TOSVERT VF-MB1. Functions for lift application
|
|
|
- Calvin Small
- 9 years ago
- Views:
Transcription
1 TOSVERT VF-MB1 Functions for lift application The technical information in this manual is provided to explain the principal functions and applications of the product, but not to grant you a license to use the intellectual property or any other property of Toshiba Schneider Inverter Corporation or a third party. Toshiba Schneider Inverter Corporation 2010 All rights reserved.
2 - Contents - 1. Introduction Functions Light load high-speed operation function Related parameters Mode description Automatic setting mode of high-speed operation speed (f328=1, 2) Fixed setting mode of high-speed operation speed (f328=3, 4) How to adjust parameters Automatic setting mode of high-speed operation speed (f328=1, 2) Fixed setting mode of high-speed operation speed (f328=3, 4) Braking functions Standard connection for lift application Parameter adjustment procedure for braking functions Setting sample of related parameters Braking functions Parameters for braking functions Execution of "Brake time learning" Brake timing with maximum load Abnormal phenomenon and the measures
3 1. Introduction E TOSVERT VF-MB1 has some functions for lift application. This instruction manual explains the light-load high-speed operation function and the braking function of VF-MB1 for crane and hoists applications. 2. Functions VF-MB1 has some functions for lift application. 1) Light-load high-speed operation function The function is used to increase the operating efficiency of the machine by increasing the rotational speed of the motor when it is operated under light load. The function is useful for constant-torque load applications which repeatedly drive light and heavy loads, such as lifts and transfer equipment. Since VF-MB1 has the learning function for the light-load high-speed operation, it can be easily adjusted by executing the forward run (raising) or reverse run (falling) operation. (f328=3, 4 only) 2) Braking function To ensure smooth operation, the motor produces enough torque before the brake is released. Since VF-MB1 has the learning function for the braking function, it can be easily rough set creeping frequency, creeping time and braking release time. 2
4 3. Light load high-speed operation function 3.1 Related parameters Title Commu nication No. f f Function Light-load high-speed operation selection Light-load high-speed learning function Adjustment range 0:Disabled 1: High-speed operation speed set automatically (Power running at F command: Increase) 2: High-speed operation speed set automatically (Power running at R command: Increase) 3: High-speed operation speed set with f330 (Power running at F command: Increase) 4: High-speed operation speed set with f330 (Power running at R command: Increase) 0:No learning 1:Forward run learning 2:Reverse run learning Minimum setting unit (Panel/ Communication) Default setting f Automatic light-load high-speed operation frequency 30.0 to ul Hz 0.1/0.01 (*1) f Light-load high-speed operation switching lower limit frequency 5.0 to ul Hz 0.1/ f Light-load high-speed operation load waiting time 0.0 to 10.0 sec. 0.1/ f Light-load high-speed operation load detection time 0.0 to 10.0 sec. 0.1/ f Light-load high-speed operation heavy load detection time 0.0 to 10.0 sec. 0.1/ f Switching load torque during power -250 to 250% running 1/ f Heavy-load torque during power running -250 to 250% 1/ f Heavy-load torque during constant power running -250 to 250% 1/ f Switching load torque during regenerative braking -250 to 250% 1/ (*1)The values depend on the setup menu setting. Note: Parameters f335 to f338 need adjustment according to the load. Since VF-MB1 has the learning function for the light-load high-speed operation, it can be easily adjusted by executing the forward/reverse run operation (raising/falling for lift application). (f328=3, 4 only) 3
5 3.2 Mode description E The light-load high-speed operation includes the modes below: Each mode can be set by the light-load high-speed operation selection (f328). Title/function Default setting Action 0: Disabled Light-load high-speed operation disabled. f328 Light-load high-speed operation selection 1:High-speed operation speed set automatically (Power running at F command: Increase) 2:High-speed operation speed set automatically (Power running at R command: Increase) 3:High-speed operation speed set with f330 (Power running at F command: Increase) 4:High-speed operation speed set with f330 (Power running at R command: Increase) Example: If automatic setting mode of high-speed operation speed is used, set f328 to 1 for F (forward command): Increase set f328 to 2 for R (reverse command): Increase When inverter judges to be light-load, the high-speed operation frequency is automatically set according to a detected torque. When inverter judges to be light-load, the operation is set to the automatic light-load high-speed operation frequency (f330). Note: Light load output and Heavy load output conditions of output terminal functions are different from f328 setting. 1)f328 (Light-load high-speed operation selection) =0 Light load output (Function No. 106/107) ON: Less than f335 Heavy load output (Function No. 108/109) ON: f337 or more 2) f328 (Light-load high-speed operation selection) setting is not 0 Light load output (Function No. 106/107) ON: Less than f335 or f338 Heavy load output (Function No. 108/109) ON: f335 or f338 or more f335: Switching load torque during power running f337: Heavy-load torque during constant power running f338: Switching load torque during regenerative braking 4
6 3.2.1 Automatic setting mode of high-speed operation speed (f328=1, 2) The diagram on the next page (Fig.1) is the timing chart when the automatic setting mode of high-speed operation speed (f328=1) is applied to lift application. At the operation frequency above the light-load high-speed operation switching lower limit frequency (f331) (point A in the Fig.1), if a detected torque (*1) after completion of speed reach is the switching load torque during power running (f335 setting value) or less, the inverter judges to be light-load. For light-load operation, the frequency decided with the formula is determined as a target frequency (high-speed operation frequency) and the operation is accelerated toward the target frequency. (Point B in the Fig.1 Light-load high-speed operation) Target frequency = (Value set with f335) [Base frequency (vl)] / (Detection torque) when target frequency ul ( fh) (*1) Average torque during light-load high-speed operation load detection time (f333) after light-load high-speed operation load detection waiting time (f332) (5% or more) Light-load detection is carried out after speed reach when an operation frequency is above the light-load high-speed operation switching lower limit frequency (f331). When each of conditions below is reached, the light-load high-speed operation is canceled and the operation is returned to the frequency corresponding to a speed command value. 1) The torque is exceeded the heavy-load torque (f336) during acceleration up to the high-speed operation frequency. 2) The torque is exceeded the heavy-load torque during constant power running (f337) after reaching the automatic light-load high-speed operation frequency (f330) and after a lapse of the light-load high-speed operation heavy load detection time (f334). 3) The speed command value is entered less than the light-load high-speed operation switching lower limit frequency (f331). 5
7 Example of operation Light-load high-speed operation selection (f328=1: High-speed operation speed set automatically): F (Increase) E Light-load Operation frequency (Hz) High-speed operation frequency varies with load torque. B Light-load high-speed operation switching lower limit frequency f331 Light-load high-speed operation load detection time f333 Light-load high-speed operation load detection waiting time f332 A f102 Speed reach detection band f102 Speed reach detection band Light-load high-speed operation heavy load detection time f334 Operation signal (F) ON OFF Speed reach signal OFF ON ON Torque (%) Heavy-load torque during power running f336 Heavy-load torque during constant power running f337 Switching load torque during power running f335 Output terminal: Light load output Function No.106 ON OFF Fig.1 6
8 3.2.2 Fixed setting mode of high-speed operation speed (f328=3, 4) The diagram on the next page (Fig.2) is the timing chart when fixed setting mode of the high-speed operation speed (f328=3) is applied to lift application. At the operation frequency more than the light-load high-speed operation switching lower limit frequency (f331) (point A in the Fig.2), if an average torque during the light-load high-speed operation load detection time (f333) after completion of speed reach and after the light-load high-speed operation load detection waiting time (f332) has elapsed is below the switching load torque during power running (f335), the inverter judges to be light-load detection and is more accelerated up to an automatic light-load high-speed operation frequency (f330). (Point B in the Fig.2 Light-load high-speed operation) Load torque detection is carried out after speed reach when an operation frequency is more than the light-load high-speed operation switching lower limit frequency (f331). When each of conditions below is reached, the light-load high-speed operation is canceled and the operation is returned to the frequency corresponding to a speed command value. 1) The torque is exceeded the heavy-load torque (f336) during acceleration up to the automatic light-load high-speed operation frequency (f330). 2) The torque is exceeded the heavy-load torque during constant power running (f337) after reaching the automatic light-load high-speed operation frequency (f330) and after a lapse of the light-load high-speed operation heavy load detection time (f334). 3) The speed command value is entered less than the light-load high-speed operation switching lower limit frequency (f331). 7
9 Example of operation Light-load high-speed operation selection (f328=3: High-speed operation set with f330): F (Increase) Light-load high-speed operation Automatic light-load high-speed operation frequency f330 B Light-load high-speed operation load detection time f333 Light-load high-speed operation load detection waiting time f332 Light-load high-speed operation switching lower limit frequency f331 A f102 Speed reach detection band f102 Speed reach detection band Light-load high-speed operation heavy load detection time f334 Operation signal (F) Speed reach signal OFF ON ON OFF Torque (%) Heavy-load torque during power running f336 Heavy-load torque during constant power running f337 Switching load torque during power running f335 Output terminal: Light load output Function No.106 ON OFF Fig.2 8
10 3.3 How to adjust parameters E If the light-load high-speed operation is used, it is necessary to always set the motor-related parameters (Motor constants). Refer to Section 6.21 of VF-MB1 instruction manual (E ) to set motor-related parameters. In addition, for the high-speed operation fixed setting mode (f328=3, 4), the learning action allows the light-load high-speed operation to be adjusted easily Automatic setting mode of high-speed operation speed (f328=1, 2) Adjustment method for lift application If the light-load high-speed operation is carried out with 60Hz of normal operation, follow the procedure below: 1) Set the parameter below at an arbitrary position of the status monitor display selection (f711 to f718). Torque monitor Setting No.7 Ex. of LED display q 20 2) Set f335=0 and f338=0 not to change the light-load high-speed operation. f335: Switching load torque during power running f338: Switching load torque during regenerative braking 3) Check the torque monitor value of the following conditions. And set the value to each parameters after all operation checking. (1)Setting of f335 (Switching load torque during power running) Carry out the power running operation while hanging 100% load at the vl (base frequency). Check the maximum torque monitor value after speed reach and set the value to f335. (2)Setting of f338 (Switching load torque during regenerative braking) Carry out the regenerative braking operation while hanging 100% load at the vl (base frequency). Check the maximum torque monitor value after speed reach and set the value to f338. (3)Setting of f336 (Heavy-load torque during power running) Carry out the power running operation while hanging 100% load at the vl (base frequency). Check the torque monitor value during acceleration and set the value to f336. (4)Setting of f337 (Heavy-load torque during constant power running) Carry out the power running operation while hanging 100% load at the vl (base frequency). Check the torque monitor value during constant power running and set the value to f337. 4) Carry out the power running operation while hanging a minimum load for which the light-load high-speed operation is not wanted and check that the operation does not change to the light-load high-speed operation (an operation frequency does not change). If changing to the light-load high-speed operation, reduce the setting value of the switching load torque during power running (f335). 5) Similarly, carry out the regenerative braking operation while hanging a minimum load for which the light-load high-speed operation is not wanted and check that the operation does not change to the light-load high-speed operation (an operation frequency does not change). If changing to the light-load high-speed operation, reduce the setting value of the switching load torque during power running (f338). 9
