Data Center Power Distribution and Capacity Planning:
|
|
|
- Theodore Caldwell
- 10 years ago
- Views:
Transcription
1 Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc.
2 About This Series Raritan, a leading provider of data center equipment, and PTS, a well-respected data center consulting firm and turnkey solutions provider, recently conducted a series of tests to examine the effects of heat, airflow and power usage in a working server environment. The hypothesis was that by knowing more about their real-time operational environment, data center managers would be empowered to manage smarter. Using advanced 3-D computational fluid dynamic (CFD) software and intelligent power distribution units (ipdus), among other devices, Raritan and PTS were able to monitor temperature and humidity, calculate airflow, as well as measure power for both the IT and supporting infrastructure load throughout Raritan s and PTS server rooms. This series of white papers documents their research and provides you with the key learnings of their tests. Overview With the cost of power rising dramatically and increased uncertainty of global power availability, all levels of corporate management are now more focused than ever on managing and conserving energy. Nowhere is this more critical than in the data center of the corporation, which can consume 25 percent of the total energy in a typical IT intensive organization (Raritan estimate based on U.S. Environmental Protection Agency Report to Congress on Server and Data Center Energy Efficiency Public Law ). Due to increased reliance on computing to deliver mission-critical applications and the emergence of blade technology and virtualization, server density is dramatically increasing. These increases mean that data centers are running hotter and HVAC systems are working overtime to keep the center cool. This, in turn, is driving energy costs up a growing concern for IT, given the potential for this expense to become an above-the-line IT charge. Clearly, there s a need to monitor data center power and temperatures and adjust heating, cooling and airflow to minimize power consumption while maintaining IT equipment uptime. But where should forward-thinking corporations start? What tools are available to get the data needed to design a more efficient data center? This white paper, the first in a series, takes a look at some of these thorny energy management issues and provides some relevant answers. You ll learn the following three things: The flaws in what you thought you knew about power measurement What kind of measurement instrumentation you need to calculate your data center s power efficiency How to set standards that bring your data center in alignment with Green Grid The Challenge When energy management was a low priority, IT managers could rely on simple calculations associated with nameplate specifications to predict overall power usage in their data centers. However, average data center power consumption has grown from 2.1 kilowatts per rack in 1992 to 14 kw/rack in 2006, according to HP ( HP Power & Cooling, August 31, 2006). Simply multiplying the number of servers by their nameplate ratings does not jive with the reality of actual energy consumption statistics. DatacenterDynamics, in their Spring 2007 Conference Survey, found that the average power density among all respondents in the U.S. was 5.5 kw/rack and the average maximum power density was 11.6 kw/rack. Page 1
3 Moreover, many industry analysts such as Gartner ( 25th Annual Data Center Conference, December 2006) have been predicting significant power shortfalls for more than a year now. While some companies have flexibility to move their data centers to locations that provide more reliable, less expensive power, most simply cannot. Which means that shortfalls, left unresolved, could force IT and facilities managers to make hard decisions about which applications to support and which ones to sacrifice to keep the business running during peak demand. As energy issues come under more scrutiny and as tools become available for accurate measurement, IT administrators and facilities managers should no longer rely on the published nameplate power ratings on their units and factor in accepted industry assumptions. While adequate in the past, close enough isn t good enough, given the potential power crisis that s just over the horizon. Only through individual server measurement can managers accurately know what power their equipment is drawing and acquire precise numbers that will aid their energy efficiency planning efforts. With the knowledge gained regarding server-by-server real-time monitoring, IT administrators can manage smarter and feel secure that they are making better decisions on what to power off because they will be able to: Identify non-working processing assets Identify low-efficiency processing assets (e.g., lots of power draw for little computational power) Assist capacity planning against the design rating for all power protection, distribution and cooling infrastructure equipment Nameplate Ratings and Assumptions Server manufacturers indicate a power rating value on the nameplate of every server. Data center administrators, however, know that this represents a worst-case scenario, and typical server power consumption never reaches the rated nameplate value. One easy way to increase server density is to simply derate the nameplate power by a certain percentage depending on the workload that s deployed on the server. PTS refers to this derated value as the design rating of the equipment. It is typically percent of the nameplate rating, and is used to size all power protection, distribution and cooling systems in the data center. This percentage is still frequently higher than what is seen in actual use, but now more accurate, real-world numbers can be obtained through the use of intelligent PDUs. For example, by measuring power consumption of individual servers using intelligent PDUs, PTS analysis of Raritan s IT equipment determined that consumption typically ranged from percent of the underlying equipments nameplate rating, averaging about 31 percent far less than the numbers typically used as the design rating of the equipment. IT Equipment Power Load vs. Total Facility Power Load Another important measurement to get a handle on is the power drawn by IT equipment in relation to the total power consumed by the facility. APC-MGE estimates that 30 percent of total power usage in a data center represents the load placed on power grids by servers and other IT equipment, while 70 percent is for everything else cooling, air movement, power distribution, lighting, etc. EYP Mission Critical Facilities, a division of HP, puts these numbers at 50 percent and 50 percent. A preliminary observation by PTS and Raritan, however, found that 71 Page 2
4 percent of the energy consumed was for the critical IT load, with only 29 percent spent for the support systems. This high percent of power going to the critical IT load is an indication that PTS and Raritan are doing a better job managing power in their data centers than is typical in the industry. It also points to an opportunity to press loading factors doing more computing with less energy. These numbers illustrate the importance of getting accurate measurements in your data center rather than relying on industry averages. Measurement Systems So how can you arrive at these measurements, efficiently and accurately? The following are some overall pieces of the puzzle to consider: Branch Circuit Monitors and Individual Device Load Measurement Branch circuit monitors are electrical devices that measure current load on all circuits on an electrical panel and alert operators when the load approaches the breaker s rating. This is especially important in data centers, for example, where additional servers can get plugged into a circuit that s already approaching its capacity. Branch circuit monitors continuously measure the current on all circuits and ensure that someone is notified before a circuit breaker reaches its rated capacity, or worse, trips. Data Center Environmental Aggregators Environmental aggregators are specifically designed to gather relevant power and environmental data center information. They can also consolidate the collected information and analyze it to help you make informed decisions related to power consumption by both IT and facilities equipment. Intelligent PDUs Intelligent rack PDUs provide IT staff the ability to monitor the power consumption of any given server, storage unit or other IT device, which is helpful to identify those that are underutilized or identify those that are approaching or exceeding their normal high range of usage. There is also the ability to monitor and control the data center power load at the facility level. Intelligent rack PDUs can be controlled remotely via a Web browser or command line interface (CLI). They can meter power at both the PDU level and the individual outlet level; support alerts based on user-defined thresholds; provide security in the form of passwords, authentication, authorization and encryption and incorporate rich environmental management capabilities. Some models are also highly customizable, support the industry s latest standards-based techniques like SNMP TRAPs/SETs/GETs, IPMI, SMASH CLP and integrate seamlessly to existing corporate infrastructures like LDAP, Active Directory, RADIUS and NFS servers. Still, these tools cannot reach their full potential if the modeling is based on just a static environment. In the real world, data centers are dynamic. Server utilization changes over time, which causes power consumption and heat generation/dissipation to change. This, in turn, requires appropriate cooling to specific racks or rows of computers. So the next step is to determine your data center s power usage effectiveness rating. Page 3
5 The Green Grid: Calculating PUE The Green Grid defines Power Usage Effectiveness (PUE) with this formula: PUE = Total Facility Power IT Equipment Power Total facility power in this equation is the power required to operate the entire data center, including servers, IT equipment, lighting, cooling, air movement, etc. IT equipment power represents the power required to operate the servers and IT equipment alone. PUE can range from 1.0 to infinity. A PUE value approaching 1.0 would indicate 100 percent efficiency (i.e., all the power is used by IT equipment only). Currently, there are no comprehensive data sets that show the true spread of the PUE for data centers. Some preliminary work by PTS indicates that many data centers may have a PUE of 3.0 or greater, but with proper design a PUE value of 1.6 should be achievable. Tools to Calculate PUE You must accurately measure power usage when calculating your PUE to establish a baseline and to measure your improvements. Raritan and PTS designed and implemented the following measurement strategy to accomplish this: A Veris H8820 data acquisition device was deployed to measure branch circuit amperage for each load, and calculated power feeding the computer room air conditioning (CRAC) units, lighting, UPS and other non-it loads. This unit was selected since it was easy to deploy and provided the data required. Geist Racsense environmental monitors were deployed with temperature probes at the top and bottom of each rack (front and back), as well as the supply and return of each CRAC unit. One humidity probe was also deployed to measure the humidity of the room. The Racsense devices provided efficient installation and cabling and simple data collection. Two Dominion PX intelligent power distribution units were deployed in each rack. This enabled capture of the active power of the critical IT loads at a per device level. This detailed critical IT load data provides the granularity of information required to measure the PUE and make recommendations on how to improve it. Average/Nameplate Maximum/Nameplate The Results Nameplate vs. Actual Power Draw The histogram to the right shows the frequency distribution of actual power consumed as a percentage of the nameplate values (capacity), based on readings in Variability in server power consumption relative to nameplate rating. Page 4
6 the Raritan data center taken from February 21 through February 26, The nameplate value indicates the maximum amount of power a device can use at any given time under any kind of workload and data center environmental condition. Current data center design rules use the nameplate value to perform capacity planning. Using this method for data center design leads to inefficiency due to overcapacity since the nameplate value is a maximum value. Derating this value by a fixed percentage reduces some of the inefficiency, but our chart below indicates that actual power consumed in operations has such a wide range that it makes it difficult to select a derating factor that balances efficiency and ensures reliable operation. For example, measuring average active power, 29 devices in Raritan s server room consumed between 21% 40% of this capacity, while 15 consumed a higher percentage of capacity and 15 devices consumed a lower percentage of capacity. While measuring maximum power, 27 devices in our server room consumed between 21% 40% of this capacity, while 23 consumed a higher percentage of capacity and 9 devices consumed a lower percentage of capacity. The main observation is that the actual power capacity consumed has a wide potential range. This means that using derated nameplate values either leaves room for being more efficient or puts reliability at risk. A derated design is the first step, but actually measuring the power a device consumes in live operations provides you with the additional information needed to be more efficient and ensure reliable operations. Calculating Raritan s PUE As the chart to the right shows, approximately 71 percent of the total average power consumption was used for Raritan s critical IT equipment 49.4 percent for servers alone while the remaining 29 percent was for support services like cooling and lighting. Support Infrastructure (5.625kw) 29% Critical Load (13.68kw) 71% To calculate Raritan s PUE based on the previous formula: Total Power = Support Infrastructure (5.625kw) + Critical Load (13.68kw) = 19.3kw Total IT Equipment Power = Critical Load (13.68kw) PUE = Total Power = 19.3kw Total IT Equipment Power = 13.7kw Raritan s PUE = 1.4 Page 5
7 Conclusions Rising energy costs and diminishing supplies were primary motivations for this survey. So over a five-month period, Raritan and PTS defined and implemented a plan to instrument Raritan s server room and measure the power usage at an IT device level and at a branch circuit level for non-it load. Based on that survey, Raritan discovered the following: Assuming at the outset that their server room had a poor PUE value, Raritan instead learned that it had a respectable PUE value of 1.4, and a total average power load for their IT equipment of 10.5kw (servers and storage combined). Implications of this is that armed with this knowledge, Raritan can take a smart approach to managing and provisioning their data center: Raritan does not have to add servers to add computational power 44 devices registered an average active power consumption equivalent to the draw of an idle server. This provided a good indication that they could save energy by consolidating those near-idle servers. Assuming a typical consolidation of 10 to 1, they could potentially decommission about 40 devices. Raritan can avoid a mission-critical disruption by deploying better load management Two devices were running at between percent of rated power capacity. If Raritan was using the industry average derating figure of percent, this could have posed a potential problem with regard to server performance. The same two devices were investigated to make sure that they were not creating hot spots or drawing power too close to power circuit capacity limits and therefore presenting a potential for problems. Raritan can reduce its OpEx expense without putting required computing at risk. Using intelligent rack PDUs gave Raritan the actual power consumption at an individual IT device level, providing the data needed to plan the next steps to become more efficient. The measurement activity also provided a number of unforeseen benefits beyond providing data to make a PUE calculation. A sudden drop in energy usage, for example, led the IT staff to discover that a circuit breaker on one of their CRAC units had tripped. This prompted a repair before hot summer weather arrived and presented a cooling problem. A temperature sensor located high in a rack alerted them to the fact that a rack fan had failed. Since industry benchmarks are based upon a broad range of averages, and each data center has its own unique attributes that cause it to deviate from the averages, this Raritan and PTS survey validated Green Grid s position: In order to improve the energy efficiency of data centers, it is first necessary to measure the energy consumption of the entire data center and each of its constituent subsystems. What s Next? In the next white paper, we will examine the use and advantages of Computational Fluid Dynamics to help make your data center more energy efficient. We ll also compare and contrast our CFD results when using actual measurements vs. nameplate data. Page 6
8 About Raritan Raritan is a leading provider of secure IT infrastructure management solutions that provide IT directors, managers and administrators the control they need to improve data center productivity, enhance branch office operations and increase overall power management efficiency. In over 50,000 locations around the world, our integrated secure in-band and out-of-band server access, control and power management products help companies better monitor and manage server access, utilization and energy consumption. Our intelligent PDUs offer remote power control and monitoring at the rack and device level, empowering data center owners with information to improve uptime and capacity planning, and efficiently utilize energy to save power and money. Raritan s OEM division provides embedded hardware and firmware for server and client management, including KVM over IP, IPMI, intelligent power management and other industry standards-based management applications. Based in Somerset, N.J., Raritan has 38 offices worldwide, serving 76 countries. For more information, please visit About PTS Founded in 1998, PTS is a turnkey solutions provider specializing in data center and computer room consulting, engineering, infrastructure, construction, and maintenance services. They offer a broad range of project experience in designing data centers, computer rooms, and technical spaces. They employ industry best practices in integrating proven, best-of-breed, critical infrastructure technologies that result in always available, scalable, redundant, fault-tolerant, manageable, and maintainable mission-critical environments. From their corporate headquarters in Franklin Lakes, New Jersey, and their branch office in Orange County, California, PTS works to fulfill their mission of creating satisfied customers by emphasizing pre-design and planning services to provide the optimal solution to meet its clients needs and resulting in an early and accurate alignment between scope, schedule and budget. For more information, please call PTSDCS1 / / [email protected]. C1019 R2
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Power Management. Raritan Description. http://www.raritan.com/products/power-management/
Raritan Description Raritan is a proven innovator of power management, infrastructure management, KVM and serial solutions for data centers of all sizes. In more than 50,000 locations worldwide, our hardware
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
EO 13514 and Smart Federal Government Data Center Management
1 Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included everything from keeping the lights on at the Lincoln Memorial to maintaining
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack An all-in-one solution for efficient data center management, spanning facilities, networking
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
Data Center Infrastructure Management: How to Optimize Data Center Operations
Data Center Infrastructure Management: How to Optimize Data Center Operations Khaled Nassoura, PE [email protected] General Manager Raritan, Inc. Question of the Day Question: Would any CFO run
Server Room Solutions: How small to midsize IT businesses can make their IT budgets appear larger than they are
Server Room Solutions: How small to midsize IT businesses can make their IT budgets appear larger than they are 2011, Raritan Inc. Server Room Solutions: How small to midsize IT businesses can make their
Intel Data Center Manager. Data center IT agility and control
Intel Data Center Manager Data center IT agility and control The Data Center Ecosystem 2 Why do we care about Data Center Management? attributed to devices connected to the Internet of Everything (up from
The role of Access and Control in DCIM
Data Center Infrastructure Management for System Administrators The role of Access and Control in DCIM Table of Contents 1. Executive Summary... 3 2. Server Access & Control... 4 2.1 Remote Access Tools
Energy Management Solutions
Energy Management Solutions Introducing the world s most innovative intelligent Power Distribution Units (ipdus) designed to simplify rack energy and environmental management of your data center. Enlogic
Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy.
Energy management White paper Greening the data center with IBM Tivoli software: an integrated approach to managing energy. May 2008 2 Contents 3 Key considerations for the green data center 3 Managing
CenterMind P+ Solution for efficient power management
CenterMind P+ Solution for efficient power management Overview Over last decade DC become significant power consuming facilities Information Technology Equipment (ITE) continue to increase computing capabilities
One unbelievable solution for rack-level data center power management. Sentry Power Manager. Solutions for the Data Center Equipment Cabinet
One unbelievable solution for rack-level data center power management. Sentry Power Manager Solutions for the Data Center Equipment Cabinet Sentry Power Manager. The most comprehensive and affordable rack-level
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara Framework to provide full convergence of
Management and Wireless in the Data Center
SOLUTIONS BRIEF Management and Wireless in the Data Center High Performance Wireless Networks Management and Wireless in the Data Center Worldwide demand for new and more powerful IT-based applications,
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Cheat Sheets to Data Center Infrastructure Management
^ Business-wise, Future-drivenTM Cheat Sheets to Data Center Infrastructure Management The Brands You Trust. Table of Contents Introduction...3 How DCIM helps operations...4 How DCIM helps planning...5
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
Energy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
Revolutionizing Data Center Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement
Case study: End-to-end data centre infrastructure management
Case study: End-to-end data centre infrastructure management Situation: A leading public sector organisation suspected that their air conditioning units were not cooling the data centre efficiently. Consequently,
Managing the Data Center One Rack at a Time
Managing the Data Center One Rack at a Time No Limits Software White Paper #6 By David Cole 2013 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,
Data Center Infrastructure Management (DCIM) Demystified
software is quickly becoming the core engine of data center operations. Only 5 years ago, manual spreadsheets, sometimes supplemented with Visio diagrams, were accepted as the default tools for data center
An Introduction to Data Center Infrastructure Management
An Introduction to Data Center Infrastructure Management 2010 Raritan Inc. Overview Worldwide demand for new and more powerful IT-based applications, combined with the economic benefits of consolidation
Understanding the Promise of (DCIM)
Understanding the Promise of Data Center Infrastructure Management (DCIM) Chuck Kramer, RCDD, NTS, CDCP, CDFOM Senior Solutions Consultant Emerson Network Power What is DCIM? The monitoring, collection
Energy Savings in the Data Center Starts with Power Monitoring
Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.
Out-of-Band Management: the Integrated Approach to Remote IT Infrastructure Management
WHITE PAPER Management: the Integrated Approach to Remote IT Management EXECUTIVE SUMMARY For decades, business imperatives for information technology (IT) have remained constant to cut costs and improve
Measuring Energy Efficiency in a Data Center
The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics
It s time to confront IT complexity and deal with it. With Avocent s Control and Manageability Solution
It s time to confront IT complexity and deal with it With Avocent s Control and Manageability Solution What makes up effective data center management and control? Chances are the answer is different for
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY
Packet Power. Data Center Solutions. Packet Power. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution
Data Center Solutions for Data Centers provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility operations. Gain
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Dominion PX. General Questions. What is Dominion PX (PX)?
Dominion PX Question General Questions What is Dominion PX (PX)? Is Raritan new to the rack power distribution unit market? Can the PX be used as a stand-alone device? Does PX work with Raritan s CommandCenter
Improve competiveness of IDC and enterprise data centers with DCIM
Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM
EO 13514 and Smart Federal Government Data Center Management
EO 13514 and Smart Federal Government Data Center Management 2011 Raritan Inc. Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included
HP power and cooling technologies for the data center
HP power and cooling technologies for the data center Technology brief, 2 nd edition Introduction... 2 ProLiant server efficiency... 2 High-efficiency features... 2 Power monitoring and reporting tools...
CenterMind P+ Intelligent Power Management for your Data Center
CenterMind P+ Intelligent Power Management for your Data Center Intelligent Power Management for your Data Center monitor and manage your data center power consumption and connectivity efficiently The
Zen Internet Case Study
Zen Internet Case Study About Zen Internet Zen Internet is an independent Internet Service Provider (ISP) that offers a full range of data, voice, and hosting services to businesses and residential users
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
Power & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
Model Manage Monitor Maximize your Data Center
NetZoomDC is the most feature rich, fully-scalable, enterprise Data Center Infrastructure Management (DCIM) software application. It enables data center professionals to Model, Manage, Monitor and Maximize
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
Rack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009
IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
MEGARAC XMS Sx EXTENDIBLE MANAGEMENT SUITE SERVER MANAGER EDITION
MEGARAC XMS Sx EXTENDIBLE MANAGEMENT SUITE SERVER MANAGER EDITION THE EXTENDIBLE MANAGEMENT SUITE EXECUTIVE SUMMARY MEGARAC XMS stands for Extendible Management Suite and this is a complete management
PE6108/PE6208/PE8108/PE8208
Energy Intelligence Solutions PE6108/PE6208/PE8108/PE8208 eco PDU Distribution Unit ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
DS Series Solutions Integrated Solutions for Secure, Centralized Data Center Management
DS Series Solutions Integrated Solutions for Secure, Centralized Data Center Management DS Series Solutions IT Infrastructure Management Tools to Reduce IT Operational Costs and Increase IT Productivity
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
About Geist. geistglobal.com
About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure. We produce affordable, quality products
How green is your data center?
Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
Technologies for Data Centres
Technologies for Data Centres BlueNet at a glance // PHILOSOPHY A passion for innovation page 5 // ENERGY MANAGEMENT The latest in efficiency page 7 // HIGH AVAILABILITY Seamless and systematic security
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013 Ted Brown Sr. Energy Management Analyst Data Center / IT Energy Efficiency [email protected]
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
How To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
Design Best Practices for Data Centers
Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market
Eaton epdu. Intelligent and flexible power distribution
Eaton epdu Intelligent and flexible power distribution Introduction and overview With today s changing technology, increasing power demands and the need for reliability, data centre professionals require
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
Smart Card Deployment in the Data Center: Best Practices for Integrating Smart Card Authentication in a Secure KVM Environment
Smart Card Deployment in the Data Center: Best Practices for Integrating Smart Card Authentication in a Secure KVM Environment 2009, Raritan Inc. Executive Summary While many organizations have employed
Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
Preparing for Your First DCIM System Deployment: Auto-Discovery and Data Collection
Table of Contents What is Auto-Discovery? Where is My Data and How Can I Get It? Why Auto-Discovery is Not Enough Where to Go to Start Collecting Your Data What Does an Operational DCIM System Provide?
The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management EXECUTION AVAILABILITY EFFICIENCY What s
MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING
MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE Chris C. Gaskins Vice President of Product Development RF Code, Inc. AUGUST 2010 Shawn Griggs Director of Product Management
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Electrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate