Generic Reliability Evaluation Method for Industrial Grids with Variable Frequency Drives
|
|
|
- Sara Richards
- 9 years ago
- Views:
Transcription
1 Energy and Power Engineering, 2013, 5, doi: /epe b016 Published Online July 2013 ( Generic Reliability Evaluation Method for Industrial Grids with Variable Frequency Drives Rongrong Yu 1, Yao Chen 1, Jiuping Pan 2, Richard W Vesel 3 1 Power Systems, ABB Corporate Research Beijing, China 2 Power Technologies, ABB Corporate Research, Raleigh, USA 3 EBoP Energy Efficiency, ABB Power Generation, Wickliffe, USA [email protected], [email protected], [email protected], [email protected] Received January, 2013 ABSTRACT The paper presents a reliability evaluation method based on fault tree analysis with set theory and minimal cut set as core algorithm, which can be used to evaluate the reliability for industrial grids with wide application of variable frequency drives. The working principle is introduced firstly, based on which the method development considering different system topology designs, backup solutions and redundancy mechanisms are analyzed in details. In the end the proposed method is applied to two cases to show the reliability performance of system with variable frequency drives. The proposed method is also suitable for analyzing the reliability performance of industrial grids with other types of power electronic converter technology. Keywords: Fault Tree Analysis; Minimal Cut Set; Reliability; Industrial Grids; Variable Frequency Drives 1. Introduction One of the most essential elements contributing to quality of industrial grids is design of its electrification scheme. Nowadays in order to increase system efficiency and reduce energy consumption losses, power electronic devices like Variable Frequency Drives (VFD) are widely applied in both power generation and distribution grids. With introduction of power electronic devices, reliability of the original system topology may be influenced. However, conventional reliability evaluation method as in [1] is designed without considering VFD. As a result, it s worthwhile finding a generic approach to evaluate the reliability of industrial grids with VFDs or other types of power electronic converter technology to appraise VFD impact and propose improvement solution. Most commonly used reliability study methods for power system include Reliability Block Diagram (RBD) [2], Markov chain [3], Monte Carlo simulation [4] and Fault Tree Analysis (FTA) [5]. Considering the feature of industrial grids, for example, multi-input and multi-output, large quantity of components, known electrification scheme, desiring to identify key component(s) with biggest impact on the entire system reliability, as well as for the purpose of reflecting reliability trend after introducing VFDs, FTA is chosen in this paper to develop a generic evaluation algorithm. Minimal cut set is embedded as basic failure event identification way in FTA. In the following parts of the paper, firstly, generic working principle of using FTA to evaluate reliability for industrial plants is introduced; Secondly, detailed calculation procedures with minimum cut set and set theory considering different system topology designs, backup solutions and redundancy mechanisms are analyzed in details; thirdly, the proposed method is demonstrated respectively with two case studies. 2. Principle Analysis of FTA 2.1. Working Principle The main steps of FTA are described in Figure 1, starting from network topology definition, e.g. single-bus or dual- bus power circuit topology; to top event identification, which usually refers to system power supply interruption; to minimum cut set categorization, to come out with groups of basic failure events that will lead to the top event; and finally to reliability indices calculation. The final indicator will be Expected Energy Not Supplied (EENS), i.e. the undesired energy losses due to reliability issues Input and Output Indices According to the basic theory of FTA, following component reliability data is required as input information to quantify the reliability indices for each failure event: total failure rate, active failure rate, repair time, switching time, stuck probability, maintenance rate and main-
2 84 R. R. YU ET AL. tenance time [1]. Output indices to measure the reliability performance for a given system include: failure rate, outage duration, average repair time and EENS. 3. Reliability Evaluation for Single-bus Bar System A typical single-bus bar system can be separated into two parts for reliability analysis: one is power supply part as in Figure 2(a), including a main path consisting of the main transformer in series with a normally close breaker, and a spare path consisting of the backup transformer in series with a normally open breaker; the other is power consumption part as in Figure 2(b), including a number of branches, each consisting of motor, individual VFD, line-side transformer and normally close breaker. The reason for this separation is that the consequences of failure occurrence in these two parts reflecting by EENS are different from the whole system point of view Reliability Evaluation for Power Supply Part In this section, reliability evaluation method for power supply part is firstly presented. By defining the following two events, A & B: Event A failure event that can be eliminated by closing the spare path; Event B event that the spare path is available before having the components of failure event a restored back to service. Figure 1. Main steps of FTA. (a) Power supply part (b) Power consumption part Figure 2. Reliability evaluation for single bus bar topology. According to total probability formula, outage duration of event A can be calculated by: ua u( A B)[1 ( ue / 8760 Ps)] (1) uab ( )( u/ 8760 P) where is annual outage duration caused by event, indicating that the spare path is always available when needed; is annual outage duration of event indicating the spare path is unavailable to restore service; is the equivalent outage duration of the spare path; is the stuck probability of breaker; 8760 indicates the hours per year. It should be noticed that besides the failure probability, the stuck breaker might also lead to the undesired outage. Two steps are needed to utilize (1) to obtain reliability indices of power supply part as in Figure 2(a), which is exactly the two items of (1). The unavailability of the spare path comprises two cases: forced outage and maintenance, which both make it unable to replace the failed main path to continue the power supply. Integrating all of them together, we totally consider three possible cases, where overlapped maintenance for both main path and spare path is not considered here. - Main path failure plus spare path failure; - Main path failure plus spare path maintenance; - Main path maintenance plus spare path failure. Based on the analysis above, we can obtain the outage duration caused by the main transformer: e u r u u P '' A1 s[1 ( e / 8760 e / 8760 s)] '' '' r ( ue / 8760 Ps) where and are the failure rate and maintenance rate of main transformer respectively; and are switching time and maintenance time of main transformer; is the equivalent outage duration of the spare path due to failure; is the equivalent outage duration of the spare path due to scheduled maintenance. By using the same method we can calculate the outage duration caused by the normally close circuit breaker, and then obtain the overall outage duration of power supply path with the unit of hours per year. Assuming the power output of such system is, EENS can be calculated by with unit of MWh/y. The higher the EENS is, the worse the reliability will be Reliability Evaluation for Power Consumption Part In this section, reliability evaluation method suitable for the power consumption part will be given. Assuming there are N branches, and N-1 redundancy mechanism is adopted, i.e. no output loss will be caused by removal of single motor branch, by iteratively using the total probability formula for N-1 times and integrating all the re- s (2)
3 R. R. YU ET AL. 85 sults together, the final EENS caused by the power consumption part can be obtained (Detailed calculation procedures are ignored here). N 1 1 i 1 EENS P0 * * u *( N i)* p *(1 p) (3) N 1 i 1 where u and p refer to the outage duration and the outage probability for each motor branch. 4. Reliability Evaluation for Dual-bus Bar System A typical dual-bus bar system is shown in Figure 3, which can also be separated into two parts for reliability analysis: one is power supply part including two bus bars as in Figure 3(a), each supplied by a transformer in series with a normally close circuit breaker, and with a normally open circuit breaker in between; the other is power consumption part including a number of branches as in Figure 3(b), each consisting of motor, VFDs, lineside transformer and normally close (or normally open) circuit breaker Reliability Evaluation for Power Supply Part In this section, reliability evaluation method for power supply part is firstly presented. Different with single bus bar topology, Set Theory should be introduced to evaluate the reliability of dual (or multiple buses) system. Assume event A is outage of bus bar 1 and event B is outage of the bus bar 2. As shown in Figure 4, the crossing section of set A and set B represents the occurrence of overlapping outage. (a) Power supply part (b) Power consumption part Figure 3. Reliability evaluation for dual bus bar topology. Figure 4. Set theory based busbar loss. Based on the set definition and the total probability formula introduced above, outage duration of busbars can be obtained using equation below: ubusbar u( AB) u( BA) u( AB) uabpb ( ) ( ) ub ( APA ) ( ) uabpb ( ) ( ) where, is the duration of bus bar 1 outage while bus bar 2 in service; is the duration of bus bar 2 outage while bus bar 1 in service, if both bus bars are symmetrical; is the duration of bus bar 1 and 2 both fail. and are the normal operation probability of bus bar 1 and 2; if both bus bars are symmetrical. The EENS of dual-bus system power supply part can be therefore calculated: EENSbusbar PL( AB) u( AB) PL ( BA) u( BA) P ( AB) u( AB) L where, is the power loss in case of failure event, namely one bus bar outage while the other bus bar in service, if both bus bars are symmetrical; is the system overall power loss Reliability Evaluation for Power Consumption Part In this section, reliability evaluation method suitable for the power consumption part will be given. Assuming there are totally N motor branches connected to bus bar 1 and 2; and N+2 redundancy mechanism is adopted, i.e. two standby branches (regardless of in the same or separate bus bars) can be switched in to maintain the output in case of the failure or maintenance event of any branch in operation, the outage duration caused by the power consumption part can be calculated as follows: umotor C P (1 P) u* 1 1 N 1 N N i N i N i i 2 C P (1 P) [( i 2) u 2 u*] where, P is probability of each motor branch outage (considering both failure and maintenance); u is outage duration of each motor branch without standby branch; u* is outage duration of each motor branch with standby branch. Assume is the rated power of the motor branch, the EENS of power consumption part can be calculated by. (4) (5) (6)
4 86 R. R. YU ET AL. 5. Case Studies 5.1. Power Plant Auxiliary System Figure 5(a) shows a simplified Single Line Diagram (SLD) of a solar thermal power plant auxiliary system [6], with both main path and spare path for the power supply part, and totally 13 motor branches with VFDs for the power consumption part. The motor branches can be further categorized into three groups as indicated in the figure. The three groups of motors respectively take responsibility for driving pumps with three types of functionality: 6 x heat transfer fluid pumps to pump the oil from the cold pipes through solar field to the hot pipes. 4 x cold tank pumps to pump the cold molten salt from the cold tank through salt-htf heat exchanger to the hot tank, to store extra solar energy during daytime. 3 x hot tank pumps to pump the hot molten salt from the hot tank through salt-htf heat exchanger to the cold tank, to discharge energy for power generation after sunset. For each group, N-1 redundancy mechanism is adopted. (a) Simplified SLD of power plant auxiliary system (b) Fault tree of power plant auxiliary system Figure 5. Reliability case study for power plant auxiliary system.. By defining the generation reduction as the top failure event, the fault tree of the given system can be drawn as shown in Figure 5(b). The analysis is commenced by calculating reliability indices of each load point in the electrical auxiliary system, e.g. load point 3 (bus bar) that will lead to complete loss of generation, and load point 9 (auxiliary motor) that will lead to partial loss of generation. Assuming the power generation capacity is 50 MW, the overall reliability indices for the single bus auxiliary system can be calculated as shown in Table 1. It can be observed that, the EENS with regard to the complete generation loss is mainly caused by power supply part, which is MWh per year; the EENS with regard to the partial generation loss caused by the motor branches is 4.14 MWh per year. Totally, for the 50MW power plant, EENS caused by VFD based auxiliary system is MWh/y. It can also be seen from Table 1 that generation loss caused by VFD is about 5.33 h/y (for each motor branch), corresponding to 3.15 WMh/y (13 motor branches), which accounts for over 8% of the overall EENS. One possible measure to further improve reliability is to utilize dual-bus topology which will be exemplified in the next section Water Pumping Station Figure 6(a) shows a simplified SLD of a water pumping station, with two bus bars in the power supply part, and totally 8 motor branches with VFDs for the power consumption part. N+2 redundancy mechanism is adopted, with two standby motor branches connected to the bus bars via normally open circuit breakers. By defining the shortage of pumped water to be the top event, the fault tree of the given system can be drawn as shown in Figure 6(b), consisting of two groups of failure events: motor branch loss, and bus bar loss. Table 1. Reliability indices for single bus power plant auxiliary system. Forced outages overlapping maintenance Failure event λ/y u (h/y) r (h) 1* * Complete loss (4) (4) Total (complete loss) EENS complete (MWh/y) Partial loss EENS partial (MWh/y) 4.14 EENS (MWh/y) Note: Bold data means it should be multiplied with 13 (number of motors) before summing.
5 R. R. YU ET AL. 87 Using the Set Theory, the basic events leading to the bus bar failure can be specified. Assuming the power capacity of each motor is MW, the overall reliability indices for the dual bus water pumping station can be calculated as shown in Table 2. The overall energy loss in this case is 9.97 MWh/y, the majority of which comes from losses on bus bars. Losses caused by VFD are only MWh/y (accounting for only 0.02% of the overall EENS), which demonstrates the superiority of dual bus design and N+2 redundancy mechanism. Compare single-bus system with dual-bus one, it can be seen that dual-bus system has better reliability than single-bus one. This is because dual busbar topology design can dramatically decrease the probability of the total plant loss. (a) Simplified SLD of water pumping station (b) Fault tree of water pumping station Figure 1. Reliability case study for water pumping station. Table 2. Reliability indices for dual bus water pumping station. Busbar 3 Busbar 11 Busbar 3 & 11 Failure event u (h/y) Failure event u (h/y) Failure event u backup fail. (h/y) u back maint. (h/y) Busbar loss (power supply loss) Busbar loss (motor path active failure loss) 1* * * * (4) (4) (4) (4) (4) (4) Bus outage duration (h/y) EENS busbar (MWh/y) * 0.07 Motor loss * * 0.00 Motor outage duration (h/y) 0.00 EENS motor (MWh/y) 0.00 EENS (MWh/y) 9.97
6 88 R. R. YU ET AL. 6. Conclusions In this paper, a generic reliability evaluation method for industry grid with VFD applications has been developed based on fault tree analysis method together with minimal cut set and set theory. Different topology design and redundancy mechanism have been considered in the algorithm design. Reliability of both single-bus and dualbus electrification schemes have been evaluated using the proposed method. Demonstrated by the two case studies, the proposed approach can not only quantify the reliability of a given system, but also differentiate the undesired outage caused by individual component, which is important to identify the weak point of the system for reliability improvement. Furthermore, it is also suitable for analyzing the reliability of industrial grids with multiple bus bars, or with other types of power electronic converter technology. REFERENCES [1] R. N. Allan, R. Billinton and M. F. Deoliveire, Reliability Evaluation of the Auxiliary Electrical Systems of Power Stations, IEEE Transactions on Power Apparatus and Systems, Vol. 5, 1977, pp doi: /t-pas [2] P. Zhou, H. G. Mou, Y. Liu and L. Zhang, Reliability Evaluation for Electromechanical Fuze Based on Series Model and Parallel Model, Journal of Detection & Control, Vo. 31, No. 6, 2009, pp [3] R. Billinton, H. Chen and J. Zhou, Generalized n+2 State System Markov Model for Station-Oriented Reliability Evaluation, IEEE Transactions on Power Systems, Vol. 12, No. 4, 1997, pp doi: / [4] Y. Ou and L. Goel, Using Monte Carlo Simulation for Overall Distribution System Reliability Worth Assessment, IEE Proceedings: Generation, Transmission and Distribution, Vol. 146, No. 5, 1999, pp doi: /ip-gtd: [5] R. S. Chanda and P. K. Bhattacharjee, A Reliability Approach to Transmission Expansion Planning Using Fuzzy Fault-Tree Model, Electric Power Systems Research, Vol. 45, No. 2, 1998, pp doi: /s (97) [6] -thermal-storage-plant-to-start-up
Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application
Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application A.Thiyagarajan Assistant Professor, Department of Electrical and Electronics Engineering Karpagam Institute of Technology
Independent analysis methods for Data Centers
Bilfinger HSG Facility Management GmbH Independent analysis methods for Data Centers Max Altmeyer / Marvin Köhler August 19 th, 2015 Agenda 1. Weak point analysis 2. Energy efficiency analysis 3. Combined
Electrical Design TABLE OF CONTENTS FOREWORD... 1. BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law
TABLE OF CONTENTS Electrical Design TABLE OF CONTENTS FOREWORD.......................................................................... 1 BASIC ELEMENTS OF ELECTRICITY..................................................
