1 Wyoming State Capitol Building Restoration and Modernization Level I / II Life Safety and Fire Protection Assessment 25 September 2013
2 Presentation Overview Project Overview Applicable Codes Non-Conformance Issues Evaluation Criteria Engineering Analysis Findings Aon Fire Protection Engineering Corporation 2
3 Project Overview Level I / II Life Safety & Fire Protection Assessment Identify matters of non-conformance with building and fire codes Identify strategies to achieve code conformance Improve overall building fire safety Respectful of the building s historic fabric Aon Fire Protection Engineering Corporation 3
4 Applicable Codes Wyoming State Building and Fire Code 2012 ICC International Building Code (IBC) 2012 ICC International Existing Building Code (IEBC) 2012 ICC International Fire Code (IFC) NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition IEBC and IBC do not provide a comprehensive method for assessing fire safety in historic structures Framework for quantifying overall life safety and protecting property and heritage Aon Fire Protection Engineering Corporation 4
5 Non-Compliance Issues Fire containment and building compartmentalization Combustible building construction materials in the attic spaces Fire suppression and control Means of egress Fire alarm Monumental stair handrails Rotunda guards Exit signage / way finding Aon Fire Protection Engineering Corporation 5
6 Non-Compliance Issues: Focus Engineering Analysis Fire containment and building compartmentalization Combustible building construction materials in the attic spaces Fire suppression and control Means of egress Fire alarm Monumental stair handrails Rotunda guards Exit signage / way finding Aon Fire Protection Engineering Corporation 6
7 Evaluation Criteria Determine Required Safety Egress Time (RSET) in a fire emergency Determine Available Safety Egress Time (ASET) in a fire emergency Time where tenable conditions can be maintained for safe occupant evacuation Life safety is achieved when ASET exceeds RSET Available Safe Egress Time (ASET) Required Safe Egress Time (RSET) Margin of Safety t d t a t i t mov Detection Time Alarm Time Decision & Action Time Evacuation Time Pre-movement Time Aon Fire Protection Engineering Corporation 7
8 Evaluation Criteria: Fire Scenarios NFPA 101 Life Safety Code Performance-Based Option was used to identify probable building fire scenarios 1. Typical fire for the occupancy 2. Ultrafast-developing fire that makes one of the exits impassable 3. Fire in a normally unoccupied room 4. Fire in a concealed wall/ceiling space adjacent to a large occupied room 5. Slowly developing fire shielded from fire protection systems 6. Most severe fire resulting from the largest possible fuel load 7. Outside exposure fire 8. Fire where the fire protection systems are rendered ineffective Aon Fire Protection Engineering Corporation 8
9 Evaluation Criteria: Fire Scenarios NFPA 101 Life Safety Code Performance-Based Option was used to identify probable building fire scenarios 1. Typical fire for the occupancy 2. Ultrafast-developing fire that makes one of the exits impassable 3. Fire in a normally unoccupied room. 4. Fire in a concealed wall / ceiling space adjacent to a large occupied room. 5. Slowly developing fire shielded from fire protection systems. 6. Most severe fire resulting from the largest possible fuel load 7. Outside exposure fire. 8. Fire where the fire protection systems are rendered ineffective. Aon Fire Protection Engineering Corporation 9
10 Engineering Analysis: RSET Computational evacuation modeling Determine time required for building evacuation Analysis assumes building population 1,214 persons Actual population is significantly less Aon Fire Protection Engineering Corporation 10
11 Engineering Analysis: ASET Fire modeling analysis Determine smoke spread, maintain safe conditions for evacuation Evaluate protection strategies to mitigate fire hazard and fire risk Aon Fire Protection Engineering Corporation 11
12 Findings Tenable conditions cannot be maintained in the existing building. Chambers large occupant load causes queuing at the stairs on Floors 2 and 3 exposing the occupants to smoke spread from the chamber fire. Mechanical smoke control system is required to maintain tenable conditions for occupant evacuation. Open monumental stairs and Rotunda enhance smoke control. Christmas tree is the most severe fire. ASET exceeds RSET in all fire scenarios with enhanced fire protection systems except the Christmas tree scenario. Aon Fire Protection Engineering Corporation 12
13 RSET General Parameters The following slides reflect evacuation modeling results including written narrative followed by evacuation simulation video. General parameters for the simulations are as follows: Simulations are not in real time. Time is shown in BOLD at upper left of simulation To play video click image on screen Videos show evacuation time only, no delay is incorporated for premovement Occupants are permitted to choose between any available exit. Simulations are shown as examples of people movement; actual times and results vary based on scenario. Aon Fire Protection Engineering Corporation 13
14 2 nd Floor Evacuation Two Stairs Available This simulation reflects evacuation from the second floor when all exits are available including both monumental stairs Observations from simulation are as follows: Queuing is observed leaving the Chambers as early as 5 seconds into the simulation Closest occupants reach monumental stairs within 10 seconds and queuing begins at stairs to exit floor By 20 seconds, a large group of people has congregated at each of the stairs, as stair travel is a limiting factor in evacuation speeds By 130 seconds (2 minutes), all occupants have reached the stair queues By 190 seconds (3 minutes), one stair has cleared and occupants choose to leave their queue and travel to open stair By 240 seconds (4 minutes), occupants have evacuated the second floor Aon Fire Protection Engineering Corporation 14
15 2 nd Floor Evacuation Two Stairs Available Aon Fire Protection Engineering Corporation 15
16 All Floors Evacuation Two Stairs Available This simulation shows a section of the building during evacuation when all exits are available. Observations from simulation are as follows: Within 5 seconds, vertical travel down the stairs can be observed Within 45 seconds, most occupants have reached an exit access stair queue Within 60 seconds (1 minute) all basement occupants have left the floor By 240 seconds (4 minutes) occupants have left the third floor and are congregated at exits from the second and first floors By 420 seconds (7 minutes), occupants have left the second floor By 450 seconds (7.5 minutes), all occupants have left the building Aon Fire Protection Engineering Corporation 16
17 All Floors Evacuation Two Stairs Available Aon Fire Protection Engineering Corporation 17
18 All Floors Evacuation One Stair Blocked This simulation shows a section of the building during evacuation when one stair from Level 2 to Level 1 is blocked. Observations from simulation are as follows: Within 5 seconds, vertical travel down the stairs can be observed Within 45 seconds, most occupants have reached an exit access stair queue Within 60 seconds (1 minute) all basement occupants have left the floor By 240 seconds (4 minutes) occupants have left the third floor and are congregated at exits from the second and first floors Large groups of occupants are observed on the second floor as only one of the two stairs are available for egress. By 420 seconds (7 minutes), occupants have left the second floor By 450 seconds (7.5 minutes), all occupants have left the building Aon Fire Protection Engineering Corporation 18
19 All Floors Evacuation One Stair Blocked Aon Fire Protection Engineering Corporation 19
20 ASET: General Parameters The following slides reflect fire modeling results including written narrative followed by modeling simulation video. General parameters for the simulations are as follows: Simulations are not in real time play is increased. Time is shown at lower left in simulation Fire starts at time = 0 Simulation runs 1200s (20 min) To play video click image on screen Scale at right hand side of simulation shows visibility in meters Blue indicates high visibility 30 m (100 ft) or greater Red indicates low visibility 10 m (30 ft) or less Smoke exhaust, where presents, initiates at approximately 2 min Aon Fire Protection Engineering Corporation 20
21 ASET: House Fire No Smoke Control This simulation reflects the previously described design fire within the House Chambers with no Smoke Exhaust in building Observations are as follows: At 240s (4 min) smoke has spread into outer rooms into the corridor on the third floor At 360s (6 min) smoke has banked down within east portion of the corridor on the third floor is spilling into Rotunda At 460s (7.5 min) smoke has spread to west portion of the corridor By 720s (12 min) the smoke layer has descended within the Rotunda space to the corridors on the second floor By 780s (13 min) smoke has filled the third floor of the Senate Chamber By 1200s (20 min) smoke has spread throughout the remainder of the second floor Aon Fire Protection Engineering Corporation 21
22 ASET: House Fire No Smoke Control Aon Fire Protection Engineering Corporation 22
23 ASET: House Fire Smoke Control This simulation reflects the previously described design fire within the House Chambers with Smoke Exhaust in building Observations are as follows: At 320s (5.5 min) smoke has spread from the Chamber and outer rooms into the corridor on the third floor From 450s until 1140s (7.5 min to 19 min), smoke banks down to less than 6 feet above a portion of the east corridor intermittently. No other smoke spread is experienced. With smoke exhaust, smoke is contained to the area of origin (House chambers) and immediate surrounding spaces with little to no impact on means of egress for other building occupants Aon Fire Protection Engineering Corporation 23
24 ASET: House Fire Smoke Control Aon Fire Protection Engineering Corporation 24
25 ASET: Stair Fire No Smoke Control This simulation reflects the previously described design fire at the base of the stair with no Smoke Exhaust in building Observations are as follows: At 90s (1.5 min) smoke has spread from the stair throughout east portion of the corridors and Rotunda on the first through third levels. At 180s (3 min) smoke has filled the Rotunda and adjacent corridors on the second and third floors At 240s (4 min) smoke has spread through the ante rooms and enters the Senate and House Chambers on the third floor By 390s (6.5 min) smoke has descended to corridors on the first floor By 930s (15.5 min) smoke has spread throughout the first floor and descended within both Chambers to the second floor Aon Fire Protection Engineering Corporation 25
26 ASET: Stair Fire No Smoke Control Aon Fire Protection Engineering Corporation 26
27 ASET: Stair Fire No Smoke Control This simulation reflects the previously described design fire at the base of the stair with Smoke Exhaust in building Observations are as follows: At 180s (3 min) smoke has spread through the third floor within the Rotunda and portions of the first floor on the east side of the Rotunda At 270s (4.5 min) smoke has been exhausted from the majority of the third floor, increasing visibility conditions to greater than 30 feet. From 270s to 690s (4.5 min to 11.5 min) visibility conditions fluctuate within area of origin. Portions of second and first floor have visibility conditions less than 30 feet intermittently. Other portions of building remain clear. After 690s (11.5 min) visibility greater than 30 feet is constant throughout the building. Smoke is shown at the fire, but is quickly exhausted from the space and does not spread to any other portion of the building. Aon Fire Protection Engineering Corporation 27
28 ASET: Stair Fire Smoke Control Aon Fire Protection Engineering Corporation 28
29 Moving Forward Acceptance of Approach NFPA 914 strategy Performance-based analysis for determining tenability Design fire scenario selection Modeling tools Further refinement of results Exhaust locations and capacities Make-up air locations Occupant load calculations Aon Risk Solutions Global Risk Consulting Fire Protection Engineering 29
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,
ON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum
Flexible strategy ON MOST schemes, the architectural design of a building is influenced by fire engineering strategy. This could be in the form of visual, physical elements such as fire doors, fire curtains,
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
FIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT SINCERE KNIT GARMENTS LTD UNIT-1 EAST ISDAIR, CHANDMARI, FATULLAH OTHER FACTORIES: FAKIR KNIT LTD. July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
FIRE PREVENTION DEPARTMENT. CONTAINMENT/RESTORATION UCDHS ILSM Procedure For Water Damage Repair
FIRENET FIRE PREVENTION DEPARTMENT January 2014 CONTAINMENT/RESTORATION UCDHS ILSM Procedure For Water Damage Repair Purpose: After staff respond to and take those immediate actions necessary to stop a
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson
Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
SECTION 903 AUTOMATIC SPRINKLER SYSTEMS
Page 25 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
Pearl River Tower, Guangzhou: Fire Protection Strategies for an Energy Efficient High-Rise Building
Pearl River Tower, Guangzhou: Fire Protection Strategies for an Energy Efficient High-Rise Building Fang Li 1, James Antell, AIA, P.E. 2 and Martin Reiss, P.E., FSFPE 3 1 Vice President, China Operations,
FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES
FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES P.L. Senez*, K.D. Calder, Hsing H (Isabella) Li Sereca Fire Consulting Ltd., Canada INTRODUCTION
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
FIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT SURAVEE GARMENTS LIMITED 2/C DARUS SALAM ROAD, MIRPUR OTHER FACTORIES: BABYLON CASUALWEAR LTD & ABONI FASHION March 29, 2014 Page 2 SUMMARY was surveyed for fire safety on
Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
Fraternity and Sorority House Fire Safety
Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.
Comparison of the Structural Provisions in the International Existing Building Code 2012 versus the Rhode Island State Rehabilitation Code
August 3, 2012 Existing Building Code 2012 versus the Rhode Island State By: Structural Engineers Association of Rhode Island, Building Code Committee Introduction At the request of the Building Code Standards
The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services
MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts
Classroom Door Security & Locking Hardware
Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
How To Check If A Building Is Safe For A Disabled Person
GENERAL SAFETY-FIRE-SECURITY SURVEY CHECKLIST CAMPUS INSPECTION DATE BUILDING NAME INSPECTOR: ASSISTED BY: OUTSIDE/INSIDE BUILDING 1. ADA (Americans with Disabilities Act) Entry/Exit (If area is designed
Practice Note 2006-27
Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two
Fire Barriers & Fire Stopping
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 [email protected] Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire
ICC CODE CORNER 2012 IFC Code & Commentary
SECTION 908 EMERGENCY ALARM SYSTEMS 908.1 Group H occupancies. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter
M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003
M E M O R A N D U M To: Partnership for Safer Buildings Date: 21 March 2003 From: Codes Assessment Subcommittee Walter Smittle III, Chairman Re: Building Code Fire Safety Concerns: NFPA 5000, Building
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
Fire Risk in Metro Tunnels and Stations
Fire Risk in Metro Tunnels and Stations Hyder Consulting Presented by: Dr. Leong Poon Ir. Richard Lau 2 Dec 2005 Metro Tunnels and Stations General Characteristics Limited to metropolitan area (hence the
Appraisal of Passive and Active Fire Protection Systems in Student s Accommodation
MATEC Web of Conferences 10, 06002 (2014) DOI: 10.1051/ matecconf/ 20141006002 C Owned by the authors, published by EDP Sciences, 2014 Appraisal of Passive and Active Fire Protection Systems in Student
Requirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
NFPA 101 2012 SELECT SIGNIFICANT CHANGES
NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com [email protected] Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
Beth Israel Deaconess Medical Center Environment of Care Manual
Beth Israel Deaconess Medical Center Environment of Care Manual Title: Interim Life Safety Measures (ILSM) Plan Policy #: EC39 Purpose: ILSM are fully adhered to in areas where the hospital/site occupants
Fire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
EVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS. Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb.
EVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS By Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb. & Jason Rogers, Grad. Dip. (Fire Safety & Risk Eng.)VUT
2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination
2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal [email protected] Andrew M. Schneider, P.E. Senior Fire Protection Engineer [email protected] Questions Submit
New York City Department of Buildings
The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International
SMOKE ALARMS CLASS 1A BUILDINGS
SMOKE ALARMS CLASS 1A BUILDINGS A smoke alarm is a device that combines both smoke detection and alarm facilities into a single unit. Smoke alarms are required to be installed in all new residential Class
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Improving fire safety through engineering (rational designs)
Improving fire safety through engineering (rational designs) Johan van den Heever Fire Safety Indaba, Cape Town 2013 'Promoting responsible fire safety in Southern Africa' 1 Introduction What is fire safety
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
New Ontario Building Code Highlights
New Ontario Building Code Highlights Part 9 This summary highlights items that are believed to be significant changes to the 2012 OBC and is not intended to include all changes made within this or other
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
NFPA 101 2015 20 Frequently Asked Questions
February 2015 NFPA 101 2015 20 Frequently Asked Questions By Ron Coté, P.E. Ask an NFPA Expert The Technical Questions Service is free with your NFPA Membership. Our Technical Questions Service provides
build safe live safe
NYC Buildings Department 280 Broadway, New York, NY 10007 Robert D. LiMandri, Commissioner BUILDINGS BULLETIN 2012-009 Technical Supersedes: Issuer: None Thomas Fariello, R.A. First Deputy Commissioner
Facility Assessment for. 11801 East Main Street, Huntley, IL
Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested
17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
Sam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems
Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems usa.siemens.com/infrastructure-cities Share current and upcoming standards
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
NEW SCIENCE FIRE SAFETY ARTICLE INNOVATING FIRE ATTACK TACTICS SUMMER 2013 UL.COM/NEWSCIENCE
NEW SCIENCE FIRE SAFETY ARTICLE INNOVATING FIRE ATTACK TACTICS SUMMER 2013 UL.COM/NEWSCIENCE NEW SCIENCE FIRE SAFETY OVERVIEW UL s dedicated team of scientists, engineers and researchers is creating New
Amendments to the 2012 INTERNATIONAL FIRE CODE
Amendments to the 2012 INTERNATIONAL FIRE CODE 2012 Edition, International Fire Code. Section 101.1 Amend to read as follows. 101.1 Title. These regulations shall be known as the Fire Code of the City
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria
Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Development of Seismic-induced Fire Risk Assessment Method for a Building
Development of Seismic-induced Fire Risk Assessment Method for a Building AI SEKIZAWA National Research Institute of Fire and Disaster 3-14-1, Nakahara, Mitaka, Tokyo 181-8633, Japan [email protected]
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2
Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,
Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012
Medicine Hat Fire Department Special Event Requirements August 202 medicinehat.ca/fire The following is a standard guide for event organizers to ensure occupant safety and compliance with the Alberta Fire
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
Instructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance
Princeton Department of Emergency & Safety Services Instructions for Obtaining a Certificate of, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance 1. Obtain an application Download from /forms
Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
DCSS (ACB) Data Center Fire Suppression Procedures
May 18, 2015 DCSS (ACB) Data Center Fire Suppression Procedures Purpose: This document is intended for all individuals who have access to the data center at 1011 West Springfield Avenue, Advanced Computation
Building evacuation, rules and reality
Building evacuation, rules and reality Peter van de Leur DGMR Raadgevende Ingenieurs BV, Den Haag, the Netherlands The paper discusses some of the problems surrounding the simulation of the evacuation
Emergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
Code Compliance Guideline: Swimming Pool Chemicals
A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) HQS INSPECTIONS Part II Site Inspections 24 CFR 982.401 & 405 1si Rev. 4-20-06 General Conditions All doors and windows accessible to the outside, must have a workable lock.
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
2012 CODES SIGNIFICANT CHANGES 2012 IBC
2012 CODES SIGNIFICANT CHANGES 2012 IBC 1. Section 303.4 added language that includes commercial kitchens which are associated with restaurants, cafeterias, and similar dining facilities to be classified
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
Indiana Building Rehabilitation Standard
Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined