WHITEPAPER CABLE CONDUCTOR SIZING

Size: px
Start display at page:

Download "WHITEPAPER CABLE CONDUCTOR SIZING"

Transcription

1 WHITEPAPER CABLE CONDUCTOR SIZING FOR MINIMUM LIFE CYCLE COST Bruno De Wachter, Walter Hulshorst, Rodolfo di Stefano July 2011 ECI Available from

2 Document Issue Control Sheet Document Title: Publication No: White Paper Cable Conductor Sizing for Minimum Life Cycle Cost Cu0105 Issue: 01 Release: 06/07/2011 Author(s): Reviewer(s): Bruno De Wachter, Walter Hulshorst, Rodolfo di Stefano David Chapman, Hans De Keulenaer, Stefan Fassbinder Document History Issue Date Purpose Prepared Approved 1 06/07/2011 Initial publication 2 3 Disclaimer While this publication has been prepared with care, European Copper Institute and other contributors provide no warranty with regards to the content and shall not be liable for any direct, incidental or consequential damages that may result from the use of the information or the data contained. Copyright European Copper Institute. Reproduction is authorised providing the material is unabridged and the source is acknowledged. Page i

3 CONTENTS Summary... 1 Optimum is several times larger than standard... 2 Cable sizing according to the standards... 2 Economical cable sizing: the basics... 4 Searching for the cross section with lowest LCC... 5 Recalculating the cost to a present value... 5 Taking the actual loading of the cable into account... 5 Isolating cable characteristics from operational and financial values... 5 Optimal cross section depending on the cable price... 6 An example of a calculation... 6 Table with optimal values... 7 Searching for the current density with lowest LCC... 7 Calculating the losses based on the current density... 7 The cost of energy losses per ton of conductor material... 8 Choosing an optimal current density for a particular economic lifetime... 8 Graphical representation... 8 Taking the scrap value into account... 9 Table with optimal values Additional advantages of larger cross sections Improved power quality Increased flexibility Round-up Annex Table with a few optimal conductor cross sections Table with a few optimal current densities Page ii

4 SUMMARY Energy prices are high and expected to rise. All CO 2 emissions are being scrutinized by regulators as well as by public opinion. As a result, energy management has become a key factor in almost every business. To get the most out of each kilowatt-hour, appliances must be carefully evaluated for their energy efficiency. It is an often overlooked fact that electrical energy gets lost in both end-use and in the supply system (cables, busbars, transformers, etc.). Every cable has resistance, so part of the electrical energy that it carries is dissipated as heat and is lost. Such energy losses can be reduced by increasing the cross section of the copper conductor in a cable or busbar. Obviously, the conductor size cannot be increased endlessly. The objective should be the economic and/or environmental optimum. What is the optimal cross section necessary to maximize the Return on Investment (ROI) and minimize the Net Present Value (NPV) and/or the Life Cycle Cost (LCC)? This paper will demonstrate that the maximizing of the ROI results in a cross section that is far larger than which technical standards prescribe. Those standards are based entirely on safety and certain power quality aspects. This means there is room for improvement a great deal of improvement in fact. We will calculate the conductor cross section for minimum LCC and maximum RoI. Two different models are used in this presentation: 1) The first model (see page 4) is more detailed and calculates the most economical cross section for a specific cable connection. 2) The second model (see page 6) is ideal for obtaining an approximation of the ROI with copper conductors and for developing a company-wide policy for cable sizing, independent of the particular rated current of a single connection. It calculates the optimal current density. Calculating the environmental optimum using a Life Cycle Analysis (LCA) is not within the scope of this whitepaper. However, it is worth mentioning that this environmental optimum lies at an even larger cable cross section than the economic one. Indeed, the environmental impact of energy losses quickly mounts to high levels compared to the environmental impact of copper a 100% recyclable material. Page 1

5 OPTIMUM IS SEVERAL TIMES LARGER THAN STANDARD The following examples show the order of magnitude of the gap between the technical minimum standard and the economic optimum. Take for instance a cable with a rated current of 100 A and a nominal voltage of 230 V. According to the minimum technical standard, this cable should have a minimum cross section of 25 mm 2 to avoid excessive heat production. The economic optimum depends on market and operational conditions. Assume an electricity price of 100/MWh, a cable price of 0.30/(mm 2 x m), a life time of 10 years, and an interest rate of 7.5%. Furthermore, suppose an average loading of 65% over 3,700 hours per year (42% of the time). Those figures result in an optimal cable section of mm 2, a cross section that is nearly three times the standard. Assuming an average loading of only 40% during a mere 1,400 hours per year (16% of the time) for the same cable, electricity prices, and lifetime of 10 years, the optimal cable section would still be mm 2, or nearly twice the safety standard. The following chapters will show how those calculations are made. CABLE SIZING ACCORDING TO THE STANDARDS The international technical standards for cable sizing take safety and certain power quality aspects into account, but NOT energy efficiency. According to these technical standards, the minimum cross section of a cable is defined by the most stringent of three restrictions: 1) The thermal impact of the maximum rated current 2) The voltage drop created by the maximum rated current 3) The electro-dynamic impact of the strongest short circuit current The first restriction is defined in the technical standard IEC (Electrical Installations for buildings): The heat production in the cable should be restricted to avoid the creation of hot spots that could affect the insulation quality or which could be dangerously hot to touch. By choosing a sufficient cross section for the cable, its electrical resistance will remain low, as will the production of heat. The second restriction is stipulated in the standard DIN : : The maximum rated current will create a voltage drop in the cable. This should not be higher than 3% of the nominal voltage to ensure the proper functioning of all appliances. By choosing a sufficient cross section for the cable, its electrical resistance will remain low, as will the voltage drop. The third restriction is defined in the technical standard IEC (Short-circuit currents in three phase AC systems): The short-circuit current I sc, multiplied by the time-current curve of the circuit breaker, should not cross the time-current characteristic expressing the electro-dynamic strength of the cable. The latter is proportional to the cable cross-section. Page 2

6 For shorter cables and/or higher voltages, the first restriction (heat production) will be the most stringent in most cases. For longer cables and/or lower voltages, the second restriction (voltage drop) that will be the most stringent in most cases. This whitepaper will demonstrate that a fourth criterion should be taken into account when choosing the conductor cross section: 4) The cost of the total energy losses in the cable over its economic lifetime should not be higher than the investment cost of the cable. This whitepaper will show that this fourth criterion will be the most stringent in the large majority of the cases. Page 3

7 ECONOMICAL CABLE SIZING: THE BASICS The power losses in a cable at a given moment in time can be calculated using the following formula: P loss = I 2 x (ρ/a) x l With: I = the current in the conductor (depending on the load) ρ = the specific electrical resistance of the conductor A = the cross section of the conductor l = the length of the cable This should be multiplied by the total time of operation over the lifetime of a cable to obtain the total lifetime energy losses E l : E losses = (I 2 x (ρ/a) x l) x t life We see that the energy losses are inversely proportional to the cross section of the conductor. The investment cost of the cable, on the contrary, increases close to linear with its cross section. The economic cable cross section will be the point where the sum of the investment cost and the cost of the losses goes through a minimum. C Total = C Investment + C Losses Page 4

8 SEARCHING FOR THE CROSS SECTION WITH LOWEST LCC Even though the basic principle is simple, calculating the cable section S leading to the lowest life cycle cost C Total introduces a few complexities. C Total = C Investment [S] + C Losses [1/S] RECALCULATING THE COST TO A PRESENT VALUE The initial step in this process is to recalculate the cost of the losses to reveal the operational cost at the date of installation. An interest rate (i) should be set, as well as the economic lifetime of the cable (n). The cost of the losses should then be multiplied by the following capitalization factor: N (i,n) = ((1 + i) n 1) / (i (1 + i) n ) Moreover, the average electricity tariff (T) over the economic lifetime of the cable should be estimated. This leads to the formula for the cost of the energy losses: C losses = (I 2 x (ρ/a) x L) x t econ life x T ariff electr ( /kwh) x N(i,n) TAKING THE ACTUAL LOADING OF THE CABLE INTO ACCOUNT A second point is that the cable will not be loaded at its rated power continuously. This means the time t is not the complete economic lifetime of the cable, but only the time the cable will be loaded: t operational hours econ life. Moreover, the current I will not be the rated current, but the average of the currents that really flow through the cable, a figure that depends on the average relative loading P loading = P load /P rated. I real = (I real /I rated ) x I rated = (P load /P rated ) x I rated = P loading x I rated with P loading a figure varying between 0 and 1 This leads to the following equation: C Losses = (P loading ) 2 (I rated 2 x (ρ/a) x l) x thours x T ariff [ /kwh] x N (i,n) ISOLATING CABLE CHARACTERISTICS FROM OPERATIONAL AND FINANCIAL VALUES Now we can put all the factors which are not cable characteristics into one operational and financial value F. F = (P loading ) 2 x t hours x T ariff [ /kwh] x N (i, n) The following table gives a few average values for F per sector. Industry Interest N (year) Energy Price (euro/mwh) Loading T (hours) F (euro/w) Iron 7,5% % ,62 Non Ferrous 7,5% % ,62 Paper 7,5% % ,62 Chemical 7,5% % ,88 Datahotel 7,5% % ,32 Office 7,5% % ,43 Page 5

9 In general industrial conditions, F will vary between 0.5 and 20 /W. The average value of F across all European industry sectors is 4.24 /W. For a long-term investment in a cable that will be constantly loaded close to its rated power, F can rise above 50 /W. The LCC formula now becomes: C T = C I + C L C T = C I[S] + 1/A x I rated 2 x ρ x length x F OPTIMAL CROSS SECTION DEPENDING ON THE CABLE PRICE The specific resistance of a copper conductor is µω*cm at a typical operating temperature of 105 C (1.720 µω*cm at 20 C) or mω*mm. Consequently, the equation for one meter of cable (1,000 mm) now becomes: C T = C c x A + 1/A x I r 2 x x F With: C c the cable price in euro per mm 2 cable cross section and per meter cable length A the cable cross section expressed in mm 2 I r the rated current in Ampère F the operational and financial value in /Watt This equation gives the total Life Cycle Cost of 1 meter of cable in euro. The optimal cross section A of a cable is the point where the curve of this equation goes through its minimum. It can be proved mathematically that this minimum will always lie at the point where the first part and the second part of the sum are equal. This occurs when: C c x A = 1/A x I r 2 x x F Or: A 2 = I r 2 x x F / Cc We can calculate the optimal cross section A from: A = I r x x (F/C c ) 1/2 With I r the rated current of the connection, F a financial and operational value varying per sector, and C c the cable price per meter and per mm 2 cross section. AN EXAMPLE OF A CALCULATION Assume a cable in the Iron Sector that will carry a rated current of 200 A. The average loading in this sector is 65%, while the average operating time is 3,700 hours per year. If the additional assumptions are an interest rate of 7.5% and an economic lifetime of 10 years, the F factor will be 7.62 euro/w. At the current copper price, the cost of one meter of cable (3 phases + neutral) can be estimated to be approximately 0.30 per square millimeter of conductor cross section: 0.30 /(mm 2 x m), or for each of the four conductors. Page 6

10 The most economical conductor cross section for this cable will be: A = 200 x x (7.62/0.30) 1/2 = mm 2 Note that according to the technical standard, the minimum conductor cross section for this cable should only be 53 mm 2. TABLE WITH OPTIMAL VALUES There is a table in the annex providing the optimal cross section for a number of representative sectors, depending on the rated current I r. SEARCHING FOR THE CURRENT DENSITY WITH LOWEST LCC The calculations executed above are relevant for anyone interest in the most economical cross section for a single connection. However, to develop a general, company-wide policy for cable sizing, the optimum should be expressed in terms that are independent of the particular rated current of a single connection. This can be accomplished by setting a general, company-wide figure for the ratio between the current and the cross section. This figure is also called the current density (A/mm 2 ). CALCULATING THE LOSSES BASED ON THE CURRENT DENSITY How can the optimal current density for a company be set? Remember that the goal is to minimize the Total Present Value of the cables throughout the entire company. This Total Present Value will be composed of an investment cost paying for the material plus the cost of losses that are induced in this material over its economic lifetime, recalculated to the present time. Those losses per amount of conductor material are related to the current density: P losses = I r 2 x ρ/a x L If J = I r /A is the current density, then it follows that: P losses = J 2 x A 2 x ρ/a x L = J 2 x A x L x ρ = J 2 x V olume x ρ In other words, the power loss per volume is: P losses / V olume = J 2 x ρ Or with the density of copper being 8.94 ton/m 3 and the value of ρ being µω*cm at an average operating temperature of 105 C (1.720 µω*cm at 20 C), we get: P losses [kw/ ton] = (J[A/mm 2 ]) 2 x 2.3 The power loss per ton of copper conductor is proportional to the square of the current density. Page 7

