3RT2027- S2/S2/S0 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2037-3RT2035- S2/S2/S2 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 3RT2037-3RT2035- S2/S2/S2 3RB2906-2JG1 3UF7102-1AA00-0 3UF7112-1AA00-0 Setting range release relay Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) The necessary current measuring modules (x = 0) or the current measuring modules / voltage measuring modules (x = 1) are specified. The corresponding basic units 3RB22 / 3RB23 / 3RB24 and 3UF7 are additionally required. Configuration Manual, 01/2016, A8E A/RS-AA/005 71

72 Selection tables 400 V AC 3.9 starter + 3RW30 soft starter 3.9 starter + 3RW30 soft starter Restriction The soft starters are dimensioned in accordance with IEC In accordance with the device standard, the maximum motor current to be taken into account is 8 times the rated motor current (locked rotor current). For the correct dimensioning of soft starters for motors with high starting current ratios (I/Ie >= 8), we recommend our Simulation Tool for Soft Starters (STS): Download ( Readme ( CLASS 10, type of coordination 1 three-phase motor 4-pole at 400 V AC 1) output P Permissible operational current (3RW) Setting range release starter starter protection 2) Soft starter Size MSP / 3RW30 Short-circuit breaking capacity Iq Ie kw A A Article No. Article No. ka RV2011-1EA10 3RW3003-1CB54 S00/- (22.5 mm) RV2011-1FA10 3RW3013-1BB14 S00/S RV2011-1HA10 3RW3014-1BB14 S00/S RV2011-1JA10 3RW3016-1BB14 S00/S RV2011-1KA10 3RW3017-1BB14 S00/S RV2021-4BA10 3RW3018-1BB14 S0/S RV2021-4DA10 3RW3026-1BB14 S0/S RV2021-4EA10 3RW3027-1BB14 S0/S ) RV2021-4FA10 3RW3028-1BB14 S0/S Configuration Manual, 01/2016, A8E A/RS-AA/005

73 Selection tables 400 V AC 3.9 starter + 3RW30 soft starter three-phase motor 4-pole at 400 V AC 1) output P Permissible operational current (3RW) Ie Setting range release starter starter protection 2) Soft starter Size MSP / 3RW30 kw A A Article No. Article No. ka RV2031-4VA10 3RW3036-1BB14 S2/S RV2031-4WA10 3RW3036-1BB14 S2/S RV2031-4JA10 3RW3037-1BB14 S2/S RV2031-4KA10 3RW3038-1BB14 S2/S2 10 Short-circuit breaking capacity Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) Discrete mounting only, without a link module. Iq Configuration Manual, 01/2016, A8E A/RS-AA/005 73

74 Selection tables 400 V AC 3.10 starter + 3RW40 soft starter 3.10 starter + 3RW40 soft starter Restriction The soft starters are dimensioned in accordance with IEC In accordance with the device standard, the maximum motor current to be taken into account is 8 times the rated motor current (locked rotor current). For the correct dimensioning of soft starters for motors with high starting current ratios (I/Ie >= 8), we recommend our Simulation Tool for Soft Starters (STS): Download ( Readme ( CLASS 10, type of coordination 1 three-phase motor 4-pole at 400 V AC 1) output P Permissible operational current (3RW) Ie Setting range release starter starter protection 2) Soft starter Size MSP / 3RW 40 kw A A Article No. Article No. ka RV2021-4AA10 3RW4024-1BB14 S0/S RV2021-4DA10 3RW4026-1BB14 S0/S RV2021-4EA10 3RW4027-1BB14 S0/S ) RV2021-4FA10 3RW4028-1BB14 S0/S RV2031-4VA10 3RW4036-1BB14 S2/S RV2031-4WA10 3RW4036-1BB14 S2/S RV2031-4JA10 3RW4037-1BB14 S2/S RV2031-4KA10 3RW4038-1BB14 S2/S2 10 Short-circuit breaking capacity Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) Discrete mounting only, without a link module. Iq 74 Configuration Manual, 01/2016, A8E A/RS-AA/005

75 Selection tables 400 V AC 3.11 starter + 3RW44 soft starter 3.11 starter + 3RW44 soft starter Restriction The soft starters are dimensioned in accordance with IEC In accordance with the device standard, the maximum motor current to be taken into account is 8 times the rated motor current (locked rotor current). For the correct dimensioning of soft starters for motors with high starting current ratios (I/Ie >= 8), we recommend our Simulation Tool for Soft Starters (STS) : Download ( Readme ( CLASS 10, type of coordination 1 three-phase motor 4-pole at 400 V AC 1) output P Permissible operational current (3RW) Ie Setting range release starter starter protection 2) Soft starter Size MSP / 3RW 44 kw A A Article No. Article No. ka 15 3) RV2021-4EA10 3RW4422-1BC44 S0/BG ) RV2021-4FA10 3RW4423-1BC44 S0/BG ) RV2031-4EA10 3RW4422-1BC46 S2/BG ) RV2031-4WA10 3RW4423-1BC46 S2/BG ) RV2031-4WA10 3RW4424-1BC46 S2/BG ) RV2031-4JA10 3RW4425-1BC46 S2/BG ) RV2031-4RA10 3RW4426-1BC46 S2/BG1 32 Short-circuit breaking capacity Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. Screw terminals or spring-loaded terminals can be selected. 3) Discrete mounting only, without a link module. Iq Configuration Manual, 01/2016, A8E A/RS-AA/005 75

76 Selection tables 400 V AC 3.11 starter + 3RW44 soft starter 76 Configuration Manual, 01/2016, A8E A/RS-AA/005

77 Selection tables 500 V AC starter + contactor CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 100 ka three-phase motor 4-pole at 500 V AC 1) output P current I Setting range release starter starter protection Contactor 2) Size kw A A Article No. Article No RV2011-0AA10 S00/S RV2011-0BA10 S00/S RV2011-0CA10 S00/S RV2011-0DA10 S00/S RV2011-0EA10 S00/S RV2011-0FA10 S00/S RV2011-0GA10 S00/S RV2011-0HA10 S00/S RV2011-0JA10 S00/S RV2011-0KA10 S00/S RV2011-1AA10 S00/S RV2011-1AA10 S00/S RV2011-1BA10 S00/S RV2011-1CA10 S00/S RV2011-1DA10 S00/S RV2011-1EA10 S00/S RV2011-1FA10 S00/S RV2011-1GA10 S00/S RV2011-1HA10 3RT2016-1AP06 S00/S RV2011-1JA10 3RT2017- S00/S RV2011-1KA10 3RT2018- S00/S RV2011-4AA10 3RT2018- S00/S00 Configuration Manual, 01/2016, A8E A/RS-AA/005 77

78 Selection tables 500 V AC 4.1 starter + contactor three-phase motor 4-pole at 500 V AC 1) output P current I Setting range release starter starter protection Contactor 2) kw A A Article No. Article No RV2011-4AA10 3RT2018- S00/S RV2021-4BA10 3RT2026- S0/S RV2021-4CA10 3RT2026- S0/S RV2021-4DA10 3RT2027- S0/S RV2021-4NA10 3RT2027- S0/S RV2021-4EA10 3RT2027- S0/S0 Short-circuit breaking capacity Iq = 36 ka 22 3) RV2021-4PA10 3RT1035- S0/S2 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other possible. 3) Discrete mounting only, without a link module. Size 78 Configuration Manual, 01/2016, A8E A/RS-AA/005

79 Selection tables 500 V AC 4.1 starter + contactor CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 100 ka three-phase motor 4-pole at 400 V AC 1) output P current (guide value) I Setting range release starter starter protection Contactor 2) Size kw A A Article No. Article No RV2011-0AA10 S00/S RV2011-0BA10 S00/S RV2011-0CA10 S00/S RV2011-0DA10 S00/S RV2011-0EA10 S00/S RV2011-0FA10 S00/S RV2011-0GA10 S00/S RV2011-0HA10 S00/S RV2011-0JA10 S00/S RV2011-0KA10 S00/S RV2011-1AA10 S00/S RV2011-1AA10 S00/S RV2011-1BA10 S00/S RV2011-1CA10 S00/S RV2011-1DA10 S00/S RV2011-1EA10 3RT2024- S00/S RV2011-1FA10 3RT2024- S00/S RV2011-1GA10 3RT2024- S00/S RV2011-1HA10 3RT2026- S00/S RV2011-1JA10 3RT2026- S00/S RV2011-1KA10 3RT2026- S00/S RV2011-4AA10 3RT2026- S00/S0 Configuration Manual, 01/2016, A8E A/RS-AA/005 79

80 Selection tables 500 V AC 4.1 starter + contactor three-phase motor 4-pole at 400 V AC 1) output P current (guide value) I Setting range release starter starter protection Contactor 2) kw A A Article No. Article No RV2021-4BA10 3RT2027- S0/S RV2021-4CA10 3RT2027- S0/S RV2021-4DA10 3RT2027- S0/S RV2021-4NA10 3RT2027- S0/S RV2021-4EA10 3RT2027- S0/S0 Short-circuit breaking capacity Iq = 36 ka 22 3) RV2021-4PA10 3RT1035- S0/S2 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Discrete mounting only, without a link module. Size 80 Configuration Manual, 01/2016, A8E A/RS-AA/005

81 Selection tables 500 V AC 4.2 starter + contactor + thermal overload relay 4.2 starter + contactor + thermal overload relay CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 100 ka three-phase motor 4-pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size Thermal overload relay Setting range release relay kw A Article No. Article No. Article No. A RV2311-0AC10 S00/S00/S00 3RU2116-0AB RV2311-0BC10 S00/S00/S00 3RU2116-0BB RV2311-0CC10 S00/S00/S00 3RU2116-0CB RV2311-0DC10 S00/S00/S00 3RU2116-0DB RV2311-0EC10 S00/S00/S00 3RU2116-0EB RV2311-0FC10 S00/S00/S00 3RU2116-0FB RV2311-0GC10 S00/S00/S00 3RU2116-0GB RV2311-0HC10 S00/S00/S00 3RU2116-0HB RV2311-0JC10 S00/S00/S00 3RU2116-0JB RV2311-0KC10 S00/S00/S00 3RU2116-0KB RV2311-1AC10 S00/S00/S00 3RU2116-1AB RV2311-1AC10 S00/S00/S00 3RU2116-1AB RV2311-1BC10 S00/S00/S00 3RU2116-1BB RV2311-1CC10 S00/S00/S00 3RU2116-1CB RV2311-1DC10 S00/S00/S00 3RU2116-1DB RV2311-1EC10 S00/S00/S00 3RU2116-1EB RV2311-1FC10 S00/S00/S00 3RU2116-1FB RV2311-1GC10 S00/S00/S00 3RU2116-1GB RV2311-1HC10 3RT2016-1AP06 S00/S00/S00 3RU2116-1HB RV2311-1JC10 3RT2017- S00/S00/S00 3RU2116-1JB RV2311-1KC10 3RT2018- S00/S00/S00 3RU2116-1KB RV2311-4AC10 3RT2018- S00/S00/S00 3RU2116-4AB Configuration Manual, 01/2016, A8E A/RS-AA/005 81

82 Selection tables 500 V AC 4.2 starter + contactor + thermal overload relay three-phase motor 4-pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size Thermal overload relay kw A Article No. Article No. Article No. A Setting range release relay RV2321-4BC10 3RT2026- S0/S0/S0 3RU2126-4BB RV2321-4CC10 3RT2026- S0/S0/S0 3RU2126-4CB RV2321-4DC10 3RT2027- S0/S0/S0 3RU2126-4DB RV2321-4NC10 3RT2027- S0/S0/S0 3RU2126-4NB RV2321-4EC10 3RT2027- S0/S0/S0 3RU2126-4EB Short-circuit breaking capacity Iq = 36 ka 22 3) 33 3RV2321-4PC10 3RT1035- S0/S2/S0 3RU2126-4PB ) 33 3RV2321-4PC10 3RT1035- S0/S2/S2 3RU1136-4FB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Discrete mounting only, without a link module. 82 Configuration Manual, 01/2016, A8E A/RS-AA/005

83 Selection tables 500 V AC 4.2 starter + contactor + thermal overload relay CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 100 ka three-phase motor 4-pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size Thermal overload relay Setting range release relay kw A Article No. Article No. Article No. A RV2311-0AC10 S00/S00/S00 3RU2116-0AB RV2311-0BC10 S00/S00/S00 3RU2116-0BB RV2311-0CC10 S00/S00/S00 3RU2116-0CB RV2311-0DC10 S00/S00/S00 3RU2116-0DB RV2311-0EC10 S00/S00/S00 3RU2116-0EB RV2311-0FC10 S00/S00/S00 3RU2116-0FB RV2311-0GC10 S00/S00/S00 3RU2116-0GB RV2311-0HC10 S00/S00/S00 3RU2116-0HB RV2311-0JC10 S00/S00/S00 3RU2116-0JB RV2311-0KC10 S00/S00/S00 3RU2116-0KB RV2311-1AC10 S00/S00/S00 3RU2116-1AB RV2311-1AC10 S00/S00/S00 3RU2116-1AB RV2311-1BC10 S00/S00/S00 3RU2116-1BB RV2311-1CC10 S00/S00/S00 3RU2116-1CB RV2311-1DC10 S00/S00/S00 3RU2116-1DB RV2311-1EC10 3RT2024- S00/S0/S00 3RU2116-1EB RV2311-1FC10 3RT2024- S00/S0/S00 3RU2116-1FB RV2311-1GC10 3RT2024- S00/S0/S00 3RU2116-1GB RV2311-1HC10 3RT2026- S00/S0/S00 3RU2116-1HB RV2311-1JC10 3RT2026- S00/S0/S00 3RU2116-1JB RV2311-1KC10 3RT2026- S00/S0/S00 3RU2116-1KB RV2311-4AC10 3RT2026- S00/S0/S00 3RU2116-4AB Configuration Manual, 01/2016, A8E A/RS-AA/005 83

84 Selection tables 500 V AC 4.2 starter + contactor + thermal overload relay three-phase motor 4-pole at 400 V AC 1) output P current I starter Starter protection Contactor 2) Size Thermal overload relay kw A Article No. Article No. Article No. A Setting range release relay RV2321-4BC10 3RT2027- S0/S0/S0 3RU2126-4BB0 3) RV2321-4CC10 3RT2027- S0/S0/S0 3RU2126-4CB0 3) RV2321-4DC10 3RT2027- S0/S0/S0 3RU2126-4DB0 3) RV2321-4NC10 3RT2027- S0/S0/S0 3RU2126-4NB RV2321-4EC10 3RT2027- S0/S0/S0 3RU2126-4EB Short-circuit breaking capacity Iq = 36 ka 22 4) 33 3RV2321-4PC10 3RT1035- S0/S2/S0 3RU2126-4PB ) 33 3RV2321-4PC10 3RT1035- S0/S2/S2 3RU1136-4FB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Can also be used in size S00 (3RU2116). 4) Discrete mounting only, without a link module. 84 Configuration Manual, 01/2016, A8E A/RS-AA/005

85 Selection tables 500 V AC 4.3 starter + contactor + 3RB3 solid-state overload relay 4.3 starter + contactor + 3RB3 solid-state overload relay Type of coordination 1, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS 10 Setting range release relay RV2311-0BC10 S00/S00/S00 3RB3016-1RB RV2311-0BC10 S00/S00/S00 3RB3016-1RB RV2311-0DC10 S00/S00/S00 3RB3016-1RB RV2311-0EC10 S00/S00/S00 3RB3016-1NB RV2311-0GC10 S00/S00/S00 3RB3016-1NB RV2311-0HC10 S00/S00/S00 3RB3016-1NB RV2311-0JC10 S00/S00/S00 3RB3016-1NB RV2311-0KC10 S00/S00/S00 3RB3016-1PB RV2311-1AC10 S00/S00/S00 3RB3016-1PB RV2311-1CC10 S00/S00/S00 3RB3016-1PB RV2311-1DC10 S00/S00/S00 3RB3016-1PB RV2311-1FC10 S00/S00/S00 3RB3016-1PB RV2311-1FC10 S00/S00/S00 3RB3016-1PB RV2311-1HC10 3RT2016- S00/S00/S00 3RB3016-1SB RV2311-1HC10 3RT2016- S00/S00/S00 3RB3016-1SB RV2311-1JC10 3RT2017- S00/S00/S00 3RB3016-1SB RV2321-4AC10 3RT2026- S0/S0/S0 3RB3026-1QB RV2321-4CC10 3RT2026- S0/S0/S0 3RB3026-1QB RV2321-4EC10 3RT2027- S0/S0/S0 3RB3026-1VB Configuration Manual, 01/2016, A8E A/RS-AA/005 85

86 Selection tables 500 V AC 4.3 starter + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS 20 Setting range release relay RV2311-0DC10 S00/S00/S00 3RB3016-2RB RV2311-0DC10 S00/S00/S00 3RB3016-2RB RV2011-0GA10 S00/S00/S00 3RB3016-2RB RV2011-0HA10 S00/S00/S00 3RB3016-2NB RV2011-0KA10 S00/S00/S00 3RB3016-2NB RV2011-1AA10 S00/S00/S00 3RB3016-2NB RV2011-1BA10 S00/S00/S00 3RB3016-2NB RV2011-1CA10 S00/S00/S00 3RB3016-2PB RV2011-1DA10 S00/S00/S00 3RB3016-2PB RV2011-1FA10 S00/S00/S00 3RB3016-2PB RV2011-1GA10 S00/S00/S00 3RB3016-2PB RV2011-1JA10 3RT2017- S00/S00/S00 3RB3016-2SB RV2011-1KA10 3RT2018- S00/S00/S00 3RB3016-2SB RV2011-4AA10 3RT2018- S00/S00/S00 3RB3016-2SB RV2021-4BA10 3RT2026- S0/S0/S0 3RB3026-2QB RV2021-4DA10 3RT2027- S0/S0/S0 3RB3026-2QB Configuration Manual, 01/2016, A8E A/RS-AA/005

87 Selection tables 500 V AC 4.3 starter + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS 30 Setting range release relay RV2311-0DC10 S00/S00/S00 3RB3113-4RB RV2011-0FA10 S00/S00/S00 3RB3113-4RB RV2011-0HA10 S00/S00/S00 3RB3113-4RB RV2011-0KA10 S00/S00/S00 3RB3113-4NB RV2011-1AA10 S00/S00/S00 3RB3113-4NB RV2011-1BA10 S00/S00/S00 3RB3113-4NB RV2011-1CA10 S00/S00/S00 3RB3113-4NB RV2011-1EA10 S00/S00/S00 3RB3113-4PB RV2011-1FA10 S00/S00/S00 3RB3113-4PB RV2011-1GA10 S00/S00/S00 3RB3113-4PB RV2011-1JA10 3RT2017- S00/S00/S00 3RB3113-4PB RV2011-1KA10 3RT2018- S00/S00/S00 3RB3113-4RB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3RA2921-1BA00 link module can only be used with screw terminals. 3) The motor starter is to be set to maximum current value. Configuration Manual, 01/2016, A8E A/RS-AA/005 87

88 Selection tables 500 V AC 4.3 starter + contactor + 3RB3 solid-state overload relay Type of coordination 2, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS 10 Setting range release relay RV2311-0BC10 S00/S00/S00 3RB3016-1RB RV2311-0BC10 S00/S00/S00 3RB3016-1RB RV2311-0DC10 S00/S00/S00 3RB3016-1RB RV2311-0EC10 S00/S00/S00 3RB3016-1NB RV2311-0GC10 S00/S00/S00 3RB3016-1NB RV2311-0HC10 S00/S00/S00 3RB3016-1NB RV2311-0JC10 S00/S00/S00 3RB3016-1NB RV2311-0KC10 S00/S00/S00 3RB3016-1PB RV2311-1AC10 S00/S00/S00 3RB3016-1PB RV2311-1CC10 S00/S00/S00 3RB3016-1PB RV2311-1DC10 S00/S00/S00 3RB3016-1PB RV2311-1FC10 3RT2024- S00/S0/S0 3RB3026-1SB RV2311-1FC10 3RT2024- S00/S0/S0 3RB3026-1SB RV2311-1HC10 3RT2026- S00/S0/S0 3RB3026-1SB RV2311-1HC10 3RT2026- S00/S0/S0 3RB3026-1SB RV2321-4AC10 3RT2026- S0/S0/S0 3RB3026-1QB RV2311-1JC10 3RT2026- S00/S0/S0 3RB3026-1SB RV2321-4CC10 3RT2027- S0/S0/S0 3RB3026-1QB RV2321-4EC10 3RT2027- S0/S0/S0 3RB3026-1VB Configuration Manual, 01/2016, A8E A/RS-AA/005

89 Selection tables 500 V AC 4.3 starter + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS 20 Setting range release relay RV2311-0DC10 S00/S00/S00 3RB3016-2RB RV2311-0DC10 S00/S00/S00 3RB3016-2RB RV2011-0GA10 S00/S00/S00 3RB3016-2RB RV2011-0HA10 S00/S00/S00 3RB3016-2NB RV2011-0KA10 S00/S00/S00 3RB3016-2NB RV2011-1AA10 S00/S00/S00 3RB3016-2NB RV2011-1BA10 S00/S00/S00 3RB3016-2NB RV2011-1CA10 S00/S00/S00 3RB3016-2PB RV2011-1DA10 S00/S00/S00 3RB3016-2PB RV2011-1FA10 3RT2024- S00/S0/S0 3RB3026-2PB RV2011-1GA10 3RT2024- S00/S0/S0 3RB3026-2PB RV2011-1JA10 3RT2026- S00/S0/S0 3RB3026-2SB RV2011-1JA10 3RT2026- S00/S0/S0 3RB3026-2SB RV2021-4AA10 3RT2026- S0/S0/S0 3RB3026-2SB RV2021-4BA10 3RT2027- S0/S0/S0 3RB3026-2QB RV2021-4DA10 3RT2027- S0/S0/S0 3RB3026-2QB RV2021-4EA10 3RT2027- S0/S0/S0 3RB3026-2QB Configuration Manual, 01/2016, A8E A/RS-AA/005 89

90 Selection tables 500 V AC 4.3 starter + contactor + 3RB3 solid-state overload relay threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS 30 Setting range release relay RV2311-0DC10 S00/S00/S00 3RB3113-4RB RV2011-0FA10 S00/S00/S00 3RB3113-4RB RV2011-0HA10 S00/S00/S00 3RB3113-4RB RV2011-0KA10 S00/S00/S00 3RB3113-4NB RV2011-1AA10 S00/S00/S00 3RB3113-4NB RV2011-1BA10 S00/S00/S00 3RB3113-4NB RV2011-1CA10 S00/S00/S00 3RB3113-4NB RV2011-1EA10 3RT2024- S00/S0/S0 3RB3123-4PB RV2011-1FA10 3RT2024- S00/S0/S0 3RB3123-4PB RV2011-1GA10 3RT2024- S00/S0/S0 3RB3123-4PB RV2011-1JA10 3RT2026- S00/S0/S0 3RB3123-4PB RV2011-1KA10 3RT2026- S00/S0/S0 3RB3123-4SB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 90 Configuration Manual, 01/2016, A8E A/RS-AA/005

91 Selection tables 500 V AC 4.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, or 3UF7 4.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, or 3UF7 Type of coordination 2, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) Setting range release relay kw A Article No. Article No. Article No. A CLASS RV2311-0EC RV2311-0GC RV2311-0HC RV2311-0JC RV2311-0KC RV2311-1AC RV2311-1CC RV2311-1DC RV2311-1FC RV2311-1FC RV2311-1HC RV2311-1HC10 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7101-1AA00-0/ 3RT2024- S00/S0 3UF7101-1AA00-0/ 3RT2024- S00/S0 3UF7101-1AA00-0/ 3RT2026- S00/S0 3UF7101-1AA00-0/ 3RT2026- S00/S0 3UF7101-1AA00-0/ Configuration Manual, 01/2016, A8E A/RS-AA/005 91

92 Selection tables 500 V AC 4.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) Setting range release relay kw A Article No. Article No. Article No. A RV2321-4BC RV2311-1JC RV2321-4CC RV2321-4EC10 Short-circuit breaking capacity Iq = 36 ka RV2321-4PC10 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT2026- S00/S0 3UF7102-1AA00-0/ 3RB2906-2JG1 3RT2027- S0/S0 3UF7102-1AA00-0/ 3RB2906-2JG1 3RT2027- S0/S0 3UF7102-1AA00-0/ 3RB2906-2JG1 3RT1035- S0/S2 3UF7102-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005

93 Selection tables 500 V AC 4.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) Setting range release relay kw A Article No. Article No. Article No. A CLASS RV2011-0HA RV2011-0KA RV2011-1AA RV2011-1BA RV2011-1CA RV2011-1DA RV2011-1FA RV2011-1GA RV2011-1JA RV2311-1JC RV2021-4AA RV2021-4BA RV2021-4EA RV2021-4EA10 Short-circuit breaking capacity Iq = 36 ka RV2021-4PA10 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2024- S00/S0 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2024- S00/S0 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2026- S00/S0 3UF7101-1AA00-0/ 3RT2026- S00/S0 3UF7101-1AA00-0/ 3RT2026- S0/S0 3UF7101-1AA00-0/ 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT1035- S0/S2 3UF7101-1AA00-0/ Configuration Manual, 01/2016, A8E A/RS-AA/005 93

94 Selection tables 500 V AC 4.4 starter + contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, or 3UF7 threephase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter Starter protection 3) Contactor 2) Size relay (electronic) kw A Article No. Article No. Article No. A CLASS RV2011-0KA RV2011-1AA RV2011-1BA RV2011-1CA RV2011-1EA RV2011-1FA RV2011-1GA RV2011-1JA RV2011-1KA RV2021-4AA RV2021-4BA RV2021-4DA RV2021-4EA10 Short-circuit breaking capacity Iq = 36 ka RV2021-4PA10 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 S00/S00 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2024- S00/S0 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2024- S00/S0 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2024- S00/S0 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2026- S00/S0 3UF7100-1AA00-0/ 3RB2906-2BG1 3RT2026- S00/S0 3UF7101-1AA00-0/ 3RT2026- S0/S0 3UF7101-1AA00-0/ 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT2027- S0/S0 3UF7101-1AA00-0/ 3RT1035- S0/S2 3UF7101-1AA00-0/ Setting range release relay Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 94 Configuration Manual, 01/2016, A8E A/RS-AA/005

95 Selection tables 500 V AC 4.5 starter + contactor assembly for star-delta (wye-delta) start + 3RU21 thermal overload relay 4.5 starter + contactor assembly for star-delta (wyedelta) start + 3RU21 thermal overload relay CLASS 5 and CLASS 10, types of coordination 1 and 2, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (thermal) Line contactor + delta contactor Star contactor Setting range release relay kw A Article No. Article No. Article No. Article No. A Type of coordination RV2311-1JC RV2311-1KC RV2311-1KC RV2321-4BC RV2321-4CC RV2321-4DC RV2321-4NC RV2321-4EC10 3RT2017-3RT2017- S00/S00/S00 3RU2116-1GB RT2018-3RT2017- S00/S00/S00 3RU2116-1HB RT2024-3RT2024- S00/S0/S0 3RU2126-1HB RT2026-3RT2026- S0/S0/S0 3RU2126-1KB RT2026-3RT2026- S0/S0/S0 3RU2126-1KB RT2027-3RT2027- S0/S0/S0 3RU2126-4AB RT2027-3RT2027- S0/S0/S0 3RU2126-4BB RT2027-3RT2027- S0/S0/S0 3RU2126-4BB Configuration Manual, 01/2016, A8E A/RS-AA/005 95

96 Selection tables 500 V AC 4.5 starter + contactor assembly for star-delta (wye-delta) start + 3RU21 thermal overload relay threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (thermal) Line contactor + delta contactor Star contactor kw A Article No. Article No. Article No. Article No. A Type of coordination RV2311-1JC RV2311-1KC RV2321-4BC RV2321-4CC RV2321-4DC RV2321-4NC RV2321-4EC10 Setting range release relay 3RT2026-3RT2026- S00/S0/S0 3RU2126-1GB RT2026-3RT2026- S00/S0/S0 3RU2126-1HB RT2027-3RT2027- S0/S0/S0 3RU2126-1KB RT2027-3RT2027- S0/S0/S0 3RU2126-1KB RT2027-3RT2027- S0/S0/S0 3RU2126-4AB RT2027-3RT2027- S0/S0/S0 3RU2126-4BB RT2027-3RT2027- S0/S0/S0 3RU2126-4BB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 96 Configuration Manual, 01/2016, A8E A/RS-AA/005

97 Selection tables 500 V AC 4.6 starter + contactor assembly for star-delta (wye-delta) start + 3RB2. electronic overload relay, or 3UF7, 3RB3 4.6 starter + contactor assembly for star-delta (wyedelta) start + 3RB2. electronic overload relay, or 3UF7, 3RB3 CLASS 5 and CLASS 10, types of coordination 1 and 2, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 1 with 3RB22, 3RB23, 3RB24 or 3UF RV2311-1JC RV2311-1KC RV2311-1KC RV2321-4BC RV2321-4CC RV2321-4DC RV2321-4NC RV2321-4EC10 3RT2017-3RT2017-3RT2018-3RT2017- S00/S00/S00 3UF7101-1AA00-0/ S00/S00/S00 3UF7101-1AA00-0/ 3RT2024-3RT2024- S00/S0/S0 3UF7101-1AA00-0/ 3RT2026-3RT2026- S0/S0/S0 3UF7101-1AA00-0/ 3RT2026-3RT2026- S0/S0/S0 3UF7101-1AA00-0/ 3RT2027-3RT2027- S0/S0/S0 3UF7101-1AA00-0/ 3RT2027-3RT2027- S0/S0/S0 3UF7102-1AA00-0/ 3RB2906-2JG1 3RT2027-3RT2027- S0/S0/S0 3UF7102-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005 97

98 Selection tables 500 V AC 4.6 starter + contactor assembly for star-delta (wye-delta) start + 3RB2. electronic overload relay, or 3UF7, 3RB3 threephase motor 4-pole at 400 V AC 1) starter Contactors 2) Size relay (electronic) or current measuring module 3) Setting range release output P current I Line contactor + delta contactor Star contactor relay kw A Article No. Article No. Article No. Article No. A Type of coordination 1 with 3RB RV2311-3RT2017-3RT2017- S00/S00/S00 3RB3016-1SB JC RV2311-1KC10 3RT2018-3RT2017- S00/S00/S00 3RB3016-1SB RV2311-3RT2024-3RT2024- S00/S0/S0 3RB3026-1SB KC RV2321-3RT2026-3RT2026- S0/S0/S0 3RB3026-1QB BC RV2321-3RT2026-3RT2026- S0/S0/S0 3RB3026-1QB CC RV2321-3RT2027-3RT2027- S0/S0/S0 3RB3026-1QB DC RV2321-3RT2027-3RT2027- S0/S0/S0 3RB3026-1VB NC RV2321-4EC10 3RT2027-3RT2027- S0/S0/S0 3RB3026-1VB Type of coordination 2 with 3RB22, 3RB23, 3RB24 or 3UF RV2311-1JC RV2311-1KC RV2311-1KC RV2321-4BC RV2321-4CC RV2321-4DC RV2321-4NC10 3RT2017-3RT2017- S00/S00/S00 3UF7101-1AA00-0/ 3RT2018-3RT2017- S00/S00/S00 3UF7101-1AA00-0/ 3RT2024-3RT2024- S00/S0/S0 3UF7101-1AA00-0/ 3RT2026-3RT2026- S0/S0/S0 3UF7101-1AA00-0/ 3RT2026-3RT2026- S0/S0/S0 3UF7101-1AA00-0/ 3RT2027-3RT2027- S0/S0/S0 3UF7101-1AA00-0/ 3RT2027-3RT2027- S0/S0/S0 3UF7102-1AA00-0/ 3RB2906-2JG Configuration Manual, 01/2016, A8E A/RS-AA/005

99 Selection tables 500 V AC 4.6 starter + contactor assembly for star-delta (wye-delta) start + 3RB2. electronic overload relay, or 3UF7, 3RB3 threephase motor 4-pole at 400 V AC 1) output P current I starter Contactors 2) Size relay (electronic) or current measuring module 3) Line contactor + delta contactor Star contactor kw A Article No. Article No. Article No. Article No. A Type of coordination 2 with 3RB RV2311-1JC RV2311-1KC RV2321-4BC RV2321-4CC RV2321-4DC RV2321-4NC RV2321-4EC10 Setting range release relay 3RT2026-3RT2026- S00/S0/S0 3RB3026-1SB RT2026-3RT2026- S00/S0/S0 3RB3026-1SB RT2027-3RT2027- S0/S0/S0 3RB3026-1QB RT2027-3RT2027- S0/S0/S0 3RB3026-1QB RT2027-3RT2027- S0/S0/S0 3RB3026-1QB RT2027-3RT2027- S0/S0/S0 3RB3026-1VB RT2027-3RT2027- S0/S0/S0 3RB3026-1VB Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The necessary current measuring modules are specified. The corresponding basic unit 3RB22 / 3RB23 or 3UF7 is additionally required. Configuration Manual, 01/2016, A8E A/RS-AA/005 99

100 Selection tables 500 V AC 4.7 starter + 3RW40 soft starter 4.7 starter + 3RW40 soft starter CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 10 ka three-phase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter protection 2) Soft starter kw A A Article No. Article No RV2011-4AA10 3RW4024-1BB14 S0/S RV2021-4DA10 3RW4026-1BB14 S0/S RV2021-4EA20 3RW4027-1BB14 S0/S ) RV2021-4FA10 3RW4028-1BB14 S0/S0 Size MSP / 3RW40 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Discrete mounting only, without a link module. 100 Configuration Manual, 01/2016, A8E A/RS-AA/005

101 Selection tables 500 V AC 4.8 starter + 3RW44 soft starter 4.8 starter + 3RW44 soft starter CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 10 ka three-phase motor 4-pole at 400 V AC 1) output P current I Setting range release starter starter protection 2) Soft starter kw A A Article No. Article No. Size MSP / 3RW RV2021-4EA10 3RW4422-1BC44 S0/BG ) RV2021-4FA10 3RW4423-1BC44 S0/BG2 Article numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link module can only be used with screw terminals. 1) Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Rated currents taken into account at 40 C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) Discrete mounting only, without a link module. Configuration Manual, 01/2016, A8E A/RS-AA/

102 Selection tables 500 V AC 4.8 starter + 3RW44 soft starter 102 Configuration Manual, 01/2016, A8E A/RS-AA/005

103 Selection tables up to 690 V starter + contactor CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 690 V AC 1) output P current I Setting range release starter motor starter with limiter function starter protection Contactor 2) kw A A Article No. Article No. Article No. Size Limiter starter / contactor RV2011-0AA10 S00/S RV2011-0BA10 S00/S RV2011-0CA10 S00/S RV2011-0DA10 S00/S RV2011-0EA10 S00/S RV2011-0FA10 S00/S RV2011-0GA10 S00/S RV2011-0HA10 S00/S RV2011-0JA10 S00/S RV2011-0KA10 S00/S RV2011-1AA10 S00/S RV2011-1BA10 S00/S RV2321-4EC10 3) 3RV2011-1CA10 S0 S00/S Size S0 3RV2011-1DA10 S0 S00/S In = 32 A starter 3RV2011-1EA10 3RV2011-1FA10 S0 S0 S00/S00 S00/S00 for starter RV2011-1FA10 S0 S00/S00 protection RV2011-1GA10 S0 S00/S RV2011-1HA10 3RT2018- S0 S00/S RV2011-1JA10 3RT2018- S0 S00/S00 Configuration Manual, 01/2016, A8E A/RS-AA/

104 Selection tables up to 690 V 5.1 starter + contactor threephase motor 4-pole at 690 V AC 1) output P current I Setting range release starter motor starter with limiter function starter protection Contactor 2) kw A A Article No. Article No. Article No. Size Limiter starter / contactor RV1331-4HC10 3) Size S2 3RV20.1-4AA10 3RT2025- S2 S00/S0, S0/S In = 50 A 3RV20.1-4BA10 3RT2028- S2 S0/S starter 3RV20.1-4CA10 3RT2028- S2 S0/S for starter protection 3RV20.1-4DA10 3RT2028- S2 S0/S0 Short-circuit breaking capacity Iq = 20 ka 4) RV2321-4EC10 3) Size S0 3RV20.1-4AA10 3RT2025- S0 S00/S0, S0/S In = 32 A 3RV2021-4BA10 3RT2027- S0 S0/S starter 3RV2021-4CA10 3RT2027- S0 S0/S for starter protection 3RV2021-4DA10 3RT2027- S0 S0/S0 : Not required 1) Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup data and rated data of the motor to be protected. 2) Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible. 3) The motor starter is to be set to maximum current value. 4) Infeed on limiter must be from above. 104 Configuration Manual, 01/2016, A8E A/RS-AA/005

105 Selection tables up to 690 V 5.1 starter + contactor CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 690 V AC 1) output P current I Setting range release starter motor starter with limiter function starter protection Contactor 2) kw A A Article No. Article No. Article No. Size Limiter starter / contactor RV2011-0AA10 S00/S RV2011-0BA10 S00/S RV2011-0CA10 S00/S RV2011-0DA10 S00/S RV2011-0EA10 S00/S RV2011-0FA10 S00/S RV2011-0GA10 S00/S RV2011-0HA10 S00/S RV2011-0JA10 S00/S RV2011-0KA10 S00/S RV2011-1AA10 S00/S RV2011-1BA10 S00/S RV2321-4EC10 3) 3RV2011-1CA10 S0 S00/S Size S0 3RV2011-1DA10 3RT2024- S0 S00/S In = 32 A 3RV2011-1EA10 3RT2024- S0 S00/S starter 3RV2011-1FA10 3RT2024- S0 S00/S0 for starter RV2011-1FA10 3RT2024- S0 S00/S0 protection RV2011-1GA10 3RT2024- S0 S00/S RV2011-1HA10 3RT2024- S0 S00/S RV2011-1JA10 3RT2024- S0 S00/S RV1331-4HC10 3) Size S2 3RV20.1-4AA10 3RT2027- S2 S00/S0, S0/S In = 50 A 3RV20.1-4BA10 3RT2028- S2 S0/S starter 3RV20.1-4CA10 3RT2028- S2 S0/S for starter protection 3RV20.1-4DA10 3RT2028- S2 S0/S0 Configuration Manual, 01/2016, A8E A/RS-AA/

106 Selection tables up to 690 V 5.1 starter + contactor threephase motor 4-pole at 690 V AC 1) output P current I Setting range release starter motor starter with limiter function starter protection Contactor 2) kw A A Article No. Article No. Article No. Short-circuit breaking capacity Iq = 20 ka 4) Size Limiter starter / contactor RV2321-4EC10 3) Size S0 3RV20.1-4AA10 3RT2025- S0 S00/0, S0/S In = 32 A 3RV2021-4BA10 3RT2027- S0 S0/S starter 3RV2021-4CA10 3RT2027- S0 S0/S for starter protection 3RV2021-4DA10 3RT2027- S0 S0/S0 : Not required 1) Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup data and rated data of the motor to be protected. 2) Rated control supply voltage 230 V AC, 50 Hz, other possible. 3) The motor starter is to be set to maximum current value. 4) Infeed on limiter must be from above. 106 Configuration Manual, 01/2016, A8E A/RS-AA/005

107 Selection tables up to 690 V 5.2 starter + contactor + thermal overload relay 5.2 starter + contactor + thermal overload relay CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 690V AC 1) output P current I motor starter with limiter function starter Starter protection Contactor 3) Size Limiter starter / contactor / thermal overload relay Thermal overload relay 4) Setting range release Thermal overload relay kw A Article No. Article No. Article No. Article No. A RV2311-0AC RV2311-0BC RV2311-0CC RV2311-0DC RV2311-0EC RV2311-0FC RV2311-0GC RV2311-0HC RV2311-0JC RV2311-0KC RV2311-1AC RV2311-1BC10 S00/S00/S00 3RU2116-0AB S00/S00/S00 3RU2116-0BB S00/S00/S00 3RU2116-0CB S00/S00/S00 3RU2116-0DB S00/S00/S00 3RU2116-0EB S00/S00/S00 3RU2116-0FB S00/S00/S00 3RU2116-0GB S00/S00/S00 3RU2116-0HB S00/S00/S00 3RU2116-0JB S00/S00/S00 3RU2116-0KB S00/S00/S00 3RU2116-1AB S00/S00/S00 3RU2116-1BB Configuration Manual, 01/2016, A8E A/RS-AA/

108 Selection tables up to 690 V 5.2 starter + contactor + thermal overload relay threephase motor 4-pole at 690V AC 1) output P current I motor starter with limiter function starter Starter protection Contactor 3) Size Limiter starter / contactor / thermal overload relay Thermal overload relay 4) Setting range release Thermal overload relay kw A Article No. Article No. Article No. Article No. A RV2321-4EC10 Size S0 In = 32 A starter for starter 3RV2311-1CC10 3RV2311-1DC10 3RV2311-1EC10 3RV2311-1FC10 S0 S0 S0 S0 S00/S00/S00 S00/S00/S00 S00/S00/S00 S00/S00/S00 3RU2116-1CB0 3RU2116-1DB0 3RU2116-1EB0 3RU2116-1FB protection 2) 3RV2311-1FC RV2311-1GC RV2311-1HC RV2311-1JC RV1331-4HC10 Size S2 In = 50 A starter 3RV23.1-4AC RV2321-4BC RV2321-4CC for starter protection 2) 3RV2321-4DC10 3RT2018-3RT2018-3RT2025-3RT2028-3RT2028-3RT2028- S0 S00/S00/S00 3RU2116-1FB S0 S00/S00/S00 3RU2116-1GB S0 S00/S00/S00 3RU2116-1HB S0 S00/S00/S00 3RU2116-1JB S2 S00/S0/S0 3RU2126-4AB S0/S0/S0 S2 S0/S0/S0 3RU2126-4BB S2 S0/S0/S0 3RU2126-4CB S2 S0/S0/S0 3RU2126-4DB Configuration Manual, 01/2016, A8E A/RS-AA/005

109 Selection tables up to 690 V 5.2 starter + contactor + thermal overload relay threephase motor 4-pole at 690V AC 1) output P current I motor starter with limiter function starter Starter protection Contactor 3) Size Limiter starter / contactor / thermal overload relay Thermal overload relay 4) kw A Article No. Article No. Article No. Article No. A Short-circuit breaking capacity Iq = 20 ka 5) RV2321-4EC10 3RV23.1-4AC Size S0 In = 32 A starter for starter protection 2) 3RV2321-4BC10 3RV2321-4CC10 3RV2321-4DC10 : Not required 3RT2025-3RT2027-3RT2027-3RT2027- Setting range release Thermal overload relay S0 S00/S0/S0 3RU2126-4AB S0/S0/S0 S0 S0/S0/S0 3RU2126-4BB S0 S0/S0/S0 3RU2126-4CB S0 S0/S0/S0 3RU2126-4DB ) Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) The motor starter is to be set to maximum current value. 3) Rated control supply voltage 230 V AC, 50 Hz, other possible. 4) The thermal overload relays of the setting ranges from 2.5 A to 16 A can be used both in size S00 and S0. 5) Infeed on limiter must be from above. Configuration Manual, 01/2016, A8E A/RS-AA/

110 Selection tables up to 690 V 5.2 starter + contactor + thermal overload relay CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 100 ka threephase motor 4-pole at 690V AC 1) output P current I motor starter with limiter function starter Starter protection Contactor 2) Size Thermal overload relay 3) Limiter starter / contactor / thermal overload relay Setting range release Thermal overload relay kw A Article No. Article No. Article No. Article No. A RV2311- S00/S00/S00 3RU2116-0AB AC RV2311-0BC RV2311-0CC RV2311-0DC RV2311-0EC RV2311-0FC RV2311-0GC RV2311-0HC RV2311-0JC RV2311-0KC RV2311-1AC RV2311-1BC10 S00/S00/S00 3RU2116-0BB S00/S00/S00 3RU2116-0CB S00/S00/S00 3RU2116-0DB S00/S00/S00 3RU2116-0EB S00/S00/S00 3RU2116-0FB S00/S00/S00 3RU2116-0GB S00/S00/S00 3RU2116-0HB S00/S00/S00 3RU2116-0JB S00/S00/S00 3RU2116-0KB S00/S00/S00 3RU2116-1AB S00/S00/S00 3RU2116-1BB Configuration Manual, 01/2016, A8E A/RS-AA/005

111 Selection tables up to 690 V 5.2 starter + contactor + thermal overload relay threephase motor 4-pole at 690V AC 1) output P current I motor starter with limiter function starter Starter protection Contactor 2) Size Thermal overload relay 3) Limiter starter / contactor / thermal overload relay Setting range release Thermal overload relay kw A Article No. Article No. Article No. Article No. A RV2321-4EC10 4) Size S0 In = 32 A starter for starter 3RV2311-1CC10 3RV2311-1DC10 3RV2311-1EC10 3RV2311-1FC10 3RT2024-3RT2024-3RT2024- S0 S0 S0 S0 S00/S00/S00 S00/S0/S0 S00/S0/S0 S00/S0/S0 3RU2116-1CB0 3RU2126-1DB0 3RU2126-1EB0 3RU2126-1FB protection 3RV2311-1FC RV2311-1GC RV2311-1HC RV2311-1JC RV1331-4HC10 4) 3RV23.1-4AC Size S2 In = 50 A starter for starter protection 3RV2321-4BC10 3RV2321-4CC10 3RV2321-4DC10 3RT2024-3RT2024-3RT2024-3RT2024-3RT2027-3RT2028-3RT2028-3RT2028- S0 S00/S0/S0 3RU2126-1FB S0 S00/S0/S0 3RU2126-1GB S0 S00/S0/S0 3RU2126-1HB S0 S00/S0/S0 3RU2126-1JB S2 S00/S0/S0 3RU2126-4AB S0/S0/S0 S2 S0/S0/S0 3RU2126-4BB S2 S0/S0/S0 3RU2126-4CB S2 S0/S0/S0 3RU2126-4DB Configuration Manual, 01/2016, A8E A/RS-AA/

112 Selection tables up to 690 V 5.2 starter + contactor + thermal overload relay threephase motor 4-pole at 690V AC 1) output P current I motor starter with limiter function starter Starter protection Contactor 2) Size Thermal overload relay 3) Limiter starter / contactor / thermal overload relay kw A Article No. Article No. Article No. Article No. A Short-circuit breaking capacity Iq = 20 ka 5) RV EC10 4) 3RV23.1-4AC Size S0 In = 32 A starter for starter protection 3RV2321-4BC10 3RV2321-4CC10 3RV2321-4DC10 : Not required 3RT2027-3RT2027-3RT2027-3RT2027- Setting range release Thermal overload relay S0 S00/S0/S0 3RU2126-4AB S0/S0/S0 S0 S0/S0/S0 3RU2126-4BB S0 S0/S0/S0 3RU2126-4CB S0 S0/S0/S0 3RU2126-4DB ) Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup data and rated data of the motor to be protected. 2) Rated control supply voltage 230 V AC, 50 Hz, other possible. 3) The thermal overload relays of the setting ranges from 2.5 A to 16 A can be used both in size S00 and S0. 4) The motor starter is to be set to maximum current value. 5) Infeed on limiter must be from above. 112 Configuration Manual, 01/2016, A8E A/RS-AA/005

113 Fused selection tables up to 690 V Short-circuit protection contactor type of coordination 1 and 2 Short-circuit protection up to 100 ka Type of coordination 1 and 2 Table 6-1 Fuse links for protection according to IEC / DIN EN Contactor Fuse links 1) Article No. P [kw] Type of coordination 2) Size S00 gg am British s BS88 gm (415 V / 80 ka) RT RT RT Size S0 3RT RT RT RT RT RT Size S2 3RT RT RT RT ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/

114 Fused selection tables up to 690 V 6.2 Short-circuit protection 3RU2 thermal overload relay, type of coordination 1 and Short-circuit protection 3RU2 thermal overload relay, type of coordination 1 and 2 Short-circuit protection up to 100 ka Type of coordination 1 and 2 Table 6-2 Fuse links for protection according to IEC / DIN EN Thermal overload relay Fuse links 1) Article No. Size S00 Setting range [A] gg am British s BS88 gg (415 V / 80 ka) Type of coordination 2) RU2116-0AB RU2116-0BB RU2116-0CB RU2116-0DB RU2116-0EB RU2116-0FB RU2116-0GB RU2116-0HB RU2116-0JB RU2116-0KB RU2116-1AB RU2116-1BB RU2116-1CB RU2116-1DB RU2116-1EB RU2116-1FB RU2116-1GB RU2116-1HB RU2116-1JB RU2116-1KB RU2116-4AB Configuration Manual, 01/2016, A8E A/RS-AA/005

115 Fused selection tables up to 690 V 6.2 Short-circuit protection 3RU2 thermal overload relay, type of coordination 1 and 2 Thermal overload relay Fuse links 1) Article No. Size S0 Setting range [A] gg am British s BS88 gg (415 V / 80 ka) Type of coordination 2) RU2126-1CB RU2126-1DB RU2126-1EB RU2126-1FB RU2126-1GB RU2126-1HB RU2126-1JB RU2126-1KB RU2126-4AB RU2126-4BB RU2126-4CB RU2126-4DB RU2126-4NB RU2126-4EB RU2126-4PB RU2126-4FB Size S2 3RU2136-4AB RU2136-4BB RU2136-4DB RU2136-4EB RU2136-4FB RU2136-4GB RU2136-4HB RU2136-4QB RU2136-4JB RU2136-4KB RU2136-4RB ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/

116 Fused selection tables up to 690 V 6.3 Short-circuit protection: Contactor + 3RU2 thermal overload relay, type of coordination 1 and Short-circuit protection: Contactor + 3RU2 thermal overload relay, type of coordination 1 and 2 Short-circuit protection up to 100 ka Type of coordination 1 and 2 Table 6-3 Fuse links according to IEC operating class gg, (NH DIAZED, NEOZED; type 3NA, 5SB, 5SE) relay thermal Contactor Fuse links 1) Article No. Setting range Article No. P [kw] Type of coordination 1 2) Size S00 Type of coordination 2 2) 3RU2116-0AB RU2116-0BB RU2116-0CB RU2116-0DB RU2116-0EB RU2116-0FB RU2116-0GB RU2116-0HB RU2116-0JB RU2116-0KB RU2116-1AB RU2116-1BB RU2116-1CB RU2116-1DB RU2116-1EB RU2116-1FB RU2116-1GB RU2116-1HB RT RU2116-1JB RT RU2116-1KB RT RU2116-4AB RT Configuration Manual, 01/2016, A8E A/RS-AA/005

117 Fused selection tables up to 690 V 6.3 Short-circuit protection: Contactor + 3RU2 thermal overload relay, type of coordination 1 and 2 relay thermal Contactor Fuse links 1) Article No. Setting range Article No. P [kw] Type of coordination 1 2) Size S0 Type of coordination 2 2) 3RU2126-1CB RT RU2126-1DB RT RU2126-1EB RT RU2126-1FB RT RU2126-1GB RT RU2126-1HB RT RU2126-1JB RT RU2126-1KB RT RU2126-4AB RT RU2126-4BB RT RU2126-4CB RT RU2126-4DB RT RU2126-4NB RT RU2126-4EB RT RU2126-4PB RT RU2126-4FB RT Size S2 3RU2136-4AB RT RU2136-4BB RT RU2136-4DB RT RU2136-4EB RT RU2136-4FB RT RU2136-4GB RT RU2136-4HB RT RU2136-4QB RT RU2136-4JB RT RU2136-4KB RT RU2136-4RB RT ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/

118 Fused selection tables up to 690 V 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay Short-circuit protection with fuses for motor feeders with 3RB30 and 3RB31, contactor mounting, and stand-alone assembly Table 6-4 Derating values for overload relay and contactor size S00 relay relay Setting range Contactor CLASS 5 / AC-3 derating values Article No. A Article No. kw 400 V 500 V 690 V 400 V 500 V 690 V 400 V 500 V 690 V 3RB3016-1RB RB3016-1NB RB3016-1PB RB3016-1SB RB3016-1TB Stand-alone assembly RT Stand-alone assembly RT Stand-alone assembly RT RT RT Stand-alone assembly RT RT RT Stand-alone assembly RT RT Configuration Manual, 01/2016, A8E A/RS-AA/005

119 Fused selection tables up to 690 V 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay Table 6-5 Derating values for overload relay and contactor size S0 relay relay Setting range Contactor CLASS 5 / AC-3 derating values Article No. A Article No. 3RB3026-1RB RB3026-1NB RB3026-1PB RB3026-1SB RB3026-1QB RB3026-1VB Stand-alone assembly kw 400 V 500 V 690 V 400 V 500 V 690 V 400 V 500 V 690 V RT Stand-alone assembly RT Stand-alone assembly RT Stand-alone assembly RT RT Stand-alone assembly RT RT RT RT Stand-alone assembly RT RT Configuration Manual, 01/2016, A8E A/RS-AA/

120 Fused selection tables up to 690 V 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay Table 6-6 Derating values for overload relay and contactor size S2 relay relay Setting range Contactor Article No. A Article No. 3RB3036-1UW1 Through hole technology 3RB3036-1UB0 3RB3036-1WW1 3RT RT RT RT Through hole technology 3RB3036-1WB Standalone installation support kw Screw terminals Standalone installation support CLASS 5E / 10E 20E 30E AC-3 derating values 400 V 500 V 690 V 400 V 500 V 690 V 400 V 500 V 690 V Screw terminals RT RT RT RT Configuration Manual, 01/2016, A8E A/RS-AA/005

121 Fused selection tables up to 690 V 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay Fuse links according to IEC Short-circuit protection up to 690 V / 100 ka Type of coordination 1 and 2 Table 6-7 Fuse links for overload relay and contactor size S00 relay relay Setting range Contactor Fuse links 1) Operating class gg 3) (690 V / 100 ka) NH type 3NA DIAZED type 5SB NEOZED type 5SE Acc. to IEC ) Operating class am (690 V / 100 ka) NH type 3ND British s BS88 4) gm (415 V / 80 ka) Type of coordination 2) Article No. A Article No. kw RB3016-1RB0 3RB3016-1NB0 3RB3016-1PB0 3RB3016-1SB0 3RB3016-1TB Stand-alone assembly RT Stand-alone assembly RT Stand-alone assembly RT RT RT Stand-alone assembly RT RT RT Stand-alone assembly RT RT ) Take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN ) NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gg 4) For BS88 fuses, fuse inserts are to be used according to the following table: Rated current [A] Fuse link 4 NIT4 6 NIT6 20 NIT20M20 25 NIT20M25 35 TIA32M35 50 TIA32M50 63 TIA32M TCP100M TCP100M200 Configuration Manual, 01/2016, A8E A/RS-AA/

122 Fused selection tables up to 690 V 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay Table 6-8 Fuse links for overload relay and contactor size S0 relay relay Setting range Contactor Fuse links 1) Operating class gg 3) (690 V / 100 ka) NH type 3NA Acc. to IEC ) Operating class am (690 V / 100 ka) NH type 3ND British s BS88 4) gm (415 V / 80 ka) DIAZED type 5SB NEOZED type 5SE Type of coordination 2) Article No. A Article No. kw RB Stand-alone assembly RB0 3RT RB Stand-alone assembly NB0 3RT RB Stand-alone assembly PB0 3RT RB Stand-alone assembly SB0 3RT RT RB Stand-alone assembly QB0 3RT RT RT RT RB Stand-alone assembly VB0 3RT RT ) Take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN ) NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gg 4) For BS88 fuses, fuse links are to be used according to the following table: Rated current [A] Fuse link 4 NIT4 6 NIT6 20 NIT20M20 25 NIT20M25 35 TIA32M35 50 TIA32M50 63 TIA32M TCP100M TCP100M Configuration Manual, 01/2016, A8E A/RS-AA/005

123 Fused selection tables up to 690 V 6.4 Short-circuit protection: Contactor + 3RB3 solid-state overload relay Table 6-9 relay Fuse links for overload relay and contactor size S2 relay Setting range Contactor Fuse links 1) Operating class gg 3) (690 V / 100 ka) NH type 3NA DIAZED type 5SB NEOZED type 5SE Type of coordination 2) According to IEC ) (690 V / 100 ka) Operating class am (690 V / 100 ka) NH type 3ND British s BS88 4) gm (415 V / 80 ka) Article No. A Article No. kw RB3036-1UW Through hole technology 3RB3036-1UB0 3RB3036-1WW1 3RT RT RT RT Through hole technology 3RB3036-1WB Standalone installation support Screw terminals Standalone installation support Screw terminals RT RT RT RT ) Take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN ) NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gg 4) For BS88 fuses, fuse links are to be used according to the following table: Rated current [A] Fuse link 4 NIT4 6 NIT6 20 NIT20M20 25 NIT20M25 35 TIA32M35 50 TIA32M50 63 TIA32M TCP100M TCP100M200 Configuration Manual, 01/2016, A8E A/RS-AA/

124 Fused selection tables up to 690 V 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 Short-circuit protection with fuses for motor feeders with 3UF7 and 3RB22/23/24 contactor mounting, and stand-alone installation Table 6-10 Derating values CLASS 5 / 10, 15 and 20 relay relay Setting range Contactor CLASS 5 / (3UF7 only) 20 AC-3 derating values Article No. A Article No. kw 400 V 500 V 690 V 400 V 500 V 690 V 400 V 500 V 690 V Size S00 3UF7100-1AA00-0/ 3UF7110-1AA00-0/ 3RB2906-2BG1 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ 3RB2906-2DG1 Size S0 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ 3RB2906-2DG1 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG Stand-alone assembly RT RT RT RT RT RT RT RT Stand-alone assembly RT RT RT RT RT RT Stand-alone assembly 3RT RT RT RT RT Configuration Manual, 01/2016, A8E A/RS-AA/005

125 Fused selection tables up to 690 V 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 relay relay Setting range Contactor CLASS 5 / (3UF7 only) 20 AC-3 derating values Article No. A Article No. kw 400 V 500 V 690 V 400 V 500 V 690 V 400 V 500 V 690 V Size S2 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG RT RT RT RT Configuration Manual, 01/2016, A8E A/RS-AA/

126 Fused selection tables up to 690 V 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 Table 6-11 Derating values CLASS 25, 30 and 35 relay relay Setting range Contactor CLASS 25 (3UF7 only) (3UF7 only) AC-3 derating values Article No. A Article No. Size S00 3UF7100-1AA00-0/ 3UF7110-1AA00-0/ 3RB2906-2BG1 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ 3RB2906-2DG1 Size S0 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ 3RB2906-2DG1 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG1 Size S2 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG1 kw 400 V 500 V 690 V 400 V 500 V 690 V 400 V 500 V 690 V Stand-alone assembly RT RT RT RT RT RT RT RT Stand-alone assembly RT RT RT RT RT RT Stand-alone assembly 3RT RT RT RT RT RT RT RT RT Configuration Manual, 01/2016, A8E A/RS-AA/005

127 Fused selection tables up to 690 V 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 Table 6-12 Derating values CLASS 40 relay relay Setting range Contactor CLASS 40 (3UF7 only) AC-3 derating values Size S00 Article No. A Article No. kw 400 V 500 V 690 V 3UF7100-1AA00-0/ 3UF7110-1AA00-0/ 3RB2906-2BG1 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ Size S0 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG1 Size S2 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG Stand-alone assembly RT RT RT RT RT RT RT RT Stand-alone assembly RT RT RT RT RT RT Stand-alone assembly RT RT RT RT RT RT RT RT RT Configuration Manual, 01/2016, A8E A/RS-AA/

128 Fused selection tables up to 690 V 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 Fuse links according to IEC Short-circuit protection up to 690 V / 100 ka, type of coordination 1 and 2 Table 6-13 Fuse links for overload relay and contactor size S00, S0 and S2 relay relay Setting range Contactor Fuse links 1) Acc. to IEC Operating class gg 3) (690 V / 100 ka) Operating class am (690 V / 100 ka) British s BS88 4) gm (415 V / 80 ka) Size S00 Type of coordination 2) Article No. A Article No. kw UF7100-1AA00-0/ 3UF7110-1AA00-0/ 3RB2906-2BG1 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ Size S0 3UF7101-1AA00-0/ 3UF7111-1AA00-0/ 3UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG Stand-alone assembly RT RT RT RT RT RT RT RT Stand-alone assembly RT RT RT RT RT RT Stand-alone assembly RT RT RT RT RT Configuration Manual, 01/2016, A8E A/RS-AA/005

129 Fused selection tables up to 690 V 6.5 Short-circuit protection contactor + 3RB22, 3RB23, 3RB24 electronic overload relay, and 3UF7 relay relay Setting range Contactor Fuse links 1) Acc. to IEC Operating class gg 3) (690 V / 100 ka) Operating class am (690 V / 100 ka) British s BS88 4) gm (415 V / 80 ka) Size S2 Type of coordination 2) Article No. A Article No. kw UF7102-1AA00-0/ 3UF7112-1AA00-0/ 3RB2906-2JG1 1) Take account of the operating voltage RT ) Assignment and short-circuit protective devices acc. to IEC ) NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gg 4) For BS88 fuses, fuse links are to be used according to the following table: 3RT RT RT Rated current [A] Fuse link 4 NIT4 6 NIT6 20 NIT20M20 25 NIT20M25 35 TIA32M35 50 TIA32M50 63 TIA32M TCP100M TCP100M200 Configuration Manual, 01/2016, A8E A/RS-AA/

130 Fused selection tables up to 690 V 6.6 Short-circuit protection: Contactor + 3RR2 monitoring relay, type of coordination 1 and Short-circuit protection: Contactor + 3RR2 monitoring relay, type of coordination 1 and 2 Short-circuit protection with fuses for motor feeders with 3RR2, contactor mounting, and stand-alone assembly Fuse links according to IEC and UL 508 Short-circuit protection up to 690 V / 100 ka, type of coordination 1 and 2 Table 6-14 Fuse links for monitoring relay and contactor size S00, S0, and S2 Monitoring relay relay Setting range Contactor Fuse links 1) Acc. to IEC ) Acc. to UL 508 4) Type of coordination 2) Article No. A Article No. kw 1 2 Size S00 3RR Stand-alone assembly Size S0 3RR Stand-alone assembly Size S2 3RR Stand-alone installation support 1) Take account of the operating voltage 3RT RT RT RT RT RT RT RT RT shortcircuit rating (600 V) High short-circuit rating RT RT RT RT ) Assignment and short-circuit protective devices acc. to DIN EN ) NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gg 4) RK1, RK5, J, CC 130 Configuration Manual, 01/2016, A8E A/RS-AA/005

131 Fused selection tables up to 690 V 6.7 Short-circuit protection: Star-delta (wye-delta) contactor 6.7 Short-circuit protection: Star-delta (wye-delta) contactor Short-circuit protection with fuses for motor feeders with 3RU21 up to 690 V / 100 ka, type of coordination 1 and 2 Table 6-15 Fuse links according to IEC operating class gg, (NH DIAZED, NEOZED; type 3NA, 5SB, 5SE) relay Contactor Fuse links 1) Line and delta Star Type of coordination 2) Article No. Setting range Article No. Article No. P [kw] 1 2 Size S00 3RU2116-0AB RU2116-0BB RU2116-0CB RU2116-0DB RU2116-0EB RU2116-0FB RU2116-0GB RU2116-0HB RU2116-0JB RU2116-0KB RU2116-1AB RU2116-1BB RU2116-1CB RU2116-1DB RU2116-1EB RU2116-1FB RU2116-1GB RU2116-1HB RU2116-1JB RU2116-1KB RU2116-4AB RT2017-3RT Configuration Manual, 01/2016, A8E A/RS-AA/

132 Fused selection tables up to 690 V 6.7 Short-circuit protection: Star-delta (wye-delta) contactor relay Contactor Fuse links 1) Line and delta Star Type of coordination 2) Article No. Setting range Article No. Article No. P [kw] 1 2 Size S0 3RU2126-1CB RT2024-3RT RU2126-1DB RT2024-3RT RU2126-1EB RT2024-3RT RU2126-1FB RT2024-3RT RU2126-1GB RT2024-3RT RU2126-1HB RT2024-3RT RU2126-1JB RT2024-3RT RU2126-1KB RT2024-3RT RU2126-4AB RT2024-3RT RU2126-4BB RT2024-3RT RU2126-4CB RT2024-3RT RU2126-4DB RT2024-3RT RU2126-4NB RT2026-3RT RU2126-4EB RT2026-3RT RU2126-4PB RT2026-3RT RU2126-4FB RT2026-3RT ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/005

133 Fused selection tables up to 690 V 6.8 Short-circuit protection: Soft starter + 3RU2 thermal overload relay 6.8 Short-circuit protection: Soft starter + 3RU2 thermal overload relay Short-circuit protection with fuses for motor feeders with 3RW30 soft starter and 3RU21 thermal overload relay up to 400 V / 65 ka, type of coordination 1 Table 6-16 Fuse links according to IEC operating class gg, (NH DIAZED, NEOZED; type 3NA, 5SB, 5SE) relay Contactor Soft starter Fuse links 1) Type of coordination 2) Article No. Setting range Article No. kw Article No. kw 1 Size S00 3RU2116-1CB RW RU2116-1DB RW RU2116-1EB RW RU2116-1FB RW RU2116-1GB RW RU2116-1HB RT RW RU2116-1JB RT RW RU2116-1KB RT RW RU2116-4AB RT RW Size S0 3RU2126-4BB RT RW RU2126-4CB RT RW RU2126-4DB RT RW RU2126-4NB RT RW RU2126-4EB RT RW RU2126-4PB RT RW RU2126-4FB RT RW Size S2 3RU2136-4FB RT RW RU2136-4GB RT RW RU2136-4HB RT RW RU2136-4QB RT RW RU JB RT RW RU2136-4KB RT RW RU2136-4FRB RT RW ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/

134 Fused selection tables up to 690 V 6.9 Short-circuit protection: Solid-state contactor, type of coordination 1 and Short-circuit protection: Solid-state contactor, type of coordination 1 and 2 Short-circuit protection with fuses for 3RF34 solid-state contactor Fuse links according to IEC and UL 508 Short-circuit protection up to 600 V / 50 ka, type of coordination 1 and 2 Table 6-17 Fuse links for monitoring relay and contactor size S00 and S0 Solid-state contactor Fuse links 2) Article No. 3RF3405-1BB54 40 C [A] 400 V [kw] 1) Acc. to IEC ) Acc. to UL 508 5) 500 V 3NW / 600 V 3NA 50 ka Type of coordination 3) 600 V shortcircuit rating 480 V High shortcircuit rating 600 V High short-circuit rating ka 65 ka 65 ka On request RF BB54 3RF BB54 3RF3416-1BB Reversing contactors 3RF On request BD54 3RF BD54 3RF3410-1BD ) Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of the protected motor. 2) Take account of the operating voltage 3) Assignment and short-circuit protective devices acc. to DIN EN ) NH type 3NA, DIAZED type 5SB, NEOZED type 5SE, operating class gg 5) Class K5, RK5, RK1, J 134 Configuration Manual, 01/2016, A8E A/RS-AA/005

135 Fused selection tables up to 690 V 6.10 Short-circuit protection: feeders with 3RW3 + 3RT + 3RB30/3RB Short-circuit protection: feeders with 3RW3 + 3RT + 3RB30/3RB31 Short-circuit protection with fuses for motor feeders with 3RW30 soft starter and 3RB30 / 3RB31 electronic overload relay up to 480 V / 65 ka, type of coordination 1 Table 6-18 Fuse links according to IEC operating class gg, (NH DIAZED, NEOZED; type 3NA, 5SB, 5SE) relay Contactor Soft starter Current carrying capacity Ie at 400 V and Fuse links 1) Type of coordination 2) Article No. Setting range Article No. kw Article No. kw 40 C 50 C 60 C 1 Size S00 3RB3016-1PB RT RW RT RW RB3016-1SB RT RW RT RW RT RW RB3016-1TB RT RW Size S0 3RT RW RB3026-1QB RT RW RT RW RT RW RB3026-1VB RT RW Size S2 3RT RW RT RW RT RW RB3036-1UB RT RW RB3036-1WB0 3RT RW RT RW RT RW RT RW RT RW ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/

136 Fused selection tables up to 690 V 6.11 Contactor assemblies for star-delta (wye-delta) start + 3RB30/31 solid-state overload relay and 3RT20 contactor 6.11 Contactor assemblies for star-delta (wye-delta) start + 3RB30/31 solid-state overload relay and 3RT20 contactor Short-circuit protection with fuses for contactor assemblies for star-delta (wye-delta) start with 3RB30/31 electronic overload relay and 3RT20 contactor up to 400 V / 65 ka, CLASS 10, type of coordination 1 and 2 Table 6-19 Fuse links according to IEC operating class gg, (NH DIAZED, NEOZED; type 3NA, 5SB, 5SE) threephase motor 4-pole at 400 V AC 2) relay Line contactor / delta contactor Star contactor Fuse links 1) output kw Size S00 current A Article No. Setting range A Article No. Article No. Type of coordination 2) RB3016-1PB RB3016-1SB RT RB3016-1TB RT2018-3RT Size S RB3016-1SB RT2024-3RT RB3026-1QB RT2024-3RT RT2026-3RT RT2026-3RT RT2027-3RT ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Configuration Manual, 01/2016, A8E A/RS-AA/005

137 Fused selection tables up to 690 V 6.12 Contactor assemblies for star-delta + electronic overload relay 3RB2. or 3UF7 and contactor 3RT Contactor assemblies for star-delta + electronic overload relay 3RB2. or 3UF7 and contactor 3RT20 Short-circuit protection with fuses for contactor assemblies for star-delta (wye-delta) start with 3UF7 electronic overload relay and 3RT20 contactor up to 400 V / 65 ka, CLASS 10, type of coordination 1 and 2 Table 6-20 Fuse links according to IEC operating class gg, (NH DIAZED, NEOZED; type 3NA, 5SB, 5SE) three-phase motor 4-pole at 400 V AC 2) output kw Size S00 current A relay Article No. Setting range A Line contactor / delta contactor Star contactor Fuse links 1) Article No. Article No. Type of coordination 2) UF7100-1AA00-0/ RB2906-2BG UF7101-1AA00-0/ RT RT2018-3RT Size S UF7101-1AA00-0/ RT2024-3RT RT2024-3RT RT2026-3RT RT2026-3RT RT2027-3RT ) Please take account of the operating voltage 2) Assignment and short-circuit protective devices acc. to DIN EN Note The specified maximum fuse only provides short-circuit protection in the case of fuse values where line overload protection can only be achieved with a larger conductor cross-section than can be connected to the device. When this fuse is used, the line overload protection in accordance with VDE 0100 must be ensured at another point e.g. by means of an overload relay. Configuration Manual, 01/2016, A8E A/RS-AA/

138 Fused selection tables up to 690 V 6.12 Contactor assemblies for star-delta + electronic overload relay 3RB2. or 3UF7 and contactor 3RT Configuration Manual, 01/2016, A8E A/RS-AA/005

139 Installation guidelines Mounting variants under different conditions of use The load feeders can be mounted horizontally or vertically. Horizontal installation Vertical installation 1) Maximum 6 load feeders Configuration Manual, 01/2016, A8E A/RS-AA/

140 Installation guidelines 7.1 Mounting variants under different conditions of use The following table shows the installation guidelines for the fuseless load feeders. Table 7-1 Mounting variants - fuseless load feeders with link module Combination Setting range Distance between feeders starter and contactor A mm h, v C Permissible installation: h = horizontal, v = vertical Max. ambient temperature Ta Use under increased vibration and shock load 1) 3RA21 direct-on-line starter, screw terminal, DIN rail or wall S h, v 60 Unlimited h 60 0 h, v 40 S h, v 60 Unlimited h 60 0 h, v 40 S h, v 60 Unlimited 3RA21 direct-on-line starter, screw terminal, busbar S h 40 Vibration and shock kit 8US1998-1CA10 10 h 60 required 10 v h h, v 40 S h 40 Vibration and shock kit 8US1998-1CA10 10 h 60 required 10 v h h, v 40 S h, v 60 Vibration and shock kit 8US1998-1DA10 required 65 0 h, v 40 Vibration and shock kit 8US1998-1DA10 required 140 Configuration Manual, 01/2016, A8E A/RS-AA/005

141 Installation guidelines 7.1 Mounting variants under different conditions of use Combination Setting range Distance between feeders starter and contactor A mm h, v C 3RA22 reversing starter, screw terminal, DIN rail or wall Permissible installation: h = horizontal, v = vertical Max. ambient temperature Ta S h, v 60 Unlimited h 60 0 h, v 40 Use under increased vibration and shock load 1) S h, v 60 DIN rail adapter required h 60 (already included with 3RA22) 0 h, v 40 S h, v 60 Unlimited 3RA22 reversing starter, screw terminal, busbar S h 60 Vibration and shock kit 8US1998-1CA10 0 v 40 required h v 40 S h 60 Vibration and shock kit 8US1998-1CA10 0 v 40 required h v 40 S h, v 60 Vibration and shock kit 8US1998-1DA10 required 65 0 h, v 40 Vibration and shock kit 8US1998-1DA10 required Configuration Manual, 01/2016, A8E A/RS-AA/

142 Installation guidelines 7.1 Mounting variants under different conditions of use Combination Setting range Distance between feeders starter and contactor A mm h, v C 3RA21 direct-on-line starter, spring-loaded terminal, DIN rail or wall Permissible installation: h = horizontal, v = vertical Max. ambient temperature Ta S h, v 60 Unlimited h 60 0 h, v 40 S h, v 60 Unlimited 3RA21 direct-on-line starter, spring-loaded terminal, busbar h 60 0 h, v 40 Use under increased vibration and shock load 1) S h 40 Vibration and shock kit 8US1998-1CA10 10 h 60 required 10 v h v 40 S h 40 Vibration and shock kit 8US1998-1CA10 10 h 60 required 10 v h v Configuration Manual, 01/2016, A8E A/RS-AA/005

143 Installation guidelines 7.1 Mounting variants under different conditions of use Combination Setting range Distance between feeders starter and contactor A mm h, v C 3RA22 reversing starter, spring-loaded terminal, DIN rail or wall Permissible installation: h = horizontal, v = vertical Max. ambient temperature Ta S h, v 60 Unlimited h 60 0 h, v 40 Use under increased vibration and shock load 1) S h, v 60 DIN rail adapter required h 60 (already included with 3RA22) 0 h, v 40 3RA22 reversing starter, spring-loaded terminal, busbar S h 60 Vibration and shock kit 8US1998-1CA10 0 v 40 required h v 40 S h 60 Vibration and shock kit 8US1998-1CA10 0 v 40 required h v 40 Configuration Manual, 01/2016, A8E A/RS-AA/

144 Installation guidelines 7.1 Mounting variants under different conditions of use Combination Setting range Distance between feeders starter and contactor A mm h, v C starter and soft starter, screw terminal, DIN rail or wall Permissible installation: h = horizontal, v = vertical Max. ambient temperature Ta Use under increased vibration and shock load 1) S ) 2) The feeder must be screwed tight to the top of the motor starter with two screws and fastened to the bottom of the soft starter with a self-locking screw. Not approved for railways, power plants, or shipbuilding. S0 32 2) 2) The feeder must be screwed tight to the top of the motor starter with two screws and fastened to the bottom of the soft starter with a self-locking screw. Not approved for railways, power plants, or shipbuilding. S2 (only with DIN rail adapter 3RA2932-1CA00) 65 2) 2) 2) Unlimited starter and soft starter, spring-loaded terminal, DIN rail or wall S ) 2) The feeder must be screwed tight to the top of the motor starter with two screws and fastened to the bottom of the soft starter with a self-locking screw. Not approved for railways, power plants, or shipbuilding. S0 32 2) 2) The feeder must be screwed tight to the top of the motor starter with two screws and fastened to the bottom of the soft starter with a self-locking screw. Not approved for railways, power plants, or shipbuilding. starter and solid-state contactor, screw terminal, DIN rail or wall Direct-on-line starters (sizes S00 / S0) 16 2) 2) Unlimited Not approved for railways, power plants, or shipbuilding. Reversing starters (sizes S00 / S0) 7,4 2) 2) Unlimited Not approved for railways, power plants, or shipbuilding. 1) Vibration and shock tests are carried out in accordance with SN as well as with the relevant standards for railways, shipbuilding, and power plants. 2) Please consult Technical Assistance ( 144 Configuration Manual, 01/2016, A8E A/RS-AA/005

145 Installation guidelines 7.2 Minimum clearances to grounded or live parts (400 V / 500 V / 690 V AC) 7.2 Minimum clearances to grounded or live parts (400 V / 500 V / 690 V AC) Maintain the following clearances when mounting the 3RA21 / 3RA22 assemblies: Table 7-2 Installation guidelines for 400 V / 500 V / 690 V AC (size S00 / S0) Clearance from grounded or live parts as well as from molded-plastic cable ducts according to IEC starter Contactor Y [mm] X2 1) [mm] Z [mm] Rated operating voltage 400 V 3RV2.1 3RT RV2.2 3RT Rated operating voltage 500 V 3RT RV2.1 3RT RV2.2 3RT RV2.2 + limiter 3RT Rated operating voltage 690 V 3RV2.1 3RT RV2.1 / 3RV2.2 + limiter (32 A) 3RT201 / 3RT RV2.1 / 3RV2.2 + limiter (50 A) 3RT ) Minimum clearance from contactor at the front. There is no minimum clearance requirement at the front for the motor starter. Note Installation instructions for S0 motor starter s from 36 A Minimum cable length between motor starter and contactor: 150 mm. Minimum clearance between motor starter and contactor: 100 mm. Configuration Manual, 01/2016, A8E A/RS-AA/

146 Installation guidelines 7.2 Minimum clearances to grounded or live parts (400 V / 500 V / 690 V AC) Table 7-3 Installation guidelines for 400 V / 500 V / 690 V AC (size S2) Clearance from grounded or live parts as well as from molded-plastic cable ducts according to IEC starter Contactor Y1 [mm] Y2 [mm] X1 [mm] X2 [mm] Z [mm] Rated operating voltage 400 V 3RV2.3 3RT Rated operating voltage 500 V 3RV2.3 3RT203 On request 3RV2.3 + limiter (80 A) 3RT203 On request Rated operating voltage 690 V 3RV limiter (80 A) 3RT203 On request 146 Configuration Manual, 01/2016, A8E A/RS-AA/005

147 Service and support Siemens Industry Online Support Information and Service In Siemens Industry Online Support, you can obtain up-to-date information from our global support database quickly and simply. To accompany our products and systems, we offer a wealth of information and services that provide support in every phase of the lifecycle of your machine or plant from planning and implementation, through commissioning, up to maintenance and modernization: Product support Application examples Services Forum mysupport Link: Siemens Industry Online Support ( Configuration Manual, 01/2016, A8E A/RS-AA/

148 Service and support 8.1 Siemens Industry Online Support Product support You will find here all the information and comprehensive know-how covering all aspects of your product: FAQs Our answers to frequently asked questions. Manuals/operating instructions Read online or download, available as PDF or individually configurable. Certificates Clearly sorted according to approving authority, type and country. Characteristic curves For support in planning and configuring your system. Product announcements The latest information and news concerning our products. Downloads You can find here updates, service packs, HSPs and much more for your product. Application examples Function blocks, background and system descriptions, performance statements, demonstration systems, and application examples, clearly explained and represented. Technical data Technical product data for support in planning and implementing your project. Link: Product support ( 148 Configuration Manual, 01/2016, A8E A/RS-AA/005

149 Service and support 8.1 Siemens Industry Online Support mysupport With "mysupport", your personal workspace, you get the very best out of your Industry Online Support. Everything to enable you to find the right information every time. The following functions are now available: Personal messages Your personal mailbox for exchanging information and managing your contacts Inquiries Use our online form for specific solution suggestions, or send your technical inquiry directly to a specialist in Technical Support Notifications Make sure you always have the latest information - individually tailored to your needs Filters Simple management and re-use of your filter settings from Product Support and the Technical Forum Favorites / Tags Create your own knowledge database by assigning "Favorites" and "Tags" to documents simply and efficiently Entries last viewed Clear presentation of your last viewed entries Documentation Configure your individual documentation from different manuals quickly and without complications Personal data Change personal data and contact information here CAx data Simple access to thousands of items of CAx data such as 3D models, 2D dimension drawings, EPLAN macros and much more Configuration Manual, 01/2016, A8E A/RS-AA/

150 Service and support 8.1 Siemens Industry Online Support SIEMENS Industry Support App DataMatrix codes primarily enable extremely fast and convenient access to all devicespecific information relating to an article number in the SIEMENS Service&Support Portal, such as operating instructions, manuals, data sheets, FAQs, etc. We provide the SIEMENS Industry Support app free of charge for this purpose and it can be used on most commercially available smart phones and tablets. The SIEMENS Industry Support app is available for ios and Android-based devices. You can download the app from the following links: Link for Android Link for ios Link for Windows Phone 150 Configuration Manual, 01/2016, A8E A/RS-AA/005

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Programming and Operating Manual

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Programming and Operating Manual Validity 1 Improvements in STEP 7 2 SIMATIC Improvements in WinCC 3 Readme Programming and Operating Manual 07/2013 Legal information Warning notice system This manual contains notices you have to observe

More information

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller

More information

Validity 1. Installation 2 SIMATIC. WinCC flexible Tag simulator Update 1. Readme

Validity 1. Installation 2 SIMATIC. WinCC flexible Tag simulator Update 1. Readme Validity 1 Installation 2 SIMATIC WinCC flexible Readme 05/2011 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well

More information

3RV Motor Starter Protectors up to 100 A

3RV Motor Starter Protectors up to 100 A General data Overview S0 motor 3RV1 motor are compact, current limiting motor which are optimized for load feeders. The motor are used for switching and protecting three-phase induction motors of up to

More information

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels 1 Introduction 2 Overview of NEC Article 409

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

Low Voltage Controls & Distribution

Low Voltage Controls & Distribution SIRIUS Datasheet 2009 Low Voltage Controls & Distribution Answers for industry. s Pressing, equipping, transporting. These functions run in many automated production environments. You ll find everything

More information

LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2

LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2 Overview Description, device design, dimension drawing 1 Power supply Operating Instructions Mounting/Disassembly 2 Mounting position, installation clearances 3 Installation 4 Applications 5 Technical

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Controls Solid-State Switching Devices

Controls Solid-State Switching Devices Controls Solid-State Switching Devices Introduction Overview 3RF21 3RF20 3RF23 3RF29 SIRIUS SC solid-state switching devices Solid-state relays 22.5 mm solid-state relays, 5 mm solid-state relays Solid-state

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

How can a charging station for electric vehicles be set up simply and safely?

How can a charging station for electric vehicles be set up simply and safely? SB18 Building > Electromobility > Charging Station Design How can a charging station for electric vehicles be set up simply and safely? Requirement In order to supply electric vehicles with electric power,

More information

Number 1 in efficiency

Number 1 in efficiency PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why

More information

CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device

CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device SIMATIC PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device Introduction 1 Preparation 2 Learning units 3 Further Information

More information

SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2. SIMATIC ET 200S distributed I/O SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Manual 04/2007 A5E01077385-01 Safety Guidelines

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

LOGO!Power. Power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/disassembly

LOGO!Power. Power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/disassembly Overview Safety instructions 1 Power supply Operating Instructions Description, device design, dimension drawing 2 Mounting/disassembly 3 Mounting position, mounting clearances 4 Installation 5 Technical

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Frequency Converter Fv

Frequency Converter Fv 2 Bosch Rexroth AG Electric Drives and Controls Documentation Brake chopper with up to 30 kw continuous braking power Easy to operate and service (detachable fan, LCD operating panel with copy function)

More information

WinCC Runtime Professional Readme SIMATIC HMI. WinCC V11 SP1. Readme WinCC Runtime Professional. Special considerations for Windows 7.

WinCC Runtime Professional Readme SIMATIC HMI. WinCC V11 SP1. Readme WinCC Runtime Professional. Special considerations for Windows 7. WinCC Runtime Professional Readme SIMATIC HMI WinCC V11 SP1 Special considerations for Windows 7 1 Installation 2 Runtime 3 Options 4 HMI devices 5 Readme WinCC Runtime Professional System Manual Online

More information

SIMOCODE ES Online Help. SIMOCODE pro. SIMOCODE ES V12 Online Help. Tooltips SIRIUS + SIMOCODE. General information. Device configuration

SIMOCODE ES Online Help. SIMOCODE pro. SIMOCODE ES V12 Online Help. Tooltips SIRIUS + SIMOCODE. General information. Device configuration SIMOCODE ES Online Help Tooltips SIRIUS + SIMOCODE 1 General information 2 SIMOCODE pro Programming and Operating Manual Device configuration 3 Diagnostics & Online 4 Parameterization of the modules 5

More information

Safety Relays ESM/ESM-F

Safety Relays ESM/ESM-F Safety Relays ESM/ESM-F More than safety. Safety More than safety. Emil Euchner, the company s founder and inventor of the multiple limit switch, circa 1928. Around the world the Swabian specialists in

More information

Softstarters Type PSR

Softstarters Type PSR Catalog Softstarters Softstarters ABB Softstarters General To the left: A combination with PSR and a manual Motor Starter MS116 Above: PSR16, PSR30 and PSR 45 1 ABB Automation Products serve customers

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

SMC -3 Specifications

SMC -3 Specifications Technical Data SMC -3 Specifications Bulletin Number 150 Topic Page Product Overview 2 Standards Compliance and Certifications 2 Features 3 Catalog Number Explanation 4 Wiring Diagrams 6 General Specifications

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4 Present sample project 1 HMI configuration 2 SIMATIC Getting Started Insert HMI device from libraries 3 Configuring HMI connection 4 Configuring system diagnostics 5 Simulating an HMI device 6 05/2014

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Industrial Communication

Industrial Communication Industrial Communication / AS-Interface System overview /5 - Transmission technology /6 - Configuration examples /7 - Communication overview Slaves Contactors and contactor assemblies for AS-Interface

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2. SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation

More information

SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2. SIMATIC ET 200S distributed I/O SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Manual 04/2007 A5E01077339-01 Safety Guidelines

More information

Industrial Controls SIRIUS Controls

Industrial Controls SIRIUS Controls Industrial Controls SIRIS Controls Star-delta (Wye-delta) Switching of Three-phase Induction Motors Transient Current Peak Reduction using a Preferred Circuitry Configuration for Clockwise and Counterclockwise

More information

SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01

SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal

More information

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives. Load-balanced control application

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives. Load-balanced control application SINAMICS DCM DC converters from 6 kw to 2500 kw for variable-speed direct-current drives Edition 01-12/2010 SINAMICS drives SINAMICS DCM Compact User Manual Legal information Warning notice system This

More information

Protection Equipment

Protection Equipment Protection Equipment Price groups 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J, 4N1 /2 Introduction Motor starter protectors/ circuit breakers SIRIUS 3RV2 motor starter protectors/ circuit breakers up to

More information

Products and solutions for lifting systems

Products and solutions for lifting systems Products and solutions for lifting systems 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric headquarters founded

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

Safety along the complete line: SIRIUS 3SE7 cable-operated switches. sirius COMMANDING & SIGNALING

Safety along the complete line: SIRIUS 3SE7 cable-operated switches. sirius COMMANDING & SIGNALING Safety along the complete line: 3SE7 cable-operated switches sirius COMMANDING & SIGNALING Everything well under control. 3SE7 cable-operated switches With cable-operated switches from our 3SE7 product

More information

Panorama. Motor protection and control Manual motor starters, contactors and overload relays

Panorama. Motor protection and control Manual motor starters, contactors and overload relays Panorama Motor protection and control Manual motor starters, contactors and overload relays ABB sets a new standard in motor control and power switching Featuring AF technology as standard, the latest

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 2494434 (012730_C_000) Issued to: Siemens AG DF CP R&D V 3 Werner-von-Siemens-Strasse 48 Amberg, 92224 GERMANY Attention: Michael Schroeck The products listed below

More information

XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications

XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications The XFE Soft Starter range provides a combination of competitive prices, flexible

More information

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved.

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved. SIMATIC S7-1200 It s the Interplay that makes the difference SIMATIC S7-1200 Controller SIMATIC S7-1200 CPUs CPU 1211C 3 configurations per CPU Dimensions W x H x D (mm) CPU 1212C CPU 1214C DC/DC/DC, AC/DC/RLY,

More information

Performing an automated installation

Performing an automated installation Principles of an automated installation 1 Automated installation using the record / play mode 2 Automated installation via the command line 3 Parameter list 4 Return values from the installation process

More information

Rotary Disconnect Switch Specifications

Rotary Disconnect Switch Specifications Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

Siemens AG 2008. Highly flexible system-based switching, protecting and starting. SIRIUS Modular System SIRIUS. Answers for industry.

Siemens AG 2008. Highly flexible system-based switching, protecting and starting. SIRIUS Modular System SIRIUS. Answers for industry. Siemens AG 00 Highly flexible system-based switching, protecting and starting. SIRIUS Modular System SIRIUS Answers for industry. Siemens AG 00 Everything for the electrical cabinet: SIRIUS Modular System.

More information

BETA Protecting SITOR Semiconductor Fuses

BETA Protecting SITOR Semiconductor Fuses BETA Protecting SITOR Semiconductor Fuses /2 Product overview /3 /17 SITOR, cylindrical fuse design /22 SILIZED, NEOZED and DIAZED design Siemens ET B1 /2008 Product overview Overview Devices Page Field

More information

THERMAL MANAGEMENT SOLUTIONS

THERMAL MANAGEMENT SOLUTIONS t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single

More information

mecotron Safety relay ESTOP-2 For emergency stop monitoring

mecotron Safety relay ESTOP-2 For emergency stop monitoring E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated

More information

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET safe via BUS or NET AS-i 3.0 Gateways, safe via NET or BUS safe and Safe Link in one device up to 450 devices 2 / 1 Master, NET / BUS Slave AS-i Safety input slaves report via safe AS-i Safety output slaves

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

EFC 3600. Frequency converters

EFC 3600. Frequency converters 2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation

More information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

Products and solutions for pumping, irrigation and piping

Products and solutions for pumping, irrigation and piping Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12 Configuration limits for products of the SIMATIC NET PC Software V12 Communications partners and configuration limits for HARDNET-PB DP-Base 1 software Configuration limits, SOFTNET-PB DP 2 SIMATIC NET

More information

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M Compact Operating Instructions Legal information Qualified Personnel The product/system described in this documentation

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

... Electronic Softstarter...

... Electronic Softstarter... . CT-START Electronic Softstarter. 6 A. to 900. A......... CT START CT-START is a multi-function electronic system with a microcontroller and thyristors, designed for use with all 3-phase squirrel cage

More information

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks Loading the block library 1 Deleting program block Main [OB1] 2 TIA Portal SIMATIC Getting Started Copying program blocks 3 Cyclic interrupt OB 4 Copying tag tables 5 Compiling a project 6 Load project

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager

Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager SACE Emax 2 From Circuit-Breaker to Power Manager Our customers need more efficient solutions, to Increase

More information

Vilter motor starter solutions The NEW industry standard in motor starter packages

Vilter motor starter solutions The NEW industry standard in motor starter packages Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.

More information

Automation Unit TM 1703 ACP Flexible automation and telecontrol

Automation Unit TM 1703 ACP Flexible automation and telecontrol Automation Unit Flexible automation and telecontrol Power Transmission and Distribution Outstanding performance: Automate simply with Highly complex and yet fully transparent automation solutions are not

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

PNOZsigma - Base units

PNOZsigma - Base units PNOZsigma - Base units Register Login Sensors Control and Communication Electronic monitoring relays Safety Relays PNOZ X PNOZsigma PNOZelog PNOZmulti PNOZpower Configurable control systems Programmable

More information

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of

More information

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry.

Siemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry. The perfect solution for basic servo applications Brochure May 2011 SINAMICS Answers for industry. with 1FL5 servomotors The solution for basic servo applications There is a requirement to automate motion

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20 Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation

More information

13 SERIES. Electronic step relays 10-16 A 13.81 13.91

13 SERIES. Electronic step relays 10-16 A 13.81 13.91 13 Electronic step relays 10-16 A 13 13.81 - Electronic step relay - Rail mount - 1 Pole 13.91 - Electronic step relay and timing step relay Switch box mount - 1 Pole Fixed time (10 minutes) timing function

More information

MINIMAT-EC-Servo Screwdriver Spindles

MINIMAT-EC-Servo Screwdriver Spindles Screwdriving technology Automation Air motors Air tools Screwdriver Spindles electric MINIMAT-EC-Servo Screwdriver Spindles Maximum Flexibility and process Control Straight Spindle Form - Torque range

More information

TX OPEN RS232/485 module

TX OPEN RS232/485 module s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the

More information

MINI MCR-SL-R-UI(-SP)

MINI MCR-SL-R-UI(-SP) Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

Industrial OEM products

Industrial OEM products Line card Industrial OEM products Complete product offering usa.siemens.com Siemens Industry, the global leader in Industrial Automation. In response to today s increasing competitive pressure, it is more

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Variable speed drives for synchronous and asynchronous motors

Variable speed drives for synchronous and asynchronous motors Imptant infmation Altivar XXXXXX Variable speed drives f synchronous and asynchronous mots ATEX manual F ATEX applications in explosive gas atmosphere in the presence of combustible dust 0/010 S1A0 www.schneider-electric.com

More information

40.3. Control Relays and Timers

40.3. Control Relays and Timers .3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories

More information

connecdim Gateway G1 Ethernet TCP/IP to DALI

connecdim Gateway G1 Ethernet TCP/IP to DALI Gateway G1 Ethernet TCP/IP to LI Independent lighting control for up to 256 LI gears on 4 LI lines Can be expanded by connecting multiple gateways on the same network Cloud based web interface for configuration

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information