Structured Cabling Statement of Work
|
|
|
- Dora Ferguson
- 9 years ago
- Views:
Transcription
1 Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1
2 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure to be installed at their facilities located in Stockton and French Camp, California. B. CONTRACTOR QUALIFICATIONS AND REQUIREMENTS a. Contractor shall design and provide all materials in order to install a structure cabling solution supporting voice, and data. The contractor shall be responsible for providing a communications infrastructure compliant to current county standards; including the procurement of products, installation of cabling infrastructure, fire stopping, verification of performance, and documentation. b. Contractor must possess a valid C-7 California State contractor s license. This license must have been issued five (5) years prior to the date on this Statement of Work. c. Contractor and/or subcontractor will be required to have a C61 (Asbestos Certification License), by the Contractor s State License Board. A copy of this certification must be submitted with the proposal. d. The contractor must be a certified by the manufactures of the cabling solutions to be installed. To meet the requirements of this specification, the contractor must be a Panduit PCI. In addition, the contractor must have a BICSI RCDD (Registered Communications Distribution Designer) on staff (full time employee). e. Some work sites have asbestos. Tenting is required in areas with asbestos. f. After-hours and weekend work is required at several locations. These locations are identified in the Execution Section F of this document. g. This is a prevailing wage project. h. Contractor shall be responsible for all fees and permits required to any governmental agency having jurisdiction over the work in proposal. The contractor shall arrange inspections. i. Contractor employees shall act in a professional manner, and dressed appropriately for the task. No person shall bring alcoholic beverages, controlled substances, firearms, or animals to the job site. Page 2
3 j. Contractor shall clear the work area every evening. If available space exists, contractor equipment and materials may be stored at the facility with approval of the Owner. All packing material shall be disposed of at the end of each day. The Owner will not be responsible for the loss, theft, or damage of any equipment or material. k. Contractor shall follow the security policies and procedures defined by the Owner. This may include providing key access, creating access badges, and escorts for restricted areas. l. The Contractor shall take all precautions necessary to protect existing structures and furniture. Any items that are damaged during the course of the work shall be repaired or replaced by the contractor at no cost to the Owner. m. Owner will provide the contractor with reasonable access to the job site Monday-Sunday 8-5 (Federal / State holidays excluded). The Owner must approve any work that requires access outside of these parameters. n. Contractor shall take special precautions to ensure a safe work environment for the employees, contractors, and visitors. o. Contractor will make a reasonable effort to not be disruptive to other contractors, or working staff at the job site. p. Contractor will install only material that is new and undamaged. Refurbished or used materials are not acceptable. q. Owner expects the workmanship to be of high quality. All equipment shall be plumb and true with the structure. All materials shall be firmly secured in place, adequately supported, and permanent. r. Owner will consider the project complete when all work has been completed, the final documentation has been delivered, and the work site has been cleaned to the Owners satisfaction. s. Contractor agrees to replace or repair, as new, any defective work or materials, which are identified by the Owner within 2 years of final payment. C. CODES, STANDARDS, AND BEST PRACTICES a. All work and materials shall be in full accordance with the latest Page 3
4 codes, standards, and best practices. It is the responsibility of the Contractor to have access to each document. In the case that one of the following documents has a ratified update or addendum; it shall be incorporated into this scope of work. If multiple documents provide different requirements, the strictest requirement shall be followed. Not all documents may apply to this project. i. ANSI/TIA/EIA B.1 - Telecommunications Cabling Standard, Part 1: General Requirements (including all the latest ANSI/TIA/EIA B.2 - Telecommunications Cabling Standard, Part 2: Balanced Twisted Pair Cabling Components i ANSI/TIA/EIA B.3 - Telecommunications Cabling Standard, Part 3: Optical Fiber Cabling Components Standard iv. ANSI/TIA/EIA Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant v. ANSI/TIA/EIA Measurement of Optical Power Loss of Installed Multimode Fiber Cable Plant vi. v ANSI/TIA/EIA A Pathway and Spaces ANSI/TIA/EIA 606-A Administration Standard for the Telecommunications Infrastructure of Commercial Buildings (labeling identifiers will be provided by Owner) vi ANSI/TIA/EIA 607-(A) Commercial Building Grounding/Bonding Requirements ix. NFPA x. ANSI/TIA/EIA-942 Telecommunications Infrastructure Standard for Data Centers xi. ANSI/TIA/EIA-758-(A) Customer-Owned Outside Plant Manual x BICSI - Telecommunications Distribution Methods Manual (latest edition) xi BICSI - Cabling Installation Manual (latest edition) xiv. BICSI Customer-Owned Outside Plant Design Manual (latest edition) xv. FCC 47 CFR 68 xvi. NEMA 250 xv NEC - Articles 770 and 800 xvi ADA - Americans with Disabilities Act xix. ISO/IEC (International) Generic Cabling for Customer Premises Standard (including all the latest amendments and applicable addenda) xx. xxi. Title 24 (California Code of Regulation) All Federal, State, and Local Codes Page 4
5 D. Definitions a. Data Connection: A horizontal cabling solution that consists of a UTP cable terminated on a Data Jack at the work area outlet, and a Data Jack in a modular patch panel within the ER or TR. This connection will support data and VoIP connections. b. Data Jack: A Category 5E connector used to terminate a single UTP cable for data and VoIP communications.. c. Outlet Box: A housing to protect Data and Voice Jacks at the Work Area. d. Telecommunications Room (TR): An enclosed space that is used for horizontal cross-connects, and telecommunications equipment. e. Equipment Room (ER): An enclosed space that is used for housing main cross-connects, horizontal cross-connects, and telecommunications equipment. f. Telecommunications Space (TS): A generic term for a space that houses main cross-connects, horizontal cross-connects, and telecommunications equipment. g. Traditional Voice Connection: A horizontal cabling solution that consists of a UTP cable terminated on a Voice Jack in the Outlet Box, and a 66-block within the TR or ER. h. Voice Jack: A Category 3 connector used to terminate a single UTP cable for supporting traditional voice communications. This includes emergency hard lines and fax communications. i. VoIP: Voice over Internet Protocol j. Work Area: A building space where the occupants interact with Telecommunications equipment E. System Design and Clarifications a. The goal of this project is the installation of a structured cabling system for data (including VoIP), and traditional voice connections. b. 2-6 position faceplates shall be installed at each work area outlet and will be determined by Owner. The port shall be numbered 1-6, from left to right, top to bottom. The data jacks shall be placed in port #1 (required) and port #2 (required), and the traditional voice jack shall be placed in port #3 (when specified by the Owner). Blanking panels (matching in color) shall be installed on all unused ports. c. All data connections shall use Category 5E Cable terminated on Category 5E Jacks (one on each end). The cable and jacks shall be Yellow in color. d. All traditional voice connections shall use Category 5E Cable terminated on Category 3 Jacks (one on each end). The cable and Page 5
6 F. Execution jacks shall be Grey in color. e. All data jacks shall be terminated using the T568B" wiring scheme. f. UTP patch cords (Data or Traditional Voice) are not required for this project. g. SJC personnel will facilitate access and pathway identification. h. Contractor will provide tenting for work areas that contain asbestos. i. Contractor assumes all existing pathways are free and clear and additional work will be done as a change order. a. Courthouse Room 100, Cables from Printer Cubicle to Room 144 Data Closet i. Furnish and install two (2) six (6 port) Category 5E data cables complete with connectors, faceplates, labeling and testing. Location shall be on the north wall behind existing printers. i iv. Provide Patch Panel if necessary. Back pull blue cable for a string. Work to be complete after hours or weekend work. Install Firestopping on all utilized communications conduits, sleeves to re-establish the integrity of the fire rated walls or floors. b. Courthouse Room 101, Cables from North Corner to Data Closet by Stairwell. i. Furnish and install two (2) four (4 port) telecom outlets with (5) Category 5E data cables complete with connectors, faceplates, labeling and testing. i iv. Provide Patch Panel if necessary. Work to be completed after hours or weekend work. Install Firestopping on all utilized communications conduits, sleeves to re-establish the integrity of the fire rated walls or floors. Page 6
7 c. Courthouse Room 265B, Cables from 265 to Data Claset in Hallway near room 260 i. Furnish and install one (1) telecom outlet with (4) Category 5E data cables complete with connectors, faceplates, labeling and testing. i iv. Provide Patch Panel if necessary. Work to be completed after hours or weekend work. Install Firestopping on all utilized communications conduits, sleeves to re-establish the integrity of the fire rated walls or floors. d. Courthouse Room 350, Cables from 350 to Data Closet in Hallway near room 356. i. Furnish and install one (1) telecom outlet with (2) Category 5E data cables complete with connectors, faceplates, labeling and testing. i iv. Provide Patch Panel if necessary. Work to be completed after hours or weekend work. Install Firestopping on all utilized communications conduits, sleeves to re-establish the integrity of the fire rated walls or floors. e. Juvenile Justice Center, Cables from Printer Location to D.A. s Office Next Door. i. Furnish and install (4) Category 5E data cables complete with connectors, faceplates, labeling and testing. i Provide Patch Panel if necessary. Install Firestopping on all utilized communications conduits, sleeves to re-establish the integrity of the fire rated walls or floors. Page 7
