2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions Design Occupant Load Means of Egress Capacity Determination

Size: px
Start display at page:

Download "2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions. 1004.1 Design Occupant Load. 1005 - Means of Egress Capacity Determination"

Transcription

1 2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes Clay Aler, P.E. Principal Andrew M. Schneider, P.E. Senior Fire Protection Engineer Questions Submit questions in your Go To Webinar Question box Answers as time permits at the end Answers to all questions will be posted after the Webinar Koffel Associates, Inc. Expertly Engineering Safety From Fire Design Occupant Load ,Table Design Occupant Load- Areas without Fixed Seating Cumulative Occupant Loads Reformats the requirements previously located in and (Exiting from multiple levels) removed from (Egress convergence) moved to Table revised to include new terminology Occupant Load Factor (previously Floor Area in Sq. Ft. Per Occupant ) Occupant load factor for Exhibit gallery and museum added (30 net) Table Maximum Floor Area Allowances per Occupant - now includes Mall buildings - covered and open with a reference to Section where the occupant load for malls is addressed Means of Egress Capacity Determination has been broken down into multiple sections and is now Stairways Other egress components Capacity of the means of egress from any story cannot be reduced along the path of travel until termination at the public way Where more than 1 exit is required, loss of any 1 exit cannot reduce the available egress capacity to less than 50% of the required egress capacity Means of Egress Capacity Determination Reduced egress width factors for sprinklered buildings from 2000 through 2006 IBC reintroduced 0.2 inches per occupant for stairways 0.15 inches per occupant for other egress components Building must be equipped with automatic sprinkler system and emergency voice/alarm system Excludes Group H and I-2 occupancies 5 6 1

2 Accessible Means of Egress Accessible Means of Egress Interior exit access stairways and exterior areas of rescue assistance are now recognized as an accessible means of egress component ( ) Multiple modifications to Exterior areas for assisted rescue now permitted on stories above the level of exit discharge Stairways as part of MOE for exterior area for assisted rescue no longer require clear width of 48 inches between handrails in sprinkler protected buildings Revised separation requirements for exterior areas of assisted rescue ( ) Stairs in Accessible Means of Egress (1) The minimum 48 in. clear width. (2)* For stairs where egress is in the descending direction, a clear width of not less than 37 in. (940 mm), measured at and below handrail height, shall be permitted where all of the following are met: (a) An approved stair descent device is provided on each floor served by the stair. (b) Additional approved stair descent devices are provided on floors with an occupant load exceeding 200 at the ratio of one device per 200 occupants. (c) The required approved stair descent devices are provided in an approved location on the floor Evacuation Elevators 2009 Edition was Annex B Elevators for Occupant- Controlled Evacuation Prior to Phase I Emergency Recall Operations Now code requirements in 2012 Edition Fire Safety and Evacuation Plans Fire Safety and Evacuation Plans Addition: Reference to IFC and 404 for requirements regarding fire safety and evacuation plans IFC 404 requires plans in certain Group A, B, E, F, H, I, M, and R occupancies, high rise buildings, certain covered mall buildings and buildings with an atrium EXIT

3 Access-Controlled Egress Doors Relocated from to clarify it is a different kind of locking mechanism, not a different kind of door Mag Locks on Egress Doors Egress doors which require panic hardware are now permitted to be equipped with electromagnetic locks Panic hardware must be listed for use in the release of electromagnetic locks Operation of listed hardware must directly interrupt the power to the electromagnet (ensures compliance with single operation requirements of ) Special Locking Arrangements (5) Delayed-Egress Locking Systems The egress side of doors equipped with delayed-egress locks shall be provided with emergency lighting in accordance with Section (7) Access-Controlled Egress Door Assemblies The egress side of access-controlled egress doors, other than existing access-controlled egress doors, shall be provided with emergency lighting in accordance with Section Two Releasing Operations for Existing Hardware Two releasing operations shall be permitted for existing hardware on a door leaf serving an area having an occupant load not exceeding 3, provided releasing does not require simultaneous operations Smoke Barrier Doors Latching hardware shall be required on doors in smoke barriers, unless specifically exempted by Chapters 11 through Inspection of Door Openings Where required by the occupancy chapters, the following doors must be inspected and tested not less than annually: Panic hardware or fire exit hardware Exit enclosures Electrically controlled Special locking arrangements

4 Exit Discharge Number of Means of Egress Stairs and ramps that continue more than onehalf story beyond the level of discharge shall be provided with an approved means to prevent or dissuade occupants from traveling past the level of discharge during emergency building evacuation. A Section 7.4 requires a minimum number of means of egress Several occupancy chapters establish not only the minimum number of means of egress but also the minimum number of actual exits that must be provided on each floor Stairways 1012 Handrails Interior Exit Stairways Conventional exit stair enclosures required for travel distance or # of exit requirements Exit Access Stairways Groups unenclosed stairs formerly located in exceptions and exceptions Open parking garage stairs and ramps Outdoor facility stairs Technical production area stairs Balcony and mezzanine stairs Group I-3 stairs Stairs protected by draft curtains and closely spaced sprinklers Atrium stairs exception Allows transition pieces in continuous handrails to exceed the maximum permitted handrail height now clarifies that intermediate rails do not reduce egress width , Guards at Operable Windows Guard Height Guard requirements for operable windows with sill height > 72 inches above finished grade relocated from Ch. 14 to Ch. 10 Minimum window sill height at which a guard is not required has been increased from 24 to 36 inches Operable sections of windows shall not permit openings that allow passage of a 4-inch diameter sphere where such openings are located within 36 inches of the finished floor See for exceptions Window opening control devices required to comply with ASTM F Modified exception for minimum required guard height for Group R-3 occupancies and within individual R-2 dwelling units Decreased from 42 to 36 inches (to be consistent with the IRC) Occupancy must not be more than three stories above grade in height 24 4

5 Floor Level Exit Signs in Group R-1 Addition: Where exit signs are required in Group R-1 occupancies by , additional low level exit signs are now required in means of egress serving guest rooms Provide additional safety for occupants and fire fighters not familiar with surroundings when smoke layer develops and obscures normal-use exit signs Bottom shall be between 10 and 12 inches above floor Flush mounted to door or wall If mounted on wall, edge of sign must be within 4 inches of door frame on latch side Automatic Motion Sensor Lighting-Type Switches Unless prohibited by Chapters 11 through 43, automatic motion sensor type lighting switches shall be permitted within the means of egress, provided that the switch controllers comply with all of the following: (1) the switch controllers are listed (2) the switch controllers are equipped for fail-safe operation and evaluated for this purpose (3) the illumination timers are set for a minimum 15-minute duration (4) the motion sensor is activated by any occupant movement in the area served by the lighting units (5) the switch controller is activated by activation of the building fire alarm system, if provided Energy Saving Lighting * - Energy saving sensors, switches, timers or controllers shall be approved and shall not compromise the continuity of illumination of the means of egress required by A A consideration for the approval of automatic, motion-sensor type lighting switches, controls, timers or controllers is whether the equipment is listed as a fail-safe device for use in the means of egress Photoluminescent Markings Addresses photoluminescent markings in stair enclosures. Numerous changes for this edition. Still how to do it not where to do it. Manufacturers are telling people it is mandated. Similar to mandatory provisions set by local law in NYC Corridor Continuity Clarification that where the path of travel within fire-resistance-rated corridors to an exit includes travel along unenclosed exit access stairways or ramps, the fire-resistance rating must be continuous for the length of the stair or ramp until the exit & Egress Balconies and Exterior Exit Stairways and Ramps New requirement that exterior egress balconies, exit stairways and ramps be located > 10 ft from lot lines and other buildings on the same lot unless the exposing building exterior walls and openings are protected per

6 Exits from Stories Exits now permitted to be arranged where they serve a portion of a story instead of all occupants on that floor Must meet the following: Number of exits from story complies with Access to exits from each individual space in the story complies with All spaces within each portion of a story must have access to the min. number of approved exits based on O.L of that portion, but not less than two exits Exits from Mixed Occupancy Buildings Added a ratio equation used to determine if a single exit is allowed to serve the combined occupant load from multiple occupancies in a mixed occupancy building. If the sum of the ratios of the calculated number of occupants of the space divided by the allowable number of occupants for each occupancy is 1, a single exit is permitted , Table (1) - Exits from Dwelling Units & Enclosure Penetrations of Interior Exit Stairways and Exit Passageways Penetrations of fire barriers enclosing an interior exit stair or ramp or exit passageway now permitted in exterior membrane Penetrations must be properly protected in accordance with the membrane penetration provisions of Separation of Spaces under Grandstands and Bleachers Addition: If space underneath grandstands or bleachers is used for purposes other than ticket booths < 100 ft2 and toilet rooms, the space must be separated by fire barriers Barriers must comply with 711 and have at least 1-hour fireresistance-rated 35 construction Aisle Accessways Serving Seating at Tables Relocated provisions of Now all aisle and aisle accessway requirements for assembly spaces are located in

7 419, Live/Work Units Definition of Live/Work unit added to 202 Means of egress components ( 419.3) now designed in accordance with Ch. 10 based on function of residential space Plumbing facilities ( 419.9) in accordance with Ch. 29 based on the function of the nonresidential space Mezzanine Means of Egress Modification: Specific mezzanine means of egress provisions have been removed Replaced with a general reference to Ch. 10 Mezzanines must now comply with general means of egress provisions Incidental Uses - General Replaced incidental accessory occupancies with concept of incidental uses Removes relationship with mixed-occupancy provisions Incidental uses - functional extensions of a primary use which generally pose a greater level of risk to that occupancy ( 509.1) All uses listed in Table 509 Classified the same as the building occupancy in which they reside (no longer permitted to be classified as unique occupancy groups) ( 509.2) Shall not occupy > 10% of the building area of the story in which they are located (based on floor area of individual tenant space in the case of multiple tenants per floor) ( 509.3) & Normally Unoccupied Support Areas / * - Normally Unoccupied Building Service Equipment Support Area. A building service equipment support area in which people are not expected to be present on a regular basis Normally Unoccupied Equipment Areas Normally Unoccupied Support Areas Access/Egress Normally Unoccupied Building Service Equipment Support Areas * - Hazard of Contents Unless prohibited by Chapters 11 through 43, the provisions of Section 7.13 shall apply in lieu of the provisions of Section 7.1 through Section 7.12 to normally unoccupied building service equipment support areas, where such areas do not contain high hazard contents or operations. No Sprinkler Protection Sprinkler Protection < 45,000 sq ft 45,000 sq ft 90,000 sq ft Access Panel Doors Per Doors Per Access Panel Access Panel Doors Per

8 Normally Unoccupied Equipment Areas Egress Doors * - Egress from normally unoccupied building service equipment support areas shall be provided by doors complying with where the normally unoccupied building service equipment support area exceeds 45,000 ft2 in buildings not protected throughout by an approved, supervised automatic sprinkler system A Egress from normally unoccupied building service equipment support areas not exceeding 45,000 ft2 is permitted to be by access panels or other hardware not complying with the door requirements of Normally Unoccupied Equipment Areas Egress from normally unoccupied building service equipment support areas shall be provided by doors complying with where the normally unoccupied building service equipment support area exceeds 90,000 ft 2 in buildings protected throughout by an approved, supervised automatic sprinkler system The absence of sprinklers in the normally unoccupied building service equipment support area as permitted by an exemption of NFPA 13, shall not cause the building to be classified as nonsprinklered for the purposes of applying Normally Unoccupied Equipment Areas , Technical Production Area Terminology Means of Egress Path Width Head Room Exit Signage Illumination Number of Means of Egress Outdated terminology replaced Replaced fly gallery, gridiron, and pinrail with the all inclusive technical production area Means of Egress for stages and technical production areas moved to Day Care Means of Egress New section requiring a second means of egress for rooms or spaces providing care for more than 10 children (2 ½ years or younger) Group I-2 Means of Egress Group I-2 Exit Access Requirements ( ) moved to The requirements are essentially unchanged

9 Health Care Corridors Stored or Parked? (4)(c)i* Projections into the required width shall be permitted for wheeled equipment in use and carts in use. (4)(c)ii* Projections into the required width shall be permitted for wheeled medical emergency equipment not in use. (5)* Where the corridor width is at least 8 ft, projections into the required width shall be permitted for fixed furniture provided that all of the following conditions are met: (a) The furniture is securely attached to the floor or to the wall. (b) The fixed furniture does not reduce the clear unobstructed corridor width to less than 6 ft except as permitted by (2) and (3). (c) The fixed furniture is located only on one side of the corridor (d) The fixed furniture is grouped such that each grouping does not exceed an area of 50 sq ft (e) The fixed furniture groupings addressed in (7)(d) are separated from each other by a distance of at least 10 ft. (f)* The fixed furniture is located so as to not obstruct access to building service and fire protection equipment. (g) Corridors throughout the smoke compartment are protected by an electrically supervised automatic smoke detection system / Suite Intervening Rooms 18/ Sleeping Suite Arrangement. (A)* Occupants of habitable rooms within sleeping suites shall have exit access to a corridor complying with without having to pass through more than one intervening room. 18/ Suite Intervening Rooms 18/ * - Non-Sleeping Suite Arrangement. Occupants of habitable rooms within non-sleeping suites shall have exit access to a corridor complying with 18/ without having to pass through more than two intervening rooms. 18/ Non-Sleeping Suite Travel Distance. (A) Travel distance within a non-sleeping suite to an exit access door from the suite shall not exceed 100 ft. the following: (1) 100 ft where the suite is arranged with one intervening room (2) 50 ft where the suite is arranged with two intervening rooms Employee Work Areas Accessible Units in R- 1 Occupancies Maximum size of employee work areas exempt from requirement that commonuse circulation paths within work areas meet accessibility route requirements has been increased from 300 ft2 to 1000 ft2 Common use circulation path defined by permanently installed partitions, counters, casework, or furnishings New requirement consistent with ADA Guidelines 53 Modification: Not every element within or serving an Accessible unit has to be accessible Only one full bathroom need be accessible where multiple bathrooms are provided Where multiple family or assisted bathrooms serve a unit, at least 50% but not less than one room for each use at each cluster shall be accessible 5%, but not less than one bed shall be accessible 54 9

10 1109.2, Accessible Children s Facilities Added exceptions to allow for toilet facilities and drinking fountains to be designed using size provisions found in ICC A Can be installed at a lower height (30 inches for water fountains) and still be considered accessible Accessible Saunas and Steam Rooms Saunas and steam rooms now required to be accessible Exception: where saunas or steam rooms are clustered at a single location, at least 5% of the saunas and steam rooms but not less than one of each type in the cluster shall be accessible Added to ensure compliance with A117.1 technical requirements Variable Message Signs Variable message signs used in transportation facilities and emergency shelters now required to comply with A VMS signs not required in emergency shelters where equivalent information is provided in an audible manner (see exception to Minimum Kitchen Floor Area Minimum floor area requirement of 50 ft2 for kitchens has been removed Size limitation had no relation to life safety or health concerns still requires at least 3 ft of clearance between counter fronts and appliances or walls Toilet and Bathroom Requirements addressing water closet compartments relocated to addressing urinal partitions relocated to Term service sinks added to intended to protect walls and floors adjacent to plumbing fixtures from damage and decay 59 Questions and Discussion Expertly Engineering Safety From Fire 60 10

11 Future Questions. Upcoming Webinars Join our LinkedIn Discussion Groups Life Safety Code People can join the group and submit their questions or People can and submit anonymously Smoke Management Proposed Changes to the IBC Ask the Expert FAQ.Koffel.com Go to webinars.koffel.com for more information Following our webinars you will receive a link for a survey. At the end of the survey is a link for a copy of the presentation Thank You Clay Aler, P.E. Principal caler@koffel.com Andrew M. Schneider, P.E. Senior Fire Protection aschneider@koffel.com Follow us on LinkedIn Expertly Engineering Safety From Fire 11

NFPA 101 2012 SELECT SIGNIFICANT CHANGES

NFPA 101 2012 SELECT SIGNIFICANT CHANGES NFPA 101 2012 SELECT SIGNIFICANT CHANGES William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire INTRODUCTION NFPA 101 is

More information

New York City Department of Buildings

New York City Department of Buildings The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International

More information

5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.

5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness. NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure

More information

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44

More information

Errata has been identified as follows:

Errata has been identified as follows: 2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i

2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i 2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i Changes between the 2006 and 2009 Editions of the International Codes account for the vast majority of changes to the 2010 Florida Building Code. In many

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

New York City Department of Buildings

New York City Department of Buildings The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright

More information

The replacement or modification of existing windows shall comply with the following requirements:

The replacement or modification of existing windows shall comply with the following requirements: City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Building Codes Update: The 2009 International Fire Code and the Apartment Industry ! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION BC 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

CHAPTER 10 MEANS OF EGRESS. User Note: See Preface page iv ("marginal markings" for Chapter 10 reorganization information.)

CHAPTER 10 MEANS OF EGRESS. User Note: See Preface page iv (marginal markings for Chapter 10 reorganization information.) CHAPTER 10 MEANS OF EGRESS User Note: See Preface page iv ("marginal markings" for Chapter 10 reorganization information.) SECTION 1001 GENERAL 1001.1 Scope. Buildings or portions thereof shall be provided

More information

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes. 1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS

FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building

More information

Classroom Door Security & Locking Hardware

Classroom Door Security & Locking Hardware Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have

More information

Errata NFPA 1. Fire Code. 2015 Edition

Errata NFPA 1. Fire Code. 2015 Edition Errata NFPA 1 Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1

More information

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,

More information

CHAPTER 29 PLUMBING SYSTEMS

CHAPTER 29 PLUMBING SYSTEMS CHAPTER 29 SYSTEMS Note: The amendments to Chapter 29 are different than the 2009 Seattle Building Code and are not marked with margin bars or arrows. SECTION 2901 GENERAL [P] 2901.1 Scope. The provisions

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT SINCERE KNIT GARMENTS LTD UNIT-1 EAST ISDAIR, CHANDMARI, FATULLAH OTHER FACTORIES: FAKIR KNIT LTD. July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

Healthcare Engineering. Code Summary Report

Healthcare Engineering. Code Summary Report American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

http://www.iccsafe.org/

http://www.iccsafe.org/ Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the

More information

2. Farm buildings located outside the building rules jurisdiction of any municipality.

2. Farm buildings located outside the building rules jurisdiction of any municipality. 101.1 Title. These regulations shall be known as the North Carolina Building Code as adopted by the NC Carolina Building Code Council on September 14, 2010 to be effective September 1, 2011. References

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

Code Requirements for Existing Buildings

Code Requirements for Existing Buildings Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)

More information

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix

More information

17,280 square feet Overview:

17,280 square feet Overview: CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The

More information

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us

More information

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS Page 25 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

NFPA 101 2015 20 Frequently Asked Questions

NFPA 101 2015 20 Frequently Asked Questions February 2015 NFPA 101 2015 20 Frequently Asked Questions By Ron Coté, P.E. Ask an NFPA Expert The Technical Questions Service is free with your NFPA Membership. Our Technical Questions Service provides

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

Number of Sides Required to Have a Handrail

Number of Sides Required to Have a Handrail Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT 2009 AMENDMENT

STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT 2009 AMENDMENT STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT 2009 AMENDMENT Sec. 29-252-1d. State Building Code 2009 Amendment to the 2005 Connecticut Supplement The 2003 International Building Code, 2003 International

More information

CITY OF TORONTO. BY-LAW No. 349-2008

CITY OF TORONTO. BY-LAW No. 349-2008 Authority: Licensing and Standards Committee Item 12.3, adopted as amended, by City of Toronto Council on April 28 and 29, 2008 Enacted by Council: April 29, 2008 CITY OF TORONTO BY-LAW No. 349-2008 To

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 STAIRWAYS 46. LANDINGS. Section R311 IRC 2009 R311.7.5 Landings for stairways. There shall be a floor or

More information

2012 CODES SIGNIFICANT CHANGES 2012 IBC

2012 CODES SIGNIFICANT CHANGES 2012 IBC 2012 CODES SIGNIFICANT CHANGES 2012 IBC 1. Section 303.4 added language that includes commercial kitchens which are associated with restaurants, cafeterias, and similar dining facilities to be classified

More information

New Ontario Building Code Highlights

New Ontario Building Code Highlights New Ontario Building Code Highlights Part 9 This summary highlights items that are believed to be significant changes to the 2012 OBC and is not intended to include all changes made within this or other

More information

Fire Alarm Systems Requirements by Occupancy Type

Fire Alarm Systems Requirements by Occupancy Type WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building

More information

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch

More information

Page 1 of 6 COMPLIANCE CHECKLIST. > Long Term Care Facility - Nursing Unit

Page 1 of 6 COMPLIANCE CHECKLIST. > Long Term Care Facility - Nursing Unit COMPLIANCE CHECKLIST Page 1 of 6 > Long Term Care Facility - Nursing Unit The following checklist is for plan review of new long-term care facilities and new additions to existing long-term care facilities.

More information

I N T E R N A T I O N A L R E S I D E N T I A L CO D E

I N T E R N A T I O N A L R E S I D E N T I A L CO D E Visual Interpretation Of The I N T E R N A T I O N A L R E S I D E N T I A L CO D E 2006 STAIR BUILDING CODE Portions of this document reproduce sections from the 2006 International Residential Code, International

More information

2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS

2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS 2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS IBC CODE DESIGN CHECKLIST (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Transfer the resulting data on the building plans Life Safety & Building

More information

American Academy of Physical Medicine and Rehabilitation Site Survey Report

American Academy of Physical Medicine and Rehabilitation Site Survey Report American Academy of Physical Medicine and Rehabilitation Site Survey Report Introduction and Background In early 2013, the Contract Meeting Manager for the American Academy of Physical Medicine and Rehabilitation

More information

Harris County Fire Code Electronic Lock Procedures

Harris County Fire Code Electronic Lock Procedures Harris County Fire Code Electronic Lock Procedures Based on the current adopted edition of the International Building & Fire Code with Harris County Amendments For New Electronic Locking Systems March

More information

Common ADA Errors and Omissions in New Construction and Alterations

Common ADA Errors and Omissions in New Construction and Alterations U.S. Department of Justice Civil Rights Division Disability Rights Section Common ADA Errors and Omissions in New Construction and Alterations Introduction The ADA requires that new construction and alterations

More information

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable

More information

ACCESSIBILITY CHAPTER 11

ACCESSIBILITY CHAPTER 11 CHAPTER 11 ACCESSIBILITY SECTION 1101 GENERAL 1101.1 Scope. The provisions of this chapter shall control the design and construction of facilities for accessibility to physically disabled persons. 1101.2

More information

Chapter 3: Use and Occupancy Classification

Chapter 3: Use and Occupancy Classification Chapter 3: Use and Occupancy Classification General Comments Chapter 3 provides for the classification of buildings, structures and parts thereof based on the purpose or purposes for which they are used.

More information

2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101

2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101 2012 Changes of the International Building Code Compared to the National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope of

More information

ADA Scoping: New Construction

ADA Scoping: New Construction U. S. A CCESS B O A R D T E C H N I C A L G U I D E ADA Scoping: This guide provides an introduction to the scoping requirements that form the basis for the Department of Justice s 2010 ADA Standards and

More information

Single Family Residential Basement Finish

Single Family Residential Basement Finish How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete

More information

CHILD CARE CENTER INFORMATION SHEET

CHILD CARE CENTER INFORMATION SHEET CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.

R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose. R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The

More information

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

Property Maintenance Check List

Property Maintenance Check List Property Maintenance Check List Scope These minimum conditions and responsibilities of persons for maintenance of structures, equipment and exterior property shall govern. Responsibility. Owners shall

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

Minimum Housing and Health Standards

Minimum Housing and Health Standards APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).

More information

The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services

The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts

More information

The 60 minute Fire Rated Application Explained

The 60 minute Fire Rated Application Explained The 60 minute Fire Rated Application Explained One of the most confusing aspects of the code is the 60 minute fire rated application, and its easy to see why based on the questions that come up: Is 60

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.

9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards. Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and

More information

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms

More information

CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov

CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.

More information

ACCESSIBILITY CHAPTER 11

ACCESSIBILITY CHAPTER 11 CHAPTER 11 ACCESSIBILITY SECTION BC 1101 GENERAL 1101.1 Scope. The provisions of this chapter and Appendices E, N and P shall control the design and construction of facilities for accessibility to persons

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014

Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014 TOWNSHIP OF HILLSBOROUGH COUNTY OF SOMERSET Hillsborough Township Municipal Complex The Peter J. Biondi Building 379 South Branch Road Hillsborough, NJ 08844 P: (908) 369-4313 F: (908) 369-3954 Building

More information

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS CITY OF BLAINE SAFETY SERVICES Fire Inspections 10801 Town Square Drive Blaine MN 55449 Business Phone 763-785-6187 Fax 763-717-2634 City of Blaine Fire Prevention Inspection Policy FIRE SPRINKLERS IN

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire

More information

FIRE PROTECTION IN THE 2008 NEW YORK CITY BUILDING CODE

FIRE PROTECTION IN THE 2008 NEW YORK CITY BUILDING CODE FIRE PROTECTION IN THE 2008 NEW YORK CITY BUILDING CODE New York Society of Architects 24 January 2008 Presented by Joseph Razza, PE Rolf Jensen & Associates, Inc. John Lee, RA NYC Department of Buildings

More information

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1 Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers

More information

Health Care Facilities

Health Care Facilities Health Care Facilities CHAPTER 25 Joseph M. Jardin A large Illinois hospital undergoing a sprinkler retrofit quickly discovered the benefits of upgrading its system when sprinklers confined a fire caused

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

Practice Note 2006-27

Practice Note 2006-27 Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two

More information

Common ADA Errors and Omissions in New Construction and Alterations

Common ADA Errors and Omissions in New Construction and Alterations Common ADA Errors and Omissions in New Construction and Alterations Learning Objectives Course Number: 6002 Credit Hours: 1 After completing this course you will have a better understanding of numerous

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards

More information