Practice Note
|
|
|
- Beverly Chapman
- 10 years ago
- Views:
Transcription
1 Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note issued May Reference to the BCA in this Practice Note means Volume One and Volume Two of the National Construction Code Series. 1. SUMMARY Most fire fatalities occur in residential buildings while people are asleep and so are unable to smell smoke. A smoke alarm that is properly installed, regularly tested and adequately maintained will help to reduce injuries. Mandatory requirements for smoke alarms (combining both smoke detection and alarm function in a single device) are specified in the Building Code of Australia (BCA) 1 and regulations 707 and 709 of the Building Regulations 2006 (the Regulations). Regulation 707 requires self-contained smoke alarms that comply with AS 3786 to be installed in all Class 1, 2, and 3 buildings and Class 4 parts of a building constructed or for which approval was granted before 1 August The number and location of smoke alarms will depend on the building s size and layout. Regulation 709 applies to Class 9a residential care buildings and Class 1b and Class 3 buildings constructed or for which approval was granted before 1 August AS 3786 specifies requirements for the design, performance and testing of electrically operated smoke alarms. It does not detail location requirements. This Practice Note specifies the appropriate locations referred to in regulations 707 and POWER SUPPLY Smoke alarms required under regulation 707 need only have power supplied by an internal battery. Smoke alarms required under regulation 709 must be powered from the mains electricity supply if a mains electricity supply is available to the building. 3. LOCATION OF SMOKE ALARMS Smoke alarms should be positioned to detect smoke before it reaches the sleeping occupants of a building. The alarm is designed to wake the occupants and give them time to evacuate the building. 3.1 Class 1 Buildings The following provisions apply to installations in Class 1 dwellings Sleeping areas Smoke alarms must be located between each area containing bedrooms and the remainder of the dwelling. In some dwellings, bedrooms are located in a common area and connected by a hallway. In this case, the alarm must be located as shown in Diagram 1. Page 1 of 5
2 Practice Note DIAGRAM 1 Residential building with common sleeping areas Smoke alarms in hallways, located on ceiling between sleeping area and remainder of dwelling Notes: If the bedrooms are not grouped in a common area or no connecting hallway exists, then an alarm must be located within 1.5m of the entrance to each bedroom, as shown in Diagram 2. Diagram 2 Residential building with separate sleeping areas Smoke alarms within 1.5m of bedroom doorways Page 2 of 5
3 Practice Note Notes: other storeys An alarm is required on every storey, located in the path of travel people will most likely take to evacuate the building. This will ensure an alarm is sounded before smoke makes the common exit path impassable. If the bedrooms are on the first floor, then an alarm must be positioned near the area of the inter-connecting stair at ground level. If the other storey is not connected to the remainder of the building for instance, a ground floor garage then the alarm must be centrally located in the lower area. In all cases, the alarm must be audible in the other storey. Interconnecting the smoke alarm units so that alarms near the sleeping areas are activated, will meet this requirement. 3.2 Class 2 Buildings Requirements for protecting sleeping areas and positioning smoke alarms within dwellings (soleoccupancy units) are as per and In other areas (public corridors, lobbies, etc.), smoke alarms must be installed not more than 5m from any wall and not more than 10m between detectors. These alarms must be audible to sleeping residents. Other storeys not connected to the remainder of the building (for instance a garage or laundry), or not part of a public corridor, must have a centrally located alarm. In all cases, the alarm must be audible in the other storeys. As with alarms in public corridors, a cheap and effective way of achieving this would be to interconnect the smoke alarm devices so that alarms in each dwelling near the sleeping areas are activated. 3.3 Class 3 Buildings Class 3 buildings must firstly comply with the provisions for Class 1 and 2 buildings. In addition to smoke alarms within sole-occupancy units, they must also have a smoke alarm installed in all other habitable rooms. Kitchen and other areas likely to result in causing false alarms are the exception, in which case suitable selfcontained heat alarms may be installed. In all cases, alarms must be audible in the sleeping areas. Note: Some Class 3 residential buildings require additional fire and life safety equipment. A smoke detection system complying with AS1670.1, having smoke detectors installed in all sleeping areas and with alarm devices audible to all sleeping residents, is an alternative to the provision of smoke alarms that complies with the requirements of regulation Class 4 Buildings A Class 4 part of a building is a single dwelling within a building of another (non-residential) class and must comply with the provisions of Section E2.2 of the BCA Volume 1. It must also have smoke alarms installed within any non-fireisolated exit and any public corridors serving the Class 4 part of the building, unless the building is sprinkler protected. 3.5 Mounting Smoke Alarms Smoke alarms must be installed on or near the ceiling. Take special care to avoid dead air spaces. Page 3 of 5
4 Practice Note A dead air space is an area in which trapped air will prevent smoke from reaching the alarm. This generally occurs at the apex of cathedral ceilings, the corner junction of walls and ceilings, or between exposed floor joists, etc. If it is impractical to mount the smoke alarm on the ceiling, then it may be located on the wall. The top of the smoke alarm must be between 300mm and 500mm from the ceiling (see Diagram 3). The distance from the apex of a cathedral ceiling and the top of a smoke alarm must be between 500mm and 1500mm (see Diagram 3). DIAGRAM 3 Dead air space and proper mounting of smoke alarms on side walls Page 4 of 5
5 Practice Note 4. MAINTAINING SMOKE ALARMS To be effective, smoke alarms must be properly maintained. The level of maintenance required for each building classification is determined under Part 12 of the Regulations. Alarms should be tested in accordance with the manufacturer s instructions. The operation of most smoke alarms can be easily checked by depressing a button on the outside of the alarm. The battery in most smoke alarms will need replacing each year (lithium batteries lasting up to seven years are also available). Smoke alarms should emit a warning sound when the battery needs replacement. The alarm should also be cleaned annually, by carefully vacuuming to remove dust particles that may affect the operation of the unit. It is important to read the manufacturer s installation and operation details before cleaning the alarms. Neither municipal nor private building surveyors are required to check that owners maintain their smoke alarms. However, a municipal building surveyor can check that required smoke alarms are installed and operational. 5. FALSE ALARMS Other solutions include a simple time delay switch that deactivates the alarm for a period of time while the smoke clears, or opening a window to remove the contaminated air. If false alarms persist, then the smoke alarm should be moved to a more suitable location or another device installed in accordance with BCA requirements. 6. SHOULD SMOKE ALARMS BE INTERCONNECTED? If a building has a number of smoke alarms there is usually no requirement that they be interconnected (some types of alarm are capable of interconnection to other alarms so that if one alarm sounds then the other alarms are also activated). However, as it is inexpensive to interconnect alarms, it is advisable that smoke alarms be interconnected. This is particularly relevant where a detector is located within an unoccupied storey such as a garage. If you have a technical enquiry please [email protected] or phone Victorian Building Authority 733 Bourke Street Docklands VIC 3008 Smoke alarms are extremely sensitive and may detect smoke and moisture created by common household activities, such as burnt toast or steam from a bathroom. To reduce the likelihood of false alarms, the smoke alarm should not be located near cooking appliances or bathrooms. Some types of smoke alarms may be provided with a method for switching off a false alarm. Page 5 of 5
What you need to know about. Smoke alarms for residential buildings
What you need to know about Smoke alarms for residential buildings Are s compulsory? Smoke alarms are compulsory and must be installed in residential buildings on or near the ceiling of every storey. What
SMOKE ALARMS CLASS 1A BUILDINGS
SMOKE ALARMS CLASS 1A BUILDINGS A smoke alarm is a device that combines both smoke detection and alarm facilities into a single unit. Smoke alarms are required to be installed in all new residential Class
Smoke Alarms. New smoke alarm requirements for existing buildings from 1 May 2006. Introduction. Advisory note March 2006
New smoke alarm requirements for existing buildings from 1 May 2006 Advisory note March 2006 Introduction To enhance safety and minimise loss-of-life in building fires, the NSW Parliament, in July last
DOMESTIC SMOKE ALARMS
SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE
Home Owners Guide to Smoke Alarm Safety
Home Owners Guide to Smoke Alarm Safety Smoke alarms save lives. Most importantly - only working smoke alarms save lives. You and your family are at risk if: You do not have batteries in your smoke alarms
BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
Fire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
FIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings
Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
2012-01. Multi-storey residential buildings - warranty insurance exemption. This updates the previous Practice Note 2006-01 issued June 2006
Multi-storey residential buildings - warranty insurance exemption This updates the previous Practice Note 2006-01 issued June 2006 2012-01 Reference to the BCA Volume One in this Practice Note means Volume
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building
Smoke Alarms Save Lives!
Smoke Alarms Save Lives! Every year in America, almost 3000 people die in home fires. Most of these people die in homes that do not have working smoke alarms in them. Smoke alarms warn you and your family
720r Addendum: Siting the 720r
720r Addendum: Siting the 720r UK 1 Cooper Security Limited 2013 Every effort has been made to ensure that the contents of this leaflet are correct. However, neither the authors nor Cooper Security Limited
Fire precautions in dwellings. Private sector housing Providing homes building communities
Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared
Practice Note 2014-01
Practice Note 2014-01 Multi-Storey Residential Buildings Warranty Insurance Exemption This updates the previous Practice Note 2012-01 issued May 2012 Reference to the BCA Volume One in this Practice Note
Smoke Alarm Legislation Frequently Asked Questions
THE REQUIREMENT FOR SMOKE ALARMS Is it law for residential properties to have mains powered smoke alarms installed? Residential properties that are subject to sale, transfer of ownership, rent or hire
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety
OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor
Minimum Housing and Health Standards
APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix
The Alberta Fire Code requires all homes in the province to have working smoke alarms.
Your chances of dying in a home fire may be significantly reduced if a working smoke alarm is present in your home. Smoke alarms, when properly installed, tested and maintained, provide an early warning
Northern Ireland Housing Executive: HMO Fire Safety Guide
Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction
USER S MANUAL. SMDC-16 Digital Control Communicator and SMPC-32 Personal Control
SMDC-16 USER S MANUAL SMDC-16 Digital Control Communicator and SMPC-32 Personal Control Table of Contents General Descriptions Page Description of Your Alarm System 3 Description of Keypads 3 Keypad Maintenance
Know Your Smoke Alarm
Know Your Smoke Alarm Updated January 29th 2008 Port Angeles Fire Department, Washington Ver. 1.0 Purpose of Smoke Alarms A smoke detector or smoke alarm is a device that detects smoke and issues an alarm
MUNICIPALITY OF KAZABAZUA. SMOKE DETECTORS By-Law number 07-2012
MUNICIPALITY OF KAZABAZUA SMOKE DETECTORS By-Law number 07-2012 Notice of motion : August 7, 2012 Publication : September 9, 2012 Adoption : November 15, 2012 Effective November 15, 2012 Resolution: 2012-09-234
CERTIFICATE OF COMPLIANCE
CERTIFICATE OF COMPLIANCE (Smoke Detector Inspection) Smoke detectors and carbon monoxide detectors must be in the proper locations and operational. Your house must also be properly numbered in order to
Smoke Alarm Legislation
Is it law for residential properties to have mains powered smoke alarms installed? Residential properties that are subject to sale, rent or hire are required under the Building Regulations 2012 to install
LOUTH COUNTY COUNCIL STATEMENT OF POLICY ON DOMESTIC FIRE DETECTION AND ALARM SYSTEMS
LOUTH COUNTY COUNCIL STATEMENT OF POLICY ON DOMESTIC FIRE DETECTION AND ALARM SYSTEMS Louth County Council as both a Housing and Fire Authority has a responsibility to encourage compliance and best practise
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
Application Guide HMOs
Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application
INSTALLER INSTRUCTIONS
230V~ SMOKE & HEAT ALARMS ALKALINE BATTERY BACK-UP Ei141RC - Ionisation Ei144RC - Heat Ei146RC - Optical RECHARGEABLE LITHIUM CELL BACK-UP Ei161RC - Ionisation Ei164RC - Heat Ei166RC - Optical INSTALLER
READ THIS FIRST CONT.
READ THIS FIRST CONT. ALL INTERCONNECTED ALARMS OPERATE WHEN EACH TEST BUTTON IS PRESSED FOR 10 SECONDS. REMOVE UNIT FROM MOUNTING PLATE BY RELEASING CATCH AS SHOWN IN FIGURE 1, SWITCH OFF MAINS FIRST.
Fire Standards & Regulations Are you confused?
Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm
Smoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
Instructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance
Princeton Department of Emergency & Safety Services Instructions for Obtaining a Certificate of, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance 1. Obtain an application Download from /forms
1. Basic Information about your Smoke Alarm. 2. Locating your Smoke Alarm
B14464-R3-100TY-U&C-ENG.qxd 14/3/04 6:50 AM Page 1 1. Basic Information about your Smoke Alarm A Smoke Alarm is an early warning device. Used correctly it can give you and your family valuable extra time
Visit Us on the Web! www.smokealarms.com MODEL USI-1122L LONG LIFE* LITHIUM POWERCELL SMOKE & FIRE ALARM WITH SILENCE CONTROL
Visit Us on the Web! www.smokealarms.com MODEL USI-1122L LONG LIFE* LITHIUM POWERCELL SMOKE & FIRE ALARM WITH SILENCE CONTROL READ ALL INSTRUCTIONS The smoke alarm has a recommended service life of at
Smoke Alarm User s Guide
10Y29 For model: 10Y29 Smoke Alarm User s Guide Lithium (non-replaceable sealed in) Battery-Operated Optical Smoke Alarm with HUSH TM Control to temporarily silence nuisance alarms. Thank you for purchasing
Smoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services www.mass.gov/dfs M.G.L. C 148 S. 26F - THE LAW Massachusetts
BS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
SMOKE ALARM MAINTENANCE PROGRAM
SMOKE ALARM MAINTENANCE PROGRAM The intent of this program is for owners who normally do not get in to their rental units on an annual basis to make sure the smoke alarms are properly maintained. By having
Introduction. CE marked construction products
Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements
Call reduction guidance for false alarm/ unwanted fire signals
Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately
MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD
MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD Index Purpose... 3 Commencement.3 Application...3 Compliance..3 Associated Requirements... 3 Definitions... 4 Kitchen Facilities... 6 Laundry Facilities...
Fire Facts Smoke Alarms
Fire Facts Smoke Alarms Your chances of dying in a home fire may be reduced by 50 per cent if a working smoke alarm is present in your home. Smoke alarms, when properly installed, tested and maintained,
I.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
HOUSES IN MULTIPLE OCCUPATION STANDARDS. Housing Executive
HOUSES IN MULTIPLE OCCUPATION STANDARDS Housing Executive Contents 1.0 Introduction 3 2.0 Standards 4 3.0 Method of Measurement 6 4.0 Overcrowding 7 5.0 Over Occupation 8 6.0 Facilities for Storage, Preparation
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
Requirements for Smoke/Carbon Monoxide & Fire Extinguisher Certification
Requirements for Smoke/Carbon Monoxide & Fire Extinguisher Certification In order to successfully pass the inspection, your property will need to meet all regulations mandated by the state and municipality.
755 SERIES SMOKE ALARMS
755 SERIES SMOKE ALARMS Smoke Alarms save lives Tragically, each year in Australia there are over 10,000 house fi res resulting in more than 70 deaths, 1,500 injuries and millions of dollars worth of property
London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords
London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the
I.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
READ ALL INSTRUCTIONS
Visit Us on the Web! www.smokealarms.com MODEL SS-770/SS-771 SMOKE & FIRE ALARM READ ALL INSTRUCTIONS The smoke alarm has a recommended service life of at least 10 years under normal conditions. The smoke
INSTALLATION AND OPERATION MANUAL
Photoelectronic Smoke Detector with Built-in Wireless Transmitter INSTALLATION AND OPERATION MANUAL 1 Model # 1008-4 What smoke detectors can do: Smoke detectors are designed to provide early warning of
2-WAY WIRELESS SUPERVISED PHOTOELECTRIC SMOKE DETECTOR. Model: EL-4703 INSTALLATION INSTRUCTIONS
2-WAY WIRELESS SUPERVISED PHOTOELECTRIC SMOKE DETECTOR Model: EL-4703 INSTALLATION INSTRUCTIONS GENERAL DESCRIPTION Electronics Line's smoke detector is single station, photoelectric smoke detector with
Fire safety for landlords
Fire safety for landlords Acting Acting to to Protect & Save Are you a landlord and confused about your responsibilities towards fire safety? The law and regulations can often seem complicated and grey.
Building Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
Guide to Massachusetts Smoke & Carbon Monoxide Requirements
Guide to Massachusetts Smoke & Carbon Monoxide Requirements When Selling a One- or Two-Family Residence DEPARTMENT OF FIRE SERVICES Stephen D. Coan State Fire Marshal M.G.L. c 148 s. 26F - The Law Massachusetts
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
Are photoelectric smoke alarms better than ionization smoke alarms for adjacent to kitchen installations, to minimize nuisance alarms?
Are photoelectric smoke alarms better than ionization smoke alarms for adjacent to kitchen installations, to minimize nuisance alarms? Information Report Applied Research Office of the Fire Marshal March
Fire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12)
Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12) Notice: This e-learning module is intended for general information purposes only. It only highlights certain provisions of the
Ionization alarms are best suited for rooms, which contain highly combustible material. These types of material include:
Smoke Detector University Most people are aware of the danger of fire but are unaware of the fatality of smoke. More people die from breathing smoke than by burns. In fact, deaths from smoke inhalation
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4
Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the
Fire Safety Report 2014-2015. Fire Statistics 2013-2014-2015
Fire Safety Report 2014-2015 Fire Statistics 2013-2014-2015 Fire Log 2013-2014-2015 The New York Conservatory for Dramatic Arts Annual Fire Safety Report for Campus Housing 2014-2015 In August 2008, the
Department of Licenses and Inspections PARTNERS FOR GOOD HOUSING
City of Philadelphia Department of Licenses and Inspections PARTNERS FOR GOOD HOUSING Revised - April 2004 Produced by the Commissioner s Office PARTNERS FOR GOOD HOUSING The City of Philadelphia, on behalf
Smoke Detector/Carbon Monoxide Detector Inspections
MIDDLESEX COUNTY FIRE MARSHAL 1001 Fire Academy Drive Sayreville, NJ 08872 732-316-7171 (office) 732-316-7638 (fax) To: All Real Estate Agencies/Home Owners Subject: Smoke Detector/Carbon Monoxide Detector
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
City of Peterborough
City of Peterborough Building Division Basement Finishing Guide Residential Information Guides This information is intended to be used as an guide that outlines minimum requirements when finishing a basement,
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
Practice Note 2014-62
Practice Note 2014-62 Documentation Required for Applications for Building Permits Reference to the Building Code of Australia (BCA) in this Practice Note means Volume One and Volume Two of the National
H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh
Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years
Fire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
Guidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
Kidde Safety Europe, Mathisen Way, Colnbrook, SL3 0HB, UK. www.kiddefyrnetics.co.uk. Kidde Fyrnetics 2000 SAVE THIS MANUAL FOR FUTURE REFERENCE
Battery Smoke alarm Owner s Manual 9V Interconnectable Alarms For models: 19HI, 19HILL, 29I, 29ILL, 29HI, 29HILL, Thank you for choosing a Kidde Fyrnetics alarm. Please read through our guide in full.
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE. Alarm Systems. Smoke Detectors. Key and Data Storage Boxes
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE Section Alarm Systems 90.01 Purpose 90.02 Definitions 90.03 Exemptions 90.04 Registration 90.05 Violations; fines
10 YEAR LIFE SMOKE ALARM
User Manual 10 YEAR LIFE SMOKE ALARM ST-620 Please read me as I could save your life. Please retain this user manual for future reference CONTENTS INTRODUCTION 2 ALARM SMART SILENCE 11 AUTOMATIC POWER
Mobile Fire Rescue Department Bureau of Fire Prevention
222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
Basement Development Construction requirements for the development of basements in residential dwellings.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Basement Development Construction requirements for the development of basements in residential dwellings. June 2009 contents GENERAL INFORMATION 3 BUILDING
Smoke alarms in the home
CFPA-E Guideline No 10:2008 Smoke alarms in the home FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the European
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section