BRUNS-PAK Presents MARK S. EVANKO, Principal
|
|
- Paulina Reed
- 7 years ago
- Views:
Transcription
1 BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations Friday, July 13, 2007
2 Agenda I II III IV High Density Computing Equipment and the Thermodynamic Evolution High Density Impacts to Data Center Costs Thermodynamic Model Impacts to the Data Center Designs/Retrofits Questions and Answers 2
3 Part I High Density Computing Equipment and the Thermodynamic Evolution 3
4 High Density Computing Equipment and the Thermodynamic Evolution The Data Center Solution Components (chant!) A. Computer Hardware B. Computer Software C. Telecommunications (Data/Tele) D. Facility Infrastructure The Recent Data Center History of the World The Early on Watts per sq. ft. Metric 1980/1990 The High Density Discussion/Announcement Associated with Blade Server Technology
5 High Density Computing Equipment and the Thermodynamic Evolution The Data Center Facility Infrastructure Transformation Discussion/Evolution from Capacity (watts per sq. ft.) to Distribution (cfm/static) The Retraction of Uptime Institute Spring 2006 Tier Ratings The Evolution of Facility Infrastructure Reliability vs. Data Processing Uptime The Role of Thermodynamic (CFD) Modeling One Size/Standard Facility Infrastructure Metric Does Not Fit All! GREEN/LEED Considerations: A) EPA Draft April 23, 2007 Server and Data Center Efficiencies 5
6 High Density Computing Equipment and the Thermodynamic Evolution Data center facility infrastructure summary reliability rankings: Numerical Rankings Terminology Summary Definition (1) Unreliable Shared building power and cooling; no generator (2) Partially Isolated, Unreliable (3) Isolated Unreliable (4) Isolated Conditioned (5) Isolated Improved (6) Isolated, Mostly Reliable (7) Reliable (8) Reliable Redundant (9) Ultra-Reliable (10) State of the Art Dedicated power system; shared cooling system; unconditioned power; non-redundant air conditioning; no generator Dedicated power and cooling systems; unconditioned power; non-redundant dedicated air conditioning units; no generator Dedicated power and cooling systems; conditioned power; non-redundant dedicated A/C units; no generator Dedicated power and cooling systems; uninterruptible power system; non-redundant dedicated A/C units; no generator Dedicated power and cooling systems; uninterruptible power system; redundant dedicated A/C units; no generator Dedicated power and cooling systems; uninterruptible power system; redundant dedicated A/C units; generator Dedicated power and cooling systems; redundant UPS systems; redundant dedicated A/C units; redundant generators Redundant power train; redundant cooling system; redundant UPS systems; redundant dedicated A/C units; redundant generator systems; redundant fuel system Redundant power train; redundant cooling system, redundant UPS systems, redundant dedicated A/C units; redundant generator systems; redundant fuel system; site hardened for weather and geographic exposures; location minimizes exposure to jurisdictional closure from hazardous spill, terrorism, or similar risks. 6
7 High Density Computing Equipment and the Thermodynamic Evolution Tier I % Tier II % Tier III % Tier IV % 7
8 High Density Computing Equipment and the Thermodynamic Evolution A. Historical Data Center Facility Infrastructure Baseline Mainframe and mini computer equipment platforms Older technology DASD Tape and tape storage Gross sq. ft. sample densities: 20 to 45 watts/sq. ft. computer equipment 8 to 24 inch raised floor Level 7 reliability Building office space generally sufficient for structural load and/or simply modified 7 6 to 9 0 distance from raised floor to underside of suspended ceiling Buss/tag cable dams in underfloor 8
9 High Density Computing Equipment and the Thermodynamic Evolution B. The Evolution of the Server, the Blade Server, and the Super Server Stand alone Rack mounted Population growth U vs. 2U v. 3U Blade servers The density of servers per rack 1 kw to 24/41/72++ kw The super server solution announced 3000 lb. devices over a footprint of approximately 11 sq. ft. with a 30 kw demand and 67kBTU of heat rejection! Chilled water Potential announcements of computer equipment manufacturers of 50/60/70+ kw stand alone computer equipment devices. Announced
10 High Density Computing Equipment and the Thermodynamic Evolution C. The Facility Infrastructure Impact Potential. NOTE: Each client must have their short/long term computer equipment growth projection modeled independently. There are no standard guidelines. WARNING! 100, 400, 700, 1000, watts per sq. ft. as interpreted from the computer equipment floor plan. 12 to 48 inch raised floor height. Level 7, 8, 9, 10 infrastructures depending on disaster recovery/mirroring plan. WARNING: Medical community with patient care applications. Structural loading exceeding 100, 300, 500 lbs. per sq. ft. Existing multi floor building structures do not have sufficient floor to underside of deck clearances. Short term problem avoided by the add of one in a 5000 sq. ft. data center. Electrical/mechanical capacity on floor EXCEEDS present loads however thermal problems cause shutdown. 10
11 High Density Computing Equipment and the Thermodynamic Evolution Rack Dissipation Air Side 7/12kW Nominal Impact Hot/Cold Aisles Impact Double Hot/Cold Aisles Air Side Stretch kw (cfd) Water Cooling Recirculation Warning: No Standard CFD Models Strongly Recommended 11
12 Part II High Density Impacts to Data Center Costs 12
13 High Density Impacts to Data Center One of the Most Dangerous/Variable Factors in Design/Building a Data Center in 2006 and Beyond 1980/1990 Rules of Thumb in cost per sq. ft. Danger Same sq. ft. Data Center ie: 5,000 sq. ft. vary density, reliability, location, long term growth projection, scalability $416 sq. ft. - $2,140 sq. ft. The Throw Away Data Center The Gartner Mission Costs The Scheduled Delivery? 13
14 High Density Impacts to Data Center Costs The Blade Server Summit Conference Discussions of Manufacturers Hardware (4/3/2/1)..Facilities? 14
15 High Density Impacts to Data Center A. Data center facility infrastructure cost impacts Physical size (See 1-5 year computer equipment plan CRITICAL) Electrical/mechanical capacity Reliability level (See 1-10 chart) Expandability Retrofit vs. New WARNING! Time allocated to complete the project Location in the United States or Canada Type of construction labor force Support Space Costs 15
16 High Density Impacts to Data Center Costs B. Summary data center facility infrastructure cost experiences: Numerical Ranking Size (sq.ft.) Cost/sq.ft ,000 $ 1,000 $ ,000 $ 1,000 $ ,000 $ 1,000 $ ,000 $ 1,000 $ Office $ NOTE: These cost experiences are not intended to be used as detailed budgets * Electrical Density Cost differences per mw. 16
17 High Density Impacts to Data Center Costs Schedule duration for typical projects: Item Area Description Duration 1 Evaluations To determine technical alternatives/costs/schedules associated with type of data center weeks 2 Design/Engineering Detail drawings/specifications for the option selected in weeks (excludes a building shell) 3 Permits For local authorities to review/approve Allow 4 weeks 4 General Construction A function of reliability, size, and location weeks (excludes a building shell) 5 Pre-Purchase/Long Lead Time Equipment Warning based on co-location/ web hosting facilities Up to 46 weeks 6 Thermodynamic (CFD) Modeling Projects Stand alone base on information technology weeks 17
18 High Density Impacts to Data Center Costs Project Team Client Client Project Team Project Director OEM Availability Installation Planning Hardware/Software Project Manager Design/Engineering Project Manager Construction Project Manager Communications OEM Hardware Support Architectural General Data Computer Equipment Planning Computer Equipment Migration Electrical Mechanical/Fire Protection Civil/Structural Electrical/Mechanical Voice Relocation/Move Software Planning CADD Manager Disaster Recovery 18
19 Part III Thermodynamic Model Impacts to the Data Center Designs/Retrofits 19
20 Base Model The Shell, Underfloor, and Raised Floor 20
21 Base Model The Shell, Floor, CRAC's, PDU's, and Equipment 21
22 Base Model Equipment Orientation The equipment orientation is shown as the intake side of the units being blue and the exhaust side being red. It can be seen that not all equipment is orientated in a hot and cold aisle configuration, and not all equipment within the same row is oriented in the same direction. There are some front to back oriented equipment racks as noted earlier. These racks will have a tendency to pull in hot exhaust air from the rack in front them. 22
23 Base Model Equipment Powers The equipment demand can be seen here in kw. 23
24 Base Model Floor Void Pressures The static pressure below the floor seems to be lacking in the majority of the data center. This is most likely resultant from the large unsealed cable cutouts throughout the raised floor area. The highest static pressure is seen in the corner of the data center with two (2) CRAC units operating with little load on them, and very few perforated tiles or cable cutouts. 24
25 Base Model Floor Void Temperatures The floor void temperature varies based upon CRAC unit operation, as would be expected. The observation here is that the higher temperatures can be associated with the lack of a demand on these units. Since little cooling is required, the units tend to warm the supply air or pass the relatively warm return air into the supply plenum. 25
26 Base Model Perforated Tile Flow Rates The airflow through most of the perforated tiles is relatively low though uniform. This can be attributed to the majority of the air escaping through the cable cutouts. 26
27 Base Model Top of Rack Temperatures The top of the equipment rack is typically where the highest intake temperatures are seen in the data center. This is a result of this part of the rack receiving less supply air from the underfloor plenum, the higher ambient temperatures at this level of the room, or the recirculation of hot air due to low ceiling heights. It can also be seen that some cold air is being returned to the CRAC units while warm air is being exhausted into the intake of other equipment. Some short cycling is occurring where perforated tile placement allows colder air to return to the CRAC units. 27
28 Base Model Maximum Equipment Inlet Temperatures The ASHRAE recommended inlet temperature for computer equipment is between 68 and 77 deg F. This temperature is exceeded in several areas shown as green and yellow. These temperatures however are still within the allowable ASHRAE range of 59 to 90 deg F. 28
29 Base Model Potential Equipment Overheat This indicates which racks may be at risk of thermal failures due to high intake temperatures. The specific rack configurations may negate such risk if no devices are installed in the top of the rack or if devices such as patch panels are installed at the top of the racks. 29
30 Base Model CRAC Unit Cooling Demands Units shown in red are working almost at their rated capacity while several others are operating below their rated capacity. 30
31 CRAC #1 Failed Top of Rack Temperatures The overall temperature does not change significantly from the failure of CRAC #1. This unit is located in the Network Room and the installed transfer fans adequately support the ventilation needs of the space. 31
32 CRAC #1 Failed Maximum Equipment Inlet Temperatures The inlet temperatures actually decrease during this failure. This is because the CRAC units in the data center work harder to compensate for the additional heat being transferred from the Network Room. 32
33 CRAC #1 Failed CRAC Unit Cooling Demands A comparison can be made against slide 30 to see the changes in unit operation. The CRAC units adjust to the new demands as the dynamics of the room change. 33
34 CRAC #2 Failed Top of Rack Temperatures 34
35 CRAC #2 Failed Maximum Equipment Inlet Temperatures 35
36 CRAC #2 Failed CRAC Unit Cooling Demands 36
37 CRAC #3 Failed Top of Rack Temperatures 37
38 CRAC #3 Failed Maximum Equipment Inlet Temperatures 38
39 CRAC #3 Failed CRAC Unit Cooling Demands 39
40 CRAC #4 Failed Top of Rack Temperatures 40
41 CRAC #4 Failed Maximum Equipment Inlet Temperatures 41
42 CRAC #4 Failed CRAC Unit Cooling Demands 42
43 CRAC #5 Failed Top of Rack Temperatures 43
44 CRAC #5 Failed Maximum Equipment Inlet Temperatures 44
45 CRAC #5 Failed CRAC Unit Cooling Demands 45
46 CRAC #6 Failed Top of Rack Temperatures 46
47 CRAC #6 Failed Maximum Equipment Inlet Temperatures 47
48 CRAC #6 Failed CRAC Unit Cooling Demands 48
49 CRAC #7 Failed Top of Rack Temperatures 49
50 CRAC #7 Failed Maximum Equipment Inlet Temperatures 50
51 CRAC #7 Failed CRAC Unit Cooling Demands 51
52 CRAC #8 Failed Top of Rack Temperatures 52
53 CRAC #8 Failed Maximum Equipment Inlet Temperatures 53
54 CRAC #8 Failed CRAC Unit Cooling Demands 54
55 CRAC #9 Failed Top of Rack Temperatures The failure of this unit has the most significant effect in the data center. Several equipment racks have exceeded the recommended maximum intake temperatures due to the elevated ambient temperatures in this area of the room. Due to the air patterns in the room the adjacent CRAC units cannot compensate for the loss of this unit. 55
56 CRAC #9 Failed Maximum Equipment Inlet Temperatures 56
57 CRAC #9 Failed CRAC Unit Cooling Demands 57
58 CRAC #10 Failed Top of Rack Temperatures 58
59 CRAC #10 Failed Maximum Equipment Inlet Temperatures 59
60 CRAC #10 Failed CRAC Unit Cooling Demands 60
61 CRAC #12 Failed Top of Rack Temperatures 61
62 CRAC #12 Failed Maximum Equipment Inlet Temperatures 62
63 CRAC #12 Failed CRAC Unit Cooling Demands 63
64 CRAC #13 Failed Top of Rack Temperatures 64
65 CRAC #13 Failed Maximum Equipment Inlet Temperatures 65
66 CRAC #13 Failed CRAC Unit Cooling Demands 66
67 CRAC #9 Supplement Top of Rack Temperatures A supplemental unit is added in the area of CRAC #9 to compensate for the loss of that unit. While the new unit does help it does not alleviate all of the potential problems. Plenum extensions were added to selected units to help reduce the short cycling that was encountered due to perforated tiles being located in the hot aisles replacement to CRAC placement. 67
68 CRAC #9 Supplement Perforated Tile Flow Rates The recommendation to fill in all cable openings resulted in nearly doubling the overall air flow through the perforated tiles. 68
69 CRAC #9 Supplement Floor Void Pressures Filling the cable cutouts also made a significant improvement in the overall static pressures underfloor. 69
70 CRAC #9 Supplement Above Floor Air Patterns Hot air recirculation is still occurring in certain areas due to improper equipment layout. The management of hot air is the number one challenge in data centers of today. Proper hot/cold aisle configurations as well as double hot layouts for high density areas provide the most effective control of the hotter air. 70
71 Part IV Questions and Answers General Discussion Mark S. Evanko
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More informationManaging Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
More informationHPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)
HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More informationData Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
More informationAPC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
More informationData center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
More informationRittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
More informationData Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015
Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and
More informationUnified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More information- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
More informationHigh Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
More informationBenefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationOptimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
More informationIT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
More informationData Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationAir, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationSealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
More informationData Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationServer Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationHow to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
More informationUnified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
More informationIMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
More informationHow Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
More informationTen Steps to Solving Cooling Problems Caused by High- Density Server Deployment
Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationReducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
More informationSupporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationReducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationAEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationStrategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
More informationData Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.
Data Center Design Considerations Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design: Overall Expectations Need: Prime vs. Redundant vs. Mirrored
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More informationIntroducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationAnalysis of the UNH Data Center Using CFD Modeling
Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,
More informationThermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
More informationRack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
More informationSmall Data / Telecommunications Room on Slab Floor
Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure
More informationW H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers
W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be
More information2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
More informationGreat Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
More informationDriving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
More informationImproving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
More informationPower and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
More informationUsing thermal mapping at the data centre
Technical Using thermal mapping at the data centre by Gregory Stockton, CompuScanIR.com Cooling the servers in data centres efficiently is critical to increasing IT reliability, maintaining high performance,
More informationHow To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationData Center Optimization Services. Maximize Your Data Center
Data Center Optimization Services Maximize Your Data Center Energy savings was definitely the key driver in my decision to use the SmartAire dampers and DirectAire panels. - Larry Hood Senior Construction
More informationCooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
More informationData center TCO; a comparison of high-density and low-density spaces
White Paper Data center TCO; a comparison of high-density and low-density spaces M.K. Patterson, D.G. Costello, & P. F. Grimm Intel Corporation, Hillsboro, Oregon, USA M. Loeffler Intel Corporation, Santa
More informationBest Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?
More informationReducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
More informationMeasure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
More informationabstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
More informationData Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption
More informationData Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
More informationHow To Power And Cool A Data Center
Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationImproving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
More informationData Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
More informationVirtual Data Centre Design A blueprint for success
Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business
More informationData Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC
Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC About us Data centre consulting World-class products Expert national team Mike Hassaballa, Applications
More informationUsing Simulation to Improve Data Center Efficiency
A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience
More informationChallenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
More informationThermal Mass Availability for Cooling Data Centers during Power Shutdown
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,
More informationHow To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
More informationData Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
More informationBest Practices. for the EU Code of Conduct on Data Centres. Version 1.0.0 First Release Release Public
Best Practices for the EU Code of Conduct on Data Centres Version 1.0.0 First Release Release Public 1 Introduction This document is a companion to the EU Code of Conduct on Data Centres v0.9. This document
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationBlade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face
More informationEnclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
More informationPursuing Operational Excellence. Better Data Center Management Through the Use of Metrics
Pursuing Operational Excellence Better Data Center Management Through the Use of Metrics Objective Use financial modeling of your data center costs to optimize their utilization. Data Centers are Expensive
More informationAirflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
More information2014 Best Practices. The EU Code of Conduct on Data Centres
2014 Best Practices The EU Code of Conduct on Data Centres 1 Document Information 1.1 Version History Version 1 Description Version Updates Date 5.0.1 2014 Review draft Comments from 2013 stakeholders
More informationAdaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009
Adaptive Cooling in Data Centers Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Maximizing Cooling Efficiency in a Concurrently Maintainable and Fault
More informationPrediction Is Better Than Cure CFD Simulation For Data Center Operation.
Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.
More information