A Method to Detect and Locate Roof Leaks Using Conductive Tapes
|
|
|
- Ashlynn Phelps
- 10 years ago
- Views:
Transcription
1 BEST2 Moisture Measurement Session WB8-2 A Method to Detect and Locate Roof Leaks Using Conductive Tapes ABSTRACT David Vokey, P.Eng. Detec Systems, LLC Undetected roof leaks and the subsequent deterioration are considered the greatest cause of premature roof failure. This paper describes a method whereby a leak locating grid of conductors is placed on the top of a roof membrane to detect and localize leaks to within an area defined by the grid spacing. The method is particularly useful for roof designs that incorporate a waterproofing membrane under a green roof, wear-course or topping slab where direct inspection of the roof membrane is difficult or impossible. A top-of-membrane grid system can provide an accurate and cost effective method to monitor and maintain a wide range of covered roof types and sizes. The initial mock-up testing as well as examples of subsequent field installations is provided. INTRODUCTION The failure to detect, identify and correct minor roof deterioration and leakage in the earliest stages is considered the greatest cause of premature roof failure [3, 6]. This is particularly true of roofing materials applied on low-slope or flat roofs. Costly roofing problems are often the result of design deficiencies or faulty application of the roof system. Even when properly designed and applied, all roofing materials deteriorate from exposure to the weather at rates determined largely by the kind of material and the conditions of exposure. Roof designs that incorporate a waterproofing membrane under a green roof, wear-course, or topping slab greatly exacerbate the problem of locating leaks [8, 9, and 10]. Flood testing at time of construction [4] is sometimes specified to test roof membranes. The test is difficult to do and often inconclusive. The national roofing contractor associations in both Canada [5] and the US do not support this practice. Several methods [1] have been used in attempting to locate roof leaks after they have occurred. Electric capacitance meters identify leaks using an alternating current signal to measure dielectric constant changes in the roofing material as a result of moisture below the membrane. Infrared cameras allow technicians to scan roof surfaces for temperature differentials that signify moist areas through changes in thermal conductivity or evaporation. Electric field vector mapping uses a wire loop around the perimeter of the roof surface to introduce an electric potential between the structural deck and a selected roof area which is sprayed with water. The electric field potential caused by a conductive path to any roof membrane damage is then traced to the breach using a voltmeter and a pair of probes. These methods are usually employed to assist in locating roof leaks after costly water damage has occurred. Moisture detection sensors [7] can also be placed under the roof membrane to detect the presence of moisture; however several roof designs incorporate membranes that are directly adhered to the 1
2 roof deck thereby limiting the placement and effectiveness of this type of moisture sensor application. This paper describes a method whereby a leak locating grid of conductors is placed on top of a protected roof membrane to detect and localize leaks to within an area defined by the grid spacing. The method has particular application for inverted, covered and green roofs [2] where the membrane is fully adhered. The mock-up and testing of this application was supported by and carried out at the training facilities of the Roofing Contractors Association of British Columbia (RCABC). METHOD During construction, a flat two-conductor peel-and-stick grid tape is installed on top of a roof membrane to provide conductance testing between the top of the membrane and the roof deck. During a leak test, a measuring voltage is applied between the detection conductors and the roof deck. Any water path between the detection conductors and a damage site will result in a leakage current from the roof deck to the detection conductors through the insulating membrane. For potentially corrosive environments, a small cathodic protection current is applied between the tape conductors and earth ground to inhibit corrosion. In the most severe environments stainless steel conductors can be used. The individual conductors are electrically connected at one end to a switching and measuring system whereby an isolated fault current to ground measurement can be made. In operation, a selected conductor is switched to act as the input of a current sensor, and an electric potential is applied between the selected conductor and the roof deck ground. As illustrated in Figure 1, the adjacent grid conductors that read a high leakage current to ground through the water path identify the grid section with a membrane breach. Figure 1: Basic measuring circuit and illustration of membrane breach locate. 2
3 A moisture leakage path through the roof membrane will usually cause any selected grid conductor to measure some level of leakage current. To avoid stray current that can create significant error in the membrane breach location survey, all detection conductors not selected for current measurement are connected to a special guard circuit. The guard circuit forms an electric shield between the selected conductor and any other current leakage sites beyond the conductors immediately adjacent to the selected conductor. This eliminates stray current errors and makes this method feasible. EXPERIMENTAL RESULTS Initial tests of the membrane leak locate method were carried out on the roof membrane above a parking garage under construction. The membrane is hot fluid-applied rubberized asphalt with a covering protection board. As shown in Figure 2, a four foot-by-four foot moisture detection tape grid was placed over a 16 foot square section of the roof membrane. The conductor ends were spliced to connecting cables and terminated on a switching box. A 150K ohm membrane fault level was made in the area bounded by the X3-X4 and Y1-Y2 grid locations. The area was wetted down, the measurement system energized and the individual grid tape leakage currents were measured. As illustrated in Figure 2, the measured currents are drawn on the X and Y axis with the Z (or vertical) axis showing the current magnitudes at each grid line. Current maximums occur at the Y1 and Y2 grid lines on the Y axis and the X1 and X2 grid lines on the X axis which encloses the damage site. Figure 2: Leak locate test set-up on parking garage roof membrane Mock-up tests were then carried out at RCABC using a grid of detection tape conductors installed on top of a TPO roof membrane that was laid over a concrete deck (Figure 3). Six 3
4 strips of detection tape conductors were placed on top of the membrane in both X and Y directions. Connecting cables from the grid conductors were terminated on a manual switch box to allow scanning of the individual conductors for leakage current while placing all other conductors in a guard circuit arrangement. Controlled defects were then made in the membrane and the entire surface wetted. Electric conductance tests were then carried out to evaluate the effectiveness of the fault locate method. Figure 3: Photo of grid mock-up and lab test equipment used in initial evaluations Several tests were performed in various locations, all with similar results. A typical conductance scan leak locate result is shown in Figure 3. Prior to creation of a damage site the site was wetted and tested for residual leakage. No leakage current was detected. A defect of approximately 1/8 inch in diameter was made in the area bounded by the X4-X5 and Y4-Y5 grid locations. The measurement system registered a total leakage current of 1.54 ma with an applied potential of 50V dc thereby giving a fault resistance through the membrane of 32.4 k ohms. The graphs in both X and Y directions show a distinct increase in leakage current on the X4, X5, Y4, and Y5 grid conductors, which corresponds to the fault area bounded by the grid coordinates. Figure 4: Graphs of measured grid-to-deck leakage currents in X and Y directions 4
5 FIELD INSTALLATIONS Several successful installations have been carried out on over 1,500,000 square feet of waterproofing membrane on projects ranging from green roofs of several hundred square feet (Figure 5) to plaza decks and reservoir caps (Figure 6) of 270,000 square feet or more. Although not discussed in this paper, a quality control electric conductance membrane survey which uses the same measurement principal as the grid system is carried out to ensure that there are no membrane breaches prior to installation of the grid system. These systems have been deployed over the last few years with an increasing interest in application on inverted roof systems. In a few of the installations post-construction membrane leaks have been detected, located and repaired with minimum disruption of the overburden or green roof. Figure 5. Leak locate grid installed on membrane of an intensive green roof system Figure 6. Survey followed by leak locate grid installation on a large reservoir membrane DISCUSSION Leak-locate grid conductors installed on top of waterproof membranes, if monitored on a regular basis, can provide early detection and location of membrane damage. This method is particularly useful for roof designs that incorporate a fully adhered nonconductive waterproofing membrane 5
6 under a green roof, wear-course or topping slab where direct inspection of the roof membrane is difficult or impossible. By performing a routine leak detection and locate procedure, membrane breaches can be quickly identified and localized to a grid size area. A top-of-membrane grid system provides an accurate and cost effective method to monitor and maintain a wide range of covered roof types and sizes. REFERE CES 1. David M. Bailey et. al., Survey of Passive Leak Location Technologies, US Army Corp of Engineers Construction Engineering Research Laboratories, USACERL Technical Report FM-94/04 2. K.Y. Liu and A. Baskaran, Using Garden Roof Systems to Improve Performance, National Research Council Canada, NRCC Z. Lounis, D. J. Vanier and M. A. Lacasse, A discrete stochastic model for performance prediction of roofing systems, CIB World Building Congress, "Construction and the Environment", June 7-12, 1998, Gävle, Sweden 4. ASTM D 5957 Standard Guide for Flood Testing Horizontal Waterproofing Installations, Developed by Subcommittee: D08.22, Book of Standards Volume: Canadian Roofing Contractors Association/Association Canadienne Des Entrepreneurs En Couverture, Advisory Bulletin March Graeme Cesare Consiglio, Foreword: The Challenge, Building Science Insight '89, "Roofs that Work", Vokey, D., et al, (2006, summer). A Building Envelope Moisture Detection System Using Contiguous Zone Monitoring. OBEC, Hensley, Lester, Sweeping deck joints under the rug, GoStructural.com, Feature Article, Monday, May 01, Hedlin, C.P., CBD-179. Inspection and Maintenance of Flat Roofs, Canadian Building Digest, July Mendel, Bart, Anatomy of a Plaza Deck, FOCUS, CAI, Greater Los Angeles Chapter, May/June
1.0 Introduction. 2.0 Importance of Integrity Testing. 3.0 How Does EFVM Work? 6.0 Conclusion
5.4.4 Intrusion Discovery Once it was determined through water testing where the approximate location of the roof leak was, roof tiles were removed to examine the underlayment and roof sheathing. By following
Roofing & Waterproofing Forensics for the 21 st Century. Peter Brooks, President
Roofing & Waterproofing Forensics for the 21 st Century Peter Brooks, President March 20, 2013 ICRI Spring Convention Selecting the Appropriate Non-Destructive Testing Technology What is the Goal? Methodologies:
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
Chapter 3: Non-Destructive Testing
Chapter 3: Non-Destructive Testing After completion of the detailed visual inspection by the working group, on-board nondestructive testing (NDT) was performed on-site on selected wiring harness of all
Errors Related to Cable Resistance Imbalance in Three Wire RTDs
Errors Related to Cable Resistance Imbalance in Three Wire RTDs 1.0 Introduction There are multiple sources of error that can impact the accuracy of an RTD measurement. The cable incorporated into the
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES
SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon
6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20
USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure
Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado
Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
Exterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
SMA Waterproof. Cable Assembly. Filtered Audio Connector. Dataport Receptacle. Dataport Plug
INTERCONNECT SOLUTIONS FOR RUGGEDIZED COMMUNICATIONS GPS Antenna Gooseneck Adapter TNC Waterproof Cable Assembly Communication radios often carry critical public safety information and must operate reliably
WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.
WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Heating Cable. Construction
Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant
Title: Grounding and Bonding Rev-01
Procedure No.: BMEHS-002-012 Page: 1 of 12 Preparer: Owner: Approver: EHS Team Member S/H Manager Site Manager Signed Copy on File Signed Copy on File Signed Copy on File Document Revision Change Table
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller
BLZPTS-1 NOVEMBER 19, 2013 TS350 TS752 BLPS PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller DESCRIPTION The BLPS, TS350
WORLDWIDE. GW400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION
ORLDIDE G400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION GEOQUIP LIMITED Kingsfield Industrial Estate, Derby Road irksworth, Matlock, Derbyshire, DE4 4BG Tel : 01629 824891 Fax : 01629 824896
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Boggarm S. Setty, P.E., Fellow ASHRAE Setty & Associates, Ltd. 3040 Williams Drive, Suite 600, Fairfax,
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Construction Electrical Terminology. Electricians
Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.
Insulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Electric Heat Tracing INSTALLATION PROCEDURES
INSTALLATION PROCEDURES The following installation procedures are suggested guidelines for the installation of a Thermon electric heat tracing system 1. Individuals installing these products are responsible
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand [email protected] Florian Speier, Zola Windows [email protected] Paul Grahovac,
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
ACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
SECTION 19 RESIDENTIAL CONSTRUCTION IN FLOODZONES
SECTION 19 RESIDENTIAL CONSTRUCTION IN FLOODZONES The purpose of the following information and documents are to clarify procedures used by the Sonoma County Permit & Resource Management Department to enforce
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
A Guide to Retrofitting an Existing Roof to a Vegetated Green Roof
A Guide to Retrofitting an Existing Roof to a Vegetated Green Roof Marc A. Loranger, P.E., LEED AP Associate Gale Associates, Inc. Richard Stewart Buildings & Grounds Facilities Manager Simmons College
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
BLUESTAR INFRARED. Description: Thermal Properties Comparison. Project Location: Client: 759 South Federal Hwy 225 Bayshore Drive 800-216-1820
BLUESTAR INFRARED We Bring Bad Things to Light SERVING ALL OF FLORIDA Infrared Inspection Services 24 Hour Emergency Service I n f r a r e d I n s p e c t i o n R e p o r t 772-215-8794 Description: Thermal
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Roofing 101 - Signs that Your Roof Needs Repair/Replacement
By: Cherie Martel Roofing 101 - Signs that Your Roof Needs Repair/Replacement 1. Tell us a little bit about your company and its foundation. In 1963, Samuel T. Martel began a small family run roofing company,
Detection of Contact Voltage in Electric Distribution Systems
Detection of Contact Voltage in Electric Distribution Systems David Kalokitis CTO [email protected] Power Survey Company www.powersurveyco.com (888) PSC-2008 Who is Power Survey Company? Core
Essential Performance Attributes of Preapplied waterproofing
Essential Performance Attributes of Preapplied waterproofing Craig Boucher, LEED AP Grace Construction Products 62 Whittemore Ave., Cambridge, MA 02140 Phone: 617-498-4429 Fax: 617-498-4419 E-mail: [email protected]
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
Infrared Moisture Detection
What it can do for you... what it can t and why 1. Infrared camera basics 2. Examples Lew Harriman MoistureDM.com 3. Summary - The 4 most important facts about infrared moisture detection 1 of 19 Infrared
STANDARD PROCEDURES FOR ROOF MOISTURE SURVEYS
TESTING APPLICATION STANDARD (TAS) 126-95 STANDARD PROCEDURES FOR ROOF MOISTURE SURVEYS 1. Scope 1.1 This Protocol covers the procedures for nondestructive testing for the presence of moisture, and the
Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR
Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for
SELF-REGULATING PIPE TRACING HEATER CABLE
SELF-REGULATING PIPE TRACING HEATER CABLE Installation & Operation Manual TABLE OF CONTENTS GENERAL INFORMATION... 1 How Heating Systems Work...1 PRODUCT SELECTION... 1 RECEIPT & STORAGE... 1 Receipt...1
WHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
HSG Engineering Tech Bulletin
Specifications subject to change OCT 2013; Rev. 1.3 HSG Engineering Tech Bulletin Recommended RS-485 Wiring for NetAXS-4/NetAXS-123 Loops Overview This document provides the recommended RS-485 wiring for
I S S U E 1/2013 VOLUME 30 NUMBER 1. Water Testing: Richard P. Kadlubowski, AIA and Courtenay Bauer
I S S U E 1/2013 VOLUME 30 NUMBER 1 Journal of architectural technology published by Hoffmann Architects, Inc., specialists in the rehabilitation of building exteriors. Water Testing: A Tool for Owners
How To Control Water Penetration In A Window
WATER PENETRATION CONTROL FOR WINDOWS A SERVICE LIFE APPROACH David R. Ricketts, P.Eng. 1 and Silvio Plescia, P.Eng. 2 INTRODUCTION Building envelope performance problems and their close link to poor window
University of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery
University of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery Yellow Alert for Mayflower Residence hall Peak at 31.5 feet Power Plant floods from steam tunnel and shuts down 1993 Flood
DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com DET3 Contractor Series 3-Terminal DET3 Contractor Series 2 and 3 point testing
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.
SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation
Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:
Alloy 825 Sheath Custom Fabricated Heating Elements Magnesium Oxide Insulation Description: Mineral insulated cable is a metal sheathed cable that uses a metallic conductor as the heating element. The
RECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM
Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM The following is the Los Angeles Fire Department s minimum requirement for Solar Photovoltaic System Installations. The City of
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
ACL 395 Resistivity Meter
ACL 395 Resistivity Meter OPERATION MANUAL Meter is warranted for one year from the date of purchase on parts and labor. Calibration is recommended every 12 months. 840 W. 49 th Place Page 1 of 13 [email protected]
Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015
PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015 FACILITIES & MAINTENANCE By Rick Thomas Fluid-Applied Roofing for Repair and Renovation Leaking roofs are one thing which every private university facility
GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
Town House 11265 Center Highway North Huntingdon, PA 15642
APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House
Table of Contents. Inductive Loop Vehicle Detector Applications
Table of Contents Introduction Design Essentials Loop Installation Techniques Determining Loop Phasing Equipment Installation 1 020907 Inductive Loop Vehicle Detector Applications Parking Revenue Control
University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage
University of Missouri Hospitals and Clinics Structural Repair and Protection of Post-tensioned Parking Garage 1 University of Missouri Project The University of Missouri Health Care Patient and Visitor
Cable and Pipe Locating Techniques
Cable and Pipe Locating Techniques for use with 3M Dynatel Cable and Pipe Locators August 1998 80-6108-6216-3-C 1 2 Table of Contents Section 1 The Basics of Cable Locating 1. Introduction... 7 2. Applying
Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
Nondestructive Evaluation of USCG. 2401 Hawkins Pt. Road Curtis Bay, MD 21226. Provided by: HurleyIR
Nondestructive Evaluation of USCG 2401 Hawkins Pt. Road Curtis Bay, MD 21226 Provided by: HurleyIR On Tuesday May 20 th 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers of the USCG
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual
0 P a g e H.264 Color or Day/Night SurroundVideo Installation Manual Inside the box: A. Arecont Vision SurroundVideo camera B. Mounting template C. RJ45 female to female coupler D. Hex key E. Security
Complete Solar Photovoltaics Steven Magee. Health and Safety
Health and Safety Health and safety around solar photovoltaic systems is very important. In the DC circuit you will find up to 600 volts in residential and commercial systems. In utility systems you may
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box 820129 Houston, Texas 77282 (713) 465-0000
www.ableinfrared.co www.flirthermography.com INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box 820129 Houston, Texas 77282 (713) 465-0000 CLIENT: PROPERTY SURVEYED: EMAIL: DATE: In accordance
NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW
VAZATA 9651 Hornbaker Road Manassas, VA 20109 VAZATA.COM VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from the ground up to deliver highly reliable and
Aerial Infrared Roof Moisture Surveys
Aerial Infrared Roof Moisture Surveys INTRODUCTION IR P/PM (infrared predictive/preventive maintenance) is not limited to annual infrared surveys of electrical switchgear. For instance, infrared thermography