11 Change the f335 and f338 values step by step. 6) When reaching a state where it is possible to switch to the light-load high-speed operation, check that a high-speed operation frequency changes by changing a load. 7) Restore the parameter changed in 1) to an initial value if necessary. 10
12 3.3.2 Fixed setting mode of high-speed operation speed (f328=3, 4) Adjustment method using the learning function for lift application If the light-load high-speed operation is carried out with 60Hz of normal operation, follow the procedure below: 1) Set the automatic light-load high-speed operation frequency (f330). Ex.: f330=90hz 2) Set the light-load high-speed learning function (f329) to 1 (Forward run learning). 3) Carry out the 60Hz-forward power running operation while hanging a maximum load for which the light-load high-speed operation can be carried out and check that the operation changes to the light-load high-speed operation (90Hz operation). (Forward run learning) During the learning operation, t blinks on the left side of the frequency display LED. 4) Set the light-load high-speed learning function (f329) to 2 (Reverse run learning). 5) Similarly, carry out the 60Hz-reverse regenerative braking operation while hanging a maximum load for which the light-load high-speed operation can be carried out and check that the operation changes to the light-load high-speed operation (90Hz operation). 6) The parameters below are automatically adjusted by carrying out operations in 3) and 5). Title Function Default setting f335 Switching load torque during power running 50 f336 Heavy-load torque during power running 100 f337 Heavy-load torque during constant power running 50 f338 Switching load torque during regenerative braking 50 7) Hang a load for which the light-load high-speed operation is not wanted and check that a normal operation does not change for both of power running/regenerative braking operations. 8) In case of a dynamic lift off at power running operation, carry out the dynamic lift off after high-speed operation and check that the inverter operates at the normal speed. Cautions If a result of the learning operation is as follows, the learning operation should be completed when it stops without transition to the high-speed operation. Switching load torque during power running (f335) is 70% or more Switching load torque during regenerative braking (f338) is 70% or more If a detected torque exceeds 150% during acceleration of the high-speed operation, the high-speed operation should be stopped and the learning operation should be completed without reflecting the learning data. If a detected torque exceeds 100% during constant speed operation after completion of acceleration of the high-speed operation, the high-speed operation should be stopped and the learning operation should be completed without reflecting the learning data. 11
13 4. Braking functions 4.1. Standard connection for lift application <SINK logic> Braking Resistor MC2 PA/+ PC/- PBe PB MCCB MC1 MC1 R/L1 U/T1 No excitation operation brake B S/L2 Main Circuit V/T2 M T/L3 W/T3 Motor Control Circuit F Forward run signal RY1 MC2 R Reverse run signal ON MC1 Surge suppressor OFF MC1 FLA FLB FLC P24 FL Fault Relay RES S1 S2 S3 Reset Preset speed 1 (LOW speed) Preset speed 2 (HIGH speed) CC Common RY1 OUT RY G / E RC NO CC FM CC VIC VIB VIA PP [Operation] By terminal signal [Speed reference] Preset speed 1 and 2, Operation panel 3 preset speed 12
14 4.2 Parameter adjustment procedure for braking functions Set related parameters like as cmod fmod. Set vector control parameters (motor constant value) by executing the auto-tuning functions without load. Execute the brake timing learning function without load. This function provides the brake ON/OFF timing as a rough adjustment. Operate forward/reverse run with maximum load, and confirm that it doesn't have trouble like as 'inverter trip' or 'luggage shifts'. If there is 'inverter trip' or 'luggage shifts', adjust parameters for braking function. Completion 13
15 4.3 Setting sample of related parameters Title Minimum Comm. Default Setting Functions Setting range setting value Number value sample (Panel/Comm.) Notes cmod 0003 Command mode selection 0 ~ :Terminal input enabled fmod 0004 Frequency setting mode selection 1 0 ~ :Setting dial 2 acc 0009 Acceleration time ~ 3600 sec. 0.1/ dec 0010 Deceleration time ~ 3600 sec. 0.1/ fh 0011 Maximum frequency 30.0 ~ 500.0Hz 0.1/ ul 0012 Upper limit frequency 0.5~ fh Hz 0.1/0.01 (*1) 60.0 ll 0013 Lower limit frequency 0.0 ~ ul Hz 0.1/ pt 0015 V/f control mode selection 0 ~ 7 - (*1) 3 (*3) 3: Vector control sr Preset speed operation frequency 1 ll ~ ul 0.1/ Operation frequency (Low) sr Preset speed operation frequency 2 ll ~ ul 0.1/ Operation frequency (High) f Output terminal selection 2A (OUT) 0 ~ : Brake release signal (*3) f Starting frequency setting 0.1 ~ 10.0 Hz 0.1/ f Dynamic braking selection 0 ~ :Enabled (Resistor overload protection enabled) f Overvoltage limit operation 0 ~ (*4) 1:Disabled 2:Enabled (quick deceleration) f Dynamic braking resistance 1.0 ~ 1000 ohm 0.1/0.1 (*2) (*5) f Allowable continuous braking resistance 0.01 ~ 30.00kW 0.01/0.01 (*2) (*6) f Creeping time ~10.00 sec 0.01/ f Braking mode selection 0 ~ f Load portion torque input selection 0 ~ f Hoisting torque bias input (valid only when f342=4) -250 ~ 250% 1/ Refer to section 4.4. f Lowering torque bias multiplier 0 ~ 100% 1/ f Brake release time 0.00 ~ sec. 0.01/ f Creeping frequency f240 ~ 20.0Hz 0.1/ f Creeping time ~ sec. 0.01/ f Braking time learning function 0, f Auto-tuning 0 ~ 5-0 f Slip frequency gain 0 ~ 150% 1/1 50 Refer to of the VFMB1 f Automatic torque boost value 0.1 ~ 30.0% 0.1/0.1 (*2) installation manual (*3) f Motor rated capacity 0.01 ~ 22.00kW 0.01/0.01 (*2) (E : f Motor rated current 0.1 ~ 100.0A 0.1/0.1 (*2) section 5.5 or 6.21) f Motor rated speed 100 ~ 64000min -1 1/1 (*1) Power running stall continuous trip f detection time 0.00 ~ sec. 0.01/ (*7) (*1) The values depend on the setup menu setting. (*2) Default setting values depend on inverter's capacity. Refer the installation manual about the default setting values. (*3) Select the vector control in case of using braking functions (output terminal functions: 68, 69). Set au2(torque boost setting macro function)=2 (vector control + auto-tuning), or set motor constant parameters (f401 ~ f417) and pt(v/f control mode selection)=3 (vector control) (*4) f304 (Dynamic braking selection)=1~ 4(Enabled) setting process automatically as same as f305 (Overvoltage limit operation) =1 (Disabled). 14
16 (*5) It is impossible to connect the braking resistor smaller than the minimum allowable resistance value. (*6) Set this parameter to specifications of connected braking resistor's capacity. (*7) This is one of functions to prevent from falling for lift application. The function offers inverter trip by judgment of motor stalling in continuous stall prevention mode. Set the detection time to about 0.5 seconds. 15
17 4.4 Braking functions The braking function is to ensure smooth operation with the motor produces enough torque before the brake is released. Starting procedure At the run command, the inverter makes the motor produce the torque specified with parameter f343. As soon as a torque output command is issued, a brake release request signal is put out through the brake output terminal. Upon expiration of the brake release time set with f345, the motor starts to accelerate. Stopping procedure At the stop command, the operation frequency is decreased to the creep frequency set with parameter f346, and put out the braking request after the creep time 1 set with f340. And then, the creep frequency is maintained for the creep time set with f347. While the creep frequency is maintained, the brake release signal is put out through the braking signal output terminal to apply the brake. Output frequency [Hz] Torque control Speed control Creeping frequency Starting frequency Time [s] Torque Issue of torque command Br ak ing si gnal Braking request Brake release request Braking operation RUN command 16
18 4.4.1 Parameters for braking functions TITLE FUNCTIONS Setting range Default setting value Setting sample Notes f340 Creeping time ~ sec f341 Braking mode selection 0:Disabled 1:Forward winding up 2:Reverse winding up 3:Horizontal operation 0 1 f342 f343 Load portion torque input selection Hoisting torque bias input (valid only when f342=4) 0:Disabled 1:VIA 2:VIB 3:VIC 4:f (*1) -250 ~ 250% (*2) f344 Lowering torque bias multiplier 0 ~ 100% f345 Brake release time 0.00 ~ sec (*3) f346 Creeping frequency f240 ~ 20.0Hz (*3) f347 Creeping time ~ sec (*3) f348 Braking time learning function 0:Disabled 1:Learning (0 after adjustment) 0 1 f340 : Creeping time 1 Inverter puts out the braking request after the time with f340 to wait for being minimize swing of load. f341 : Braking mode selection This parameter is for selection of operation mode of brake function. Usually, the forward (F terminal) operation is winding up. f342 : Load portion torque input selection This parameter is to set the brake releasing torque value as same as load torque to prevent load gap (shifts) at brake release. Usually, set the fixed f343 (Hoisting torque bias input) value with f342 = 4. (*1) This parameter is set f342=4 by Braking time learning function (f348)". f343 : Hoisting torque bias input This parameter is hoisting torque bias value that is valid only f342 = 4. The 100% value depends on f405 (Motor rated capacity) and f417 (Motor rated speed). Usually, set f343 =100. In case of some trouble after brake learning, adjust this setting value. (*2) This parameter is set f343=100 by Braking time learning function (f348)" f344 : Lowering torque bias multiplier The torque bias value when brake released is set by f342 (Load portion torque input selection). When winding down, the torque bias value is multiplied this parameter value. Usually, a necessary torque in winding down is decreased by squaring the mechanical efficiency. The hoisting torque bias in winding down at 80% machine efficiency is 0.8*0.8=0.64 (about 60%). Usually, set f344 = 60 ~
19 f345 : Brake release time The brake release demand signal is output at the same time as outputting the set torque after the starting signal turns on. After the time set with f345 (Brake release time), it accelerates. (*3)This parameter is set by Braking time learning function" as a rough adjustment. f346 : Creeping frequency After the starting signal turns off, it becomes a brake close operation after decelerated to f346 (Creep frequency). A standard setting of the creep frequency is about motor rated slips. For example, case of 5% slips in 60Hz motor, the creeping frequency is "60Hz*5%=3Hz". (*3)This parameter is set by Braking time learning function" as a rough adjustment. f347 : Creeping time 2 After the starting signal turns off, it becomes a brake close operation after decelerated to f346 (Creep frequency). Moreover, inverter's output frequency keeps a creeping frequency while set f347 (Creeping time 2). (*3)This parameter is set by Braking time learning function" as a rough adjustment. f348 : Braking time learning function The brake learning function is executed by set f348 (Braking time learning function) to 1. Parameters of f345 (Brake release time),f346(creeping frequency) and f347 (Creeping time 2) are set by " Braking time learning function" as a rough adjustment. And f342 =4 and f343=100 are set after adjustment. Torque bias function (f342 ~ f344) Using this function, the load can be started smoothly, by the motor produces enough torque for load portion before the brake is released, Reverse run Forward run Tension torque bias as additional torque <Selection of external signals> VIA-CC 0~10V (0~250%) 1 Voltage signals VIB-CC 0~±10V (-250~250%) 2 Current signals VIC-CC 4(0)~20mA (0~250%) Additional torque (fixed direction) 18
20 4.4.2 Execution of "Brake time learning" The brake function sets automatically the timing (torque establishment when starting) of the preliminary excitation by motor's constants value. It is necessary to set related parameter before "brake time learning". Before executed "brake time learning", the brake timing may not fit a load torque. Execute "brake time learning" at light load that is no load, 3% of rated load or less. Learning function (f348) Using this function, rough settings can be made automatically and also parameters f345, f346and f347 can be set automatically. After the learning function is set, f342 will be set automatically to 4 and f343 to 100. If necessary, fine adjust the parameter setting manually. Learning operation Set parameter f348 to 1 and enter an operation command to start learning. The frequency and tun are displayed alternately. Parameter f343 (torque) is set, the brake release timing is calculated, and parameter f345 (release time) is set based on the calculation result. f346 is set automatically according to the motor constant calculated. At the stop of operation, f347 (creep time) are set. Note 1: Note 2: Note 3: Learning should be performed under light-load conditions. If a counterweight is provided, a learning error may occur. If so, make an adjustment manually. Brake learning (f348=1) should be carried out for forward rotation if f341 is set to 1 (forward winding), or for reverse rotation if f341 is set to 2 (reverse winding). Notice for braking function Note 4: For the braking functions, the pre-excitation time is automatically determined by the inverter from motor-related constants. When the VFMB1S-2022PL is used in combination with a Toshiba 4P-2.2kW-60Hz-200V standard motor, the pre-excitation time is approximately 0.1 to 0.2 seconds. Depending on the motor, the pre-excitation time may be prolonged. Note 5: Select the vector control in case of using braking functions. Set au2 (Torque boost setting macro function) =2 (vector control + auto-tuning), or set motor constant parameters (f401~f417) and pt (V/F control mode selection) =3 (vector control). Note 6: When the inverter is confirmed operation by braking functions, connect and run the combined motor. As this function calculate the timing of brake by detecting output current, calculating error is occurred without connecting the motor. 19
21 4.4.3 Brake timing with maximum load The brake timing adjustment at no-load (light load) is completed by the previous chapter. Next confirmation is the brake timing with maximum load. Please confirm next items. - Isn't there load gap (shifts) when starting on the winding up, and is the start when the brake is released smooth? - Isn't there load gap (shifts) when the brake operates? - Isn't there load gap (shifts) in case of the repetition of the start (run/stop)? - Does the allophone from the brake when start or stop, or not? - Does the inverter trip when start or stop, or not? There is no trouble after confirmation, an adjustment of the brake function is completed. Convenient function for adjustment When starting, the lift application is necessary to get enough output torque and to adjust brake release timing. When stopping, it is necessary to shutdown the inverter output with being sure brake-on. Therefore, the state that the motor is restrained to some degree is generated when start/stop. In case of a short restrained time, it happens that load shifts. But, in case of long restrained time, the inverter trip is caused by increased motor current. Please use next parameter when adjustment that can confirm a peak output current. Usually, a peak output current is about 150% of inverter's rated current. Title Function Setting range f709 Standard monitor hold function 0:Real time 1:Peak hold 2:Minimum hold Default setting value Setting sample Notes f710 Initial panel display selection 0 ~ Output current f750 EASY key function 0:Easy/standard setting mode switching function 1:Shortcut key 2:Local/remote key 3:Monitor peak minimum hold trigger The status monitor is changed "Peak hold value of output current" by above parameter settings. This peak value is changed when the peak value of the output current is updated by start/stop. When push the "EASY" key, the peak hold value is reset. 20
22 4.4.4 Abnormal phenomenon and the measures Abnormal phenomenon and the measures (adjustment item) according to load and operating condition Load condition Operating condition Abnormal phenomenon Countermeasure (adjustment item) 1. Set f345 (Brake release time) to short value. No-load At start When winding down operation, wind down after a little winding up. 2. Set f344 (Lowering torque bias multiplier) to 5% down. 3. Set f343 (Hoisting torque bias input) to 5 ~ 10% down. No-load or load At start When winding up operation, it happens a little load gap/shift (a little winding down). 1. Set torque bias value of f342 (Load portion torque input selection) and f343 (Hoisting torque bias input) to increased 10 ~ 20%. No-load or load At start or stop When winding up operation with inching, it happens a little load gap/shift (a little winding down). 1. Set f345 (Brake release time) to short value. Notice of adjustment When adjust f345 (Brake release time) and f347 (Creeping time 2), these setting value have to be changed step by step. If these values are too large or small, the load may fall in worst case because of not matched "brake operation" and "generating motor torque" timing. 21
A1000 Cheat Sheet (Open Loop Vector)
A1000 Cheat Sheet (Open Loop Vector) The following procedure is a supplement to supplied with this equipment and will guide the user in properly wiring the A1000 and. It will also show the user how to
GPD 506/P5 Start-up Procedure and Checklist
GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass
FRENIC5000MS5 for Machine Tool Spindle Drives
FRENIC5MS5 for Machine Tool Spindle Drives Yoshikazu Tanaka Hiroaki Hayashi Hiroshi Takahashi 1. Introduction Fig.1 External view of FRENIC5MS5 In AC spindle drive systems for machine tools, operation
Altivar 212. Variable speed drives for asynchronous motors. Programming Manual 09/2011. www.schneider-electric.com S1A53838
Altivar 22 Variable speed drives for asynchronous motors Programming Manual 9/2 SA53838 www.schneider-electric.com The information provided in this documentation contains general descriptions and/or technical
J1000. System configuration
YASKAWA JZ J1000 The basic inverter V/f controlled inverter Good torque performance (150% / 3 Hz) Double rating ND 120%/1min and HD 150%/1 min Overload detection function (150% during 60s) thermal function
User Manual. MODBUS-RTU Option Board for SV-iS5 Series. LG Industrial Systems
User Manual MODBUS-RTU Option Board for SV-iS5 Series Read this manual carefully before using the MODBUS-RTU Option board and follow the instructions exactly. After reading this manual, keep it at handy
1000 Hz High Frequency Custom Software
YASKAWA AC Drive - V1000 Option 1000 Hz High Custom Software Supplement Software No. VSV91005X To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance.
SAFETY INSTRUCTIONS WARNING
Important User Information Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this
TAKEDO -3VF V20 INSTRUCTION MANUAL. www.sms.bo.it 3 18-10-2013. REL. DATE T.M. Check and Approval
TAKEDO -3VF V20 INSTRUCTION MANUAL 3 18-10-2013 REL. DATE T.M. Check and Approval www.sms.bo.it PAGE INTENTIONALLY LEFT BLANK 1 INTRODUCTION TAKEDO-3VF V20 is a new type of drive with built-in EMC filter,
NX Series Inverters. HVAC Pocket Programming Guide
NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product
Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S
New Products Introduction Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S Takashi Sekiguchi Masahiro Kidou Yuusuke Shimura Yuji Ide Masahisa Koyama Michio Kitahara
Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA
Speed Control Methods of Various Types of Speed Control Motors Kazuya SHIRAHATA Oriental Motor Co., Ltd. offers a wide variety of speed control motors. Our speed control motor packages include the motor,
Apéndice E Listado de constantes
Listado de constantes Operation U1 Monitor U1--01 Frequency Ref Hz -- -- Q Q Q Q U1--02 Output freq Hz -- -- Q Q Q Q U1--03 Output current A -- -- Q Q Q Q U1--04 Control Method -- -- -- Q Q Q Q U1--05
SAFETY INSTRUCTIONS WARNING
Thank you for purchasing LG Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are
3753 en - 04.2004/b VE/B - VE/RG Va V riable speed drives
3753 en 04.2004/b Variable speed drives LEROYSOMER's drives provide SPEED VARIATION for a DC motor, SIMPLY and ECONOMICALLY from a singlephase power supply. CMStype technology is used. These products conform
MOVFR ELECTRICAL ADJUSTMENTS. G.A.L. MFG. CORP. NEW YORK CITY U.S.A. http://www.gal.com
MOVFR ELECTRICAL ADJUSTMENTS G.A.L. MFG. CORP. NEW YORK CITY U.S.A. http://www.gal.com 1 ELECTRICAL ADJUSTMENTS ADJUSTING INSTRUCTIONS FOR THE G.A.L. VARIABLE FREQUENCY CLOSED LOOP DOOR OPERATOR TYPE MOVFR
YASKAWA AC Drive A1000
YASKAWA AC Drive A1000 Crane Software Application Manual Software No. VSA90507X Type: CIMR-AC Models: 200 V Class: 0.4 to 110 kw (1.2 to 160 kva) 400 V Class: 0.4 to 300 kw (1.4 to 460 kva) To properly
SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring.
Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are
VLT 6000 HVAC. Contents
Contents Introduction Safety...3 Safety Guidelines...3 Warnings Against Unintended Start...3 Introduction...4 About this manual...4 Assumptions...4 References...4 Trademarks...5 Programming the VLT 6000
Manual No. YEG-TOE-S616-55.1-OY. VARISPEED F7 Vector Control Frequency Inverter USER S MANUAL
Manual No. YEG-TOE-S616-55.1-OY VARISPEED F7 Control Frequency Inverter USER S MANUAL Table of Content Warnings... VII Safety Precautions and Instructions for Use... VIII EMC Compatibility... X Line Filters...
INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2
INDUCTION MOTOR PERFORMANCE TESTING WITH AN INVERTER POWER SUPPLY, PART 2 By: R.C. Zowarka T.J. Hotz J.R. Uglum H.E. Jordan 13th Electromagnetic Launch Technology Symposium, Potsdam (Berlin), Germany,
SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring.
Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are
Emotron VSA Variable Speed Drive
Emotron VSA Variable Speed Drive Instruction manual English Quick Start Guide This guide is designed to assist in installing and running the variable speed drive to verify that the drive and motor are
UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING.
UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING. Group # First Name Last Name UserID @uwaterloo.ca Experiment #3: DIRECT CURRENT
Application Engineering
Application Engineering February 2011 Electronic Unit Controller Table of Contents 1. Introduction and Features... 2 1.1 Technical Specifi cations... 3 1.2 Pressure Probe Error Bypass... 3 1.3 Bump Start...
Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1
Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status
TABLE OF CONTENTS. Fig. 1 EV Pictorial Wiring Diagram 5. Section 2 Inverter Option Modules 6
TABLE OF CONTENTS Introduction.. 3 Section 1 Safety Precautions.. 3 1.1 Preface.. 3 1.2 Receiving and Inspection... 3 1.3 Installation and Pre-operation 4 1.4 During Power ON. 4 Fig. 1 EV Pictorial Wiring
Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations
Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations Addendum to: IMPULSE G+ Series 3 Manual (140-10258) IMPULSE VG+ Series 3 Manual (140-10257) This addendum should be used when a 24VDC
Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz
HV Solar Inverter System GUI Overview January 2012 TMS320C2000 Systems Applications Collateral The HV Solar Inverter System GUI provides a simple interface to evaluate some of the functionalities of the
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following
WINDOW's Programming Software USER MANUAL
www.danahermotion.com High frequency inverter ACO5000 by ACOMEL WINDOW's Programming Software USER MANUAL DANAHER MOTION S.A. La Pierreire 2, CH-1029 Villars-Ste-Croix Telephone +41 21 631 33 33, Telefax
VCM Installation and Operations Manual. Table of Contents
Table of Contents VCM Installation and Operations Manual 1.0 Introduction... 1 2.0 Product Inspection... 2 2.1 Nameplate Layout... 2 3.0 Operating Precautions... 3 3.1 Before Power up... 3 3.2 During Power
SJ200 Series Inverter Quick Reference Guide
SJ2 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB6501XA March 24 Caution:
VS-606V7 Series Instruction Manual COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL)
VS-606V7 Series Instruction Manual COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) PREFACE YASKAWA s VS-606V7 is such a small and simple inverter; as easy as using a contactor. This instruction
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
BIG SAVINGS FOR A LOT MORE APPLICATIONS
MSF SOFT STARTERS BIG SAVINGS FOR A LOT MORE APPLICATIONS Soft Starters from Emotron Unique features built into Emotron MSF Soft Starters reduce costs significantly for many more applications when compared
Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
MEMOBUS/Modbus Communications
2 2.1 MEMOBUS/MODBUS CONFIGURATION............260 2.2 COMMUNICATION SPECIFICATIONS..............261 2.3 COMMUNICATION TERMINAL RESISTANCE........262 2.4 CONNECTING A PLC...........................263 2.5
For speed control of 3-phase induction motor Low-Noise Inverter M1S Series Operating Instructions
For speed control of 3-phase induction motor Low-Noise Inverter M1S Series Operating Instructions Be sure to provide the customer with a copy of this manual. Thank you for purchasing a Panasonic Inverter.
Application Note AN-SERV-006
THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT IS SUPPLIED "AS IS", WITHOUT ANY GUARANTEE OF ANY KIND. These documents are provided by our technical support department to assist others.
POWERDRIVE MD. Variable speed drive. Commissioning manual. 3871 en - 2011.05 / h. Digital input polarity 8.29. Input or output.
Digital input or output DIO 8.29 Digital input polarity Negative Input or output selection Positive 8.3 Output DIO state 8. Invert 8. Input Digital input or output 2 DIO2 DIO2 state 8.2 Input or output
DC Motor control Reversing
January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical
2011 Industrial Catalog. DRIVES, PAC, PLCs. Industrial Catalog 2011. www.toshiba.com/ind
www.toshiba.com/ind 2011 Toshiba International Corporation Rev. 110504 Industrial Catalog 2011 13131 W. Little York Road Houston, TX 77041 Tel: 713-466-0277 Fax: 713-466-8773 US: 800-231-1412 Canada: 800-872-2792
32VFD Variable Frequency Drives for Centrifugal Chillers
32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to
ACS800. Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program
ACS800 Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program Master/Follower Application Guide Supplement to Firmware Manual ACS800 Standard Application
$MPTFE -PPQ 4UFQQJOH 4ZTUFN XJUI /FUXPSL #BTFE.PUJPO $POUSPMMFS
2 $MPTFE -PPQ 4UFQQJOH 4ZTUFN XJUI /FUXPSL #BTFE.PUJPO $POUSPMMFS 2 Position Table Function Position Table can be used for motion control by digital input and output signals of host controller. You can
CPW Current Programmed Winder. Application Handbook. Copyright 2002 by Eurotherm Drives, Inc.
CPW Current Programmed Winder Application Handbook Copyright 2002 by Eurotherm Drives, Inc. All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted, in
IQAN MDM Operation Manual
IQAN MDM Operation Manual Purpose The primary purpose of this document is to inform a user of the IQAN system on the ease of adjustments of the system. A person can create a much smoother machine control
Properties of electrical signals
DC Voltage Component (Average voltage) Properties of electrical signals v(t) = V DC + v ac (t) V DC is the voltage value displayed on a DC voltmeter Triangular waveform DC component Half-wave rectifier
How To Use The Vacon 0 Machinery
vacon 0 machinery how would you like your ac drive today? easy adaptation for customer requirements The Vacon 0 Machinery is an extremely compact AC drive for machine builders in the power range from 0.25
NXL Series Inverters. HVAC Inverters made simple
NXL Series Inverters HVAC Inverters made simple Honeywell s Voice Of the Customer process unveils a range of requirements expressed by specifiers and installers, that are ideally covered by the NXL inverter
CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual
Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
GSM AUTO DIALER. Remote Monitoring & Control using your mobile phone. www.gsm-activate.co.uk
GSM AUTO DIALER Remote Monitoring & Control using your mobile phone www.gsm-activate.co.uk Product Information Our GSM Auto-Dialer is a versatile unit which can be attached to many of your electronic devices
KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual
KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual Patented Ultra Fast CL Circuit Prevents Demagnetization in PM Motors Installation and Operating Instructions
Siemens Standard Drives. Application Handbook
Siemens Standard Drives Application Handbook Martin Brown Siemens Standard Drives Congleton December 1997 1. Introduction....4 1.1 What is a Variable Speed Drive?...4 1.2 The Variable Frequency Inverter...7
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
User manual. MODBUS-RTU SV-iC5. LG Industrial Systems
User manual MODBUS-RTU SV-iC5 Read this manual carefully before installing, wiring, operating, servicing or inspecting the drive. Keep this manual within easy reach for quick reference. LG Industrial Systems
HVDP. High Voltage Dynamic Power supply/source. 1, 2.5 and 5kW Output DC + Sine Wave Family
Milano, 12 March 2015 HVDP High Voltage Dynamic Power supply/source 1, 2.5 and 5kW Output DC + Sine Wave Family HVDP (High Voltage Dynamic Power) is a family of power supply/source designed to generate
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply
1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,
Operational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual
ELECTRIC MOTORS, GEARMOTORS AND DRIVES Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual We, EC Declaration of Conformity In accordance with EN45014:1998 Leeson Electric Corporation
Printed in China. Issue 4 AT&T 12/11. Message Guard is a registered trademark of Advanced American Telephones.
www.telephones.att.com 2011 Advanced American Telephones. All Rights Reserved. AT&T and the AT&T logo are trademarks of AT&T Intellectual Property licensed to Advanced American Telephones, San Antonio,
Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits
Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
GSM HOME SECURITY SYSTEM
Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.
Number 1 in efficiency
PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why
OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3
2 Phase Stepping Motor Driver 2M542 OPEATING MANUAL Table of contents Introduction page 2 Specifications page 2 Timing chart page 3 Setting page 4 Current set page 4 educe current function page 4 Micro
YASKAWA AC Drive Compact V/f Control Drive J1000
YASKAWA YASKAWA AC Drive Compact V/f Control Drive 100 V CLASS, SINGLE-PHASE INPUT: 0.1 to 1.1 kw 200 V CLASS, THREE-PHASE INPUT: 0.1 to 5.5 kw 200 V CLASS, SINGLE-PHASE INPUT: 0.1 to 2.2 kw 400 V CLASS,
A.3 ALARMS (SERIAL SPINDLE)
A.3 ALARMS (SERIAL SPINDLE) NOTE*1 Note that the meanings of the indications differ depending on which LED, the red or yellow LED, is on. When the red LED is on, the indicates a 2 digit alarm number. When
VLT AutomationDrive for Marine winch applications
MAKING MODERN LIVING POSSIBLE VLT APPLICATION NOTE VLT AutomationDrive for Marine winch applications This Application note is meant to be a guideline for using Danfoss VLT AutomationDrive in winch applications.
IV. Three-Phase Induction Machines. Induction Machines
IV. Three-Phase Induction Machines Induction Machines 1 2 3 4 5 6 7 8 9 10 11 12 13 Example 1: A 480V, 60 Hz, 6-pole, three-phase, delta-connected induction motor has the following parameters: R 1 =0.461
AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use:
AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use: advanced soft start and soft stop control protection functions that operate even when
CHAPTER 11: Flip Flops
CHAPTER 11: Flip Flops In this chapter, you will be building the part of the circuit that controls the command sequencing. The required circuit must operate the counter and the memory chip. When the teach
HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE
HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3
LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems
LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring
1115 4G SERIES GOVERNOR. 4-20 ma ANALOGUE DIGITAL SPEED SETTING
1115 4G SERIES GOVERNOR with 4-20 ma ANALOGUE & DIGITAL SPEED SETTING PO Box 28, 9300AA Roden, The Netherlands Tel: +31 505019888 Fax: +31 505013618 E-mail: [email protected] 1115 4G
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Programming Guide TR200 BAS-SVP04B-EN. November 2009
Programming Guide TR200 November 2009 BAS-SVP04B-EN Table of Contents Safety 1-1 High Voltage Warning 1-1 Before commencing repair work 1-4 Special conditions 1-4 IT line power 1-5 Introduction 2-1 Copyright,
ABB general purpose drives. Firmware manual ACS580 standard control program
ABB general purpose drives Firmware manual ACS580 standard control program List of related manuals Drive manuals and guides ACS580 firmware manual ACS580-01 hardware manual ACS580-01 quick installation
BLY17MDA Series. 24V, 10A Brushless Controller/Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.
BLY17MDA Series 24V, 1A Brushless Controller/Motor User s Guide A N A H E I M A U T O M A T I O N 91 East Orangefair Lane, Anaheim, CA 9281 e-mail: [email protected] (714) 992-699 fax: (714) 992-471
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD
Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: 200137 Tel: 86-21-5012789 Fax: 86-21-58675966 E-mail: [email protected] LINE 1 LINE 3 LINE 5
PowerFlex Dynamic Braking Resistor Calculator
Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing
Multi-Protocol decoder 76 400
Multi-Protocol decoder 76 For locomotives with DC motors on digital layouts operating in the DCC- and Motorola data format. Features Regulated multi-protocol decoder for DCC and Motorola Suitable for DC
XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications
The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications The XFE Soft Starter range provides a combination of competitive prices, flexible
LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: [email protected] url: http//www.len.
MA511 General Index 1 INTRODUCTION... 3 1.1 HARDWARE FEATURES:... 4 2 INTERFACE... 5 2.1 KEYBOARD... 6 2.2 POWER ON... 7 2.3 POWER OFF... 7 2.4 DETECTOR CONNECTION... 7 2.5 DETECTOR SUBSTITUTION...7 3
AC Kinetics Variable Frequency Drive Comparative Transient Inertial Testing. This document was prepared by Advanced Energy.
AC Kinetics Variable Frequency Drive Comparative Transient Inertial Testing This document was prepared by Advanced Energy. December 12 th, 2014 Introduction In June of this year, AC Kinetics contacted
Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111
, GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,
LIFT CONTROL SYSTEMS CATALOGUE 2007
LIFT CONTROL SYSTEMS CATALOGUE 2007 All Your Needs For Elevators INDEX 1. Lift Control Cards... 3 2. Speed Control Units... 7 3. Emergency Rescue Cards... 8 4. Lift Control Panels... 10 5. Photocells...
Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors
Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,
Business/Home GSM Alarm System. Installation and User Manual
Business/Home GSM Alarm System Installation and User Manual Brief Introduction: GSM 900/1800/1900 bands, can be used in most parts of the world Full duplex communication with the host Monitor the scene
VEHICLE SPEED CONTROL SYSTEM
PL VEHICLE SPEED CONTROL SYSTEM 8H - 1 VEHICLE SPEED CONTROL SYSTEM TABLE OF CONTENTS page DESCRIPTION AND SPEED CONTROL SYSTEM...1 SPEED CONTROL SERVO-PCM OUTPUT....2 SPEED CONTROL SWITCHES PCM INPUT...2
User manual. magnetic absolute positioning drive AG03/1
User manual magnetic absolute positioning drive AG03/1 1 GENERAL REMARKS... 3 1.1 DOCUMENTATION... 3 1.2 BLOCK DIAGRAM... 3 2 FUNCTIONAL DESCRIPTION... 4 2.1 SYSTEM STATUS WORD... 4 2.2 OPERATING MODES...
PIN CONFIGURATION FEATURES ORDERING INFORMATION ABSOLUTE MAXIMUM RATINGS. D, F, N Packages
DESCRIPTION The µa71 is a high performance operational amplifier with high open-loop gain, internal compensation, high common mode range and exceptional temperature stability. The µa71 is short-circuit-protected
Direct Current Motors
Direct Current Motors DC MOTORS The DC machine can operate as a generator and as a motor. Chap 5. Electrical Machines by Wildi, 6 e Lecturer: R. Alba-Flores Alfred State College Spring 2008 When a DC machine
BLE Series. Data setting software MEXE02 OPERATING MANUAL. Tabel of contents 1 Synchronization with the driver...2 2 Monitor function...
HP-5046 Data setting software MEXE02 BLE Series OPERATING MANUAL Thank you for purchasing an Oriental Motor product. This operating manual describes product handling procedures and safety precautions.
Content. Operational manual for RBU
Content Operational manual for RBU 1 Safety Precautions...1 1.1 Safety definition... 1 1.2 Warning symbols... 1 1.3 Safety guidelines... 1 2 Inspection...4 2.1 Unpacking inspection... 4 2.2 Application