Copper Patch Cords. Impact On Network Performance and Reliability
|
|
|
- Jemimah Blair
- 9 years ago
- Views:
Transcription
1 Copper Patch Cords Impact On Network Performance and Reliability 1
2 The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on an organization s productivity and competitive position, it becomes increasingly important to select a reliable end-to-end structured cabling system that will allow for future network growth. To maximize usable network bandwidth, it is critical that patch cords properly support the performance, quality, and dependability of the entire structured cabling system. The performance of the link between the switch and computer is most impacted by noise generated in the area of the channel closest to the active equipment. This is where the patch cords are located and where quality should never be compromised by using off-brand patch cords. It is vital that patch cords have the following design features: Mated performance with connecting hardware to maximize cancellation of near-end-crosstalk Robust construction to ensure long-term reliability of the network under day-to-day moves, adds and change conditions Certified component performance to ensure maximum network availability Investing in high quality patch cords ensures the channel components work together as an end-to-end solution to maximize performance and reliability. Various testing scenarios, as outlined below, provide quantifiable results to support the importance of high quality patch cords. Importance of Mated Connecting Performance One of the key factors to achieve high-end channel bandwidth is the optimum mated performance of the patch cord plug and the jack connector. Fundamentally, connectors and plugs are designed to have equal but opposite component pair coupling effects. A properly tuned jack compensates for the noise generated by the patch cord plug. Thus, mated performance is achieved when the crosstalk within the patch cord plug is cancelled by the compensation in the connector. The TIA/EIA 568-B.2 Category 6 standard addresses the issue of mated performance by establishing a de-embedding procedure to test the electrical performance of modular plugs. De-embedding is a process that uses a reference jack connector with known values to obtain the NEXT loss values for plugs. The mated performance of a typical Category 6 connector has a bell shape performance curve across the de-embedded patch cord plug range. If a jack connector is designed correctly, the optimal mated performance is at the center of the Category 6 de-embedded test plug range. Graph PANDUIT Corp. All rights reserved. 2
3 Conversely, the connector must also meet the mated connecting hardware pair-to-pair NEXT loss specification across the allowable Category 6 de-embedded test plug NEXT loss range. In the case of pair combination 3,6-4,5, the optimum performance is with a centered deembedded plug of 37.0 at 100 MHz (shown in Graph 1) but the connector must also pass the mated connecting hardware pair-to-pair NEXT loss specification with test plugs ranging from 36.4 to When a plug is outside of this range, mated performance declines and is no longer compatible to the connecting hardware. A jack connector that performs well when mated to a patch cord plug with high or low de-embedded NEXT may not provide the same performance when mated with a patch cord plug that is centered in the de-embedded range. In some cases, that connector may even fail the Category 6 connecting hardware requirements when using a patch cord plug at the other end of the de-embedded range. In other words, when a connector is not optimized with a centered plug, it minimizes backward compatibility and interoperability with other channel components. This can limit network performance. Conversely, the PANDUIT MINI-COM TX6 PLUS Jack Module and DP6 Patch Panels are designed with complementary technology to meet the connecting hardware pair-to-pair NEXT specification with the de-embedded NEXT loss ranges. However, if one of these connectors is mated with an off-brand patch cord that is not tightly centered to the de-embedded range, the channel performance could be significantly degraded. To deliver superior reliability, the PANDUIT TX6 PLUS Category 6 Patch Cords are manufactured with plugs that are tightly centered in the Category 6 de-embedded plug NEXT loss ranges for maximum performance when mated with the PANDUIT MINI-COM TX6 PLUS Jack Module or DP6 Patch Panels. The PANDUIT TX6000 Copper Cabling System delivers usable bandwidth beyond 300 MHz (shown in Graph 2), over 50% higher than specified by the TIA/EIA Category 6 standard! Graph 2 NEXT Standard PANDUIT NEXT Insertion Loss Standard PANDUIT Attenuation Affects of Besides having properly mated patch cords and connectors to ensure maximum performance during initial installation, patch cords also have to be designed to easily handle frequent moves, adds, and changes. Due to the handling that patch cords receive, TIA/EIA 2006 PANDUIT Corp. All rights reserved. 3
4 568-B.2 requires mechanical stress testing of patch cords to ensure they continue to operate under real-world conditions. Per the TIA/EIA 568-B.2 requirements, patch cords are mechanically tested for performance after bending in various configurations: Patch Cord put into a 6-inch diameter cable loop, up to 10 loops total Patch Cord compressed into a 2.5-inch coil to form an ellipse Patch Cord rotated on one end on the coil ellipse by to form a figure eight 2006 PANDUIT Corp. All rights reserved. 4
5 Testing of off-brand patch cords by PANDUIT Laboratories has shown consistent deterioration of electrical performance to levels below the TIA/EIA 568-B.2 specifications resulting in non-compliant patch cords and degraded channel performance. TIA/EIA 568-B.2 Mechanical Stress Test of Off-Brand Patch Cords NEXT BEFORE NEXT AFTER NEXT NEXT SPEC '12-78 SPEC '12-78 Return Loss BEFORE Return Loss AFTER RETURN LOSS RETURN LOSS SPEC PAIR 45 PAIR 12 PAIR 36 PAIR SPEC PAIR 45 PAIR 12 PAIR 36 PAIR PANDUIT Corp. All rights reserved. 5
6 TIA/EIA 568-B.2 mechanical stress test of high quality patch cords, such as the PANDUIT TX6 Patch Cords shows electrical performance that exceeds the TIA/EIA 568-B.2 specifications resulting in superior long-term channel performance and increased network reliability. TIA/EIA 568-B.2 Mechanical Stress Test of PANDUIT Patch Cords NEXT BEFORE NEXT AFTER NEXT NEXT SPEC ' SPEC '12-78 Return Loss BEFORE Return Loss AFTER RETURN LOSS RETURN LOSS SPEC PAIR 45 PAIR 12 PAIR 36 PAIR SPEC PAIR 45 PAIR 12 PAIR 36 PAIR PANDUIT Corp. All rights reserved. 6
7 To ensure PANDUIT patch cords withstand the stress of actual installations, PANDUIT has incorporated the following innovative features in its design for maximum channel performance, reliability and usability: Patented tangle free latch prevents snags and provides easy release, which saves time on frequent moves, adds and changes Slender strain relief boot provides easy access in highdensity applications and mechanical reliability for longterm consistent performance of your channel Contacts plated with 50 micro inches of gold for robust and reliable connection to support sensitive PoE applications Plug uses an integral pair manager to optimize performance and consistency by reducing untwisting of conductors within the plug and effectively reducing cord-to-cord variability Tight conductor twist rates and cable construction for advanced performance and long term mechanical reliability Plug compliance with all applicable FCC part 68 Subpart F requirements and exceed IEC 6060J-7 specifications 100% Component Testing Beyond mated performance and mechanical testing, an additional measure to ensure patch cord performance is to test each patch cord to the TIA/EIA-568-B.2 component requirement. PANDUIT implements a strict ISO 9001 quality procedure that 100% tests every PANDUIT patch cord to the electrical transmission requirements per TIA/EIA-568-B.2. Every patch cord assembly produced is tested for Wire Map, NEXT, and Return Loss using a Fluke * Digital Cable Analyzer. Each patch cord is then shipped with a quality control label, which is referenced to actual test data verifying high performance. *Fluke is a registered trademark of Fluke Corporation PANDUIT Corp. All rights reserved. 7
8 Conclusion Patch cords are an integral component impacting the performance of the entire structured cabling system. Investment should be made in patch cords that utilize advanced features to deliver maximum reliability and usability of the network. Off-brand patch cords jeopardize network performance due to: High degree of plug variability which leads to degradation of channel performance Inferior design features which do not perform over time due to the mechanical stresses of real-world conditions Untested, low quality patch cords which may not meet electrical requirements In addition, patch cords must be properly mated and tuned to connecting hardware (jacks, panels, and horizontal cable) to keep the network running at peak performance. This directly minimizes the impact of costly network downtime. The proven performance of high quality PANDUIT Copper Patch Cords, tested to exceed TIA/EIA 568-B.2 specifications as a key component of the complete end-to-end solution, helps ensure maximum network bandwidth. Specifying and installing these patch cords can support the critical network demands for today and tomorrow. Additional References: 1. The Weakest Link in High-Performance Cabling Systems, Fluke Networks, 5/ A-US-N rev B 2. Testing Proves Most Cords Fail TIA Requirements (Buyers are not getting what they paid for), Quabbin Wire & Cable Co., Inc., 4/ PANDUIT Corp. All rights reserved. 8
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......
Innovative Connectivity Solution for Maximum Performance and Security
Innovative Connectivity Solution for Maximum Performance and Security Financial Institutions Supports high performance backbone which enables transfer of real-time financial information through voice,
Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)
within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options
Enhanced Category 5 Cabling System Engineering for Performance
Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance
R&Mfreenet Advanced Cat 6 A Unshielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions
Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)
Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Introduction The purpose of this document is to: 1) provide background information beneficial to specifiers
Panduit 28 AWG Patch Cords Installation Guideline
Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER
Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission
Network Engineers Everywhere:
Network Engineers Everywhere: Relax Your Minds Not Your Standards DataMax Commercial Ethernet Patch Cable The Strongest Link. DataMax Commercial Ethernet Patch Cable The Strongest Link. DataMax Patch Cable
PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security
PANDUIT TX6 GIG SHIELDED COPPER CABLING SYSTEM Innovative Connectivity Solution for Maximum Performance and Security Gigabit Ethernet over Copper With ever increasing bandwidth requirements, advancements
Total Solutions Verification
Total Solutions Verification 3rd Party Electrical Performance Testing Author: Tom Boucino Applications Engineer Uniprise Solutions CommScope has always designed cables with connectivity in mind. Our engineers
Category 8 Cabling Standards Update
White Paper Category 8 Cabling Standards Update TIA TR42.7 Study Group for Class II Limits Contents 1 Background 3 2 Impact of this approval on Category 7 A cabling 3 3 Differences between Class I and
114-22008. 8-Position Cat5e (EMT) Modular Plug Connectors. Application Specification
Application Specification 114-22008 02/May/2008 Rev H 8-Position Cat5e (EMT) Modular Plug Connectors NOTE All numerical values are in metric units [with U.S. customary units in brackets]. Dimensions are
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.
Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s
How to Choose the Right Cable Category
How to Choose the Right Cable Category Why do I need a different category of cable? Not too long ago, when local area networks were being designed, each work area outlet typically consisted of one Category
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek
Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek Supporters Mike Grimwood Broadcom Will Bliss Broadcom Dariush Dabiri APM Dan
Category-6 / Class-E Cabling
Category-6 / Class-E Cabling IEEE 802 Tutorial July 7, 1998 San Diego, CA by: Luc Adriaenssens SYSTIMAX Systems Applications Director Bell Labs of Lucent Technologies How were the ISO Cat-6 Targets set?
Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable
Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd
SYSTIMAX Copper Solutions Designed for the Digital Generation
SYSTIMAX Copper Solutions Designed for the Digital Generation SYSTIMAX Structured Connectivity Solutions www.systimax.com SYSTIMAX Solutions is the global leader in the enterprise cabling sector with a
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
CABLE TERMINATION BEST PRACTICES A guide to improved cable performance through proper termination and installation.
B E C A U S E Y O U R B U S I N E S S R U N S T H R O U G H U S CABLE TERMINATION BEST PRACTICES A guide to improved cable performance through proper termination and installation. Outstanding products
The Effect of Network Cabling on Bit Error Rate Performance. By Paul Kish NORDX/CDT
The Effect of Network Cabling on Bit Error Rate Performance By Paul Kish NORDX/CDT Table of Contents Introduction... 2 Probability of Causing Errors... 3 Noise Sources Contributing to Errors... 4 Bit Error
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category
The High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester
Accelerating Light. Copper Cabling Solutions. Category 6A
Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
Copper Cabling Troubleshooting Handbook
NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The Automated DTX Series Diagnostics 5 Causes of Cabling
An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware
for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved
Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk
Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Introduction At the IEEE 802.3 Working Group meeting in July of 2012, the Next Generation BASE-T Call for
Patch Cords / Cable / Cable Assemblies. Patch. Cords/Cable/ Premise Connectivity Systems. Cable Assemblies
Patch Cords / Cable / Cable Assemblies Premise Connectivity Systems Patch Cords/Cable/ Cable Assemblies w w w. s i g n a m a x. c o m Category 6A 10G Patch Cords C1 Patch Panels and Cross- Category 6 Patch
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
Patch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
Managing Physical Security Risk in Physical Layer Infrastructure Solutions
Managing Physical Security Risk in Physical Layer Infrastructure Solutions Protecting Against Network Intrusion Using Keyed Connectivity Systems www.panduit.com WP-05 November 2008 Introduction Industries
Ethernet Patch Cord Wiring
Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring
PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS
PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS Bandwidth Requirements Push Fiber Optic Solutions Offices, Operations
The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT
The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings Focus on the IBDN System 4800LX from NORDX/CDT Table of Contents Introduction... 3 Bandwidth and Information
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka What is a network? A computer network is two or more computers connected together using a telecommunication system for the purpose
Power over Ethernet with Panduit Copper Cabling
Power over Ethernet with Panduit Copper Cabling Introduction Power over Ethernet (PoE) is a common way to reduce installation costs and time by allowing power and data onto a single twisted-pair cable.
White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems
White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems Asef Baddar, RCDD Principal Engineer / Applications Engineering Supervisor Leviton Network Solutions C/7 - #1928 Table of Contents Background
Impedance Matching. Throughput SOLUTIONS NETWORK PERFORMANCE. Only the TrueNet Impedance-matched System Protects Network Performance
Throughput SOLUTIONS Impedance Matching Protects NETWORK PERFORMANCE Original 100BaseT MLT-3 signal transmission Only the TrueNet Impedance-matched System Protects Network Performance Networks for today
White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?
White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
White Paper. Power over Ethernet Plus Update and Cabling Considerations
White Paper Power over Ethernet Plus Update and Cabling Considerations Power over Ethernet Plus Update and Cabling Considerations TABLE OF CONTENTS 1. Introduction...3 2. Application Objectives...5 3.
Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk
Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving
Data Communications Competence Center
Importance of Cable Balance For Improving Noise Susceptibility Data Communications Competence Center DCCC03101702 July 11, 2007 Summary In a study of category 5e and category 6 UTP cables, a strong correlation
Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug
Simpler all over. Simpler all round. No special tools required for field ASSEMBLY Cat.6 A 10 GB ether. 500 MHz fully shielded Poe+ Data Voice MFP8 Cat.6 A Field assembly RJ45 plug Less fuss. More flexibility.
Physical Infrastructure Management PanView iq (PViQ ) System Hardware
Physical Infrastructure Management PanView iq (PViQ ) System Hardware Because we are concerned about access to our network, audit ability, and the capacity to detect unauthorized connectivity as it relates
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
AMP CO Plus Insert for Cat. 6 A Applications
Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide
Installation & Weatherproofing Guide for ENCOM Broadband Radios
Installation & Weatherproofing Guide for ENCOM Broadband Radios Read the following instructions before proceeding with your ENCOM Wireless Radio installation. Keep these instructions in safe location for
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Abstract: This document examines the alien NEXT performance of various bundled cables and measures the impact upon various networks performance.
Title: Alien Crosstalk and Network Performance Source: Paul Vanderlaan Belden Electronics Division 2200 US Hwy 27 South Richmond, IN 47374 Phone (765)-983-5811 Fax (765)-983-5825 Email: [email protected]
ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification
ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification Abstract Presented in this document are the standards to implement Electrical & Optical Ethernet components, cabling, connections,
GigaSPEED X10D Solution How
SYSTIMAX Solutions GigaSPEED X10D Solution How White Paper June 2009 www.commscope.com Contents Modal Decomposition Modeling and the Revolutionary 1 SYSTIMAX GigaSPEED X10D Performance MDM An Introduction
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair
Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;
White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems
White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems Originally ratified by IEEE in 1999 and 2003 respectively, gigabit Ethernet (1000BASE-T) and power over Ethernet
Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels
Fiber Systems Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels 1 Introduction Data centers are the central location for data interchange and are found in enterprises, government
Intelligent Data Center Solutions
Intelligent Data Center Solutions Panduit s Unified Physical Infrastructure (UPI): a Guiding Vision A unified approach to physical and logical systems architecture is imperative for solutions to fully
Data Center Architecture with Panduit, Intel, and Cisco
Data Center Architecture with Panduit, Intel, and Cisco 0GBASE-T Application Note Integrating Panduit Category 6A Interconnects with the Cisco Nexus TM and Intel Ethernet Server Adapter X0-T 0 PANDUIT
Transmission of High-Speed Serial Signals Over Common Cable Media
Transmission of High-Speed Serial February 0 Introduction Technical Note TN066 Designers are often faced with moving serial data from one location to another, over moderate distances, and in the most efficient
Case Study. Molex PDS Delivers Voice and Data Streams around Shanghai Unicom Tower
, the headquarters office of China Unicom Shanghai Branch, is a 26-floor building located at 1031 Changning Road, Shanghai. The cabling system (PDS) to be installed here is to carry all the voice and data
SIEMON Data Center Solutions. www.siemon.com
SIEMON Data Center Solutions www.siemon.com DATA CENTER SOLUTIONS 8 Future Proof Performance 8 Space Saving Through Optimum Density 8 Robust Security and Regulatory Compliance 8 Asset Management 8 Downtime
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS
. HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or
Open System Architecture
Open System Architecture What is Open System Architecture? If you are installing a Category 5e, 6 or 6A infrastructure, there is a sizeable selection of well know products available. What makes one product
SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions. www.commscope.
SYSTIMAX Solutions GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions www.commscope.com The SYSTIMAX GigaSPEED X10D Shielded Solution provides unprecedented performance
Data Centre & Enterprise Solutions. RapidNet
H E L L E R M A N N T Y T O N Data Centre & Enterprise Solutions RapidNet data centre & Enterprise solutions HellermannTyton is a leading global manufacturer of network cabling solutions which connect,
CCNA Discovery Chapter Four
CCNA Discovery Chapter Four By Chief Eng. Amna Ahmed Institute of Telecommunication [email protected] Modified by Vincenzo Bruno Hacklab Cosenza Chapter 4 Explain what the internet is Every day millions
INTELLIGENT INFRASTRUCTURE MANAGEMENT
F/ System F/ Assemblies, 9.0 W W W. S I E M O N. C O M SECTION CONTENTS System...............................9. IM Software........................... 9. Analyzers..............................9. System
Standards Affecting a Premise T-1 Installation
Standards Affecting a Premise T-1 Installation The T-carrier system originated many years ago as a technology developed by AT&T. The intended use of the scheme was to increase the voice channel capacity
Terminating 25-Pair Cable and 4-Pair Cross Connects
Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
Lynx Broadband Installation Manual for Residential Packages with a 20 db Amp Quick Start Guide (first two pages)
Lynx Broadband Installation Manual for Residential Packages with a 20 db Amp Quick Start Guide (first two pages) 1. Be sure that your kit includes all the parts shown in the Check the Equipment section
Model CFA-24 Transparent Cable Farm Automation Switch
Model CFA-24 Transparent Cable Farm Automation Switch Ideal for Broadband Forum s ID-337 G.fast Certification and TR-249 VDSL2 Vectoring Testing High performance transparent solution designed to automate
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
CommScope Intelligent Building Infrastructure Solutions (IBIS)
SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides
SMARTen 24 STP Patch Panels
Features Support 24 ports per 1U High performance, supportable bandwidth up to 500MHz supporting IEEE 802.3an 10Gbps application Conform to ANSI/TIA/EIA-568-B.2-10, ISO/IEC 11801 2.1 edition and CENELEC
Safety & Performance in the Wire and Cable Industry
Safety & Performance in the Listed vs. Verified: Marks, Logos and Programs Written by: Antoine Pelletier, Team Leader, Global Cabling Products Larry Todd, Chief Engineer Intertek [email protected] 1-800-WORLDLAB
IT Cabling Solutions
IT Cabling Solutions Signamax & Hitachi Cable America System Performance Signamax & Hitachi Cable America (Hitachi) system quality assurance testing is based on the worst-case model - four-connector 100-meter
HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks
HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This
MPO. Fast Fibre Solution for Data Centres
MPO Fast Fibre Solution for Data Centres Benefits The Plug & Play MPO solution of Nexans Cabling Solutions provides a comprehensive line of pre-terminated and pre-tested assemblies to meet the current
SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS
STRUCTURED CABLING SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS INTRODUCTION In recent years, communications have taken on a crucial role in development for businesses. Communications
TIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
Nathan Dayton ADNET. ADNET SYSTEMS, Inc. [email protected]. Slide Number 1
Nathan Dayton SYSTEMS, Inc. [email protected] Slide Number 1 NETWORK DESIGN Slide Number 2 Previously there have been two phases in the design of a network Department Design Interconnect Design
Open Office Cabling Architecture SYSTIMAX. Structured Cabling System Opens Office Cabling to New Possibilities
Open Office Cabling Architecture SYSTIMAX Structured Cabling System Opens Office Cabling to New Possibilities An Architectural Design That Can Slash Costs for Years to Come Today, the most commonly hidden
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
Cat7/Class F New Installation Concept New infrastructure. Handbook
Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