Designed for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
Availability Assessment of Generating Units of Balimela Hydro Electric Power Station (510 MW) A Markovian Approach
American Journal of Engineering Research (AJER) 24 American Journal of Engineering Research (AJER) e-issn : 232-847 p-issn : 232-936 Volume-3, Issue-2, pp-44-49 www.ajer.org Research Paper Open Access
Powerformer chosen for Swedish combined heat and power plant
Powerformer chosen for Swedish combined heat and power plant Powerformer, a radically new type of generator developed by ABB, has been chosen for a combined heat and power plant in Eskilstuna, Sweden.
Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems
Centre for Sustainable Electricity and Distributed Generation Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Predrag Djapic and Goran Strbac July 2008 FUNDED BY BERR URN 08/1144
Reliability Modeling Software Defined
Reliability Modeling Software Defined Using Titan Reliability Modeling Software May 30, 2014 Prepared by: The Fidelis Group 122 West Way, Suite 300 Lake Jackson, TX 77566 Fidelis Group, LLC All Rights
Hybrid Power System with A Two-Input Power Converter
Hybrid Power System with A Two-Input Power Converter Y. L. Juan and H. Y. Yang Department of Electrical Engineering National Changhua University of Education Jin-De Campus, Address: No.1, Jin-De Road,
Guideline for Energy Efficient Electrical systems for building. Presentation by TERI
Guideline for Energy Efficient Electrical systems for building Presentation by TERI Objective of study The study highlights how BBMP can implement energy efficiency measures in building in co-ordination
Study on Differential Protection of Transmission Line Using Wireless Communication
Study on Differential Protection of Transmission Line Using Wireless Communication George John.P 1, Agna Prince 2, Akhila.K.K 3, Guy Marcel 4, Harikrishnan.P 5 Professor, Dept. of EEE, MA Engineering College,
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission
Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
Phase Balancing of Distribution Systems Using a Heuristic Search Approach
Phase Balancing of Distribution Systems Using a Heuristic Search Approach Lin, Chia-Hung*, Kang, Meei-Song**, Chuang, Hui-Jen**, and Ho, Chin-Ying** *National Kaohsiung University of Applied Sciences **Kao
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
Design of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
Solar One and Solar Two
Solar One and Solar Two Solar One generated electricity between 1982 and 1988. (178-182) Solar One generated steam directly from water in its receiver, but its direct steam system had low efficiency in
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection Y. Damchi* and J. Sadeh* (C.A.) Abstract: Appropriate operation of protection system
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection Y. Damchi* and J. Sadeh* (C.A.) Abstract: Appropriate operation of protection system
Research on the UHF RFID Channel Coding Technology based on Simulink
Vol. 6, No. 7, 015 Research on the UHF RFID Channel Coding Technology based on Simulink Changzhi Wang Shanghai 0160, China Zhicai Shi* Shanghai 0160, China Dai Jian Shanghai 0160, China Li Meng Shanghai
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
Local Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
Automatic Train Control based on the Multi-Agent Control of Cooperative Systems
The Journal of Mathematics and Computer Science Available online at http://www.tjmcs.com The Journal of Mathematics and Computer Science Vol.1 No.4 (2010) 247-257 Automatic Train Control based on the Multi-Agent
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Modelling framework for power systems. Juha Kiviluoma Erkka Rinne Niina Helistö Miguel Azevedo
S VISIONS SCIENCE TECHNOLOGY RESEARCH HIGHLIGHT 196 Modelling framework for power systems Juha Kiviluoma Erkka Rinne Niina Helistö Miguel Azevedo VTT TECHNOLOGY 196 Modelling framework for power systems
Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling
Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling Yefu Wang1, Xiaorui Wang1,2, and Yanwei Zhang1 ABSTRACT The Ohio State University 14 1 1 8 6 4 9 8 Time (1 minuts) 7 6 4 3
How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse
How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission
A reliable and experienced supplier
Email : [email protected] A reliable and experienced supplier A joint venture to increase efficiency Two CATERPILLAR dealers for more than 75 years decided to associate their experiences and skills
Electrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
Alejandro D. Domínguez-García, George Gross, and Philip T. Krein
nalysis of Design lternatives for Supplying Electric Power to Mission-Critical Loads in Data Centers: Reliability, Environmental, and Efficiency spects lejandro D. Domínguez-García, George Gross, and Philip
16 West Coast Regional Plan
16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast
Analyses of delivery reliability in electrical power systems
Risk, Reliability and Societal Safety Aven & Vinnem (eds) 2007 Taylor & Francis Group, London, ISBN 978-0-415-44786-7 Analyses of delivery reliability in electrical power systems T. Digernes MathConsult,
Wind Power and District Heating
1 Wind Power and District Heating New business opportunity for CHP systems: sale of balancing services Executive summary - Both wind power and Combined Heat and Power (CHP) can reduce the consumption of
13.10: How Series and Parallel Circuits Differ pg. 571
13.10: How Series and Parallel Circuits Differ pg. 571 Key Concepts: 5. Connecting loads in series and parallel affects the current, potential difference, and total resistance. - Using your knowledge of
Glossary of Terms Avoided Cost - Backfeed - Backup Generator - Backup Power - Base Rate or Fixed Charge Baseload Generation (Baseload Plant) -
Glossary of Terms Avoided Cost - The incremental cost Flint Energies would pay for the next kilowatt-hour of power in the open marketplace for energy. Flint Energies Board of Directors sets this Avoided
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
Paralleling Power Sources Which Share a Common Neutral
Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share
AORC Technical meeting 2014
AORC Technical meeting 2014 http : //www.cigre.org C4-1012 Alarm System Improvement in the Northern Region Dispatching Center of Thailand Mr. Manu PONGKAEW, Mr. Phathom TIPSUWAN Electricity Generating
ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact
ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact Authors Carl Ejnar Sölver, ABB High Voltage Products Rasmus Larsson, ABB High Voltage Products 2 ABB ABB
GLOSSARY. Glossary of Terms for Capacity Based Demand Response PUBLIC. Issue 3.0 GOT-1
PUBLIC GOT-1 GLOSSARY Glossary of Terms for Capacity Based Demand Response Issue 3.0 This document provides a glossary of terms with definitions used in the Capacity Based Demand Response program. Public
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS
Page 1 of 16 CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS PROPOSED TERMS AND CONDITIONS January 2015 Page 2 of 16 TABLE OF CONTENTS 1. Definitions... 3 2. Curtailable Load Options... 6 3. Nomination
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
Reliability centered asset management tool
Reliability centered asset management tool The development of RACalc Claes Böös and Richard Göransson Degree project in Electromagnetic Engineering Second Level, 30.0 HEC Stockholm, Sweden 2009 XR-EE-ETK
L.S. de Carvalho, J. M de Oliveira Neto 1. INTRODUCTION IAEA-CN-164-5P01
IAEA-CN-164-5P01 Advanced Technology Application Station Blackout Core Damage Frequency Reduction The Contribution of AN AC Independent Core Residual Heat Removal System L.S. de Carvalho, J. M de Oliveira
Understand Hybrid Generator Battery Systems
Understand Hybrid Generator Battery Systems For off-grid applications powered by diesel generators, move to cyclic operation to save costs Telecommunications operators in Africa, India and other developing
OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT
OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT L.A.F.M. Ferreira, P.M.S. Carvalho IST S.N.C. Grave L.M.F. Barruncho L.A.
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
DISTRIBUTION RELIABILITY USING RECLOSERS AND SECTIONALISERS
ABB DISTIBUTION ELIABILITY USING ECLOSES AND SECTIONALISES obert E. Goodin Chief Engineer ABB Inc. Lake Mary, FL Timothy S. Fahey, PE Sr. Application Engineer ABB Inc. aleigh, NC Andrew Hanson, PE Executive
Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards
Redundancy = Protection from Network Failure. Redundancy Standards WP-31-REV0-4708-1/5 Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards For a very
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
A CASE STUDY: PERFORMANCE AND ACCEPTANCE TEST OF A POWER AND DESALINATION PLANT. Keywords : Power Plant, Boiler Capacity, Electrical Power
A CASE STUDY: PERFORMANCE AND ACCEPTANCE TEST OF A POWER AND DESALINATION PLANT Atef M Al Baghdadi Water and Electricity Authority Abu Dhabi, U.A.E Keywords : Power Plant, Boiler Capacity, Electrical Power
PROJECT RISK MANAGEMENT
11 PROJECT RISK MANAGEMENT Project Risk Management includes the processes concerned with identifying, analyzing, and responding to project risk. It includes maximizing the results of positive events and
Optimization of Asset Management in High Voltage Substation Based on Equipment Monitoring and Power System Operation
Optimization of Asset Management in High Voltage Substation Based on Monitoring and Power System Operation Yotaro Suzui, Hiroi Kojima, Naoi Hayaawa, Fumihiro Endo, Hitoshi Oubo Nagoya University Furo-cho,
Series and Parallel Circuits
Series and Parallel Circuits Direct-Current Series Circuits A series circuit is a circuit in which the components are connected in a line, one after the other, like railroad cars on a single track. There
Proof of the conservation of momentum and kinetic energy
Experiment 04 Proof of the conservation of momentum and kinetic energy By Christian Redeker 27.10.2007 Contents 1.) Hypothesis...3 2.) Diagram...7 3.) Method...7 3.1) Apparatus...7 3.2) Procedure...7 4.)
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
FIXED CHARGE: This is a cost that goes towards making the service available, including
ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer
The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control
The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems
Brochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
Maximizing UPS Availability
Maximizing UPS Availability A comparative assessment of UPS designs and deployment configurations for the highavailability data center By Chris Loeffler Product Manager, BladeUPS & Data Center Applications
Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
An Approach for Water Cost of Cooling Water System in Oil Refinery
CHEMICAL ENGINEERING TRANSACTIONS Volume 21, 2010 Editor J. J. Klemeš, H. L. Lam, P. S. Varbanov Copyright 2010, AIDIC Servizi S.r.l., ISBN 978-88-95608-05-1 ISSN 1974-9791 DOI: 10.3303/CET1021018 103
Operation and Control Microgrid and Distributed Generation. Mohammad Shahidehpour Illinois Institute of Technology
Operation and Control Microgrid and Distributed Generation Mohammad Shahidehpour Illinois Institute of Technology Outline Introduction - Microgrids High Reliability Distribution Systems Perfect Power System
BoilerMate SP. benchmark. user instructions A - C L A S S
A - C L A S S BoilerMate SP user instructions benchmark TM The code of practice for the installation, commissioning & servicing of central heating systems In the interest of continuously improving the
Bundling small-scale energy efficiency projects
Bundling small-scale energy efficiency projects Issue Paper Introduction Energy efficiency projects are characterised by a large variety of size in terms of reduction of energy inputs and emissions Whereas
Reliability Block Diagram RBD
Information Technology Solutions Reliability Block Diagram RBD Assess the level of failure tolerance achieved RELIABIL ITY OPTIMIZATION System reliability analysis for sophisticated and large scale systems.
Essential Power System Requirements for Next Generation Data Centers
Essential Power System Requirements for Next Generation Data Centers White Paper #4 Revision 4 Executive Summary Effective mission critical installations must address the known problems and challenges
Power products and systems. Intelligent solutions for power distribution Zone concept
Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical
Calculating power requirements for HP ProLiant rack-mounted systems
Calculating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device VA rating... 3 Device input power...
Control Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, [email protected].
Wireless Sensor Networks Coverage Optimization based on Improved AFSA Algorithm
, pp. 99-108 http://dx.doi.org/10.1457/ijfgcn.015.8.1.11 Wireless Sensor Networks Coverage Optimization based on Improved AFSA Algorithm Wang DaWei and Wang Changliang Zhejiang Industry Polytechnic College
Series and Parallel Circuits
Series and Parallel Circuits Components in a circuit can be connected in series or parallel. A series arrangement of components is where they are inline with each other, i.e. connected end-to-end. A parallel
Fault Analysis in Software with the Data Interaction of Classes
, pp.189-196 http://dx.doi.org/10.14257/ijsia.2015.9.9.17 Fault Analysis in Software with the Data Interaction of Classes Yan Xiaobo 1 and Wang Yichen 2 1 Science & Technology on Reliability & Environmental
Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager
Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager SACE Emax 2 From Circuit-Breaker to Power Manager Our customers need more efficient solutions, to Increase
Guidelines for Monthly Statistics Data Collection
Guidelines for Monthly Statistics Data Collection Final version Data Expert Group 31 May 2015 1. Table of contents 1. Table of contents... 2 2. Remarks... 3 3. Introduction... 3 4. Geographical perimeter
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
Overview brochure. Energy Storage Keeping smart grids in balance
Overview brochure Energy Storage Keeping smart grids in balance Reliable power, where and when it s needed Energy storage is not a new concept in itself. It has been an integral component of electricity
Transmissão em Corrente Contínua
Transmissão em Corrente Contínua Panorama Atual e Perspectivas Futuras no Brasil Multi-Terminal HVDC Classic Some Considerations Brazilian SC B4 Paulo Fischer de Toledo, ABB Basic considerations Traditional
Laddomat 21-60 Charging unit
Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the
Energy efficiency and fuel consumption of fuel cells powered test railway vehicle
Energy efficiency and fuel consumption of fuel cells powered test railway vehicle K.Ogawa, T.Yamamoto, T.Yoneyama Railway Technical Research Institute, TOKYO, JAPAN 1. Abstract For the purpose of an environmental
FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN
FULL ELECTRICAL LN PLANTS: HIHEST AVAILABILITY AND ENERY EFFICIENCY THROUH OVERALL SYSTEM DESIN Dr. Edwin Lerch Siemens A Infrastructure and Cities Sector, IC S SE PTI, ermany Phone: 49-9131-7-34052 Fax:
Alternating Current and Direct Current
K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating
Electrical Efficiency Modeling of Data Centers
Electrical Efficiency Modeling of Data Centers By Neil Rasmussen White Paper 113 Executive Summary The conventional models used to estimate electrical efficiency of data centers are grossly inaccurate
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
IESO Supply Deliverability Guidelines
PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents
imagine SOLAR AIR CONDITIONING MADE EASY
imagine SOLAR AIR CONDITIONING MADE EASY WHY SOLAR COOLING? Imagine...being able to fit a solar air conditioning system to your building that would result in dramatic reductions in electricity consumption