DCSS (ACB) Data Center Fire Suppression Procedures
|
|
|
- Jane Riley
- 10 years ago
- Views:
Transcription
1 May 18, 2015 DCSS (ACB) Data Center Fire Suppression Procedures Purpose: This document is intended for all individuals who have access to the data center at 1011 West Springfield Avenue, Advanced Computation Building. The objective is to provide education about the fire suppression components and fire safety instructions for the Advanced Computation Building. The fire safety instructions should be followed by all personnel in the event a fire breaks out or smoke is evident in the data center. If the smoke alarm is activated it is strongly recommended that everyone leave the data center immediately and exit the building. The four stage VESDA fire suppression system does not activate the fire suppression sprinkler system until it reaches stage four. System Details: The fire suppression system at the Advanced Computation Building 2 nd floor Data Center is a VESDA (Very Early Smoke Detections Apparatus) system. This unit protects the data center (room 200) and the staging area (room 202) from fire by sampling the quality of the air in the rooms. The sprinkler system is set up in zones so that the VESDA system will target the effected location of the fire without activating all the sprinklers within the room. The VESDA system monitors the area for chemicals in the air indicative of smoke or fire by capturing air samples through the cone shaped fixtures that are in the ceiling tiles of rooms 200 and 202 and in the sub-floor and return air in room 200. Once initiated the VESDA system begins a countdown before activating the fire extinguishing process. When the VESDA system is activated the audible fire alarm will sound, associated strobe light will flash and UIUC Public Safety and Urbana Fire Department will be notified. All personnel should evacuate the area immediately when the fire alarm sounds. In order to contain the fire, the sliding door will drop down from the ceiling to block the glass wall on the West side of the data center. Once the room is contained, the sprinkler system for the zone where the fire/smoke has been detected will be activated. 1 P a g e
2 The equipment in the zone where the sprinkler system is activated may sustain substantial water damage while the fire is being extinguished. All other equipment outside the zone where the sprinkler system was activated should not be effected. Personnel in the room are at risk of electrical shock if power to the room is not properly discontinued before the sprinkler system is activated to extinguish the fire. At the time of this writing, the material used for some of the power cords is not plenum grade and therefore is toxic when burned. Inhalation of the toxic fumes can overwhelm the respiratory system causing unconsciousness and suffocation. The smoke alarm system can be activated manually by pulling down the arm on any of the fire alarm units found in the area. The RED buttons found in an enclosed case throughout room 200 can be used to immediately kill all power to the room in the event a fire has started and evacuation is in progress. Evacuation Procedure: At the first sign of a fire in the data center, exit the building immediately. When the audible alarms and strobe lights flash the UIUC Public Safety Office and the Urbana Fire Department are notified. Use the following exits to escape the data center and leave the building: North East door will take you down the staircase to an EXIT door, the West door will allow you to exit to room 202 where you can exit the building using any staircase. Call UIUC Public Safety immediately at 911 once you re in a safe location. Do not re-enter the building until the fire department has given the all clear. DCSS Data Center Fire Suppression Procedures and Location of VESDA Units 2 P a g e
3 The VESDA system monitors three areas on the 2 nd floor data center room 200: subfloor, ceiling and return air vent and the ceiling of room 202. The control panels for room 200 are located in the basement mechanical area just off the loading dock and in the janitor closet in room 202 for room 202. These systems monitor air samples from the designated locations for particles in the air signaling smoke or fire is present. These systems will activate the fire extinguishing sprinkler system and automatically notify UIUC Public Safety and Urbana Fire Department in the event there is fire or smoke present. There are four stages to the Vesda monitoring system: Alert, Action, Fire 1 and Fire 2. During all four stages the gauge on the VESDA system will visually reflect the escalation of fire and smoke in the area being monitored. Stage One (Alert) In stage one the system has detected incipient smoke that is invisible to the human eye and the Alert indicator on the Vesda system monitoring the area where smoke is indicated will be activated. No smoke alarms or notifications are activated during this stage. Stage Two (Action) During stage two smoke is visible in the area where detected by the VESDA system and the Action indicator is illuminated on the VESDA unit monitoring the area where smoke is detected. The audible smoke alarm and strobe lights are activated requiring immediate evacuation of the area. UIUC Public Safety and Urbana Fire Department are notified of a fire in the room. Stage Three (Fire 1) Fire 1 is the stage where a flaming fire is identified. If the fire is not extinguished the fire suppression system will be activated when stage four is reached. Stage Four (Fire 2) When this stage is reached, the fire suppression system will activate the sprinkler system for the affected zone in the area where fire and intense heat have been identified. 3 P a g e
4 In the event of a fire the smoke alarm system can be activated manually by pulling down the arm on any of the fire alarm units found in the area. In the event fire evacuation is in progress the RED buttons found in the enclosed case can be used to immediately kill all power to room 200. Cold Aisle Containment The metal brackets on the cold aisle containment curtains will melt under high temperatures. The curtain material is connected to the frame with hooks that will melt and release the curtain at 130 degrees. The fire suppression system activates at 165 degrees so the curtain will not cause any obstruction to the fire suppression. Routine Maintenance All VESDA units are evaluated annually by F&S. A chemical is sprayed into the sensor in order to simulate a fire and the VESDA unit is monitored to verify the chemical is detected and functions appropriately. They also check the backup batteries that are housed in each VESDA unit and replace them as needed. UIUC Facilities Management Phone Numbers for notification Emergency dial 911 UIUC F&S (Shop 25) (217) UIUC Public Safety (217) P a g e
5 DCSS On-call (217) P a g e
DCSS (DCL) Data Center Fire Suppression Procedures
May 18, 2015 DCSS (DCL) Data Center Fire Suppression Procedures Summary: This document is intended for personnel who have access to the data center in DCL. The objective is to provide an awareness of the
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
FIRE AND LIFE SAFETY TRAINING
FIRE AND LIFE SAFETY TRAINING 1 Objectives General Information Emergency Evacuation Plans / Regulatory Requirements Notification Systems Emergency Exits and Fire Doors Electrical Safety Fire Prevention
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
Workplace Fire Safety
Teaching Guide Workplace Fire Safety for staff Seattle Fire Department Fire Prevention Division Workplace Fire Safety Instructor Outline Introduction Goals: To ensure that employees are knowledgeable in
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES
SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES "Chime" Digit 1 "Partial Arm" Digit 2 "Quick Arm" Digit 3 ENTRY / EXIT DELAY TIMES Exit Delay Time Entry Delay Time Secondary
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
Fire Response Plan - Code Red
Fire Response Plan - Code Red SUMMARY & PURPOSE The purpose of the Fire Response Plan Code Red is to provide guidelines for hospital personnel to follow during a Code Red. As more fully described below,
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
NY Fire Safety Institute
NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing
ESTABLISHMENT OF A NEW BUSINESS
ESTABLISHMENT OF A NEW BUSINESS ATTENTION BUSINESS OWNERS Certificate of Occupancy Permit Requirements & Application Prior to any materials associated with your business being moved into the property that
SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Area 1 Area 2 Area 3 AREA LISTINGS SPECIAL CODES "Quick Arm" Digit "Partial Arm" Digit "Chime" Digit ENTRY / EXIT DELAY TIMES Exit Delay
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18
INHEP DIGITAL IDS S E C U R I T Y Users Guide to Keypad Functions MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Away Arm Stay
SPECIAL CODES AUXILIARY CODES SYSTEM NOTES
Installing/Service Company Monitoring Center SPECIAL CODES Master Code Duress Code AUXILIARY CODES "Quick Arm" " Chime" 08 02 09 03 10 04 11 05 12 06 13 07 14 SYSTEM NOTES Exit Delay Time Entry Delay Time
Users Guide to Keypad Functions
Users Guide to Keypad Functions MANUAL NO. 700-175-01J ISSUED JAN 2002 VERSION 1.41 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Panic Fire Medical Away Arm Stay Arm Stay Arm &
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
EMERGENCY RESPONSE PROCEDURE
EMERGENCY RESPONSE PROCEDURE 1. Introduction The Office of the Information Commissioner (the Office) Emergency Response Procedure has been designed to ensure the safety of all staff and visitors to the
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
How To Evacuate The University Of California Building
University of California Washington Center Emergency Evacuation Plan UC Washington Center 1608 Rhode Island Ave., NW Washington, DC 20036 Revised February 16, 2012 I. Purpose of the Plan II. Building Description
2015 Annual Fire Safety Report
2015 Annual Fire Safety Report The Higher Education Opportunity Act enacted on Aug. 14, 2008, requires institutions that maintain on-campus housing facilities to publish an annual fire safety report that
SECURITY SYSTEM NOTES SPECIAL CODES. Security System Configuration
Installing / Service Company: SECURITY SYSTEM NOTES For Service Call: Master Code SPECIAL CODES Duress Code Security System Configuration Auxiliary Code(s) Quick Arm" Digit: 2 9 3 10 4 11 5 12 6 13 7 14
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
NetworX NX-6V2. LED Keypad User Manual
NetworX NX-6V2 LED Keypad User Manual POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
North York General Hospital Policy Manual
Page 1 of 6 POLICY STATEMENT North York General Hospital staff is responsible to follow the guidelines outlined in this document in the event of a fire to minimize injury and/or damage. DEFINITIONS Code
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
TABLE OF CONTENTS HOW TO AVOID FALSE ALARMS... 2
TABLE OF CONTENTS HOW TO AVOID FALSE ALARMS... 2 THE BRINK S HOME SECURITY SYSTEM Equipment in the Standard Systems... 3 Optional Equipment... 4 Optional Features... 5 Description of the Keypad... 6 OPERATING
SAN FRANCISCO EMERGENCY INFORMATION. San Francisco Marriott Marquis. 780 Mission St. San Francisco CA 94103 T 415-896-1600, F 415-486-8101,
SAN FRANCISCO EMERGENCY INFORMATION San Francisco Marriott Marquis 780 Mission St. San Francisco CA 94103 T 415-896-1600, F 415-486-8101, Table of Contents Building Description 4 Building Life Safety Features
Residential Fire Safety Policies
Residential Fire Safety Policies Introduction University Housing and Campus Code Compliance and Fire Safety at the City University of New York at Queens College in compliance with the Higher Education
SECURITY SYSTEM NOTES
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function This system is is not partitioned. EMERGENCY ACTIVATION KEYS
NOTE: The home screen always displays the day and month, time, & P1 (Partition 1)
GE Concord 4 System NOTE: The home screen always displays the day and month, time, & P1 (Partition 1) STAY AWAY DISARM The Asterisk key on your user interface pad is the most commonly used key. This is
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
SECURITY SYSTEM NOTES. Security System Configuration
Installing / Service Company: For Service Call: SECURITY SYSTEM NOTES Security System Configuration Master Code: Auxiliary Code(s) 2 3 4 5 6 "Quick Arm" Digit: Exit Delay Time Auxiliary Exit Delay Time
SECURITY SYSTEM NOTES
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary
Hotel Fire Safety for staff
Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in
OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety
OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor
SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Installation Date / / Central Station Duress Code EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary Emergency Police PROGRAMMED
DOMESTIC SMOKE ALARMS
SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE
USER INSTRUCTIONS CONTENTS
CONTENTS Full Set [1]...2 Part Set [2]...2 Night Set [3]...3 Unsetting...3 Unsetting after or during an alarm...3 Testing the system [5]...3 Isolating zones [6]...4 Reprogramming codes [8]...4 Chime facility
SECURITY SYSTEM NOTES SPECIAL CODES AUXILIARY ARM / DISARM CODES ENTRY / EXIT DELAY TIMES ZONE DESCRIPTIONS
SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES Master Code Duress Code "Quick Arm" Digit "Chime" Digit "Entry-Guard" Digit AUXILIARY ARM / DISARM CODES 02 12 22 03 13 23
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
Smoke Alarms Save Lives!
Smoke Alarms Save Lives! Every year in America, almost 3000 people die in home fires. Most of these people die in homes that do not have working smoke alarms in them. Smoke alarms warn you and your family
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
TABLE OF CONTENTS HOW TO AVOID FALSE ALARMS... 1
TABLE OF CONTENTS HOW TO AVOID FALSE ALARMS... 1 THE BRINK S HOME SECURITY SYSTEM Equipment in the Standard Systems... 2 Optional Equipment... 3 Description of the Keypad... 5 OPERATING THE BRINK S SYSTEM
St. John s University Fire Safety Plan
St. John s University Fire Safety Plan Flynn Hall St. John s University Fire Safety Plan Part 1-Building Information Section Flynn Hall 300 Howard Ave. Staten Island, N.Y. 10301 Fire Safety Director: Address:
PhoneWatch Smart Security System User Manual - Domonial
PW0002 10/13 Customer Support: 1850 753 753 PhoneWatch Ltd., Unit 3/4, Sandyford Park, Burton Hall Rd, Sandyford Industrial Estate, Dublin 18. Email: [email protected] PhoneWatch Smart Security System
Print Shop/Mail Room
Chapter XVIII Print Shop/Mail Room Page 110 CHAPTER XVIII Print Shop/Mail Room ARCHITECTURAL/STRUCTURAL A. BUILDING EXTERIOR 1.0 EXTERIOR WALLS The exterior walls are comprised of stone veneer. There were
The Johns Hopkins Hospital and The Johns Hopkins University Health, Safety and Environment Manual Fire Safety:
Page 1 of 10 Keywords: Emergency Room, Evacuation, Evacuation Plans, Fire, Fire Incident Responsibilities, Fire Safety, Gas Shutoff, Inpatient Area, Intensive Care, JHH Fire Incident Responsibilities,
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
Ionization alarms are best suited for rooms, which contain highly combustible material. These types of material include:
Smoke Detector University Most people are aware of the danger of fire but are unaware of the fatality of smoke. More people die from breathing smoke than by burns. In fact, deaths from smoke inhalation
GE Concord 4 Quick User Guide
GE Concord 4 Quick User Guide GE Concord 4 Quick User Guide Page 1 Before Calling Is the keypad beeping? Press *. This will silence the beeping and let you know where the trouble is. Is there a flashing
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Emergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
CANTON FIRE DEPARTMENT
CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
Fire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 [email protected] Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
Environment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
User s Guide. Security Systems D220
User s Guide Security Systems D220 Table of Contents About This User s Guide... 3 Introduction... 3 Security System Basics... 4 Controlled Points... 5 24-Hour Points... 6 Keypad Keys... 6 Keypad Lights...
IFE Level 4 Certificate in Fire Science and Fire Safety (HL)
IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June
Consumer Information. FCC Notice
Consumer Information FCC Notice This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
Understanding Alarm Systems
Understanding Alarm Systems A false alarm occurs when an alarm signal designed to elicit an immediate emergency Law Enforcement, Fire, or Medical response is activated, when in fact no emergency exists.
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building
Fire Standards & Regulations Are you confused?
Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm
Quality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Generator fire up Generator 1 hour load test Generator 4 hour load test Fire extinguisher integrity checks Fire extinguisher certification Fire drills Fire door integrity Fire signage lighting Fire alarm
Standard Message Library
Standard Message Library ALERT AL1 AL2 AL3 AL4 AL5 AL6 AL7 AL8 This is a fire alert. This is a fire alert. Await further instructions. Await further instructions. There is an emergency. Await further instructions.
City of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
How To Check If A Building Is Safe For A Disabled Person
GENERAL SAFETY-FIRE-SECURITY SURVEY CHECKLIST CAMPUS INSPECTION DATE BUILDING NAME INSPECTOR: ASSISTED BY: OUTSIDE/INSIDE BUILDING 1. ADA (Americans with Disabilities Act) Entry/Exit (If area is designed
Town of Bellingham Fire Department
Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- [email protected] Lieutenant Bangma- [email protected] Fire Safety Inspection Guidelines for
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
VERIFY HARD COPY AGAINST WEB SITE IMMEDIATELY PRIOR TO USE
Nuclear Safe Work Practice 6.7 Safety Signs/Tapes/Ropes/Chains and Tags 1.0 PURPOSE/SCOPE To provide consistent standards for using safety signs, tapes, ropes and chains (barriers) to communicate existing
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
4 Starts to flash when the system triggers an alarm/fault
1 4 Starts to flash when the system triggers an alarm/fault Emergency button if programmed 2 Deactivate 1 Activate 3 Partly Activate Note: The buttons on the wireless key fob are sensitive. Kindly handle
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
Fire detection, alarm, and suppression systems are installed to:
Fire detection, alarm, and suppression systems are installed to: Notify occupants to escape a fire Summon emergency responders Initiate suppression systems Supervise suppression systems for operational
(Sample) Building Emergency Plan
(Sample) Building Emergency Plan for XXXXXX 2815 Commons Way Cincinnati, OH 45221 August 2016 University of Cincinnati Department of Public Safety Department a 2 Table of Contents A. Introduction B. Components
Residential & Commercial Alarm Systems by Gross Security, LLC
151 Main Street, Suite, 1, Get these great features with a landline or cellular alarm system from Gross Security, LLC Alarm system prices include installation Base system includes one hour of training
Class A - Wood, paper, cloth, trash, plastics Solid combustible materials that are not metals. (Class A fires generally leave an Ash.
Not all fires are the same, and they are classified according to the type of fuel that is burning. If you use the wrong type of fire extinguisher on the wrong class of fire, you can, in fact, make matters
NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version)
NetworX Series NX- 4/8 Code Pad User Manual (Australian Version) Table Of Contents Code Pad Diagram... Inside Front Glossary of Terms...2 Understanding the Code Pad lights...3 Code Pad Tones...4 Fully
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
EMERGENCY PROCEDURES
EMERGENCY PROCEDURES Introduction Being prepared is the first step towards preventing and/or handling emergency situations. Because your safety is of utmost importance, SOLEX College has created this document