8 f. Firestop g. Labeling i. Firestop shall be installed for all through-wall or throughfloor penetrations as required by the NEC. All firestop products shall be installed in accordance with the manufacturer recommendations. Each firestop shall have a minimum 1-hour rating, and shall be identified in the final documentation. i. All cables will be labeled following the ANSI/ETA/TIA 606- A. This installation shall be treated as a Class IV. The Owner will provide specific labeling identifiers (site, building, etc ), after the contract is awarded. i All labels shall be printed by a mechanical device (printer, label maker), and shall be legible viewing at 12. On horizontal cabling, printed labels shall be provided within 12 of each end of the cable, on the patch panel, and on the workstation faceplace. h. Testing i. All traditional voice connections shall be tested for continuity and wire map. The Owner reserves the right to have a representative present during testing. All Data Connections (Category 5E) shall be tested to the Category 5E Permanent Link performance specification. All data connections shall support 1000BaseT connectivity. The Owner reserves the right to have a representative present during testing. i The tester shall be a Fluke DSP 4000, Fluke DTX 1800, LANTEK 6 or 7, or equivalent tester. The tester must be certified by ETL or UL. iv. Each data and traditional voice connection shall be tested after labeling is complete. Page 8
9 G. Documentation a. Performance Test Results i. The contractor shall provide tester generated documentation for the Voice Connections and Data Connections. The results shall be provided in hard and soft copy formats. The soft copy results shall be provided on CD-R media, in a non-proprietary format. H. Products a. All products shall be installed in compliance with the manufactures instructions. The Owner has identified products, which are approved for this installation. No substitutions of identified products shall be allowed. This will ensure a quality installation, guarantee performance, and reduce on-going maintenance costs for the life of the solution. b. This is a Graybar VIP Project. Graybar provides enhanced pricing and services for this project. c. This is not a complete parts list. Additional products may be required to complete this installation. d. Horizontal Cabling: The horizontal cabling solution must conform to the Category 5E Cabling Specification. Plenum cable shall be used where required by code. i. UTP Cable 1. The cable to be used for data drops is the Landmark 350 by Berk-Tek. The cable jacket shall be plenum rated and yellow in color. The approved part number is: a. 5EXHNP4P24-YL-P-BER-AP 2. The cable to be used for voice drops is the Landmark 350 by Berk-Tek. The cable jacket shall be plenum rated and grey in color. The approved part number is: a. 5EXHNP4P24-GY-P-BER-AP Connectivity 3. The workstation jack to be used for data drops is the Page 9
10 Panduit Mini-Com TX5e Jack Module, which is yellow in color. The approved part number is: CJ5E88TYL 4. The workstation jack to be used for voice drops is the Panduit Mini-Com Mini-Jack Cat 3 Jack Module, Grey in color, and USOC Coded. The approved part number is: a. CJ66UIG i Faceplates 1. The faceplates shall be the Panduit 4-port Executive Faceplate that is White in color. The approved part number is: a. CFPE4WHY iv. Patch Panels 1. The patch panels shall be a 48-port modular patch panel by Panduit. The approved part number for the panel is: a. CPP48WBLY Page 10
11 Page 11
12 Page 12
13 Page 13
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
The High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester
Telecommunications Systems Narrative Page 1 The Engineering Enterprise
I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based
CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL. Fiber Optic and Data Cabling Project Shelby Township Police Building
CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL The Charter Township of Shelby is soliciting proposals to install fiber optic and data cabling to serve a new Police Building that is under construction
SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)
SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head
Wired and Wireless Network Request for Proposal New Washington County High School Facility
Washington County Board Of Education P.O. Box 716 501 Industrial Drive Sandersville, GA 31082 (478) 552-3981 FAX (478) 552-3128 Description Wired and Wireless Network Request for Proposal New Washington
DEPARTMENTAL REGULATION
U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...
Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)
The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,
Data and Voice Network Infrastructure
Data and Voice Network Infrastructure Denis Levesque Mike Milne Sponsored By Data and Voice Network Infrastructure Page 1 Copyright APPA 2015 Published by APPA: APPA is the association of choice serving
Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
Request for Proposal DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS. Kalispell Public Schools
Request for Proposal DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For Kalispell Public Schools 2015 TABLE OF CONTENTS I. PROJECT DESCRIPTION / GENERAL SCOPE OF WORK...3 II. PROJECT
Nathan Dayton ADNET. ADNET SYSTEMS, Inc. [email protected]. Slide Number 1
Nathan Dayton SYSTEMS, Inc. [email protected] Slide Number 1 NETWORK DESIGN Slide Number 2 Previously there have been two phases in the design of a network Department Design Interconnect Design
FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS
FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3
Cabling Services (price per pull)
Cabling Services (per pull) - Labor Only Price Sheet - Standard Hours 14, Cat 5 cable - installed, terminated, tested and labeled including wall plate, jack and certification report. 0-0 Feet $ 77.00 $
ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534
DATE: August 25, 2015 TO: All Plan Holders ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534 FROM: Jim Vernon, Architectural Partners PROJECT NAME: Nelson
IT&T Infrastructure Standards
Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...
CONTRACT DATA SHEET TELEPHONE/DATA INSTALLATION & REPAIR CONTRACT #: 1015-14 CONTRACT DATES: 12/16/14-11/30/15
CONTRACT DATA SHEET Monroe County Division of Purchasing 200 County Office Building, Rochester NY 14614 TITLE: TELEPHONE/DATA INSTALLATION & REPAIR CONTRACT #: 1015-14 CONTRACT DATES: 12/16/14-11/30/15
VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE
VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE 1 C O N T E N T S Security Systems can be integrated into any IT Network The Network Manager s New Responsibility The Problem
Request for Proposal (RFP) IP Cameras/Door Access Control
WAHPETON PUBLIC SCHOOLS Information Technology Department Request for Proposal (RFP) IP Cameras/Door Access Control Inquiries and requests regarding this RFP should be directed to: Jason Pfahl, Director
Structured Cabling Network Services & Equipment Inside/Outside Plant Design Trenching
Structured Cabling Network Services & Equipment Inside/Outside Plant Design Trenching 502 Buffalo Rd., Ft. Pierre, SD 57532 (605) 224-1111 or (800) 747-6427 www.windcircle.net [email protected] Computers
Information and Communication Technology Network Cabling Infrastructure Standard
Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and
SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.
SECTION 27 20 00 - PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and Prior Addenda if any, as identified above.
To: All Vendors Bidding on The College of New Jersey Security Cameras Phase III From: Roselle Horodeski Finance and Business Services Date: April 10, 2015 ADDENDUM NO. 1 ISSUE DATE: April 10, 2015 REFERENCE:
Division 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces May 1, 2014 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012
TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications
ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6
050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY
DIVISION 27. Telecommunications Systems
DIVISION 27 Telecommunications Systems Abstract Division 27 governs the infrastructure for the low-voltage information transport systems (ITS), which include voice, data, and CATV systems and their pathways
UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS
UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS University of Toronto Scarborough Cable Systems Specification 1/23 Network Administrators Glenn Attwood Manager,
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance
IS Network Services Senior Facilities Management Group 2 Hill Farms West Division of State Facilities
POSITION SUMMARY Under the general supervision of the DOA/DSF and the DSF Telecom Supervisor, this position works closely with other Agency Telecom Services, Voice Services, Network Services, and Wide
March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1
March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be
Deployment of Secure VoIP Networks Over Zone Cabling Applications
Deployment of Secure VoIP Networks Over Zone Cabling Applications Overview The growing popularity of Voice over Internet Protocol (VoIP) solutions within a secure communications network is driving the
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD
BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize
A. Provide roughing-in, including the empty boxes, conduit, pull strings, etc. under Division 26 for the following related Sections:
SECTION 270500 COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
Discontinued. Volition. Fiber Optic Cable. 3Innovation
Volition Fiber Optic Cable Tough enough to take it. Easy to handle. The Volition Network Solution from 3M includes horizontal and backbone cable with 62.5/125 µm and 50/125 µm multimode fiber, and 9/125
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
Design Guide. Universal Connectivity Grid. SYSTIMAX Solutions from CommScope
Design Guide Universal Connectivity Grid SYSTIMAX Solutions from CommScope CONTENTS Introduction 3 Commercial building network overview 4 Zone cabling 5 Universal Connectivity Grid 6 UCG cell size 7 Integrating
B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.
SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Cabling and Building Infrastructure for Technology
Cabling and Building Infrastructure for Technology by: Ernest J. Schirmer, Director Information Technology Infrastructure Design CUH2A Architecture Engineering Planning 211 Carnegie Center Princeton, NJ
Cabling Standards and Guidelines Commonwealth of Massachusetts
Cabling Standards and Guidelines Commonwealth of Massachusetts Information Technology Division Cabling Standards and Guidelines Version 2.2 August 2002 Document History Date Version Number Summary 1995
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew [email protected] J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards
Copper Pre-terminated Assemblies
Copper Pre-terminated Assemblies Copper Pre-Terminated Trunk Assemblies Overview Copper Pre-Terminated trunk assemblies are the perfect solution for Enterprise / Premise & Data Centre applications where
REQUEST FOR PROPOSAL: STRUCTURED CABLING, LAN SWITCHES, LONG DISTANCE SERVICE, ELECTRONIC FAXING, AND HOSTED VOIP SPECIFICATIONS
SECOND ADDENDUM TO RFP DOCUMENTS REQUEST FOR PROPOSAL: STRUCTURED CABLING, LAN SWITCHES, LONG DISTANCE SERVICE, ELECTRONIC FAXING, AND HOSTED VOIP SPECIFICATIONS 11/9/2015 To All Potential Bidders: This
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
STATE OF NEVADA Department of Administration Division of Human Resource Management CLASS SPECIFICATION
STATE OF NEVADA Department of Administration Division of Human Resource Management CLASS SPECIFICATION TITLE GRADE EEO-4 CODE DIGITAL TELECOMMUNICATIONS SUPERVISOR 37 B 6.963 SERIES CONCEPT Digital Telecommunications
2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
TrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
Data Centre & Enterprise Solutions. RapidNet
H E L L E R M A N N T Y T O N Data Centre & Enterprise Solutions RapidNet data centre & Enterprise solutions HellermannTyton is a leading global manufacturer of network cabling solutions which connect,
21 st Century Campus Network Responsibility Matrix 5/26/10
Definitions: DoIT Standards This column details the minimal configuration, which DoIT has defined in order to provide a campus-wide standard level of service. Departments may request services, which exceeds
Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District
15579 Eighth Street Victorville, CA 92392 Phone 760. 245-1691 Fax 760.245-6245 www.vesd.net 02-26-03 TABLE OF CONTENTS Introduction 3 Overview of Standards 3 Equipment Specifications 4 Material Specifications
Vertical Phone System Upgrades 2014. Scope of Work
Vertical Phone System Upgrades 2014 Scope of Work Project Overview Install new Vertical phone system and phones on site. Complete testing with API helpdesk. Remove old phone system, phones and box up for
Harvard University Information Technology Standards Construction Specifications Institute Master Format Division 270000
Harvard University Information Technology Standards Construction Specifications Institute Master Format Division 270000 10/1/2014 DIVISION 270000 COMMUNICATIONS TABLE OF CONTENTS SECTION 27 00 00 COMMUNICATIONS
http://www.icetech.net
Because your network solution depends upon a solid foundation, we can provide comprehensive design, installation, analysis and service of your physical layer. Copper Cabling Installation: Category 3 (Voice)
Generic Category 5e Cabling Specification
Telecommunications Cabling System Technical Specification Category 5e Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 10 00 (August 2011) ---------------------------- Preparing Activity: NAVFAC Superseding UFGS-27 10 00 (January 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
Master Format Division 27 - Communications
CLEMSON UNIVERSITY Master Format Division 27 - Communications Charlie Breece, RCDD CCIT Network Services and Telecommunications Revised 10-2013 Master Format Division 27 Communications DIVISION 27 COMMUNICATIONS
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
Monash University. Communications Cabling Manual. (Sites running VoIP only)
Monash University Communications Cabling Manual (Sites running VoIP only) Communications & Networks Information Technology Services Monash University Monash Cabling Specifications (VOIP sites)doc Page
Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial
Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,
Excel Pre-terminated Copper and Fibre Optic Systems
Excel Pre-terminated Copper and Fibre Optic Systems Excel is a world-class premium performing end-to-end infrastructure solution - designed, manufactured, supported and delivered - without compromise.
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman This document defines the standards used for voice and data wiring in buildings used by MSU