Current transformer selection for Allen-Bradley series overcurrent and differential relays
|
|
- Morgan Evans
- 7 years ago
- Views:
Transcription
1 pplicatti ion otte Current transformer selection for llen-bradley series overcurrent and differential relays ron core current transformers (CT) are accurate in amplitude and phase when used near their nominal values. t very low and at very high currents they are far from ideal. For overcurrent and differential protection, the actual performance of CTs at high currents must be checed to ensure correct function of the protection relay. 1. CT classification according EC , 1996 CT model Figure 1 CT equivalent circuit. Lm is the saturable magnetisation inductance, L is secondary of an ideal current transformer, RCT is resistance of the CT secondary winding, RW is resistance of wiring and RL is the burden i.e. the protection relay. Composite error C ron core current transformers (CT) are accurate in amplitude and phase when used near their nominal values. t very low and at very high currents they are far from ideal. For overcurrent and differential protection, the actual performance of CTs at high currents must be checed to ensure correct function of the protection relay. 1 T ( K is ip ) dt T 0 C 100% (eq. 1) P T = Cycle time K = Rated transformation ratio Primary/secondary is = instantaneous secondary current ip = instantaneous primary current P = Rms value of primary current
2 pplication ote ote: ll current based protection functions of llen-bradley relays, except arc protection, thermal protection and nd harmonic blocing functions, are using the base frequency component of the measured current. The EC formulae include an RMS value of the current. That is why the composite error defined by EC is not ideal for llen-bradley relays. However the difference is not big enough to prevent rough estimation. Standard accuracy classes t rated frequency and with rated burden connected, the amplitude error and phase error and composite error of a CT shall not exceed the values given in the following table. ccuracy class mplitude error at rated primary current (%) Phase displacement at rated primary current ( ) Composite error C at rated accuracy limit primary current (%) 5P P 3-10 Maring: The accuracy class of a CT is written after the rated power. E.g. 10 V 5P10, 15 V 10P10, 30 V 5P0 ccuracy limit current L Current transformers for protection must retain a reasonable accuracy up to the largest relevant fault current. Rated accuracy limit current is the value of primary current up to which the CT will comply with the requirements for composite error C. ccuracy limit factor The ratio of the accuracy limit current to the rated primary current. = L/. (eq. ) The standard accuracy limit factors are 5, 10, 15, 0 and 30. Maring: ccuracy limit factor is written after the accuracy class. E.g. 10 V 5P10, 15 V 10P10, 30 V 5P0. Si S (eq. 3) S S i Figure This figure of equation 3 shows that it is essential to now the winding resistance RCT of the CT if the load is much less than the nominal. 10 V 5P10 CT with 5% load gives actual values from when the winding resistance varies from 0.5 to = ccuracy limit factor at rated current and rated burden Si = nternal secondary burden. (Winding resistance RCT in Figure 1 S = Rated burden of the CT S = ctual burden including wiring and the load. The actual accuracy limit factor depends on the actual burden. (Figure )
3 pplication ote 3 f the current is an asymmetric short circuit current lie in Figure 3 the needed accuracy limit factor should be multiplied by coefficient DC: 1 (eq. 4) DC = ngle frequency f = Time constant of the short circuit current 15 Current () Time (s) Figure 3 symmetric short circuit current with time constant = 50ms. CT requirements for differential protection When the through current equals and exceeds x there may be enough secondary differential current to trip a relay although there is no inzone fault. This is because the CTs are unique and they do not behave equally when saturating. To avoid false tripping caused by heavy through faults the actual accuracy limit factor of the CTs should obey equation: Tra c DC (eq. 5) CT c = Safety factor. See Table 1. = Maximum through fault short circuit current Tra = Rated current of the transformer CT = Rated primary current of the CT DC = Extra coefficient for decaying dc component according equation 4.
4 pplication ote 4 Table 1 Safety factor c for accuracy limit factor. Using slightly smaller safety factor than indicated in the table will increase the setting inaccuracy. Protection application Safety factor c Overcurrent 1.4 Transformer differential, -winding or unearthed Y-winding 3 Transformer differential, earthed Y-winding 4 Generator differential 3 Formula to solve needed CT power rating S By replacing the complex power terms with corresponding resistances in equation 3 we get R R CT (eq. 6) RCT RW RL where the nominal burden resistance is S R (eq. 7) CT sec RCT = Winding resistance (See Figure 1) RW = Wiring resistance (from CT to the relay and bac) RL = Resistance of the protection relay input S = ominal burden of the CT CTsec = ominal secondary current of the CT By solving S and substituting according equation 5, we get S c R R R R DC Tra CT W L CT CT sec (eq. 8) CT Example 1 Transformer: 16 MV Yd11 Z = 10% 110 V / 1 V (84 / 440 ) CTs on HV side: 100/1 5P0 15 V Winding resistance RCT = 0.3 (RCT depends on the CT type, CT and power rating. Let's say that the selected CT type, 100 and an initial guess of 15 V, yields to 0.3.) Safety factor c = 4. (Table1. Transformer differential, earthed Y.) CTs on LV side: 500/1 5P0 15 V Winding resistance RCT = 0.4 (RCT depends on the CT type, CT and power rating. Let's say that the selected CT type, 500 and an initial guess of 15 V, yields to 0.4.) Safety factor c = 3. (Table 1. Transformer differential,.) Maximum through fault short circuit current =10 x
5 pplication ote 5 RL = 0.05 Typical burden of an llen-bradley relay 1 current input. RWHV = Wiring impedance of high voltage side. (x16 m Cu, 4 mm ) RWLV = Wiring impedance of low voltage side. (x10 m Cu, 4 mm ) f = 50 Hz Frequency = 50 ms DC time constant Equation 4 gives: DC = x 0.05 = 16.7 The needed CT power on HV side will be (eq. 8) S V 15 V is a good choice for HV side! nd on the LV side S V 15 V is a good choice for HV side! 3. CT requirements for overcurrent protection Undirectional overcurrent protection does not set as high requirements for a CT as the differential protection. The nominal primary current should be enough for the maximum short circuit current according equation: CTpri (eq. 9) 100 CTpri = ominal primary current of the CT = Maximum short circuit current The needed minimum value for the actual accuracy limit factor (equation 3.) depends on the highest setting value, the applied delay type definite/inverse and the needed fault current grading for selectivity. reasonable actual accuracy limit factor for most cases should be according equation 9. c (eq. 10) SET DC c = Safety factor. See Table 1. SET = Relative setting of the most coarse overcurrent stage DC = Extra coefficient for decaying dc component according equation 4.
6 pplication ote 6 The needed power rating for the CT is c DC SET S RCT RW RL RCT CT sec (eq. 11) Example etwor: = 30 Maximum short circuit current RL = Typical burden of an llen-bradley relay 5 current input. RW = 0.09 Secondary wiring impedance CT: 1000/5 10P10 30 V (10P10 10% 10x1000 ) RCT = 0.4 Secondary winding resistance Settings of the most coarse overcurrent stage: set = 10 x = Delay type = definite time f = 50 Hz Frequency = 50 ms DC time constant ccording equation 9 the CT primary value is o (30/1000 = 30 and 30 is well under 100). Equation 4 gives: DC = x 0.05 = 16.7 ext we chec if the power rating is adequate (equation 11) S V This is an impractical big CT. We must either use a CT with 1 nominal secondary or ignore the DC-component. The latter choice may increase trip time at heavy faults. Let's ignore the DC effect S V 10 V is enough, but only if we ignore the decaying DC component.
7 pplication ote 7 4. Maximum allowed wiring distance between CT and a relay From equation 11 we can solve the maximum possible wiring resistance: S RW RCT RCT RL max (eq. 1) CT sec c SET This resistance corresponds to a wire length of L R max (eq. 13), where Lmax = Maximum wire length R = Wiring resistance = Cross-sectional area of the wire = unit resistance of the wire The corresponding distance will be half of the wire length, because there are two wires from the CT to the relay. Max. distance = Lmax/ (eq. 14) Example 3 Let us calculate the maximum possible distance between CT and protection relay with in the following case. CT = 500/5 10P10 FL = 10 ccuracy limit factor at rated current and rated burden according CT specification. CTsec = 5 ominal secondary current of the CT S = 15 V Rated burden of the CT RL = Burden of an llen-bradley relay 5 current input RCT = 0.6 Secondary winding resistance c = 1.4 Safety factor. See Table 1. SET = 8x Overcurrent setting Wire =.5 mm Cu Cross-sectional area and material Cu = 17. nm Unit resistance of copper DC = 1 This ignores any decaying DC component From equation 11 we get the maximum allowed wiring resistance R W max and from equation 13 we get the corresponding wire length Lmax 669m Thus the maximum possible distance will be according equation 14 Distancemax = 669/ = 330 m
8 pplication ote 8 Keywords : Current transformer, Current selection, Current requirements, Current accuracy class, Current accuracy limit, Current power rating, Current wiring Medium Voltage Products, 135 Dundas Street, Cambridge, O, 1R 5X1 Canada, Tel: (1) , Fax: (1) , Publication 857-P019-E-P June 011 Copyright 011 Rocwell utomation, nc. ll rights reserved. Printed in Canada.
Calculation of the Current Transformer Accuracy Limit Factor Application Note
Calculation of the Current Transformer Application Note kansikuva_bw 1MRS 755481 Issued: 09.11.2004 Version: A/09.11.2004 Calculation of the Current Transformer Application Note Contents: 1. Scope...4
More informationTHE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.
THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies
More informationDIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
More informationCurrent transformer selection guide
The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary
More informationEnhanced Quality with a Touch of Style
Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying
More informationT 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationInstrument Transformers Application Guide
Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden
More informationCT Application Guide for the 489 Generator Management Relay
g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates
More informationVrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012
Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationSelecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
More informationOVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.
OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in
More informationRM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
More informationEE 221 Circuits II. Chapter 13 Magnetically Coupled Circuits
EE Circuits II Chapter 3 Magnetically Coupled Circuits Magnetically Coupled Circuits 3. What is a transformer? 3. Mutual Inductance 3.3 Energy in a Coupled Circuit 3.4 inear Transformers 3.5 Ideal Transformers
More informationThe Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
More informationDRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationChapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.
Chapter 16 Current Transformer Design Table of Contents 1. Introduction 2. Analysis of the Input Current Component 3. Unique to a Current Transformer 4. Current Transformer Circuit Applications 5. Current
More informationTA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More informationMedium voltage circuit breaker
Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationHigh Efficiency Motor Protection. Industry White Paper
High Efficiency Motor Protection Industry White Paper 2 High Efficiency Motor Protection High Efficiency Motor Protection - An Overview Electric motor protection depends on the accurate selection of overloads,
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationRectifier circuits & DC power supplies
Rectifier circuits & DC power supplies Goal: Generate the DC voltages needed for most electronics starting with the AC power that comes through the power line? 120 V RMS f = 60 Hz T = 1667 ms) = )sin How
More informationCurrent transformers (CT) & Shunts
Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar
More informationUsing Current Transformers with the 78M661x
A Maxim Integrated Products Brand Using Current Transformers with the 78M661x APPLICATION NOTE AN_661x_021 April 2010 Introduction This application note describes using current transformers (CT) with the
More information2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
More informationTransformer Thermal Overload Protection - What s It All About?
Transformer Thermal Overload Protection - What s It All About? Glenn Swift, Dave Fedirchuk, Zhiying Zhang APT Power Technologies, Winnipeg, Canada Presented at the 25th Annual Western Protective Relay
More informationREVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
More informationUSER MANUAL THE RESOLVER
USR MANUAL TH RSOLVR ICP Department 4 has developed and produced a wide range of transmitter type resolvers for military and industrial applications. From a mechanical viewpoint, these products have been
More informationCT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK
Presentation 09.1 CT Analyzer: Coming to the Rescue Tony Porrelli, OMICRON, UK Introduction The Current Transformer (CT) may exist for many applications but for this paper we can think about them being
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationTransformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)
Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) 2 European MEPS for transformers The EU MEPS (European Minimum Energy Performance Standard) Transformers
More informationPower Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
More informationMedium-voltage transformers
Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: info@mbs-ag.com Web: www.mbs-ag.com Contents Current transformers Technical characteristics
More informationApplication Note. So You Need to Measure Some Inductors?
So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),
More informationCoupled Inductors. Introducing Coupled Inductors
Coupled Inductors From power distribution across large distances to radio transmissions, coupled inductors are used extensively in electrical applications. Their properties allow for increasing or decreasing
More informationLOW-VOLTAGE CURRENT TRANSFORMERS
LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS
More informationPHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid
More informationFREJA 300 Relay Testing System
Relay Testing System A Megger Group Company FREJA 300 Relay testing system The FREJA 300 relay testing system is a computer-aided relay testing and simulation system. The weight of FREJA 300 is only 15
More informationTape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current
More informationParalleling Power Sources Which Share a Common Neutral
Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationPower-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
More informationCambridge International Examinations Cambridge International Advanced Subsidiary and Advanced Level
Cambridge International Examinations Cambridge International Advanced Subsidiary and Advanced Level *0123456789* PHYSICS 9702/02 Paper 2 AS Level Structured Questions For Examination from 2016 SPECIMEN
More informationProblem Solving 8: RC and LR Circuits
MASSACHUSETTS INSTITUTE OF TECHNOLOGY Department of Physics Problem Solving 8: RC and LR Circuits Section Table and Group (e.g. L04 3C ) Names Hand in one copy per group at the end of the Friday Problem
More informationOp amp DC error characteristics and the effect on high-precision applications
Op amp DC error characteristics and the effect on high-precision applications Srudeep Patil, Member of Technical Staff, Maxim Integrated - January 01, 2014 This article discusses the DC limitations of
More informationPower Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
More informationCONDUCTOR SHORT-CIRCUIT PROTECTION
CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating
More informationStep response of an RLC series circuit
School of Engineering Department of Electrical and Computer Engineering 332:224 Principles of Electrical Engineering II Laboratory Experiment 5 Step response of an RLC series circuit 1 Introduction Objectives
More informationManual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
More informationChapter 14: Inductor design
Chapter 14 Inductor Design 14.1 Filter inductor design constraints 14.2 A step-by-step design procedure 14.3 Multiple-winding magnetics design using the K g method 14.4 Examples 14.5 Summary of key points
More informationMeasurement of Capacitance
Measurement of Capacitance Pre-Lab Questions Page Name: Class: Roster Number: Instructor:. A capacitor is used to store. 2. What is the SI unit for capacitance? 3. A capacitor basically consists of two
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationType SA-1 Generator Differential Relay
ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes
More informationResidual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
More informationDistribution Dry Type Transformers
8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg
More informationLOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
More informationThe full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
More informationCurrent and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
More informationEARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
More informationPower supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E
Power supplies EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E EE328 POWER ELECTRONICS Outline of lecture Introduction to power supplies Modelling a power transformer
More informationHPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationInductors in AC Circuits
Inductors in AC Circuits Name Section Resistors, inductors, and capacitors all have the effect of modifying the size of the current in an AC circuit and the time at which the current reaches its maximum
More informationPOWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
More informationTransformer circuit calculations
Transformer circuit calculations This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
More informationELR: ABB range of front panel residual current relays Protection device according to IEC/EN 60947-2 Annex M
ELR: ABB range of front panel residual current relays Protection device according to IEC/EN 60947-2 Annex M Tested, certified, reliable Network monitoring and protection The electronic residual current
More informationGS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks
GE Power Controls GS Semiconductor fuselinks TYPE GS Semiconductor Fuselinks Technical information Full GS range of fuselinks are designed to the requirements of IEC269 -IV (1986) Precise Pre-determined
More informationChapter 15: Transformer design
Chapter 15 Transformer Design Some more advanced design issues, not considered in previous chapter: : n Inclusion of core loss + + Selection of operating flux i 1 density to optimize total loss v 1 v Multiple
More information6 ELECTRICAL PARAMETERS
6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities
More informationContact expander modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:
More informationModeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
More informationES250: Electrical Science. HW7: Energy Storage Elements
ES250: Electrical Science HW7: Energy Storage Elements Introduction This chapter introduces two more circuit elements, the capacitor and the inductor whose elements laws involve integration or differentiation;
More information1587/1577. Insulation Multimeters. Technical Data. Two powerful tools in one.
1587/1577 Insulation Multimeters Technical Data Two powerful tools in one. The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter
More informationContact expansion modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts
More informationPROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B
WHITE PAPER PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS BULLETIN 1497, 1497A, AND 1497B CONTROL CIRCUIT TRANSFORMERS The proper selection of the control circuit transformers is important for suitable
More informationLM 358 Op Amp. If you have small signals and need a more useful reading we could amplify it using the op amp, this is commonly used in sensors.
LM 358 Op Amp S k i l l L e v e l : I n t e r m e d i a t e OVERVIEW The LM 358 is a duel single supply operational amplifier. As it is a single supply it eliminates the need for a duel power supply, thus
More informationSOLUTIONS TO CONCEPTS CHAPTER 15
SOLUTIONS TO CONCEPTS CHAPTER 15 1. v = 40 cm/sec As velocity of a wave is constant location of maximum after 5 sec = 40 5 = 00 cm along negative x-axis. [(x / a) (t / T)]. Given y = Ae a) [A] = [M 0 L
More informationCurrent Sensor: ACS755xCB-050
Package CB-PFF 5 4 The Allegro ACS75x family of current sensors provides economical and precise solutions for current sensing in industrial, automotive, commercial, and communications systems. The device
More informationTechnical data UNIBLOCK UBSF 180 625
Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationYour Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
More informationReyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy
Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay
More informationCirculating Current Relay. Type IRXm
Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
More informationErrors Due to Shared Leadwires in Parallel Strain Gage Circuits
Micro-Measurements Strain Gages and Instruments Errors Due to Shared Leadwires in Parallel Strain Gage Circuits TN-516 1. Introduction The usual, and preferred, practice with multiple quarterbridge strain
More informationEDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC
More informationThree-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41
Data sheet Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 The three-phase monitoring relays CM-PSS.x1 monitor the phase parameters phase sequence, phase failure as well as over- and undervoltage.
More informationCHAPTER 28 ELECTRIC CIRCUITS
CHAPTER 8 ELECTRIC CIRCUITS 1. Sketch a circuit diagram for a circuit that includes a resistor R 1 connected to the positive terminal of a battery, a pair of parallel resistors R and R connected to the
More informationLM337. Three-terminal adjustable negative voltage regulators. Features. Description
Three-terminal adjustable negative voltage regulators Datasheet - production data current limit, thermal overload protection and safe area protection. All overload protection circuitry remains fully functional
More informationFeatures. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
More informationAdvanced Monolithic Systems
Advanced Monolithic Systems FEATURES Three Terminal Adjustable or Fixed oltages* 1.5, 1.8, 2.5, 2.85, 3.3 and 5. Output Current of 1A Operates Down to 1 Dropout Line Regulation:.2% Max. Load Regulation:.4%
More informationPilot-wire differential relay for lines with two or more terminals
Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More informationMeasurement devices Accessories for analogue and digital instruments
Accessories for analogue and digital instruments 1 2CSC96F0001 Current transformers Used to transform primary currents (max. 6000 A) into.../5 A and.../1 A low secondary currents indirectly supplying power
More information