1 Fuses Introduction. There are many theories going around about the necessity for protecting PDUs (Power Distribution Unit / multiple socket / socket, etc.). A fuse is by definition a Single Point of Failure (SpoF) and therefore undesirable in a data centre. However, there are situations in which a fuse is necessary, sometimes even obligatory. We cannot therefore dispose of them by saying we don t want it and we therefore don t need them. Schleifenbauer Products has attempted to lay things out for you and has made an overview of what you should know about fuses in a PDU. Fuses can be applied in all types of PDUs but are mandatory in 32A models with 16A outlets, to guarantee safety. Fuses are also used to limit the damage caused by errors to just one segment on a PDU. Because of the intelligent measurements in the Schleifenbauer PDU, power consumption can in any case be monitored and an alarm can be given if it escalates into the danger zone. Measuring is knowing. Fusing is a drastic safety method. If the current exceeds a certain norm for a certain time, then it is abruptly switched off and all the devices after the fuse become powerless. It is as though you were in the dark on the edge of an abyss. Schleifenbauer PDUs are fitted with power meters that accurately indicate the actual power consumption. This enables you to take timely action if power consumption rises too high. It is, however, not always possible to measure power at every sublevel and short-circuits cannot be predicted by ampere meters. Therefore, fuses despite the presence of meters are unavoidable and you should make an informed choice about their application. Who chooses? The responsibility for choosing whether to use fuses or not, or which fuses will be used, is at all times the end user s, as long as it remains within the legal framework. From the information below, it will be apparent that no single best solution exists. The best solution will depend on the specific situation in your data centre and can therefore differ for every client. Schleifenbauer Products offers you the possibility to choose exactly the fusing that appears to be best for your situation. That is why we customise our PDUs for each customer.
2 Why fuses? There are two reasons for installing fuses in a PDU: 1) safety: one outlet (plug) must be protected from overloading by maximally the nominal value of the outlet. This means that a PDU that is connected to a 32A feed and has outlets with a maximum load of 16A (such as earth, Wieland or C19), must be protected by fuses of maximally 16A (C13 is an exception because one C13 has a maximum load of 10A, but since they are usually grouped together, it is permissible to protect them likewise with 16A fuses). 2) isolation of errors: another reason for fusing is the isolation of errors to a certain segment. A PDU without protection will be completely switched off in an error situation. A PDU with protection can isolate the error to a limited segment of the PDU and thereby guarantee the continuity of the remaining equipment. Safety at various levels has been incorporated into the installation network. See the diagram below. You could view a PDU in the same way. They are often connected to a power circuit with its own protection (sometimes shared with several other PDUs). If an error occurs after 2, then it is desirable that only fuse 2 is activated and not 1, because then the rest of the PDU would also be switched off. This is called selectivity. This is one of the most important parameters that must be well understood in order to make a proper decision about the use of fuses. 2 1 main fuse There is selectivity if one fuse will act sooner than the previous (main) fuse. If, in the above case, 2 always reacts earlier than 1, then we call this 100% selectivity of 2 with respect to 1. In practice however, 2 is only selective with respect to 1 up to a certain short-circuit current and not beyond it. What do you want to protect? sub-devider board It is good to first determine what you want to protect: do you wish to avoid the risk of overloading, short-circuiting or both? Overloading: Overloading takes place if more current is used over the long term than is permitted for the components in question. The speed at which the fuse is activated depends on the type and specifications of the fuse. Because our PDUs are always fitted with over-rated wiring, they can withstand such overloads and the fuse does not need to activate quickly. For protection against overloading only, we therefore advise a simple thermal fuse on a bi-metal basis. When the fuse is activated, it can be reset by the users themselves by pressing in the protruding switch. Short-circuiting: A short-circuit is a direct contact between the phase and the neutral (or earth), by which a current is created that is equal to the maximum short-circuit value at that point. It is important to know this value in order to make a proper choice for a safety device. The short-circuit current is greatest close to the source (transformer or UPS) and then reduces due to damping and losses in the wiring and transition resistance between all the intervening links and safety devices. A good electrician or installer can make a calculation of all the short-circuit currents in the data centre. Safety switches provide protection to a certain maximum short-circuit current. If the short-circuit current after a safety device (fuse) is higher than the value on this safety device, the risk of electrical arcing arises in the safety device. This can lead to fires and the current to the error is not(!) interrupted. This is thus extremely undesirable.
3 Types of fuse In the table below, you will find an overview of the fuses that can occur in Schleifenbauer PDUs. type Regular fuse Automatic fuse Thermal breaker remarks Consists of a cartridge and a holder. Fusing against overloading and short-circuiting by means of physical (and chemical) operation. Only interrupts the phase. Needs current to operate (voltage drop mV) There are 2 types of holder: simple holders with a screw cap without indication or DIN rail holders (the same shape as MCBs) with a bayonet fitting and indication. Has to be replaced after an error. Can be replaced by a different type of fuse. High resistance to short-circuiting. Accelerated aging with changing loads (in-rush current) MCB (Miniature Circuit Breaker) Operates on the basis of thermal energy (overloading) and a magnetic relay (short-circuit). Uses slightly less energy than a fuse. Also optional interruption of ZERO. Resettable after error or manual switch-off. More vulnerable to breakdowns than regular fuses. Must be replaced after 3 5 short-circuits. The fuses cannot be adapted. Selectivity has to be established by means of calculations. Normal short-circuit resistance of 6kA, also available with 10kA. Thermal (bi-metal) protection against overloading. Resettable after error. Uses relatively little power (voltage drop 240mV). Switches only the phase. Does not react (too slow) to short-circuiting and is thus not selective. Low short-circuit resistance of 2kA. Small and cheap. What do you need to know? In order to make a decision regarding fuses in your PDU, you will have to make a number of matters clear. Below, you will find a list of terms occurring in the decision process, with a brief explanation. Selectivity: As previously stated, selectivity is one of the most important characteristics of a fuse. Selectivity is a number that indicates to what extent a fuse will protect you against short-circuiting before the previous fuse(s) is/are activated. Between fuses there is a legally applicable selectivity of 1.6. This means that a 16A fuse is selective with respect to a 32A fuse but not a 25A fuse ( is 25.6). The selectivity between MCBs or in a mixed environment is more difficult to establish. We then have to project the time-link graphs for both fuses over each other, so that it becomes clear at what short-circuit current which fuse will activate first. The MCBs are usually provided with an indication of their selectivity class. This number doesn t mean anything yet, however. You have to have a calculation of the short-circuit current made in every location in the data centre. Only then, if you know the technical data of the previously placed fuse, can you establish whether a fuse is selective with its predecessor in the chain. Short-circuit current: The short-circuit current is the maximum current that can be generated at a certain point in the electrical system. The shortcircuit current close to the transformer or the batteries of the UPS is many times higher than the current that can arise in a 19 cabinet. This has to do with the damping influences of the power cables and all the transition resistances in the system. From this, it follows that a rack close to distribution panel will have a higher short-circuit current than a rack tens of metres
4 further away. There are programs that can calculate short-circuit currents. However, we advise you to have your electrician make a comprehensive diagram in which all the short-circuit currents are noted. With this document you will be better able to take decisions with regard to fuses in a PDU. Absorbed power: A fuse absorbs power. Since a fuse always reacts thermally (sometimes also magnetically), it is logical that a certain amount of the electrical energy is used to develop heat. If it is much too hot (current too high) then the fuse activates. The absorbed power is often indicated by the voltage drop across a fuse. This voltage drop multiplied by the current (I) is the absorbed power. A fuse that is heavily loaded (<80% of Inominal) will absorb a few (3 5) Watts of power. An MCB absorbs a little less power than a fuse. In the case of several fuses in a PDU (often with thermal breakers) the number of fuses more or less cancels out the lower power per fuse: 10 breakers each of 1.5A take up about the same power as 1 breaker of 15A passing through it. Environmental temperature: The environmental temperature affects the nature of a fuse. The higher the temperature, the sooner a fuse will react to overloading. You should take this into account if the PDU is mounted directly in the exhaust of the rack equipment. Maximum throughput energy: A fuse allows a certain amount of energy through before power transmission is interrupted. This energy is the throughput energy and can be calculated using the following formula: I 2 t (the short-circuit current squared times the time) this energy must be small enough so that no fires or damage can occur to the equipment or wiring. Usually, a regular fuse has a much smaller throughput energy than an MCB because the melting process is faster than the thermal-mechanical process in an MCB. Short-circuit resistance: This term indicates to what extent a safety device is resistant to short-circuit currents. A normal MCB usually has a shortcircuit resistance of 6000A (6kA). It is capable of switching loads up to 6kA. When the actual short-circuit current is higher than 6kA it means that there are chances of serious damage to the MCB, fire or the occurrence of a persistent electric arc, which allows the current through to the following wiring and will almost certainly cause a fire as well, are high. It is therefore very important to know what the short-circuit current is in the spot where you want to put a fuse. Thermal fuses usually have a higher short-circuit resistance: when the wire has melted, there is a great distance between the phase and the descending wiring. In a sand-filled fuse, the melting silver wire reacts with the silicon in the fuse and a type of glass wire with infinite resistance is created. Flexibility: Once an MCB or thermal fuse is built in, it cannot be replaced without removing the whole PDU. If it breaks down or wears out, the PDU has to be dismantled. A fuse can always be replaced without dismantling. A danger with this is that they could also be replaced with a fuse of the wrong value. A fixed fuse does not have this risk. Reliability: MCBs and thermal fuses work on a mechanical principle. The regular fuse works on the basis of physical and chemical reactions (melting and reacting). Both principles have advantages and disadvantages. MCBs have more than 100 components, which is in itself more vulnerable than a single silver (or any alloy) wire. In normal circumstances, the MCB has already proven itself as a reliable instrument. On the other hand, if an MCB has undergone several (3 5) short-circuit situations with high short-circuit currents, it must be replaced. Moreover, an MCB can fail in two ways: through long-term lack of use it can sometimes fail to switch off when necessary and sometimes, it will not switch back on after switching off. A regular fuse seems easier: it either works or it doesn t... however, a regular fuse can be weakened by brief power surges that create small melted points in the metal wire, due to which the characteristics of the fuse can change. Regular fuses also have more problems with aging than MCBs. Actually, regular fuses should be replaced every 2 3 years.
5 Ease of use: MCBs are unmistakably easier to use. A breakdown is immediately visible (even if the manual switch is fitted with a lock pin) and after an error, it can immediately be activated. MCBs must be replaced after 3 5 short-circuit situations. Therefore, an administrative system that registers which MCBs have had errors also has to be implemented. A regular fuse must be replaced after one error. The user must know where they are located. A logistics system has to be implemented for this. There is also the possibility that the fuse will be replaced by the wrong one, through which dangerous or undesirable situations could possibly arise. A defective cartridge can be replaced without any fuss and the holders seldom or never break down. MCBs, on the other hand, can break down due to their complexity or stick, due to which they will no longer switch when necessary. If an MCB breaks down, the whole PDU has to be switched off and repaired. The choice: The choice for a certain safety switch is ultimately the client s responsibility. This document is exclusively intended to provide you with information so that you can make the choice with more substantive knowledge. Two choices will have to be made: which fuse and how many? If protection from overloading only is sufficient for you, then a thermal breaker is a good and inexpensive option. You will hereby fulfil the legal requirements with regard to the protection of outlets. If you wish to protect against both overloading and short-circuiting, then the decision is a bit more complicated: you can choose from MCBs (installation of automatic) or regular fuses. The choice depends on the desired selectivity. It could follow from this that a regular fuse is preferable to an automatic one. The disadvantage of regular fuses is that the manager of the data centre has to implement a logistics system for the availability of the correct (!) fuses. A regular fuse can also easily be replaced by the wrong one, a risk that does not occur with MCBs. A disadvantage of MCBs is that they have to be replaced after a number of short-circuits. This means that the whole PDU has to be dismantled. MCBs contain more than 100 mechanical components, which makes them more vulnerable than regular fuses. These, however, have the disadvantage that they age over time which affects the values of the fuse and actually (depending on the loading) should be replaced every few years. In short, ideal protection does not (yet) exist. Indeed, there are developments in the field of electronic safety switches, but they are not yet available and will probably be much more expensive than current solutions. To make the proper choice you must therefore make sure that you have as much information as possible about your infrastructure (short-circuit currents, selectivity, etc.) and that you understand the consequences of your choice. The number of fuses you will use will depend on a number of situations: If there is a 32A feed present, you will have to use at least two 16A fuses, otherwise you can only use 16A of the 32A present. However, you can also opt to install more than 2 fuses, to limit errors in the system to as small an area as possible. If you also wish to apply this for short-circuiting, then you must pay close attention to the selectivity of the chosen fuse. A thermal breaker, for example, is not selective for short-circuiting. Regular fuses with MCB-shaped fuse holders and MCBs both take up a great deal of space.
6 MCB (automatic) Regular fuse advantages -Reusable -Optionally switch both phase and neutral -Can be used as a switch -More practical than regular fuses -Use (slightly) less power -After an error a new cartridge -More selective than MCBs -Allow less energy throughput -Can be replaced by a cartridge with different characteristics disadvantages -Have to be replaced after a number (3 to 5) of errors (short-circuits), depending on the shortcircuit current (how should it be administered?) -Less selectivity than regular fuses -Higher energy throughput than regular fuses -Take up a relatively large amount of space -Are relatively vulnerable -The PDU has to be dismantled with replacement -Not reusable -Logistics system needed for spare cartridges -Can conceal wrong cartridge -Age more quickly Conclusion. If you wish to protect your system against overloading and/or short-circuiting, you will have to analyse the chances of this occurring and the costs incurred if it happens. Overloading can be largely prevented by the readings on the ampere meters but short-circuits cannot be predicted. If the risks are too high, you will have to install fuses to limit the errors. The proper choice for the type of fuse can only take place if you have a detailed picture of the electrical system in your data centre. Schleifenbauer then makes a PDU with the fuses that are most suitable for your situation. Interesting background information on the subject of fuses can be found on the web site of EATON HOLEC: in the section vaktechniek (professional technology). Here you will find readable documents that go further into the technical details of safety devices. (Dutch only, sorry)
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
More informationPower Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
More informationData Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has
More informationTrade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More informationConsiderations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
More informationCircuit Breakers in Data Centers: The Hidden Danger
Circuit Breakers in Data Centers: The Hidden Danger How to efficiently protect critical IT equipment by choosing the most reliable overcurrent protection device for your Rack Power Distribution Unit. By
More informationCHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
More information6.0 Electrical Installations
6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is
More informationSection B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
More informationFire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
More informationUnit 4: Electricity (Part 2)
Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State
More informationSELECTION OF FINAL CIRCUIT PROTECTION
SELECTION OF FINAL CIRCUIT PROTECTION By Phil Williams, Product Marketing Manager, Power Distribution Components, Eaton Executive summary The selection of devices for final circuit protection in electrical
More informationPower distribution in data centres
Power distribution in data centres by Manuel Lotz / Matthias Ribbe White Paper 09 Copyright 2008 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49 (0)2772 505-0 Fax
More informationFuse Selection Guide
Fuse Selection Guide Although care is taken to properly design electrical and electronic circuits; overcurrents in the form of short-circuits and overload can occur. The sole purpose of fuses and circuit
More informationOdyssey of the Mind Technology Fair. Simple Electronics
Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right
More informationSSPI-APPN OTES: PARALLEL C ONNECTIONS
There are two distinct reasons to connect power supplies in parallel: Current Sharing and Redundancy. Combining of these reasons is common, and there are many ways to implement them. The unique considerations
More informationApplication Briefs: Remote Office Environment
Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small
More informationWHITEPAPER CABLE CONDUCTOR SIZING
WHITEPAPER CABLE CONDUCTOR SIZING FOR MINIMUM LIFE CYCLE COST Bruno De Wachter, Walter Hulshorst, Rodolfo di Stefano July 2011 ECI Available from www.leonardo-energy.org/node/156451 Document Issue Control
More informationABB Fuses Competitive Advantages
GPMM Tomasz Komalski 2009 ABB Fuses Competitive Advantages May 14, 2009 Slide 1 Basic comments ABB is a global manufacturer of both current limiting and expulsion (non-current limiting) fuses for medium
More informationTriac Printed Circuit Board Replacement
Technical Service Bulletin: Triac Printed Circuit Board Replacement TRONIC 5000C Pro Models: WH17, WH27, WH36 Introduction Fig. 1 ELECTRICITY IS EXTREMELY DANGEROUS. TAKE EXTRA PRECAUTIONS AND ENSURE ALL
More informationThe Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
More information2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved.
2 12 2010 PulteGroup, Inc. All Rights Reserved. circuit breakers Circuit breakers protect your home s system from power failure. The wiring in your home is protected by circuit breakers. Circuit breakers,
More informationIncreasing safety, reliability and efficiency for today s data centers
Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides
More informationCONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
More informationOptimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
More informationThe Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
More informationi ChatterBox! Motorcycle Security
i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before
More informationIntelligent power measurement in data centres
Intelligent power measurement in data centres Table of contents 1. About Schleifenbauer 02 2. Why measure power? 03 3. Portfolio of products 04 4. Customer-oriented, durable quality products 07 5. The
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
More informationCONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2
IT Power Solutions CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational
More informationAdvantages of a Company Switch vs. a Safety Switch Receptacle Combination:
Advantages of a Company Switch vs. a Safety Switch Receptacle Combination: Why a Company Switch Delivers Greater Benefits A Lex Products Corporation Whitepaper. Copyright 2012. Overview: Advantages of
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationDaker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
More informationProper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
More informationManage Data Center Power Consumption with Appropriate Intelligent Rack PDUs
Manage Data Center Power Consumption with Appropriate Intelligent Rack PDUs A report revealed by the NY Times on 2012-09-22 astonished the industry. Titled Power, Pollution and the Internet and based on
More informationTable of Contents. 1. Introduction...1. 2. PDU Package...2. 3. Function...3. 4. Installation...5. 5. Web Interface...7
PDU User Manual Table of Contents 1. Introduction...1 2. PDU Package...2 3. Function...3 4. Installation...5 5. Web Interface...7 1. Introduction The PDU is an Internet ready device designed and is equipped
More informationCo-location Interconnect Power Panel (CIPP) Installation Guide
Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...
More information3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
More informationComparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationElectrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
More informationPOWER AND VOLTAGE RATING
POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished
More informationHow To Protect A Motor From Overcurrent
Phase ailure elays Type PS and PD Class 8430 Catalog 04 CONTENTS Description.....................................................Page Product Description and Definitions......................................
More informationBrake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!
Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationData Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency
Data Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency White Paper STI-100-010 November 2013 HEADQUARTERS - NORTH AMERICA Server
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More informationTechnical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205. 8201 Schaffhausen 1 / 10
ABB ABB Schweiz AG Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205 09.04.2014 Page: 8201 Schaffhausen 1 / 10 Please use also the assembly instruction S800-RSU-H Remote
More informationDEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
More informationPARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS
PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS 2 Table of Contents Safety... 4 Introduction... 5 Features and Benefits... 6 Control Overview... 7
More informationshopinkelowna.com/mr--electric---home- Electrician-West-Kelowna/648681.htm
shopinkelowna.com/mr--electric---home- Electrician-West-Kelowna/.htm Website Visibility: by Search Engine % Keyword Rankings: Summary Search engine Keywords Moved Up/Down - - Keyword Rankings Keyword Affordable
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationVisit us on the web: www.autoshop101.com
This Automotive Series CIRCUIT PROTECTION has been developed by Kevin R. Sullivan Professor of Automotive Technology Skyline College All Rights Reserved Visit us on the web: www.autoshop101.com CIRCUIT
More informationMission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
More informationhttp://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for
More informationStructured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
More informationArc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
More informationHelp protect your home, possessions and family.
Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of
More informationTHE MclNTOSH MC 2100 SOLID STATE STEREO POWER AMPLIFIER
THE MclNTOSH MC 2100 SOLID STATE STEREO POWER AMPLIFIER Price $1.25 Your MC 2100 stereo amplifier will give you many years of pleasant and satisfactory performance. If you have any questions concerning
More informationServer Technology Inc.
Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,
More informationFIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
More informationCEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61
FUSES Catalogue CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More information101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
More informationLS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
More informationIMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
More informationInfrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
More informationOperating instructions Capacitive sensors
Operating instructions Capacitive sensors UK 700 / 00 0 / 009 Contents Safety instructions Functions and features Installation. Notes on flush and non-flush installation Electrical connection. Wiring.
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More informationHM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
More informationInstructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
More informationLDG DTS-4/4R Desktop Coaxial Switch / Remote
LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com
More information5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
More informationFuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.
Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting
More informationUser Manual of Grid Tie Inverter with Limiter
User Manual of Grid Tie Inverter with Limiter Grid Tied Inverter With Limiter (GTIL) 1 www.chinesegrid.com 2014-8-1 All rights reserved Why we produced the GTI-L --- It is in response to the overwhelming
More informationRC NETWORKS SALES GUIDE
SALES GUIDE INTRODUCTION TO Recent developments in electronic equipment have shown the following trends: Increasing demands for numerical control machines, robotics and technically advanced appliances
More informationWhat are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
More informationAlternating Phase Power Distribution at the Data Center Rack PDU
Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 November 2013 - Updated August 2014 By Steve Hammond, Product Manager, Server Technology Marc Cram, Director of
More informationPS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.
PS-6.1 Explain how the law of conservation of energy applies to the transformation of various forms of energy (including mechanical energy, electrical energy, chemical energy, light energy, sound energy,
More informationNEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL info@tuncmatik.com / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
More informationUncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection
More informationUser Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
More informationBe careful when designing robots with multiple motors under simultaneous or heavy loading. There are three main points to consider:
One of the most frustrating things that can happen to a team is losing control of their robot during a match. Please consider the following things that have been seen to cause problems at competition:
More informationPart 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
More informationTECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting
Sequence of Operations 1 Power supply and field wiring block 2 Energy Cut Off (ECO) 3 Water flow plunger and cold inlet 4 Magnetic flow switch 5 Water temperature thermistor 6 Control panel and circuit
More informationExploring the Necessity of the Hot Hipot Test
Exploring the Necessity of the Hot Hipot Test Introduction In an industry comprised of workers with varying electronics knowledge, a Hipot test can seem a daunting task for some. Indeed, many test operators
More informationApplication Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship
Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship By: Jason Smith; Manager Applications Engineer and Pat Malloy; Sr. Applications Engineer How much output voltage,
More informationNothing s BetterThan the Original MODAN Power Distribution Systems
MODAN www.eaton.com Nothing s BetterThan the Original MODAN Power Distribution Systems Modan Modular switchboard system Controlling and Distributing Power Safely Thinking further. Questioning the well-established
More informationCommon Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
More informationDucoterra Radiant Heating Panel Installation Manual
Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationRELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationPower & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
More informationResidual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
More information