11 THE COST OF ENERGY LOSSES PER TON OF CONDUCTOR MATERIAL If the cable is fully loaded all the time, we must multiply P losses by 8,760 hours (one year) to get the annual energy losses. However, while not impossible, this is almost never the case. We therefore need a correction factor, the Hour-Loss-Equivalent (HLE). This figure is calculated by taking the average over the year of the (actual power/rated power) 2. To give an idea of this figure, the HLE in the electricity distribution grid in France is 3,050 hours. In most industrial sectors, this figure will probably be lower. A good estimate for HLE is HLE = 0.65 x W annual [TWh] / P total [MW] = 0.65 x HPE with W annual the total annual energy consumption of the site (= Work), P total the total power of the site, and HPE the Hour-Power-Equivalent. The annual cost of energy losses C annual energy loss of one ton of copper conductor: C annual energy loss / ton = T ariff [ /kw] x HLE x J 2 x 2.3 With T ariff the electricity tariff, HLE the Hours of Load Equivalent, and D the current density. CHOOSING AN OPTIMAL CURRENT DENSITY FOR A PARTICULAR ECONOMIC LIFETIME In the optimal economic situation, the sum of the losses that are induced in one ton of copper conductor over its economic lifetime should be equal to the investment cost, namely the cost of one ton of copper. If: The cost of 1 ton of copper cable = the cost of the energy losses induced in this ton of copper over its lifetime Then: The economic optimal current density is achieved This means the optimal current density can be calculated using: J = (C 1ton / (T ariff [ /kwh] x HLE x 2.3 x N(i, n))) 0.5 GRAPHICAL REPRESENTATION A graphical representation of the current density can be derived from the above equation. Suppose a current density of 1.4 A/mm². Note that this density is consistent with the example in the former calculation model (page 6), where the optimal conductor cross section was calculated to be 144 mm 2 for a cable of 200 A rated current. Page 8

12 Furthermore, suppose an HPE of 3,700 hours, an electricity price of 0.1 /kwh, and a copper price of 6,000 /ton. This copper price needs to be multiplied with an adjustment factor to get the actual cable price. A factor of 1.3 is a good estimate for this ratio, giving a cable price of 7,800 per ton of copper conductor used. INPUT DATA density (A/sq.mm) 1,4 loss (kw/ton) 4,508 HPE (hours) 3700 HLE/HPE 0,65 HLE/HPE x HPE 2405 electricity price ( /kwh) 0,1 yearly cost of loss ( ) 1084 cable price / ton copper 7800 Scrap value / new value 0 The graph that follows presents the curves for the cumulative annual losses, recalculated to the present time with interest rates of respectively 5% (purple), 7.5% (blue), and 10% (orange). The green curve represents the investment cost. Thus the economic lifetime of the cable will be 8.5 years, 10 years, and 12.5 years respectively. Varying the current density causes the economic lifetime to vary as well. The optimal current density can be found for a specific economic lifetime through iteration. Note that the payback period of 10 years for an interest rate of 7.5% is exactly the same as given in the example of the former model (page 6), meaning that both models are consistent. TAKING THE SCRAP VALUE INTO ACCOUNT There is still one element missing in the former example. When a copper cable is dismantled, the copper is not thrown away but recycled. The owner will receive a significant sum for the scrap. This scrap value should be recalculated according to current prices and subtracted from the investment value. Suppose for example a scrap value that is 50% of the value of new copper. INPUT DATA density (A/sq.mm) 1,4 loss (kw/ton) 4,508 HPE (hours) 3700 HLE/HPE 0,65 HLE/HPE x HPE 2405 electricity price ( /kwh) 0,1 yearly cost of loss ( ) 1084 cable price / ton copper 7800 Scrap value / new value 0,5 Page 9

13 In this case, the curves of the former example are as follows: The economic lifetime is reduced to approximately 5.5 years. To achieve a higher economic lifetime, a larger cable cross-section should be chosen. The higher the scrap value, the lower the current density should be chosen (= higher cross sections) to achieve a particular economic life-time of the cable. TABLE WITH OPTIMAL VALUES In the annex you can find a table providing the optimal current density depending on the loading (Hour Power Equivalent) and the chosen economic lifetime n. ADDITIONAL ADVANTAGES OF LARGER CROSS SECTIONS The advantages of a larger cable cross section are not limited to economic and ecological benefits. A larger cable cross section also has certain technical advantages, including increased power quality and the flexibility of the connection. IMPROVED POWER QUALITY When the cross section of a conductor is increased, the voltage drop over the line is reduced. This means that the voltage variation between a loaded and unloaded cable is reduced as well. As a result, power quality issues (harmonics, voltage dips, transients, etc.) will be less severe. Furthermore, since the line will be carrying a lower load, the risk of a power outage caused by an overload will be lower. INCREASED FLEXIBILITY The power of the load has to be estimated when a new connection is designed. This is not always an easy task. An increased cross section of the cable makes the connection more flexible in regards to a future increase in the load. As long as the cable remains within safety limits, the load increase will not require an immediate replacement of the cable. Page 10

14 ROUND-UP Technical standards prescribing the minimum cross section of cables take only safety and certain power quality arguments into account. However, the most economical cross-section is several times larger. This economical cross section follows from the minimum Net Present Value (NPV) of the cable, taking the energy losses over the lifetime of the cable into account. Calculating the NPV requires the rated current of the connection, as well as a few boundary values, such as the actual loading, the electricity tariff, the interest rate, and a chosen economic lifetime. A company-wide policy for choosing economic cable sections can be established by determining a preferred current density. This optimal current density will minimize the NPV of each ton of copper conductor, taking the energy losses over its lifetime into account. Calculating this current density requires the average loading of the cables, the electricity tariff, the interest rate, and a chosen economic lifetime. Once a company-wide current density is established, the optimal cross-section for each individual connection follows directly from the rated current. The optimal current density will be even lower if the scrap value of the copper is taken into account. This means the optimal cross-sections will differ even more from the standard. Note that economic and environmental advantages are not the only ones derived from using a larger cable cross section. It will also have a positive influence on power quality and increase flexibility regarding future load increases. Page 11

15 ANNEX TABLE WITH A FEW OPTIMAL CONDUCTOR CROSS SECTIONS For a cable price of 0.3 /(mm 2 x m) Economic cross section (mm2) I rated F = 2.43 (office) F = 7.62 (iron, paper) Standard cross section (mm2) , , TABLE WITH A FEW OPTIMAL CURRENT DENSITIES Optimal current density for lowest NPV of losses Economic HPE = 2000 HPE = 3000 HPE = 4000 Standard (approximately) n = 5 years n = 8 years n = 10 years n = 15 years i = 7.5% HLE/HPE = 0.65 Copper price = 6000 Cable price = 6000 x 1.3 = 7800 /ton of copper conductor Electricity cost = 0.1 /kwh Scrap value = 50% of the value of new copper Page 12

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

Energy Saving systems for Induction motors.

Energy Saving systems for Induction motors. Energy Saving systems for Induction motors. Are they a sham? Do they work? There seems to be a resurgence in interest in the Nola energy saving algorithm for induction motors, with a number of manufacturers

More information

Fuses. Introduction. Measuring is knowing. Who chooses?

Fuses. Introduction. Measuring is knowing. Who chooses? Fuses Introduction. There are many theories going around about the necessity for protecting PDUs (Power Distribution Unit / multiple socket / socket, etc.). A fuse is by definition a Single Point of Failure

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS 3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS Pierre FRISTOT Olivier CONSTANT Catherine MONCET Omegawatt - France Omegawatt - France SDET - France pierre.fristot@omegawatt.fr

More information

Cable Size Selection for Energy Efficiency

Cable Size Selection for Energy Efficiency Cable Size Selection for Energy Efficiency Introduction The traditional method for determining the appropriate cable size for a particular installation involves the selection of the smallest size conductor

More information

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR Standards : CENELEC HD 22.4 NF C 32-102-4 DIN VDE 0282-1 and VDE 0282-4 BS 6007 and BS 6500 IEC 60245-4 Rated voltage Rated voltage: 450/750 V (Use up to

More information

Life Cycle Cost: what does it really mean?

Life Cycle Cost: what does it really mean? Afdruk dd.27-12-2011 p.1 van 6 Life Cycle Cost: what does it really mean? Until recently BIM, Building Information Modelling, was the word of the town. Nowadays everyone seems to be talking about Life

More information

Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship

Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship By: Jason Smith; Manager Applications Engineer and Pat Malloy; Sr. Applications Engineer How much output voltage,

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Chapter 14: Inductor design

Chapter 14: Inductor design Chapter 14 Inductor Design 14.1 Filter inductor design constraints 14.2 A step-by-step design procedure 14.3 Multiple-winding magnetics design using the K g method 14.4 Examples 14.5 Summary of key points

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

The Electrical Properties of Materials: Resistivity

The Electrical Properties of Materials: Resistivity The Electrical Properties of Materials: Resistivity 1 Objectives 1. To understand the properties of resistance and resistivity in conductors, 2. To measure the resistivity and temperature coefficient of

More information

Inverter technology. bulletin

Inverter technology. bulletin Inverter technology application bulletin What is the inverter component? The inverter is an electronic power component that continuously varies the electricity supply frequency of an electric motor. The

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

POWER AND VOLTAGE RATING

POWER AND VOLTAGE RATING POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Eðlisfræði 2, vor 2007

Eðlisfræði 2, vor 2007 [ Assignment View ] [ Print ] Eðlisfræði 2, vor 2007 30. Inductance Assignment is due at 2:00am on Wednesday, March 14, 2007 Credit for problems submitted late will decrease to 0% after the deadline has

More information

Graphing Linear Equations in Two Variables

Graphing Linear Equations in Two Variables Math 123 Section 3.2 - Graphing Linear Equations Using Intercepts - Page 1 Graphing Linear Equations in Two Variables I. Graphing Lines A. The graph of a line is just the set of solution points of the

More information

Improved PFC Boost Choke using a Quasi-Planar Winding Configuration Dave Shonts Schott Corporation 1000 Parkers Lake Road Wayzata, MN 55391

Improved PFC Boost Choke using a Quasi-Planar Winding Configuration Dave Shonts Schott Corporation 1000 Parkers Lake Road Wayzata, MN 55391 Improved PFC Boost Choke using a Quasi-Planar Winding Configuration Dave Shonts Schott Corporation 1000 Parkers Lake Road Wayzata, MN 55391 Abstract- A novel approach to boost inductor design using a quasi-planar

More information

10 ma LED driver in SOT457

10 ma LED driver in SOT457 SOT457 in SOT457 Rev. 1 20 February 2014 Product data sheet 1. Product profile 1.1 General description LED driver consisting of resistor-equipped PNP transistor with two diodes on one chip in an SOT457

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

AS COMPETITION PAPER 2007 SOLUTIONS

AS COMPETITION PAPER 2007 SOLUTIONS AS COMPETITION PAPER 2007 Total Mark/50 SOLUTIONS Section A: Multiple Choice 1. C 2. D 3. B 4. B 5. B 6. A 7. A 8. C 1 Section B: Written Answer Question 9. A mass M is attached to the end of a horizontal

More information

Calculation of the Current Transformer Accuracy Limit Factor Application Note

Calculation of the Current Transformer Accuracy Limit Factor Application Note Calculation of the Current Transformer Application Note kansikuva_bw 1MRS 755481 Issued: 09.11.2004 Version: A/09.11.2004 Calculation of the Current Transformer Application Note Contents: 1. Scope...4

More information

Charger Output AC Ripple Voltage and the affect on VRLA batteries

Charger Output AC Ripple Voltage and the affect on VRLA batteries TECHNICAL BULLETIN 41-2131 Charger Output AC Ripple Voltage and the affect on VRLA batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products.

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW

A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW WE BRING GREEN SOLUTIONS TO YOU A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW Provided by A COOLER PLANET A Cooler Planet 1 The Complete Solar Guide WHY GO SOLAR? TOP FIVE FACTORS TO CONSIDER FOR ADDING

More information

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price

More information

50 W Power Resistor, Thick Film Technology, TO-220

50 W Power Resistor, Thick Film Technology, TO-220 50 W Power Resistor, Thick Film Technology, TO-220 FEATURES 50 W at 25 C heatsink mounted Adjusted by sand trimming Leaded or surface mount versions High power to size ratio Non inductive element Material

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

Current transformers (CT) & Shunts

Current transformers (CT) & Shunts Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar

More information

Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models

Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models Dave Staton, Douglas Hawkins and Mircea Popescu Motor Design Ltd., Ellesmere, Shropshire,

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

7. What is the current in a circuit if 15 coulombs of electric charge move past a given point in 3 seconds? (1) 5 A (3) 18 A (2) 12 A (4) 45 A

7. What is the current in a circuit if 15 coulombs of electric charge move past a given point in 3 seconds? (1) 5 A (3) 18 A (2) 12 A (4) 45 A 1. Compared to the number of free electrons in a conductor, the number of free electrons in an insulator of the same volume is less the same greater 2. Most metals are good electrical conductors because

More information

ISSN 1611-616X VULKAN-VERLAG ESSEN 2 2010 INTERNATIONAL MAGAZINE FOR INDUSTRIAL FURNACES HEAT TREATMENT PLANTS EQUIPMENT

ISSN 1611-616X VULKAN-VERLAG ESSEN 2 2010 INTERNATIONAL MAGAZINE FOR INDUSTRIAL FURNACES HEAT TREATMENT PLANTS EQUIPMENT ISSN 1611-616X VULKAN-VERLAG ESSEN 2 2010 HEAT PROCESSING INTERNATIONAL MAGAZINE FOR INDUSTRIAL FURNACES HEAT TREATMENT PLANTS EQUIPMENT http://www.heatprocessing-online.com Business ratios and their basic

More information

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions

More information

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Errors Related to Cable Resistance Imbalance in Three Wire RTDs Errors Related to Cable Resistance Imbalance in Three Wire RTDs 1.0 Introduction There are multiple sources of error that can impact the accuracy of an RTD measurement. The cable incorporated into the

More information

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747 POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609

More information

Vimpex Volt Drop Calculator

Vimpex Volt Drop Calculator Vimpex Volt Drop Calculator Instructions When a number of electrical/electronic products are connected to a cable (such as fire alarm sounders to a sounder circuit), the electrical current flowing in the

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

GroundRod AC Substation Earthing Tutorial

GroundRod AC Substation Earthing Tutorial 1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities

More information

Module 10: Assessing the Business Case

Module 10: Assessing the Business Case Module 10: Assessing the Business Case Learning Objectives After completing this section, you will be able to: Do preliminary assessment of proposed energy management investments. The measures recommended

More information

Ampacity simulation of a high voltage cable to connecting off shore wind farms

Ampacity simulation of a high voltage cable to connecting off shore wind farms Ampacity simulation of a high voltage cable to connecting off shore wind farms Eva Pelster 1, Dr. David Wenger 1 1 Wenger Engineering GmbH, Einsteinstr. 55, 89077 Ulm, mail@wenger-engineering.com Abstract:

More information

Using Excel (Microsoft Office 2007 Version) for Graphical Analysis of Data

Using Excel (Microsoft Office 2007 Version) for Graphical Analysis of Data Using Excel (Microsoft Office 2007 Version) for Graphical Analysis of Data Introduction In several upcoming labs, a primary goal will be to determine the mathematical relationship between two variable

More information

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

New OIML Document Surveillance of utility meters in service based on sampling inspections

New OIML Document Surveillance of utility meters in service based on sampling inspections COMMITTEE DRAFT OIML CD3 Date: 13 July 2010 Reference number: CD3 Supersedes document: CD2 (2006.02.16) OIML TC 3/SC 4 Circulated to P- and O-members and liaison international bodies and external organisations

More information

Voltage Drop. Voltage Drop 1

Voltage Drop. Voltage Drop 1 Voltage Drop The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences. Qualified person is defi ned in Article 100 of

More information

PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082

PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 General PTC-resistor temperature sensors (also called PTC-resistors or thermistors) are temperatur dependent semiconductor resistors

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an

More information

Rules for Classification and Construction Additional Rules and Guidelines

Rules for Classification and Construction Additional Rules and Guidelines VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 6 Test Requirements for Electrical Machinery Edition 1999 The following Guidelines

More information

Data Center Integrated solutions

Data Center Integrated solutions Data Center Integrated solutions PERFORMANCE AND RELIABILITY AT THE HEART OF DATA CENTERS The growing number of business and technical demands placed on data centers today are becoming increasingly critical:

More information

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5

More information

UPS Applications and VRLA Battery Sizing

UPS Applications and VRLA Battery Sizing TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the

More information

120W High Bay II Datasheet

120W High Bay II Datasheet 120W High Bay II Datasheet Solid-State Lighting Series Features : Solid State Lighting Technology Superior Light Quality Reduce CO₂ Emission Energy Saving(120W) Ecologically Friendly Long Life-Time IP65

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox HOME APPLICATION NOTES Iron Powder Cores for Switchmode Power Supply Inductors by: Jim Cox Purpose: The purpose of this application note is to cover the properties of iron powder as a magnetic core material

More information

Features. High Brightness LED Light source

Features. High Brightness LED Light source www.edison-opto.com Solid-State Lighting Series 6W MR16 DATASHEET Features High Brightness LED Light source Ecologically Friendly Energy Efficient General Information... 1 Product Dimensions... 2 Product

More information

Using NTC Temperature Sensors Integrated into Power Modules

Using NTC Temperature Sensors Integrated into Power Modules Using NTC Temperature Sensors Integrated into Power Modules Pierre-Laurent Doumergue R&D Engineer Advanced Power Technology Europe Chemin de Magret 33700 Mérignac, France Introduction Most APTE (Advanced

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

Lecture Notes: ECS 203 Basic Electrical Engineering Semester 1/2010. Dr.Prapun Suksompong 1 June 16, 2010

Lecture Notes: ECS 203 Basic Electrical Engineering Semester 1/2010. Dr.Prapun Suksompong 1 June 16, 2010 Sirindhorn International Institute of Technology Thammasat University School of Information, Computer and Communication Technology Lecture Notes: ECS 203 Basic Electrical Engineering Semester 1/2010 Dr.Prapun

More information

Chapter 21: The Discounted Utility Model

Chapter 21: The Discounted Utility Model Chapter 21: The Discounted Utility Model 21.1: Introduction This is an important chapter in that it introduces, and explores the implications of, an empirically relevant utility function representing intertemporal

More information

A 2020 Vision for Energy Efficiency in the UK

A 2020 Vision for Energy Efficiency in the UK Voltage Power Optimisation ESTA Bradford Event 28 th April 2010 A 2020 Vision for Energy Efficiency in the UK Presented by: Barry Taylor The challenges Financial Legislative Volatile electricity prices

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Transmission System Total Cost of Ownership

Transmission System Total Cost of Ownership Transmission System Total Cost of Ownership February 2013 Featuring GatesAir s Geoff Mendenhall Technology Advisor Copyright 2015 GatesAir, Inc. All rights reserved. Transmission System - Total Cost of

More information

Constant Voltage Charger Selection for VRLA Batteries

Constant Voltage Charger Selection for VRLA Batteries TECHNICAL BULLETIN 41-2129 Constant Voltage Charger Selection for VRLA Batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products. While much

More information

Carbon Cable. Sergio Rubio Carles Paul Albert Monte

Carbon Cable. Sergio Rubio Carles Paul Albert Monte Carbon Cable Sergio Rubio Carles Paul Albert Monte Carbon, Copper and Manganine PhYsical PropERTieS CARBON PROPERTIES Carbon physical Properties Temperature Coefficient α -0,0005 ºC-1 Density D 2260 kg/m3

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Estimation of electrical losses in Network Rail Electrification Systems

Estimation of electrical losses in Network Rail Electrification Systems Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16 Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE

More information

Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems

Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems 21, rue d Artois, F-75008 PARIS B1-215 CIGRE 2012 http : //www.cigre.org Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems Mike FAIRHURST (1), Ankit GOWADIA (1),

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models

Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models EE Modul 1: Electric Circuits Theory Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models EE Modul 1: Electric Circuits Theory Current, Voltage, Impedance Ohm

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Copper wire figures. AWG Table

Copper wire figures. AWG Table Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Copper wire figures NOTE: This information and the circuits

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive

More information

MATHEMATICS FOR ENGINEERING BASIC ALGEBRA

MATHEMATICS FOR ENGINEERING BASIC ALGEBRA MATHEMATICS FOR ENGINEERING BASIC ALGEBRA TUTORIAL 3 EQUATIONS This is the one of a series of basic tutorials in mathematics aimed at beginners or anyone wanting to refresh themselves on fundamentals.

More information

Photovoltaic System Overcurrent Protection

Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Introduction Solar Photovoltaic (PV) systems have, over the last fifty years, evolved into a mature, sustainable and

More information

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I) 00-00-//$0.00 (c) IEEE IEEE Industry Application Society Annual Meeting New Orleans, Louisiana, October -, Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part

More information

At Load Power Factor Correction Phase 2: Refrigerated Vending Machines

At Load Power Factor Correction Phase 2: Refrigerated Vending Machines At Load Power Factor Correction Phase 2: Refrigerated Vending Machines A Pilot Project to determine the feasibility and economics of small scale At Load Power Factor Correction Richard Ellenbogen, MEE

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

Definition AC Power Distribution

Definition AC Power Distribution COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility

More information

LOW-VOLTAGE CURRENT TRANSFORMERS

LOW-VOLTAGE CURRENT TRANSFORMERS LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS

More information

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 FUSES Catalogue CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Options for real options Dealing with uncertainty in investment decisions for electricity networks

Options for real options Dealing with uncertainty in investment decisions for electricity networks Options for real options Dealing with uncertainty in investment decisions for electricity networks Ype C. Wijnia Risk Manager of Asset Management Essent Netwerk Den Bosch, The Netherlands Ype.Wijnia@Essent.nl

More information