Roofing & Waterproofing Forensics for the 21 st Century. Peter Brooks, President
|
|
|
- Brianna James
- 10 years ago
- Views:
Transcription
1 Roofing & Waterproofing Forensics for the 21 st Century Peter Brooks, President March 20, 2013 ICRI Spring Convention
2 Selecting the Appropriate Non-Destructive Testing Technology What is the Goal?
3 Methodologies: 1. Infrared & Nuclear Moisture Scans Locate and document extent of wet materials (insulation) in the system. Can help locate leaks, but is not designed or intended for that purpose. Should not be represented as a leak locating service. 2. Electronic Leak Detection Pinpoints breaches (holes) in roofing and waterproofing membranes. Finds leaks - does not define the actual location and extent of moisture damage.
4
5 Nuclear Roof Moisture Gauge
6 Infrared & Nuclear Moisture Scans - Typical Applications: 1. Testing an existing roof system to pinpoint locations and extent of moisture damage for removal, before re-roofing materials or coatings are applied. 2. Condition Assessment Provides excellent information about the true condition of the system for prioritizing multiple roofs, and budgeting.
7 3. Maintenance Pinpoints problem areas for more accurate, cost-effective repairs. 4. Quality Assurance Testing Unbiased, costeffective tool for evaluating the condition of newly installed roofing materials. 5. Dispute Resolution Science-based, objective approach establishes and documents the true condition of the system. Data based evaluation - not judgment or opinion based.
8
9 High & Low Voltage Electronic Leak Detection - Typical Applications: 1. Integrity testing of roofing and waterproofing membranes. 2. Inspections to locate, document, and repair holes caused by construction activity.
10 3. Pinpointing leaks on waterproofing membranes with overburden. 4. Pinpointing leaks in traditional insulated roofing systems breaches can be quickly located, repaired and retested. 5. Dispute Resolution Science-based, objective approach establishes and documents the true condition of the system. Data based evaluationnot judgment or opinion based.
11 Electronic Leak Detection
12 A Better Way to Find Leaks First developed in Europe, Electronic Leak Detection is rapidly redefining the process of finding leaks in commercial roofing and waterproofing systems. Electronic Leak Detection uses a procedure known as Vector Mapping to pinpoint membrane breaches by tracing the flow of an electric current across the membrane surface.
13 Electronic Leak Detection How Does It Work? An electrical current is introduced above the membrane, and it will connect to a ground under the membrane only where there are breaches. Two conditions must be met for the testing to be effective.
14 1. The membrane must be nonconductive (high Dielectric Strength). Most roofing and waterproofing membranes have high Dielectric Strengths.
15 Typical non-conductive membranes (relatively high Dielectric Strength) Thermoplastics: PVC Polyvinyl Chloride TPO Thermoplastic Polyolefin CPE Chlorinated Polyethylene Modified Bitumen Built-up Roofing Fluid Applied Rubberized Asphalt
16 2. A ground must be available to receive the electrical current. For example, a structural reinforced concrete deck or steel deck will readily accept the current that passes through a breach.
17 Low Voltage Vector Mapping
18 Low Voltage Vector Mapping
19 Low voltage vector mapping equipment includes pulse generator, trace wire spool, test probes, mobile detector unit and related accessories.
20 Trace Wire Trace wire is placed around the boundary of the area to be tested Typically encompasses area from 2,000 to 7,000 sf Pulse generator supplies 38 volt DC current to the trace wire
21
22 Isolation Loops Metal penetrations must be isolated from the testing field to prevent unwanted grounding. Areas inside the loops and outside the boundary wires are not in the test bed.
23
24
25
26
27
28 Vector Mapping is Ideal for Quality assurance testing of new roofing and waterproofing membranes Warranty verification Acceptance testing Integrity testing 3 rd Party verification
29
30 Vector Mapping is Ideal for Pinpointing leaks in existing roofing and waterproofing systems, including most systems with overburden Green roofs Paver systems Ballasted systems
31
32
33
34
35
36 Report Documentation
37 High Voltage Electronic Leak Detection
38 High Voltage Electronic Leak Detection Works on the principle of Arcing Arcing is current flow through normally non-conductive media such as air. The electrical energy used in High Voltage ELD can jump a gap as great as ¾.
39 The equipment provides various testing voltages Adjustable from 1,000 to 30,000volts DC Can test from extremely thin coatings of a few mils up to 5/8 thick membranes Virtually no amperage, no danger to technician, membrane or building
40 High Voltage Electronic Leak Detection
41 High voltage test equipment includes a portable charger, grounding leads, phosphor bronze brush electrode, drum brush electrode, and related accessories.
42
43
44
45 High Voltage Electronic Leak Detection is ideal for vertical surfaces Parapet walls Flashings Foundation waterproofing
46
47
48 Insulated Roofing Systems Single-ply membrane Insulation Deck
49 High Voltage Electronic Leak Detection
50 High Voltage Electronic Leak Detection
51 High Voltage Electronic Leak Detection
52 Alternative Grounding: Installation of Conductive Mesh
53
54
55
56
57
58 Hybrid Systems 1st Utilize High Voltage Testing as the integrity test on vertical surfaces, at transitions and close to metal penetrations. 2nd Place trace wire and test the field of the membrane with Low Voltage technology. 3rd Install trace wire and connection boxes after testing is completed to provide for future Low Voltage Vector Mapping w/overburden in place.
59 Hybrid Systems Utilize High Voltage testing as the integrity test Install trace wire and connection boxes after the testing is completed This provides the opportunity to test the membrane with Low Voltage technology after the overburden is installed
60 VM Applications Insulated and non-insulated low-slope roof systems Ballasted roofs (LV) Quality Assurance Warranty Verification Membrane integrity testing Green Roofs Plaza Decks Horizontal and vertical waterproofing membranes Parking garages Pools, liners
61 Vector Mapping is Metal-coated and carbon black EPDM membranes Non-conductive decks, unless conductive mesh is installed to provide the grounding medium Systems with an electrically insulating barrier (like a polyethylene vapor barrier) between the membrane and the structural deck, unless there are active leaks Not Suitable for
62 Vector Mapping Benefits Pinpoints membrane defects for efficient repairs Repairs can be immediately re-tested Green roofs can be tested with soil in place (LV) Direct (non-interpretive) detection of breaches (HV) Sloped membranes & vertical flashings can be easily tested (HV) Less expensive, faster, safer, more reliable, and more accurate than flood testing
63 Low Voltage Testing Advantages Only technique that pinpoints breaches in systems with overburden
64 High Voltage Testing Advantages Trace wire not needed for testing Water not needed for testing (dry membrane surface), so 2 nd person is not needed Ideal for vertical surfaces & any membrane areas isolated by Low Voltage Testing. Typically quicker and less expensive than low voltage, especially on larger projects, and membranes with many penetrations
65 Ideal procedure; Technician has both testers and uses the best technique for the testing specification, weather conditions and membrane being surveyed. Ideal procedure; Roofing contractor is on site during the inspection to repair any defects. These repairs can then be quickly retested so that when the Technician completes the testing we can provide a Breach Free Certification.
66
67 Why Use Electronic Leak Detection? It s a Win-Win-Win.
68 Owners Win Greater assurance that their newly completed membrane is breach-free. Roofs with overburden Now have an in- place system to pinpoint future leaks much more quickly and cost-effectively. Greater peace of mind about the quality and integrity of their investment.
69 Contractors Win Greater certainty that the new membrane is breach-free, and that the end result will be a very satisfied customer. Fewer call backs. Faster, safer, more reliable, more accurate and usually less expensive than flood testing.
70 Contractors Win Frees up personnel to do more profitable production work. Increased professionalism state-of-the-art high tech verification methodologies demonstrate the contractor s commitment to the highest professional standards.
71 Manufacturers Win Greater assurance that the membrane is breachfree and that the end result will be happy customers owner, contractor, specifier. Increased professionalism state-of-the-art high tech verification methodologies demonstrate the manufacturer s commitment to the highest professional standards.
72 Questions? Call Me:
73 Thank you!
1.0 Introduction. 2.0 Importance of Integrity Testing. 3.0 How Does EFVM Work? 6.0 Conclusion
5.4.4 Intrusion Discovery Once it was determined through water testing where the approximate location of the roof leak was, roof tiles were removed to examine the underlayment and roof sheathing. By following
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
A Method to Detect and Locate Roof Leaks Using Conductive Tapes
BEST2 Moisture Measurement Session WB8-2 A Method to Detect and Locate Roof Leaks Using Conductive Tapes ABSTRACT David Vokey, P.Eng. Detec Systems, LLC Undetected roof leaks and the subsequent deterioration
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado
Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR
Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for
Nondestructive Evaluation of USCG. 2401 Hawkins Pt. Road Curtis Bay, MD 21226. Provided by: HurleyIR
Nondestructive Evaluation of USCG 2401 Hawkins Pt. Road Curtis Bay, MD 21226 Provided by: HurleyIR On Tuesday May 20 th 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers of the USCG
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
Crescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko
A Guide to Retrofitting an Existing Roof to a Vegetated Green Roof
A Guide to Retrofitting an Existing Roof to a Vegetated Green Roof Marc A. Loranger, P.E., LEED AP Associate Gale Associates, Inc. Richard Stewart Buildings & Grounds Facilities Manager Simmons College
Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities
Roof Restoration System For building owners, property management firms and facility managers seamless possibilities Extending your roof life Think of your existing older roof custom fit with a seamless,
Best Practices in Roof Design: Sustainable Energy Efficient Reroofing
Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practice Roof Design: Sustainable Energy Efficient Reroofing Presented by Edis Oliver, PE Principal 9511 Lake Creek Parkway Austin,
The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois
Wiss, Janney, Elstner Associates, Inc. 10 South LaSalle Street, Suite 2600 Chicago, Illinois 60603 312.372.0555 tel 312.372.0873 fax www.wje.com The Building Group First Tuesdays October 2, 2012 Jason
Roofing Sustainability
Williams Engineering Canada Inc. Roofing Sustainability Gord Rajewski R.E.T. November 19, 2009 Overview History of Williams Engineering Canada Who WE are today Roofing 101 Low slope (flat) roofs Sloped
THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING
DIVISION 7 THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING 07110. MEMBRANE WATERPROOFING: The following are minimum requirements to assure adequately designed waterproofed floors for machine and equipment
The Harold J. Becker Company, Inc.
The Harold J. Becker Company, Inc. It is the mission of The Harold J. Becker Company, Inc. to deliver the absolute best possible quality product at the most efficient cost to our clients, while providing
!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
0845 0098 980 www.nicholsonsts.com
0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution
Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015
PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015 FACILITIES & MAINTENANCE By Rick Thomas Fluid-Applied Roofing for Repair and Renovation Leaking roofs are one thing which every private university facility
HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION
HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION ADVANCED TECHNOLOGY FROM OWENS CORNING TRUMBULL ASPHALT TruLo Lo Odor and TruLo Max asphalt raising the roof on asphalt performance.
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
R E S I D E N T I A L H O U S I N G
HL 252 Rev. April 1997 R E S I D E N T I A L H O U S I N G CONTROLLING EXTERNALWATER PROBLEMS FOR RESIDENCES I II III IV V Lot Drainage Gutter Water Management Foundation Waterproofing Floor Slab Waterproofing
Firestone Warranty Program
EPDM Warranty Pricing ***For Red Shield Contractors Only*** Red Shield 20 Years $0.10 $500.00 No Dollar Limit 15 Years $0.07 $400.00 No Dollar Limit 10 Years $0.04 $350.00 No Dollar Limit When Firestone
Construction Coatings
Deck Coatings Decorative Rooftop Living Plaza Deck Waterproofing Low Odor Metal and Roof Membrane Restoration Mechanical Room Waterproof Coating POLYTUFF SYSTEMS INTERNATIONAL www.polytuffus.com Decorative
Solicitation DTFACN-11-R-00079 Attachment #9
These specs are only a general overview of the typical VOR Roof construction. These are for reference only. Each individual project will have its own specifications. 1 VOR Roof Projects IDIQ Solicitation
PIPELINE INSPECTION COMPANY LTD. Portable Holiday Detectors. OPERATING INSTRUCTIONS SPY PORTABLE HOLIDAY DETECTORS Models 780, 785, & 790
PIPELINE INSPECTION COMPANY LTD. Portable Holiday Detectors OPERATING INSTRUCTIONS SPY PORTABLE HOLIDAY DETECTORS Models 780, 785, & 790 Safety Disclaimer Only trained and responsible personnel should
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Maintenance & repair Solutions
Maintenance & repair Solutions low-slope ROOFING We ve got what you need in the sizes you need them and the options to match the results that building owners want Seal-fast Temporary roof sealer Now you
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
Aerial Infrared Roof Moisture Surveys
Aerial Infrared Roof Moisture Surveys INTRODUCTION IR P/PM (infrared predictive/preventive maintenance) is not limited to annual infrared surveys of electrical switchgear. For instance, infrared thermography
Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building
Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
Durapax Coal Tar BUR Application Guide
400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof
Seamless Waterproofing. Systems
Seamless Waterproofing Systems Pitched/Corrugated Roofs Liquid Rubber Instant Set is the ideal solution for pitched roof waterproofing providing a seamless fully bonded finish. RapidRoof is suited to smaller
Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer
Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Leak Buster Repair & Maintenance Products Quality You Can Trust Since 1886...From North America s Largest Roofing Manufacturer
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design
Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
CREEK Technical Services, LLC
EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality
The existing roof angle change terminations and flashings when sound and intact can be reused.
January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing
EPDM System Repair and Cleaning
EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer
BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION
07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
How to repair your existing low slope flat roof.
How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:
I S S U E 1/2013 VOLUME 30 NUMBER 1. Water Testing: Richard P. Kadlubowski, AIA and Courtenay Bauer
I S S U E 1/2013 VOLUME 30 NUMBER 1 Journal of architectural technology published by Hoffmann Architects, Inc., specialists in the rehabilitation of building exteriors. Water Testing: A Tool for Owners
The Perfect Fit For Metal Retrofit
D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
OPERATING INSTRUCTIONS
PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3
TARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
DIVISION 7 - THERMAL AND MOISTURE PROTECTION Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s Contract Documents. SECTION 07 1000
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
Paint Test Equipment. Holitech DC Holiday Tester Data Sheet
Paint Test Equipment Holitech DC Holiday Tester Data Sheet Coating Thickness Gloss Porosity Adhesion Surface Roughness Surface Cleanliness Climatic Conditions Electrostatic Inspectors Accessories Complies
Proteus Waterproofing roof systems are tested to the most rigorous international standards, ensuring they will easily deal with our climate.
INTRODUCTION Manufactured in the UK, the Proteus Waterproofing range of high performance roof & balcony systems has been engineered to meet the harshest of weather conditions and provide a lasting and
VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10
VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 SECTION B1: PREPARATION GUIDE B1.1 INTRODUCTION... B1-1
Product Systems AQUAFIN-IC CEMENTITIOUS CRYSTALLINE PENETRATING WATERPROOFING. Waterproofing Specification
AQUAFIN-IC CEMENTITIOUS CRYSTALLINE PENETRATING WATERPROOFING Typical s Table of Contents: No. 4 5 6 7 8 9 0 External waterproofing of below ground concrete wall & slab Internal waterproofing of foundation
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
COMMERCIAL ROOFING. Learning Objectives. Commercial Roofing Fundamentals May 2, 2012
COMMERCIAL ROOFING The Fundamentals Firestone Building Products is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned on completion of this program
Exterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
RECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR
UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR Any copyrighted material
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
Fall Protection Susan Harwood Grant Training Program 2013 Commercial Roof Fall Safety. OSHA Susan Harwood Training - AGC
Fall Protection Susan Harwood Grant Training Program 2013 Commercial Roof Fall Safety Learning Objectives Understand the difference between a low sloped roof and high slope roof Understand the responsibilities
Roof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection: