A1000 Cheat Sheet (Open Loop Vector)
|
|
|
- Pauline Jacobs
- 10 years ago
- Views:
Transcription
1 A1000 Cheat Sheet (Open Loop Vector) The following procedure is a supplement to supplied with this equipment and will guide the user in properly wiring the A1000 and. It will also show the user how to configure the A1000 in open loop vector mode for a general purpose application. Danger: Improper wiring can and will cause bodily harm as well as damage to the equipment. When installing the system, be sure to follow good wiring practices and all applicable codes. Ensure that the mounting of components is secure and that the environment, such as extreme dampness, poor ventilation, etc. will not cause system degradation. 1 A1000 Model Identification and Mounting To make sure you received the correct model, it is essential to verify the A1000 nameplate with your order and make sure the A1000 has the correct rating so it can be used with your. Please check the nameplate information as shown in the example below. Drive Spec Drive Model Normal / Heavy Duty Amps Output Software Version Weight Serial UL File 2 The environmental specifications such as avoiding excessive dampness, extreme temperatures, chemical exposure, corrosive areas, etc. to avoid damage to the equipment and to maintain safety. B1 - B2 From the main reference press once until the Digital Operator shows the Auto-Tuning menu then press Motor Rotation Test once until the shows parameter Enter Motor in kw (Kilowatt) DC Bus terminals location varies by model. Motor HP to kw = HP x Example: 10HP = 10 x = 7.46 kw Digit First Digit Green LED turns on. To change direction of rotation swap any two of the three leads (See 2) to chassis 1Ø * 3Ø Fig. 1 and Output Motor Electrical ions for Models: 2_0004-2_0056, 4_0002-4_0044 and 5_ to move the cursor one to increase the frequency reference (d1-01) to Hz. to save frequency reference Hz NOT USED BUS TERMINALS: DO NOT CONNECT TO GROUND on the. The on the. If rotation is not correct, then either reverse Phase Order using parameter b1-14 or power down the drive, wait five minutes and swap 2 leads. To change direction of rotation swap any two of the three leads (See 2) to chassis DANGER minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components. 1Ø * 3Ø Fig. 2 and Output Motor Electrical ions for Models: 2_0110 & Larger and 4_0058 & Larger * Make sure the A1000 has been properly sized for single phase input power. For best performance, the drive input supply voltage must be at least equal to or greater than the rated voltage. use to select the digit you would like to change and to adjust value and press to save. to select the next parameter and follow the same procedure described above to adjust its value. T1-04 Rated Voltage (e.g. 230 V, 460 V) T1-04 Rated current (e.g A, 22.0 A) T1-05 Rated Frequency (e.g Hz) T1-06 of Poles (e.g. 4 Poles) T1-07 Rated Speed (e.g rpm) For standard AC s use the default setting for base frequency (60Hz), poles (4) and rated speed. After setting parameter T1-07 press to select the Auto-Tuning start command. should now be operating at low speed running in the correct forward (clockwise) direction. position to the right and Improper removal of the A1000 terminal cover as well as front cover can cause extensive damage to the A1000. To avoid damage to these items, please pay particular attention to the A1000 User Manual, Document No. SIEP C A, Section 3.5, Removing and Attaching the Terminal Cover. Open Chassis In this step the A1000 is setup for use with the. Make sure all protective covers have been re-attached then apply power to the A1000. DO NOT RUN THE MOTOR. T1-02 Mtr Rated then press Removing and Attaching the Terminal Cover NEMA 1 4 Rotational Auto-tuning (De-couple Motor from Load) cover is fastened and all wiring connections are secure. minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components. WARNING DO NOT CONNECT ANY OF THE FOLLOWING TERMINALS TO EARTH GROUND Please read this cheat sheet and provided with the A1000 thoroughly before attempting any installation. In this step the is checked for proper direction and operation. This test is to be performed solely from the digital operator. Apply power to the A1000 after all the electrical connections have been made and protective covers have been re-attached. At this point, DO NOT RUN THE MOTOR, the should display as shown in. DANGER; LETHAL VOLTAGES ARE PRESENT- Before Mounting the A1000 The clearances to be maintained around the enclosure for adequate ventilation. Check Motor Direction (Motor uncoupled from Load) applying power to the A1000, ensure that the terminal In the case of systems with more than one A1000, follow the above procedure for each A1000 and. 3 Fig.1 & 2 below show the electrical connections for the input power and terminals for various A1000 models. Select the proper diagram for the model you are installing (see 1). WITH POWER OFF make the appropriate connections. Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is ed properly as shown in fig. 1 Check that the available power will meet the input power requirements. Ensure that the output power from the A1000 is compatible with the requirements. The mounting of the A1000 is extremely important regarding environment and accessibility. Depending on your system, there are various models available and the mounting dimensions (footprint) may be different. Because the mounting procedure is fairly extensive, it is beyond the scope of this document; the user is referred to the A1000 User Manual (Document No. SIEP C A) received with the A1000, Section 2.2 Mechanical Installation. Match the model that you received and follow the procedure described in the manual to ensure a safe and functional installation. In cases where the system has more than one A1000, refer to the proper clearances required for adequate ventilation. Please pay particular attention to: Motor and Line Page 1 of 2 turned off. Use precaution, and refer to Fig.1 or 2, swap any two of the three output leads to the (U/T1, V/T2 and W/T3). After the wiring change, repeat 3 and recheck direction. Warning Sudden movement hazard. The A1000 and may start unexpectedly during Auto-Tuning. Warning Electric Shock Hazard. High voltage will be supplied to the when stationary Auto-Tuning is performed. Do not touch the during auto-tuning. Notice: Auto-Tuning will not function properly when a brake is engaged on the load. Ensure the shaft can freely rotate. Never perform an Auto-Tune with connected to a load. on the. The A1000 will now start the Auto-tuning procedure. The display will show message Tune Successful when the Auto-Tuning procedure has been successfully completed. Please reference the A1000 User Manual or repeat the procedure again if the display shows an error message.
2 A1000 Cheat Sheet (Open Loop Vector) Page 2 of 2 5 Changing Parameters and Monitoring the A Selecting Start/Stop and Speed Method 7 Quick Start Parameters This step shows how to access and modify a A1000 parameter as well as how to monitor A1000 signals such as output frequency and current. Make sure all protective covers have been re-attached and power Access Parameter Menu and Change Parameter Value two times until the digital operator shows the parameter menu. This step shows how to setup the sequence and reference method of the A1000. The sequence method determines how the A1000 drive receives its start and stop command and the reference method determines how the speed of the is controlled. Make sure all protective covers have been re-attached and power This section may require you to change one or more A1000 parameters. Please refer to 5 for a detailed explanation on how to change parameters. 1. Adjust speed / frequency from the SELECT SPEED METHOD b1-01 The following table lists the general purpose application parameters as well as frequently asked questions. This section may require you to change one or more A1000 parameters. Please refer to 5 for a detailed explanation on how to change parameters. GENERAL PURPOSE APPLICATION PARAMETERS Parameter Default Value Description Comments b b Reference Source Speed Control Method Run Source / Start/Stop Control Method b Stop Method Selection 0 = (Adjust Motor Speed from keypad) 1 = Terminals (Speed Pot. / 0 10V / 4 20mA) 0 = (Start/Stop from keypad) 1 = Terminals (Start/Stop using external contact / switch) 0 = Ramp to stop (Motor ramps down at stop command) 1 = Coast to stop (Motor freewheels at stop command) To adjust frequency use / and press. b Operation 0 = Allow to run in reverse direction 1 = direction prohibited 2. Adjust speed / frequency from external terminals (0-10V / 4-20mA Signal) C sec. Acceleration Time The time it takes to ramp up from 0 to maximum speed. Select Digit C sec. Deceleration Time The time it takes to ramp down from maximum speed to 0. C Heavy / Normal Duty 0 = Heavy Duty (Use for conveyor, mixer, applications) 1 = Normal Duty (Use for fan and pump applications) V AC V- A1 A2 A3 FM AM AC MP RP AC V AC V- A1 A2 A3 FM AM AC MP RP AC d Hz Frequency Reference Frequency setting when speed is set from the keypad. d % Frequency Upper Limit Maximum speed allowed (e.g. 100 % = Max rpm) Go to Next Digit Potentiometer 2K Ohm 0 ~ 10Vdc V AC V- A1 A2 A3 FM AM AC MP RP AC Located inside the drive on the terminal board d % Frequency Lower Limit Minimum speed allowed (e.g. 100 % = Max rpm) E2-01 * Motor Rated Current Motor nameplate current L Motor Overload Selection 0 = Disabled 1 = Standard Fan Cooled Motor 2 = Standard Blower Cooled Motor 3 = Vector Duty Motor Note: 2 nd row of terminal board is shown here. 4 ~ 20mA L min Motor Overload Time Sets the thermal overload protection time. FREQUENTLY ASKED QUESTIONS to Edit Mode Modify Value Save New Value Monitor Motor Frequency and Motor Current SELECT START / STOP CONTROL METHOD 1. Start / Stop Control from b1-02 Question: How do I reset the drive back to factory default settings? Go to parameter A1-03 and set value 2220 for 2 wire control or 3330 for 3 wire control (Please refer to 6 for wiring diagram) Question: How do I adjust the time it takes the to speed up or slow down? A1000 power-up state Output Frequency and Motor Current can be monitored simultaneously. 2. Start / Stop Control from external terminals (switch or relay contact) ( Factory Default) Adjust the acceleration time parameter C1-01 and deceleration time C1-02. Question: How do I prevent my drive from tripping on an OV fault (overvoltage) while my is ramping down? Increase deceleration time parameter C1-02. To monitor output frequency and current or signals Question: How do I prevent my drive from tripping on an OL1 fault (overload) while my is ramping down? individually, press once, the press Use. Next press to select monitor to select monitor signal. U1-02 Output Frequency Please refer to the A1000 User Manual, (Document No. SIEP C A) on how to access drive monitors. Digits Forward Wiring Diagram: 2-Wire Control Use for maintained contacts Note: 3 rd row of terminal board is shown here. Start Stop Wiring Diagram: 3-Wire Control Use for momentary contacts (Set Parameter A1-03 to 3330) NOTE: It is beyond the scope of this document to program the A1000 drive for network communication control. Please refer to the refer to the A1000 User Manual, (Document No. SIEP C A) for this selection. Open Closed Verify rated current parameter E2-01 and overload parameter settings L1-01 Motor overload selection, L1-02 Motor overload protection time. Question: I want to run my above the nominal speed? Increase the value of parameter E1-04 Maximum Frequency Warning Verify that the and system allow for this. Yaskawa America, Inc Norman Drive South Waukegan, IL (800) YASKAWA ( ) Fax (847) [email protected] Document : TM.A /4/2011 Yaskawa America, Inc.
3 A1000 Cheat Sheet (Closed Loop Operation) Page 1 of 3 The following procedure is a supplement to supplied with this equipment and will guide the user in properly wiring the A1000, and encoder. It will also show the user how to configure the A1000 in closed loop mode operation using a PG-X3 card for a dedicated applications. Danger: Improper wiring can and will cause bodily harm as well as damage to the equipment. When installing the system, be sure to follow good wiring practices and all applicable codes. Ensure that the mounting of components is secure and that the environment, such as extreme dampness, poor ventilation, etc. will not cause system degradation. Please read this cheat sheet and provided with the A1000 thoroughly before attempting any installation. 1 A1000 Model Identification and Mounting To make sure you received the correct model, it is essential to verify the A1000 nameplate with your order and make sure the A1000 has the correct rating so it can be used with your. Please check the nameplate information as shown in the example below. Drive Model Output Weight Serial UL File Check that the available power will meet the input power requirements. Ensure that the output power from the A1000 is compatible with the requirements. In the case of systems with more than one A1000, follow the above procedure for each A1000 and. Mounting the A1000 The mounting of the A1000 is extremely important regarding environment and accessibility. Depending on your system, there are various models available and the mounting dimensions (footprint) may be different. Because the mounting procedure is fairly extensive, it is beyond the scope of this document; the user is referred to the A1000 User Manual (Document No. SIEP C A) received with the A1000, Section 2.2 Mechanical Installation. Match the model that you received and follow the procedure described in the manual to ensure a safe and functional installation. In cases where the system has more than one A1000, refer to the proper clearances required for adequate ventilation. Please pay particular attention to: The clearances to be maintained around the enclosure for adequate ventilation. The environmental specifications such as avoiding excessive dampness, extreme temperatures, chemical exposure, corrosive areas, etc. to avoid damage to the equipment and to maintain safety. Removing and Attaching the Terminal Cover Improper removal of the A1000 terminal cover as well as front cover can cause extensive damage to the A1000. To avoid damage to these items, please pay particular attention to the A1000 User Manual, Document No. SIEP C A, Section 3.5, Removing and Attaching the Terminal Cover. NEMA 1 Open Chassis Drive Spec Normal / Heavy Duty Amps Software Version Motor and 2 Line 3 Install PG-X3 Feedback Card and wire encoder feedback Fig.1 & 2 below show the electrical connections for the input power and terminals for various A1000 models. Select the proper diagram for the model you are installing (see 1). WITH POWER OFF make the appropriate connections. Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is ed properly as shown in fig. 1 DANGER; LETHAL VOLTAGES ARE PRESENT- Before applying power to the A1000, ensure that the terminal cover is fastened and all wiring connections are secure. minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components. WARNING DO NOT CONNECT ANY OF THE FOLLOWING TERMINALS TO EARTH GROUND B1 B Ø * DC Bus terminals location varies by model. to chassis to chassis 3Ø NOT USED 1Ø * 3Ø Fig. 1 and Output Motor Electrical ions for Models: 2_0004-2_0056, 4_0002-4_0044 and 5_ To change direction of rotation swap any two of the three leads (See 2) BUS TERMINALS: DO NOT CONNECT TO GROUND To change direction of rotation swap any two of the three leads (See 2) Fig. 2 and Output Motor Electrical ions for Models: 2_0110 & Larger and 4_0058 & Larger * Make sure the A1000 has been properly sized for single phase input power. For best performance, the drive input supply voltage must be at least equal to or greater than the rated voltage. In this step the PG-X3 encoder feedback card is installed. WITH POWER OFF install the PG-X3 card as shown below. Make sure to follow good wiring practices and all applicable codes. Ensure that the feedback card is ed properly as shown in fig. 3 item H. This option card can be inserted into either the CN5-B or CN5-C connectors located on the drive s control board. If only one option card is connected to the drive, use the CN5-C connector. If two option cards are connected, use both CN5-B and CN5-C. See the A1000 User Manual, Document No. SIEP C A, Section 3.5, for directions on removing the front cover. Option Card Installation PG-X3 Option Card Insert the PG-X3 card (connector CN5) into the matching CN5 connector on the A1000 control card. Next use the screws to fasten the card into place. one of the lead lines to the terminal with one of the screws. Two separate lead lines have been included with the option card. Use the longer one when the option card is plugged into connector CN5-C on the A1000 control card side and use the shorter one if the PG-X3 card is plugged into connector CN5-B. Supply (Max. 200mA) Select Supply (IP IG TB2) with Jumper CN3. Default Ground Lead IMPORTANT: Verify Supply ion A single channel encoder can only be used in V/f PG control mode (A1-02 = 1). It is required to use a quadrature encoder in Flux Vector control mode (A1-02 = 3). (PG) signals to TB1 terminals of the PG-X3 card as shown below. power supply from the PG-X3 card (TB1 Terminals IP and IG) to the (PG). TB2 A PG-X3 Terminals IP IG SG a a- b b- z z - TB1 PG A- B B- Z Z- SD FE Signals A B C D E F G A B C D E F G H I J K L Single Channel Feedback (A Only) Set F1-37 = 0 (default) Suitable only for V/f with Feedback. Terminal block TB1 Ground terminal (installation hole) Jumper for PG power supply voltage (CN3) Terminal block TB2 Model number Installation hole or (CN5) or CN5-C or CN5-B or CN5-A Drive ing terminal (FE) Insert connector CN5 here Option card Mounting screw Lead line Ground Use wire cutters to create an opening for cable lines Front cover Terminal cover TB2 - PG-X3 Wiring A PG-X3 Terminals IP IG SG a a- b b- z z TB1 PG A- B B- Z Z- SD FE Signals Quadrature / Dual Channel Feedback (A & B) Set F1-37 = 1 (Required for FLUX Vector Operation) Suitable for V/f or Flux Vector with Feedback.
4 A1000 Cheat Sheet (Closed Loop Operation) 4 Check Motor Rotation in Open Loop (Motor uncoupled from Load) In this step the is checked for proper direction and operation. This test is to be performed solely from the digital operator. Apply power to the A1000 after all the electrical connections have been made and protective covers have been re-attached. At this point, DO NOT RUN THE MOTOR, the should display as shown in. Changing Parameters and Monitoring the A Make sure all protective covers have been re-attached and power Access Parameter Menu and Change Parameter Value Rotational Auto-Tuning Closed Loop (De-couple Motor from Load) This step shows how to access and modify a A1000 parameter as well as how to monitor A1000 signals such as output frequency and current. two times until the digital operator shows the parameter menu. Page 2 of 3 In this step the A1000 is setup for use with the in closed loop operation. Make sure the following has been done: (PG) connected correctly to the PG-X3 Card All protective covers have been re-attached Ensure the can spin freely and any connected mechanical brake is released ed machinery should be allowed to rotate the IMPORTANT: To achieve optimal drive performance use rotational Auto-Tuning with the load decoupled from the. If and load can not be decoupled, reduce the load so that it is no greater than 30% of the rated load. Performing rotational Auto-Tuning with a higher load can result in incorrect parameters and may cause irregular rotation. Next apply power to the A1000. DO NOT RUN THE MOTOR. A1-02 Select Closed Loop Control Method V/f with PG Select Closed Loop Control Method Control method suitable for applications that require accurate speed regulation (0.02%) but do not require a high speed response. Motor Rotation Test Select V/f with PG Method or Closed Loop Vector Control Method Go to parameter A1-02, Select Digit To adjust control method use / and press Closed Loop Vector (Recommended) Control method suitable for applications that medium to high speed control accuracy, high torque response and full torque at 0 speed.. First Digit Green LED turns on. Direction Go to Next Digit Auto-tuning Procedure Start here to move the cursor one position to the right and Check the speed monitor U1-05 while turning the manually in forward direction (CW). If the sign displayed is negative, power down the drive, wait at least five minutes until the charge indicator extinguishes completely then swap encoder wires A with A- on the PG-X3 card. Next power-up the drive and repeat this test. Or reverse the encoder direction with parameter F1-05. For encoders with only A & B outputs, exchange A & B. From the main reference press to increase the once until the shows the Auto-Tuning menu then press frequency reference (d1-01) to Hz. For standard AC s use the default setting for T1-04 Rated current (e.g A, 22.0 A) base frequency T1-05 Rated Frequency (e.g Hz) (60Hz), poles (4) and rated speed. T1-06 of Poles (e.g. 4 Poles) T1-03 Rated Voltage (e.g. 230 V, 460 V). T1-07 Rated Speed (e.g rpm) to save frequency reference. T1-08 / PG of Pulses per Rev. (e.g. 1024) to Edit Mode Hz Modify Value Save New Value After setting parameter T1-08 press Monitor Motor Frequency and Motor Current on the. The to select the Auto-Tuning start command. should now be operating at low speed running in the correct forward (clockwise) direction. A1000 power-up state Output Frequency and Motor Current can be monitored on the. If rotation is not correct, then either reverse Phase Order using parameter b1-14 or power down the drive, wait five minutes and swap 2 leads. simultaneously. once until the shows parameter T1-02 Mtr Rated then press To monitor output frequency and current or signals turned off. Use precaution, and refer to Fig.1 or 2, swap any two of the three output leads to the (U/T1, V/T2 and W/T3). After the wiring change, repeat 3 and recheck direction. individually, press once,. Next press Motor HP to kw = HP x Example: 10HP = 10 x = 7.46 kw the press Digit to select monitor Use to select monitor signal. Digits use U1-02 Output Frequency Please refer to the A1000 User Manual, (Document No. SIEP C A) on how to access drive monitors. may start unexpectedly during Auto-Tuning. Warning Electric Shock Hazard. High voltage will be supplied to the when stationary Auto-Tuning is performed. Do not touch the during auto-tuning. Enter Motor in kw (Kilowatt) DANGER minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards or components. Warning Sudden movement hazard. The A1000 and to select the digit you would like to change and to adjust value and press to save. to select the next parameter and follow the same procedure described above to adjust its value. Notice: Auto-Tuning will not function properly when a brake is engaged on the load. Ensure the shaft can freely rotate. Never perform an Auto-Tune with connected to a load. on the. The A1000 will now start the Auto-tuning procedure. The display will show message Tune Successful when the Auto-Tuning procedure has been successfully completed. Please refer to the A1000 User Manual or repeat the Continue procedure again if the display shows an error message.
5 A1000 Cheat Sheet (Closed Loop Operation) Page 3 of 3 7 Selecting Start/Stop and Speed Reference Sources 8 Motor Performance Fine Tuning This step shows how to setup the run and reference source of the A1000. The run source determines how the A1000 drive receives its start and stop command and the reference source determines how the speed of the is controlled. Make sure all protective covers have been re-attached and power This section may require you to change one or more A1000 parameters. Please refer to 5 for a detailed explanation on how to change parameters. 1. Adjust speed / frequency from the To adjust frequency use / and press. 1. Start / Stop Control from SELECT RUN SOURCE 2. Start / Stop Control from external terminals (switch or relay contact) SELECT REFERENCE SOURCE b Adjust speed / frequency from external terminals (0-10V / 4-20mA Signal) V AC V- A1 A2 A3 FM AM AC MP Potentiometer 2K Ohm Note: 2 nd row of terminal board is shown here. 0 ~ 10Vdc RP AC V AC V- A1 A2 A3 FM AM AC MP RP AC V AC V- A1 A2 A3 FM AM AC MP RP AC 4 ~ 20mA ( Factory Default) Located inside the drive on the terminal board b1-02 The following tables show how to fine tune operation for V/f with PG and Closed Loop Vector Operation. Please refer to the A1000 User Manual (Document No. SIEP C A) for additional information. V/f Control with encoder feedback (A1-02 = 1) Problem Parameter Action Default Suggested Setting Motor is hunting and oscillation at speeds between 10 and 40Hz. Motor noise Motor hunting and oscillation at speed up to 40Hz Poor torque or speed response Motor hunting and oscillation Poor torque at speeds below 10 Hz Motor hunting and oscillation Poor torque at low speeds Motor instability at start Poor speed precision Closed Loop Vector Control (A1-02 = 3) Poor torque or speed response Motor hunting and oscillation n1-02 Hunting Prevention Gain C6-02 Carrier Frequency Selection C4-02 Torque Compensation Primary Delay Time C4-01 Torque Compensation Gain E1-08 Mid Output Voltage A E1-10 Minimum Output Voltage C5-01 ASR Proportional Gain 1 <3> C5-02 ASR Integral Time 1 <4> If insufficient torque relative to the size of the load causes hunting reduce the When hunting and oscillation occur with a light load increase Lower this setting if hunting occurs when using a with a relatively low inductance such as a high-frequency or a with a larger frame size. If the noise is too loud increase the carrier frequency. When hunting and oscillation occur at speeds up to 40 Hz lower the carrier frequency. The default setting for the carrier frequency depends on the drive capacity (o2-04) and the Duty Selection (C6-01). If torque and speed response are too slow, decrease the If hunting and oscillation occur, increase the If torque is insufficient at speeds below 10 Hz, increase the if hunting and oscillation with a relatively light load, decrease the If torque is insufficient at speeds below 10 Hz, increase the If instability occurs at start, decrease the Note: The recommended setting value shown is for 200 V class drives. Multiply value x 2 for 400V class drives and x for 575V class drives. Adjust the ASR proportional gain 1 (C5-01) and the ASR integral time 1 (C5-02) to (2 khz) 1 to max. setting 200 ms <1> 100 to 1000 ms to 1.50 E1-08: 15.0 V <2> E1-10: 9.0 V <2> C5-01: 0.20 C5-02: Default setting ±5 V Prop. gain = 0.10 to 1.00 Int. time = to Problem Parameter Action Default Suggested Setting Trouble maintaining the ASR proportional gain or the integral time at the low or high end of the speed range C5-01 ASR Proportional Gain 1 <4> C5-03 ASR Proportional Gain 1 <4> C5-02 ASR Integral Time 1 <4> C5-04 ASR Integral Time 2 <4> C5-07 ASR Gain ing Frequency <4> Motor hunting and oscillation C5-06 ASR Primary Delay Time Constant <4> Motor noise Motor hunting and oscillation occurs at speeds below 3 Hz C6-02 Carrier Frequency Selection If torque and speed response are too slow, gradually increase the ASR gain setting by 5. If hunting and oscillation occur, decrease the Parameter C5-03 needs to be adjusted only if C5-07 > 0. Perform ASR Auto-Tuning if possible If torque and speed response are too slow, decrease the If hunting and oscillation occur, increase the Parameter C5-04 needs to be adjusted only if C5-07 > 0. Have the drive switch between two different ASR proportional gain and integral time settings based on the output frequency. If torque and speed response are too slow, gradually decrease the setting by If the load is less rigid and subject to oscillation, increase this If there is too much noise, the carrier frequency is too low. If hunting and oscillation occur at low speeds, reduce the carrier frequency. Note: The default setting for the carrier frequency depends on the drive capacity (o2-04) and Drive Duty Selection (C6-01) to s to s 0.0 Hz 0.0 to max. freq. output s to 0.020s 1 2KHz to max. setting Forward Start Open Overshoot or undershoot when the speed changes with high inertia load Use S-Curve: C2-01, C2-02, C2-03, C Wiring Diagram: 2-Wire Control Use for maintained contacts Stop Closed <1> Default setting value is dependent on parameter A1-02, Control Method Selection, and o2-04, Drive Model Selection. <2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. <3> ASR in V/f Control with PG only controls the output frequency, and therefore does not allow for high gain settings like in Close Loop Vector control. <4> Refer to C5: Automatic Speed Regulator (ASR) in the A1000 User Manual (Document No. SIEP C A) for details on Automatic Speed Regulator (ASR). Note: 3 rd row of terminal board is shown here. Wiring Diagram: 3-Wire Control Use for momentary contacts (Set Parameter A1-03 to 3330) NOTE: It is beyond the scope of this document to program the A1000 drive for network communication control. Please refer to the refer to the A1000 User Manual, (Document No. SIEP C A) for this selection. Yaskawa America, Inc Norman Drive South Waukegan, IL (800) YASKAWA ( ) Fax (847) [email protected] Document : TM.A /4/2011 Yaskawa America, Inc.
GPD 506/P5 Start-up Procedure and Checklist
GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass
1000 Hz High Frequency Custom Software
YASKAWA AC Drive - V1000 Option 1000 Hz High Custom Software Supplement Software No. VSV91005X To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance.
VLT 6000 HVAC. Contents
Contents Introduction Safety...3 Safety Guidelines...3 Warnings Against Unintended Start...3 Introduction...4 About this manual...4 Assumptions...4 References...4 Trademarks...5 Programming the VLT 6000
NX Series Inverters. HVAC Pocket Programming Guide
NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following
VLT AutomationDrive for Marine winch applications
MAKING MODERN LIVING POSSIBLE VLT APPLICATION NOTE VLT AutomationDrive for Marine winch applications This Application note is meant to be a guideline for using Danfoss VLT AutomationDrive in winch applications.
APPENDIX. SureSERVO QUICK START GUIDE. In This Appendix... Quick Start for SureServo Drives...A 2. Tuning Quick Start for SureServo Drives...
SureSERVO QUICK START GUIDE APPENDIX BA In This Appendix... Quick Start for SureServo Drives.............A 2 Spin the Motor......................................A 2 Position Mode Quick Start (Pt & Pr)......................A
TOSVERT VF-MB1. Functions for lift application
TOSVERT VF-MB1 Functions for lift application The technical information in this manual is provided to explain the principal functions and applications of the product, but not to grant you a license to
J1000. System configuration
YASKAWA JZ J1000 The basic inverter V/f controlled inverter Good torque performance (150% / 3 Hz) Double rating ND 120%/1min and HD 150%/1 min Overload detection function (150% during 60s) thermal function
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
YASKAWA AC Drive A1000
YASKAWA AC Drive A1000 Crane Software Application Manual Software No. VSA90507X Type: CIMR-AC Models: 200 V Class: 0.4 to 110 kw (1.2 to 160 kva) 400 V Class: 0.4 to 300 kw (1.4 to 460 kva) To properly
HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE
HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3
CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual
Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual
Instruction Manual Copy Adapter "CPAD-C1A" "CP Fuji Electric Systems Co., Ltd. INR-SI47-0886a-EU Rev 052010
Instruction n Manual Copy Adapter "CPAD-C1A" Thank you for purchasing our Copy Adapter CPAD-C1A. This product is designed to copy function codes and their data, which are stored in the FRENIC-Mini series
VLT Series 3500 Adjustable Frequency Drive Instruction Manual
Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software
Addendum to the Operating Instructions
Drive Technology \ Drive Automation \ System Integration \ Services Addendum to the Operating Instructions MOVIMOT with AS-Interface and AC Motor DT/DV Unit Replacement MOVIMOT MM..C -> MM..D with MLK3A
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
How To Use The Vacon 0 Machinery
vacon 0 machinery how would you like your ac drive today? easy adaptation for customer requirements The Vacon 0 Machinery is an extremely compact AC drive for machine builders in the power range from 0.25
Multi-Protocol decoder 76 200 with Load regulation
Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder
ACS800. Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program
ACS800 Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program Master/Follower Application Guide Supplement to Firmware Manual ACS800 Standard Application
Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual
ELECTRIC MOTORS, GEARMOTORS AND DRIVES Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual We, EC Declaration of Conformity In accordance with EN45014:1998 Leeson Electric Corporation
Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations
Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations Addendum to: IMPULSE G+ Series 3 Manual (140-10258) IMPULSE VG+ Series 3 Manual (140-10257) This addendum should be used when a 24VDC
SAFETY INSTRUCTIONS WARNING
Important User Information Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015
Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) The standard tuning values used in ADVANCED Motion Controls drives are conservative and work well in over 90%
Description. Dimensions. Features. www.pwb-encoders.com. precision works better
Description The MEC22 is a high resolution optical hollow shaft encoder that can be fixed quickly and easily on different sizes of motor shafts. The encoder provides two square wave outputs in quadrature
Manual No. YEG-TOE-S616-55.1-OY. VARISPEED F7 Vector Control Frequency Inverter USER S MANUAL
Manual No. YEG-TOE-S616-55.1-OY VARISPEED F7 Control Frequency Inverter USER S MANUAL Table of Content Warnings... VII Safety Precautions and Instructions for Use... VIII EMC Compatibility... X Line Filters...
How To Power A Schen
Automation / Mini Type SCH32F Hollow Shaft Encoder - Ø 32 mm Hollow Bore: Ø 6 mm to Ø 3/8 inch Resolution up to 5000 ppr IP 65 (IP 50 for IDC connector option) Electrical Specifications Code: Resolution:
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
Material: Weight: Bearing Life: Shaft Speed: Starting Torque: Mass Moment of Inertia: Shaft Loads:
Automation / Mini Type SCH32F Hollow Shaft Encoder - Ø 32 mm Hollow Bore: Ø 6 mm to Ø 3/8 inch Resolution up to 5000 ppr IP 65 (IP 50 for IDC connector option) Electrical Specifications Code: Resolution:
BLWR23MDA Series. 24V, 15A Brushless Controller / Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.
BLWR23MDA Series 24V, 15A Brushless Controller / Motor User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: [email protected] (714) 992-6990 fax:
Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S
New Products Introduction Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S Takashi Sekiguchi Masahiro Kidou Yuusuke Shimura Yuji Ide Masahisa Koyama Michio Kitahara
CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.
7I29 MANUAL Rev 1.5 CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB. THE 7I29 IS INTENDED FOR USE BY OEMS THAT WILL INTEGRATE IT INTO A SYSTEM WITH INTERLOCKS AND
Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C
F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety
Application Note AN-SERV-006
THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT IS SUPPLIED "AS IS", WITHOUT ANY GUARANTEE OF ANY KIND. These documents are provided by our technical support department to assist others.
SX460. Generator Automatic Voltage Regulator Operation Manual
SX460 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX460* * Use for reference purpose only and not a genuine Newage product. 1.
Fan Coil EC Motor Control
Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed
Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
MOVFR ELECTRICAL ADJUSTMENTS. G.A.L. MFG. CORP. NEW YORK CITY U.S.A. http://www.gal.com
MOVFR ELECTRICAL ADJUSTMENTS G.A.L. MFG. CORP. NEW YORK CITY U.S.A. http://www.gal.com 1 ELECTRICAL ADJUSTMENTS ADJUSTING INSTRUCTIONS FOR THE G.A.L. VARIABLE FREQUENCY CLOSED LOOP DOOR OPERATOR TYPE MOVFR
MDC151-024031 Series
MDC151-024031 Series 24V, 3A Brushless DC Controller User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: [email protected] (714) 992-6990 fax: (714)
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Instruction Manual. Cascade Controller Option VLT 6000 HVAC VLT 8000 AQUA
Instruction Manual Cascade Controller Option VLT 6000 HVAC VLT 8000 AQUA Contents Safety and precautions... 3 Safety regulations... 4 Warning against unintended start... 4 Operation modes... 6 Cascade
FRENIC5000MS5 for Machine Tool Spindle Drives
FRENIC5MS5 for Machine Tool Spindle Drives Yoshikazu Tanaka Hiroaki Hayashi Hiroshi Takahashi 1. Introduction Fig.1 External view of FRENIC5MS5 In AC spindle drive systems for machine tools, operation
EFC 3600. Frequency converters
2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation
VCM Installation and Operations Manual. Table of Contents
Table of Contents VCM Installation and Operations Manual 1.0 Introduction... 1 2.0 Product Inspection... 2 2.1 Nameplate Layout... 2 3.0 Operating Precautions... 3 3.1 Before Power up... 3 3.2 During Power
SAFETY INSTRUCTIONS WARNING
Thank you for purchasing LG Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Contents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
DMX-K-DRV. Integrated Step Motor Driver + (Basic Controller) Manual
DMX-K-DRV Integrated Step Motor Driver + (Basic Controller) Manual DMX-K-DRV Manual page 1 rev 1.33 COPYRIGHT 2007 ARCUS, ALL RIGHTS RESERVED First edition, June 2007 ARCUS TECHNOLOGY copyrights this document.
Analog Servo Drive 25A8
Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit
CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual
Instruction Manual Option Card for Frequency Divider Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description
Technical Guide No. 100. High Performance Drives -- speed and torque regulation
Technical Guide No. 100 High Performance Drives -- speed and torque regulation Process Regulator Speed Regulator Torque Regulator Process Technical Guide: The illustrations, charts and examples given in
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
DC Motor control Reversing
January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical
1 Temperature Derating Guide
VLT HVAC Drive FC 02 Application Note Temperature Derating Guide Temperature Derating Guide.. Abstract This paper provides detailed data regarding the operation of the VLT HVAC Drive FC02 at varying ambient
MC1000 Series Installation and Operation Manual
MC1000 Series Installation and Operation Manual NOTE! The manual covers software version M108314 and above. Refer to parameter 63 for the software version of the drive you are working with. If you are
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
ABB Drives. User s Manual HTL Encoder Interface FEN-31
ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions
Installation & Operation Manual for Energenics Air-Flow Optimizer
1470 Don Street Naples, Florida 34104 Telephone: (239) 643-1711 Fax: (239) 643-6081 Customer Service: (800) 944-1711 Installation & Operation Manual for Energenics Air-Flow Optimizer Table of Contents
Datasheet of the Easy Servo Drive ES-D808. 24-75VDC, 8.2A Peak, Close-loop, No Tuning. Version 0.1.0. http://www.leadshine.com
Datasheet of the Easy Servo Drive ES-D808 4-75VDC, 8.A Peak, Close-loop, No Tuning Version 0.1.0 http://www.leadshine.com Features Step and direction control Closed position loop for no loss of movement
WINDOW's Programming Software USER MANUAL
www.danahermotion.com High frequency inverter ACO5000 by ACOMEL WINDOW's Programming Software USER MANUAL DANAHER MOTION S.A. La Pierreire 2, CH-1029 Villars-Ste-Croix Telephone +41 21 631 33 33, Telefax
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &
Speed Control Relays SX2
SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................
NXL Series Inverters. HVAC Inverters made simple
NXL Series Inverters HVAC Inverters made simple Honeywell s Voice Of the Customer process unveils a range of requirements expressed by specifiers and installers, that are ideally covered by the NXL inverter
Panorama. Softstarters The complete range
Panorama Softstarters The complete range Why does soft starting matter? Controlling industrial electricity. The vast majority of the world s industrial applications are driven by motors. It is estimated
Material: Weight: Bearing Life: Shaft Loads: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:
Oil & Gas / Heavy Industry EX-Proof Stainless Steel Shaft Encoder - Ø 68 mm Shaft - Ø 10 mm to Ø 5/8 inch Resolution up to 10,000 ppr IP 66 (IP 67 option) ATEX certified EX-Proof IECEx certified EX-Proof
LIFT CONTROL SYSTEMS CATALOGUE 2007
LIFT CONTROL SYSTEMS CATALOGUE 2007 All Your Needs For Elevators INDEX 1. Lift Control Cards... 3 2. Speed Control Units... 7 3. Emergency Rescue Cards... 8 4. Lift Control Panels... 10 5. Photocells...
LIFT CONTROL SYSTEMS CATALOGUE 2007
LIFT CONTROL SYSTEMS CATALOGUE 2007 All Your Needs For Elevators INDEX 1. Lift Control Cards... 3 2. Speed Control Units... 7 3. Emergency Rescue Cards... 8 4. Lift Control Panels... 10 5. Photocells...
Installation, Operation and Maintenance Manual
Installation, Operation and Maintenance Manual VLT 6000 Series Adjustable Frequency Drive 12/01 23-6108-00 Revision K Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly
Talon and Talon SR User Manual
Talon and Talon SR User Manual Brushed DC motor controller Version 1.3 Cross the Road Electronics, LLC www.crosstheroadelectronics.com Cross The Road Electronics, LLC Page 1 4/2/2013 Device Overview Clear,
Contactless Encoder RI360P0-QR24M0-INCRX2-H1181
Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
YASKAWA AC Drive 1000-Series Option EtherNet/IP. Technical Manual
YASKAWA AC Drive 1000-Series Option EtherNet/IP Technical Manual Type: SI-EN3 To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
Multi-Protocol decoder 76 400
Multi-Protocol decoder 76 For locomotives with DC motors on digital layouts operating in the DCC- and Motorola data format. Features Regulated multi-protocol decoder for DCC and Motorola Suitable for DC
Contents. Safety Warnings... 1
Contents Safety Warnings... 1 Unpacking the GQ600... 1 Introduction... 2 GQ600 Filter Characteristics... 2 1/3 Octave Centre Frequencies... 4 Front Panel Functions... 5 Rear Panel Functions... 6 Specifications...
SJ200 Series Inverter Quick Reference Guide
SJ2 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB6501XA March 24 Caution:
YASKAWA AC Drive-J1000
YASKAWA AC Drive-J1000 Compact V/f Control Drive Quick Start Guide Type: CIMR-JU Models: 200 V Class, Three-Phase Input: 0.1 to 5.5 kw 200 V Class, Single-Phase Input: 0.1 to 2.2 kw 400 V Class, Three-Phase
PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit
PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives
BLY17MDA Series. 24V, 10A Brushless Controller/Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.
BLY17MDA Series 24V, 1A Brushless Controller/Motor User s Guide A N A H E I M A U T O M A T I O N 91 East Orangefair Lane, Anaheim, CA 9281 e-mail: [email protected] (714) 992-699 fax: (714) 992-471
MEMOBUS/Modbus Communications
2 2.1 MEMOBUS/MODBUS CONFIGURATION............260 2.2 COMMUNICATION SPECIFICATIONS..............261 2.3 COMMUNICATION TERMINAL RESISTANCE........262 2.4 CONNECTING A PLC...........................263 2.5
We will discuss common industrial applications with guides for the proper use of electric motors on these.
INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which
AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use:
AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use: advanced soft start and soft stop control protection functions that operate even when
AUTODIALLER / QUICKDIALLER - SA132
AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING
Automation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
POWERDRIVE MD. Variable speed drive. Commissioning manual. 3871 en - 2011.05 / h. Digital input polarity 8.29. Input or output.
Digital input or output DIO 8.29 Digital input polarity Negative Input or output selection Positive 8.3 Output DIO state 8. Invert 8. Input Digital input or output 2 DIO2 DIO2 state 8.2 Input or output
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.
TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection
MODEL 2202IQ (1991-MSRP $549.00)
F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...
August 2004. www.danahermotion.com SECO DC DRIVES. Table of Contents
SECO DC DRIVES SECO AC/DC DC Drives DRIVES Table of Contents August 2004 www.danahermotion.com Tel : 800 554 8466 Web site : www.danahermotion.com Mechanical and Electro-Mechanical Product Solutions by
3753 en - 04.2004/b VE/B - VE/RG Va V riable speed drives
3753 en 04.2004/b Variable speed drives LEROYSOMER's drives provide SPEED VARIATION for a DC motor, SIMPLY and ECONOMICALLY from a singlephase power supply. CMStype technology is used. These products conform
Installation & Operation Manual Dial-A-Flow Adjustable Frequency Drives
GM 04-13 Installation & Operation Manual Dial-A-Flow Adjustable Frequency Drives for 1/8 HP thru 1HP 3-Phase AC Motors rated 208 230 VAC, 50 & 60 Hz NEMA-1 / IP-40 Operates from 115 and 208/230 Volt 50/60
GSM Door Phone System
GSM Door Phone System System Installation, Setting and Operation Manual User Manual (263-S V1) Please read this user manual completely before operating this system and keep it in a safe place for future
PSR The compact range Description
Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides
Housing diameter Shaft diameter 1. Flange (Mounting of housing) Protection class shaft input (EN 60529) Protection class housing (EN 60529)
Direct mounting without coupling Flexible hollow shaft design up to diameter 4 mm Through hollow shaft or as end shaft (blind shaft) Easy installation by means of clamping shaft or blind shaft Short overall
PERF10 Rubidium Atomic Clock
Owner s Manual Audio Stanford Research Systems Revision 1.0 February, 2011 2 Certification Stanford Research Systems certifies that this product met its published specifications at the time of shipment.
