Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012
|
|
|
- Kelley Cobb
- 9 years ago
- Views:
Transcription
1 Medicine Hat Fire Department Special Event Requirements August 202 medicinehat.ca/fire
2 The following is a standard guide for event organizers to ensure occupant safety and compliance with the Alberta Fire Code. Please follow this guide carefully, as these items will be reviewed for compliance during required routine walkthroughs by Fire Service personnel. Should you have any questions or concerns contact the Fire Prevention Bureau at Special Events A special event can be any event held within or outside buildings which deviate from regular operations of the space or building. These can include but are not limited to the following; home shows, trade shows, auto/boat/rv shows, concerts, rodeos, street festivals, fundraisers, large public celebrations, fairs and any other special event of public assemblage. Special Event Approval The MHFD must receive an information package for review and approval at least 30 days prior to the event. The information package shall include the following; Event information sheet (Form can be found at the end of this document) Floor plans / Site Plans Emergency Response Plan in case of a fire or other emergency Special circumstances Floor Plans / Site Plans Plans shall include a detailed physical layout of the event and must include individual tent/booth site plans. Floor and Site Plans must specify; Access to exits and exit locations Site / booth layout of the entire show Location of all tents / canopies Location and type of cooking booths, concessions or vendors Location and dimension of all isles and cross isles Size and location of stages or other performing areas Location and accessibility of all required fire extinguishers, pull stations or other safety equipment Outdoor emergency access routes minimum 6m wide.
3 Fire Department Approval Plans must be approved by the Fire Department prior to any event set-up unless the set-up is a standard arrangement pre-approved by the MHFD Fire Prevention Bureau. Copies of the approved plans will be stamped and returned to the event coordinator prior to set-up. Approvals are subject to final inspection by a MHFD Fire Safety Codes Officer (Fire SCO). No modification of the set-up shall occur once the approved plan has been established without prior written approval on the plans from the MHFD Fire Prevention Bureau. Inspections will be conducted according to the approved plans. Special Circumstances If the following situations and/or circumstances are to occur during an event, then detailed plans of use shall be included in the information package:. Displays and operation/use of any open flame, candles, lamps, torches, cooking etc. 2. Fire performers using spinners or other flaming devices 3. Use of Liquefied Petroleum Gas / Liquefied Natural Gas. 4. Use, handling or storage of any pyrotechnic materials or devices. 5. Temporary membrane structures, tents, canopies, or covered exhibit booths. 6. Display or use of any motorized or non-motorized vehicles in the public area. Structures and Exhibit Booth Requirements. Decorative material, including but not limited to; signs, banners, drapes, theatre curtains, acoustical material, hay/straw, split bamboo, shavings, mulch, canvas, cardboard, plastic displays etc shall not be used indoors or adjacent to crowds or along exit routes unless they are made of non-flammable material conforming to CAN/ULC-S09, Flame Tests of Flame Resistant Fabrics and Films, or treated and maintained in a flame retardant condition by means of a flame retardant solution to ensure that the material will pass the match flame test in NFPA 705, Field Flame Test for Textiles and Films. Plastic cloth and certain other plastic materials, tar-paper, nylon, oilcloth, etc cannot be rendered flame retardant and are prohibited. Any decorative material may be subject to testing, materials in violation shall be immediately removed. 2. Combustible materials that are 0mm (3/8 inch) or more in thickness or glass may be used without flame retardant treatment. Exception: paper, cardboard or foam products. 3. All electrical fixtures and appliances must be approved and carry the appropriate ULC or CSA listing: a) Three wire grounded cords shall not be plugged into two wire extension cords. b) Extension cords shall not run under carpets/rugs unless designed to be used in these locations. c) There shall be sufficient clearance from lights or other heat sources to any combustible or display materials to prevent any possible ignition or heat damage. d) All electrical plugs and extension cords must be of appropriate gauge, free from defects and designed to be used in the specific location. ( eg. outdoors)
4 4. Booths that include tents, canopies and/or other structures inside a building shall not be constructed with any roof, ceiling or other obstruction larger than 27.9m2 (300 sq ft) without written approval of the MHFD Fire Prevention Bureau. 5. Booths that include tents, canopies and/or other structures inside a building having between 9.3m2 (00 sq ft) and 27.9m2 (300 sq ft) of roof, ceiling or other obstruction shall provide a listed single station smoke alarm. 6. Booths that include tents, canopies and/or other structures inside a building having between 9.3m2 and 27.9m2 of roof, ceiling and/or other obstruction with a source of ignition shall provide a listed single station smoke alarm plus a 2A-0BC fire extinguisher within. 7. Tents and canopies used indoors must be approved for indoor use and have a permanently attached label indicating conformance to CAN/ULC-S09, Flame Tests of Flame Resistant Fabrics and Films. 8. Minimum of 3m separation is required between each 27.9m2 aggregate of tents, canopies or other structures located indoors. 9. All required EXIT signs shall be visible from any location in a tent or room. Drapes, curtains or displays shall not obstruct view of EXIT signs. Temporary directional EXIT signs may be required to clearly indicate the direction of egress. 0. Exits and aisles shall be clear and free of obstructions. Primary aisles at front and back of hall shall be a minimum of 3.5m wide, secondary aisles shall be a minimum of 2.5m wide.. Tents or enclosed areas which require 25m or more travel distance to reach an exit aisle shall have a minimum of two (2) exits remote from each other. 2. Fire extinguishers, standpipe connections and other fire appliances shall be maintained, clearly visible and accessible at all times. 3. The number of persons allowed within any event shall not exceed the occupant load permitted for the facility 4. Pressurized tanks and other similar hazards shall be properly secured to prevent tipping over or damage. 5. Any additional requirements shall be determined by the MHFD Fire Prevention Bureau for each event. Cooking/Warming. Cooking and/or warming appliances shall be listed and labeled for commercial use by a recognized testing laboratory. (CSA or ULC) 2. Cooking or warming appliances used indoors shall be electric. Exception: approved commercial cooking appliances that use no more than (2) 0-ounce non-refillable LPG/butane containers or one 5lb propane cylinder connected directly to the appliance shall be allowed. Containers shall not be used with a manifold. 3. Chafing fuel may be used for warming trays, other open flame devices are prohibited indoors without appropriate permits from MHFD. 4. Cooking or warming appliances used indoors or in an enclosure (tent, trailer or truck) that produce grease laden vapors must meet NFPA 96 requirements. Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. 5. Cooking/warming appliances shall be isolated from the public having a minimum of m separation on all sides, or by providing a sturdy mounted separation shield between the appliance and the public.
5 6. Individual cookware and warming devices used indoors shall not exceed.5m x m (8in x39in) in area. 7. The surfaces, on which cooking/warming appliances are located, shall be constructed and arranged such that their proximity to combustibles will not pose a fire danger. When cooking equipment generates high temperatures the surface will be provided with adequate protection. 8. Fire protection shall be provided for any booth utilizing cooking/warming appliances. Each booth shall have the following fire protection equipment: a) A mounted 2A-0BC extinguisher b) A portable K class extinguisher. (if using or producing grease laden vapors) c) A smothering lid for each individual piece of cookware. 9. All extinguishers must be listed, labeled and tagged. 0. Cooking appliances must be placed on a stable base to limit the risk of the appliance tipping. Outdoor Tents In addition to the cooking/warming section, cooking appliances and/or heaters may be used in a tent with the following provisions:. Tents must be CAN/ULC-S09 Flame Resistant certified. 2. No open flame cooking appliances or heaters are permitted in tents. Exception: chafing dishes 3. If grease laden vapors are being produced and NFPA 96 requirements are not met, appliances shall be located outside of tents and may be protected from weather by a non-combustible cover no larger than 3m2. These appliances must be placed so they are a minimum of one meter from the outside tent wall and protected from public access. 4. Electric heaters may be used provided they are located a minimum of m from tent sides and ceiling. 5. LPG/LNG heaters must be located outside of the tent with suitable ducting used to supply warm air. Outdoor Canopies In addition to the cooking/warming section, cooking appliances may be used under a canopy with the following provisions:. Canopies shall be CAN/ULC-S09 Flame Resistant certified. 2. Canopies shall be cleaned prior to set up. 3. A maximum of two cooking appliances that may produce grease laden vapors are permitted per canopy space of 3m2. 4. There shall be a vertical clearance of at least m from the cooking appliance to the ceiling. 5. Canopies used for cooking shall be a minimum of 3m from any other tent, canopy or building. 6. The public are not allowed to be under canopies being used for cooking.
6 Display of Motorized & Non-Motorized Vehicles When motorized vehicles are to be displayed indoors the following will apply:. Vehicles shall not be started or operated within any assembly building during show hours. 2. All fuel tank openings shall be locked or sealed in an approved manner. Where it is not feasible to lock or seal the opening, the fuel tank should be empty. Draining of the tank shall not occur in a building. 3. Adding or removing fuel indoors is prohibited. 4. Vehicle fuel shall not exceed one quarter (25%) of the tank capacity or 20L, whichever is less. 5. Vehicles, boats, RV s, trailers and similar exhibited products having over 9.3m2 (00sq ft) of roofed area shall have a listed single station smoke alarm installed. 6. Vehicles, boats, RV s, trailers and similar exhibited products between 9.3m2 (00 sq ft) and 27.9m2 (300 sq ft) of roof area, with a single source of ignition, external power or vehicle batteries still connected, shall have a listed single station smoke alarm installed and a 2A-0BC fire extinguisher. 7. Previously stated aisle widths of 3.5m primary and 2.5m secondary must be maintained without fishtailing. Clearance between RV s shall be at least.5m in all other locations. Measurements will be taken from closest point of each unit including slide-out and/or extended step. 8. Vehicles fuelled by LPG/LNG/CNG are not permitted in assembly occupancies. Inspection of the Event In order to maintain compliance with Fire and Life Safety requirements, periodic inspections may be conducted by a MHFD Fire Safety Codes Officer. These inspections may include: A walk-through inspection with the event coordinator during the move-in/set-up period with deficiencies corrected immediately or within agreed upon time frame. Once the event has opened, daily visits by a Fire SCO may be conducted. Cooking and motor vehicle displays may be spot checked by a Fire SCO. During the closing/move-out and removal of materials used in the event, a Fire SCO may inspect for emergency access and exiting. Onsite Fire Safety Codes Officer At the discretion of the Medicine Hat Fire Department, one or more MHFD Fire SCO s may be required to be present at the event. If a Fire SCO is used, the event will be billed at the current MHFD fee rates. Event Interruption/Shutdown Upon finding any unsafe act or condition or any act or condition that constitutes immediate danger, the Medicine Hat Fire Department has the authority to stop the event until such condition is corrected.
7 Event Information Sheet Event Name: Venue Name: Venue Address: Event Date(s): Event Time(s): Setup Date: Move Out Date: Description of Event: Maximum Estimated Number of Attendees: Event Coordinator Name: Address: Phone: Cell: Fax: Alternate contacts: Name: Phone: Name: Phone: Fax completed information sheet to: Fire Prevention Bureau
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Orange County Fire Rescue Division Fire Loss Management Bureau 109 East Church Street Lower Level Orlando, Florida 32801-3319
Standard 6005 Orange County Fire Rescue Division Fire Loss Management Bureau 109 East Church Street Lower Level Orlando, Florida 32801-3319 Orange County Fire Loss Management Bureau Standard 6005 AUTHORITY
Fire and Life Safety Requirements for Special Events and Temporary Use of the Facilities at the Kitsap County Fairgrounds.
Fire and Life Safety Requirements for Special Events and Temporary Use of the Facilities at the Kitsap County Fairgrounds. PURPOSE This document is developed to assist event planners and responsible parties
SPECIAL EVENTS CHAPTER 17
CHAPTER 17 SPECIAL EVENTS SECTION 1701 GENERAL 1701.1 Scope. Special events including trade shows and exhibitions, outdoor assembly events, outdoors mazes, special amusement buildings, and special scaffolding
LOS ANGELES CITY FIRE DEPARTMENT
LOS ANGELES CITY FIRE DEPARTMENT Division 5 Permit LOCATION INFORMATION FD USE ONLY Date of Use: Date Granted PERMIT # Date Expires Name Phone#: City: Los Angeles State: California Zip: 90089 CONTRACTOR
PLACES OF ASSEMBLY CHAPTER 17
CHAPTER 17 PLACES OF ASSEMBLY SECTION 1701 GENERAL 1701.1 Scope. Places of assembly, including trade shows and exhibitions, outdoor assembly events, outdoors mazes, special amusement buildings and special
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
Special events and tents Fire and life safety requirements
Special events and tents Fire and life safety requirements Section A - Temporary Use Occupancies or Operations Fire and Life Safety Requirements In order to provide a standard method of inspection of temporary
The Fire Safety Manager at 312 791 6079 (FAX 312 791 6013) can answer any questions or provide a set of fire code information.
FIRE SAFETY REGULATIONS Fire Prevention reserve the right to make any final decisions regarding the outlined requirements, according to Section 2 36 220 of the Municipal Code of Chicago on Fire Prevention.
Fire Regulations for Exhibitors
The purpose of these requirements is to maintain an acceptable level of fire safety within the Metro Toronto Convention Centre. The fire protection systems built into the Convention Centre have been designed
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
FIRE AND SAFETY REGULATIONS
FIRE AND SAFETY REGULATIONS Fire Prevention reserves the right to make any final decisions regarding the outlined requirements, according to Section 2-36-220 of the Municipal Code of Chicago on Fire Prevention.
MONARCH FIRE PROTECTION DISTRICT
MONARCH FIRE PROTECTION DISTRICT 13725 OLIVE BLVD., CHESTERFIELD, MO 63017 314-514-0900, EXT. 309 [email protected] www.monarchfpd.org TENT / BOOTH REQUIREMENTS To help insure the safety, health
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
INFORMATION BULLETIN Bulletin No. 2005-01 Bureau of Fire Prevention Date: June 10, 2005 Revised: March 8, 2007
SAN FRANCISCO FIRE DEPARTMENT DIVISION OF FIRE PREVENTION & INVESTIGATION INFORMATION BULLETIN Bulletin No. 2005-01 Bureau of Fire Prevention Date: June 10, 2005 Revised: March 8, 2007 SUBJECT: Fire Department
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES
CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES > SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. SECTION 2402 DEFINITIONS 2402.1 Definitions.
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Exhibit Space & Booth Layout Guidelines
Exhibit Space & Booth Layout Guidelines Exhibit Space & Booth Display Rules The following display rules have been designed using the IAEE (International Association of Exhibitions and Events) guidelines
Town of Bellingham Fire Department
Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- [email protected] Lieutenant Bangma- [email protected] Fire Safety Inspection Guidelines for
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES 3103.1 General. All temporary tents and membrane structures shall comply with this section. 3103.2 Approval required. Tents
Errata NFPA 1. Fire Code. 2015 Edition
Errata NFPA 1 Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES
Page 25 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
CANTON FIRE DEPARTMENT
CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS
FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS A. Inherently Fire Retardant or Flame Retardant Treatment 1. All decorations, drapes, signs, banners, plastic displays, hay, straw, moss, split bamboo
Exhibit Space & Booth Layout Guidelines
Exhibit Space & Booth Layout Guidelines Exhibit Space & Booth Display Rules The following display rules have been designed using the IAEE (International Association of Exhibitions and Events) guidelines
Tents and Other Membrane Structures
ORANGE COUNTY FIRE AUTHORITY Safety & Environmental Services Section 1 Fire Authority Road, Building A, Irvine, CA 92602 714-573-6180 www.ocfa.org Tents and Other Membrane Structures Approved and Authorized
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services
MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts
Exhibit Space & Booth Layout Guidelines
Exhibit Space & Booth Layout Guidelines Exhibit Space & Booth Display Rules The following display rules have been designed using the IAEE (International Association of Exhibitions and Events) guidelines
Permit Application for Mobile Food Truck
Date Received / / Office Use Only By: Date Approved / / By: Comp # Element Type: Entered By: Annual Permit Fee: Check #: Receipt #: AMANDA #: Permit Application for Mobile Food Truck NOTE: This application
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
BOOTH DESIGN RULES NEW! [email protected]
BOOTH DESIGN RULES All exhibits must conform to the dimensions outlined below in order to assure ease of movement of participants and clear lines of visibility in the exhibit hall. For more information
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
Exhibit Space & Booth Layout Guidelines
Exhibit Space & Booth Layout Guidelines Exhibit Space & Booth Display Rules The following display rules have been designed using the IAEE (International Association of Exhibitions and Events) guidelines
Commercial Kitchen Fire Safety
Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and
FIRE AND LIFE SAFETY TRAINING
FIRE AND LIFE SAFETY TRAINING 1 Objectives General Information Emergency Evacuation Plans / Regulatory Requirements Notification Systems Emergency Exits and Fire Doors Electrical Safety Fire Prevention
Waste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
A. Fire Protection Plan. B. Access and Parking
Standards for Construction Site Fire Safety For Use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire Code (CFC) These standards are intended to prescribe
Sample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
LAS VEGAS CONVENTION CENTER RULES AND REGULATIONS
LAS VEGAS CONVENTION CENTER RULES AND REGULATIONS CONTACT INFORMATION ARAMARK Food & Beverage Services: (702) 943 6910 COX Business: (702) 943 6500 FedEx: (702) 943 6780 Las Vegas Convention Center: (702)
Display Rules & Regulations CHFA WEST / CHFA EAST / CHFA QUEBEC
CHFA WEST / CHFA EAST / CHFA QUEBEC Display rules and regulations ensure that all exhibitors, regardless of exhibit size or location, enjoy an environment that is conducive to successful interaction with
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
Guidelines for Display Rules & Regulations
Guidelines for Display Rules & Regulations You are reminded that a booth design, including flooring and fixtures, is REQUIRED in order for your company to maintain consideration for future shows. Booth
ADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
LIQUEFIED PETROLEUM GASES
CHAPTER 38 LIQUEFIED PETROLEUM GASES SECTION 3801 GENERAL 3801.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems
City of Glendale. Fire Marshal s OFFice Building Safety Planning And Tax & License
City of Glendale Guide to Minor & Major Events Fire Marshal s OFFice Building Safety Planning And Tax & License Permit Requirements Table of Contents Overview....... 3 Special Event General Requirements.....4
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
Guidelines for Display Rules & Regulations
The following Guidelines for Display Rules and Regulations have been established in accordance with guidelines set forth by All Baby & Child (ABC), based on those established by the International Association
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers
A Health and Safety Guideline for Your Workplace Introduction Fire extinguishers are designed to put out or control small fires. A small fire, if not checked immediately, will soon spread out of control.
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
Orange County Convention Center Rules and Regulations
Orange County Convention Center Orlando, FL Orange County Convention Center Rules and Regulations Guidelines for All Exhibits For the protection of our facility and for those guests either working or attending
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
Fire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
CHILD CARE CENTER INFORMATION SHEET
CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Guidelines for Booth Display/ Rules & Regulations
Guidelines for Booth Display/ Rules & Regulations The Car Wash Show requires that Exhibitors with island or peninsula booths 400 square feet and above must submit a floor plan with dimensions, including
NORTH LAS VEGAS FIRE CODE
NORTH LAS VEGAS FIRE CODE CODE AMENDMENTS FOR ADOPTION OF THE 2009 INTERNATIONAL FIRE CODE Effective July 5, 2011 North Las Vegas Fire Department 4040 Losee Road North Las Vegas, NV 89030 702.633.1102
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
FDNY C14 Certificate of Fitness Quiz
FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational