Paralleling Power Sources Which Share a Common Neutral
|
|
|
- Rafe Norton
- 9 years ago
- Views:
Transcription
1 Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share a common neutral, care must be taken to limit neutral circulating currents. In these applications, it is important that voltages produced by the generating equipment are as closely matched as possible. To properly match voltages, not only do the RMS values need to be similar but the instantaneous values, which are determined by the voltage waveshapes, should be similar as well. This is not always possible, especially when paralleling generators with dissimilar pitches or paralleling different alternative energy supplies with the Utility. When neutral circulating current is excessive, it can cause generator overheating and/or false tripping of overcurrent protection. To limit neutral circulating current, impedance can be added in the circulating path but this must be done without restricting the fault current path. By applying a unique multiple winding reactor, neutral circulating currents can be reduced by more than 75% with minimal effect on the short circuit impedance of the system. Generator Circulating Current Controlling circulating currents in the common neutral of parallel generator applications can be difficult especially if the generators have dissimilar pitch configurations. Heavy neutral currents can also appear when alternative energy sources are paralleled with the Utility. This would include distributed generation (DG) equipment such as diesel or natural gas generators, wind turbines, solar panels, microturbines and fuel cells when paralleled in 4-wire systems. Heavy neutral circulating currents can appear in the shared neutral as a result of slight differences in the voltage waveforms produced by the generating equipment. When these currents get excessive, they can cause overheating in the generator windings and false protection trips, particularly in ground fault protection schemes. These conditions are most troublesome in permanently connected parallel applications but can also be an issue during closed transition transfers in peak shaving or back-up generation applications. When neutral circulating current is excessive, it can cause generator overheating and/or false tripping of overcurrent protection. To reduce these circulating currents, which are usually triple frequency in nature, a uniquely wound, multiple winding reactor can be used to block the flow of circulating current while introducing minimal effect on the short circuit impedance of the system. PARALLELING POWER SOURCES Generator Pitches, Harmonics And Voltage Waveshape Ideally, all generator sources would produce output voltage waveforms that were purely sinusoidal. Even with their best efforts however, generator manufacturers cannot reach this goal and therefore, generator voltages will always be somewhat distorted and contain harmonics. Which harmonic numbers are present and their level of magnitude is related to how the voltage is being generated. In synchronous generators for example, the harmonic voltages generated are influenced by the particular winding pitch of the generator s alternator. A generator s winding pitch is defined as the ratio between coil pitch and pole pitch. The pole pitch of a generator is the angular distance between adjacent pole centers. In a 4-pole machine, this is 90 mechanical degrees. If the stator coil spans the same 90 degrees, the generator is considered to be full pitch. In the interest of reducing costs, stator coils are typically not wound to their full pole pitch. In a fractional pitch machine where the coil spans only 60 degrees, the winding pitch is 60/90 or 2/3. In addition to reducing copper costs, fractional pitch machines typically produce voltage waveforms that are slightly more sinusoidal and therefore contain less harmonic distortion. Harmonic voltages will still be present though, with their specific magnitudes determined by the machine s specific winding pitch. Table 1 shows the pitch factors for synchronous generators of various pitch types [1][2]. These pitch factors are multiplied by the respective harmonic fluxes produced by the generator to predict the harmonic voltages [2]. Since differently pitched machines have different pitch factors for each harmonic number, their harmonic voltages and voltage waveshapes will be different as well. PITCH FUND. 3RD 5TH 7TH 9TH 2/ / / / Table 1: Pitch factor impact on harmonic voltage magnitudes in synchronous generators. Figure 1: How differences in instantaneous voltages of paralleled equipment can produce line-to-neutral voltages that result in circulating currents. Powerline September/October
2 Figure 1 provides examples of the line-to-neutral voltages of two dissimilarly pitched generators, G1 and G2. G1 generates a voltage with a slightly higher peak (typical of 5/6 pitch generators) while G2 generates a somewhat flat-topped voltage waveform (typical of a 2/3 pitch generator). When paralleled, these generators will produce a phase-to-neutral voltage that reflects the instantaneous differences in the two voltages, even when the RMS values are perfectly matched. Since this voltage passes Figure 2: Flow of circulating current in a 3-wire paralleled generator application with neutrals connected and ungrounded. three cycles in the time that the individual generator voltage passes a single cycle (the fundamental frequency), it is primarily triple frequency in nature (180 Hz on a 60 Hz system). Circulating currents will appear as shown in Figure 2 and will also be predominantly triple frequency. The amount of circulating current introduced by each phase will be proportional to the magnitude of the differential instantaneous voltage for that phase and the zero phase sequence impedance of the system (generators and connecting cables). The total circulating current in the common neutral will be the sum of the circulating current in each phase. Since the zero phase sequence impedance of the cables is normally quite small relative to that of the sources, it can typically be ignored. For the system shown in Figure 2 then, the circulating current can be calculated using the following equation: Equation 1 It is important to note that it is not the generator s specific pitch value that causes the circulating current but rather the difference in voltage waveshape of the two differently pitched generators. Therefore, the fact that a 2/3 pitch generator has a very low pitch factor for the 3rd harmonic does not mean that it will perform any better in paralleling operations. In fact, a 2/3 pitch generator has very low zero sequence reactance and therefore, has less impedance to reduce the flow of circulating neutral current [3]. Circulating currents can result with any generator pitch type when it is not matched with a similarly pitched unit or it is paralleled with the Utility. Further complicating the issue is that this analysis has assumed that the generator loading is linear. Today s power electronic loads (such as variable speed drives, UPS systems, computer equipment, AC/DC rectifiers, etc.) are nonlinear in nature and as such, are current sources of harmonics. During their operation, the current harmonics they draw will increase the voltage distortion throughout the distribution system. This includes the output terminals of the generator where the generator s source impedance (particularly the subtransient reactance or Xd ) will create voltage drops at each harmonic number in relation to the nonlinear load harmonic currents [4]. These voltage drops will introduce additional harmonic distortion at the generator s output terminals. Differently pitched generators will have different impedances to the various harmonics and therefore, the differential voltage may be much greater than would be expected with linear loading. Phoenix Products Your Premier Manufacturer of Generator Enclosures and Base Tanks [email protected] DESIGN MANUFACTURE INSTALLATION SUPPORT Manufacturing facilities in Jacksonville, FL and Oakdale, CA Powerline September/October 2011
3 Traditional Methods Of Treatment The requirement to parallel generators is not new and therefore, circulating currents in the common neutral is also not a totally new phenomenon. What has changed however is the frequency that these incidences are occurring as the use of DG equipment increases. One method of limiting circulating currents has been to ensure that all generators have the same pitch. This, of course, is not always possible or even preferred especially when expanding a site that has older, existing generators. Another approach is to add impedance in the common neutral. Standard reactors could be used for this purpose but any impedance added to reduce the circulating neutral current would also significantly reduce the single phase fault level in the system. A slight reduction in fault level may be preferred in large systems where the fault level is initially high but normally the level of impedance required to suitably reduce the circulating current will reduce the fault current to unacceptable levels. A fault level that is too low can be a serious safety concern since it can prevent overcurrent protection from operating and lead to fire hazards, such as arcing faults. Occasionally, an ungrounded system is employed and the generator neutrals are not connected together. In this scenario, there will be no path for the circulating current to flow. There will also be no path for single phase fault currents so ground fault monitoring and other measures used for ungrounded systems must be employed. Application Of A Multiple Winding Reactor To Reduce Circulating Current A multiple winding reactor can be used to reduce neutral circulating currents in parallel generator applications. It is installed in the common neutral of paralleled generators (see Figures 3 to 5) in order to add impedance to block the flow of circulating currents. It does this without significantly decreasing the 1-phase fault level by ensuring that the impedance of the fault path to ground remains low. Also there is no change to the phase-to-phase fault level. The reactor has three sets of terminal connections X, Y and Z. The coils are wound such that the impedance through the Y and Z terminals is several times larger than the impedance between either the Y or the Z terminal to X. The Y to Z impedance is approximately 45% at the triple frequency of the circulating neutral current. The impedance to 1-phase fault current, on the otherhand, is < 1%. This is due both to the unique winding configuration of the reactor and to the fact that the core will become saturated during a fault condition, lowering its impedance. The system s 1-phase fault level therefore, will be reduced only minimally. 3-phase and phase-to-phase faults will not pass through the reactor so fault level under these conditions will be unaffected. The multiple winding reactor is used when two or more generators of dissimilar pitch are paralleled together or a generator is paralleled with an alternate source, such as the Utility. In applications where multiple generators of the same pitch are being paralleled with one or more generators of a different pitch, the multiple winding reactor need only be installed in the neutral connection between the two sets of similar pitched generators as shown in Figure 4. Figure 3: Installation of a multiple winding reactor to prevent the flow of circulating current in a 3-wire paralleled generator application with ungrounded neutral. Figure 4: Installation of a multiple winding reactor where multiple generators of similar pitch are connected to one or more generators of a different pitch. Figure 5: Installation of a multiple winding reactor to prevent the flow of circulating current in a 4-wire paralleled generator application. In 3-wire systems, the neutral may or may not be grounded. If grounded, it should be grounded at the X terminal of the multiple winding reactor. If left ungrounded, the power system must be equipped with ground fault monitoring as per electrical code requirements. Figure 5 shows how the multiple winding reactor should be connected in a 4-wire application where the neutral is being used as a return path for 1-phase, phase-to-neutral loads. The diagram shows the neutral being grounded at the switchboard, which is the recommended location, but it can alternatively be grounded at the X terminal of the multiple winding reactor or at the common neutral anywhere else in the distribution system. Powerline September/October
4 The requirement is simply that the neutral be properly grounded and grounded at only one location. Also to reduce stray fluxes, it is recommended that the neutral conductors be run in the same conduit as the phase conductors. Sizing The Multiple Winding Reactor The amount of current which will circulate between dissimilarly pitched generators or other paralleled sources with somewhat different voltage waveshapes, can be relatively difficult to determine precisely. As discussed earlier, it will be proportional to the level of instantaneous phase voltage between the sources and the zero phase sequence impedance of these sources. This information is not often readily available however. Fortunately, a conservative analysis can be done to ensure that significant reduction is achieved and that the mitigation device is appropriately sized to handle the load placed upon it. Using Equation 1, various configurations of paralleled sources can be analyzed to determine the level of neutral current that could be expected. These calculations then can be repeated but with the impedance of the multiple winding reactor included. From these calculations, a sizing table was established (see Table 2) which allows for easy selection of conservatively sized units based on the kva or kw capacity of the paralleled power system. For 4-wire applications, where the neutral is being used as a return path for 1-phase, phase-to-neutral loads, the reactor must be sized for the return neutral current as well as the circulating current. For this purpose, a dual current rating is applied with the highest rating being for the returned neutral current. Sizing the reactor involves first determining the total kw or kva capacity of all generators or other paralleled sources. Then from the table, the reactor current rating that corresponds to the total capacity in the appropriate system voltage column is selected. This will size the unit for a return neutral current rating that is at least 50% of the full phase current rating of the application. For V systems, where it is much more likely to have phase-to-neutral loads, the return neutral rating will be at least 85% of the full phase current rating of the application. If the actual return neutral current is expected to be higher than these levels, then a larger sized unit can be selected. The larger size will be just slightly less effective in reducing circulating current. For 3-wire applications or for applications where return neutral current is known to be lower, the next smaller size unit can be selected. Reactor Rating (Amps) Total Capacity of all Paralleled Sources - kw [kva] Return Neutral Circulating V V V V [85] 250 [312] 320 [400] 360 [450] [200] 640 [800] 800 [1000] 900 [1120] [420] 1280 [1600] 1600 [2000] 1800 [2250] [625] 2000 [2500] 2400 [3000] 2720 [3400] [840] 2500 [3126] 3200 [4000] 3600 [4500] [1050] 3200 [4000] 4000 [5000] 4500 [5625] [1250] 3800 [4750] 4800 [6000] 5475 [6843] Table 2: Multiple winding reactor selection table for 60 Hz systems [5]. Powerline September/October
5 Application With Dissimilarly Pitched Generators A restaurant industry distribution facility in Conroe, Texas expanded its standby generation capacity by adding a 1000 kw generator to the existing 750 kw unit at the site. A 1-Line of the installation is shown in Figure 6. When energized, the electrical contractor noticed that there was an excessive amount of current in the common neutral of the two generators. The contractor was concerned that this extra current would cause the generators to overheat. When the new generator was purchased, it was bought from the same manufacturer but being unaware of any issue associated with matching generator pitches, the purchaser never specified a particular pitch configuration. As it turned out, the new 1000 kw generator had a 5/6P winding while the existing 750 kw generator was 6/7P. This difference in pitch was enough to create the circulating current which was measured by the contractor to be in excess of 150A. In order to reduce the circulating current, a multiple winding reactor was installed in the common neutral between the two generators (see Figures 7 and 9). A 1300A unit was selected based on the total 1750 kw generator capacity. (This size was available at the time but now a 1500A unit would be used.) Figure 8 shows the residual current in the neutral after the multiple winding reactor was installed and running under peak load condition. The total of 38A was a significant reduction from Figure 8: Flow of neutral current after installation of multiple winding reactor. the initially measured value. It is important to note that most of this current is return neutral current from phase-to-neutral loads. Virtually all of the circulating current was eliminated. Figure 9: Photo of multiple winding reactor installation. Figure 6: Installation of dissimilarly pitched parallel generators at a distribution facility. Generator Paralleled With Utility Application Use of the multiple winding reactor to control neutral circulating current is not only limited to paralleling of dissimilarly pitched generators. It can also be effective in other parallel source applications with common neutrals and dissimilar voltage waveforms. For example, when a generator is operated in parallel with a Utility source, the voltage waveforms are likely to be somewhat dissimilar and therefore result in neutral circulating current [6]. This can occur in either permanently paralleled applications or during closed transition transfers in peak shaving or backup generation applications. Also, other sources of distributed generation, such as wind turbines, solar panels, fuel cells, microturbines, etc., can have excessive circulating neutral currents when paralleled with the Utility in 4-wire systems. After the Heating Plant at an American College was fit up with peak shaving generators, it was found that circulating current in the neutral reached over 900A even with relatively light loading on the system. Two similarly pitched 800 kw generators were paralleled with a 1500 kva Utility transformer (see Figure 10). The excessive neutral current was causing the Utility transformer and generators to run hot even under light loading. Figure 7: Installation of 1300A multiple winding reactor at a distribution facility Powerline September/October 2011
6 Figure 10: Simplified 3-Line Diagram at an American College Heating Plant. Figure 11: Simplified 3-Line Diagram at an American College Heating Plant with multiple winding reactor. The total supply capacity of this application was 3500 kva (1500 kva transformer plus 1000 kva for each generator). From the selection table, this would normally require a 2500A multiple winding reactor but based on the amount of 1 ph loads, it was decided that a 2000A unit would be sufficient. Figure 11 shows the system 3-Line with the multiple winding reactor connected and the measured neutral current values while operating at peak load. After installation of the reactor, neutral circulating current was essentially eliminated. The remaining neutral current is the result of 1 Phase, Ph-to-N loads such as the 277V lighting. The reduction was enough to dramatically lower the load on the Utility transformer and generators allowing for their safe operation. Summary When paralleling multiple generators with dissimilar winding pitches or power sources with differing voltage waveshapes, heavy circulating currents can appear in the common neutral. These circulating currents can be effectively reduced by the application of a multiple winding reactor. A uniquely wound reactor introduces high impedance in the path of neutral circulating current (triple or any other frequency) but very minimal impedance in the fault current path. This significantly reduces the circulating current by more than 75% with negligible effect on the system fault level. It is very simple to install and, as a purely passive reactor, is extremely reliable. References: [1] John P. Nelson, A Better Understanding of Harmonic Distortion in the Petrochemical Industry, IEEE Transactions on Industry Applications, Vol. 40, Issue 1, Jan.-Feb. 2004, pp [2] Generator Winding Pitch and Harmonics, Engine Data Sheet EDS 70.4, Caterpillar, March 1993 [3] Graham R. Phillips, Design of Stand-by Generators for Nonlinear Loads, IEEE Industry Applications Society 1992 Conference Proceedings, pp Vol. 1, Oct [4] Lineator Advance Universal Harmonic Filter Questions and Answers, MIRUS-FAQ002-A1, pp7-8, Feb. 28, http// [5] Mirus International DPNL Technical Data Sheet, DPNL- S0002-A4, April 2011 [6] Stephen Drouillhet, Preparing an Existing Diesel Power Plant for a Wind Hybrid Retrofit: Lessons Learned in the Wales, Alaska, Wind-Diesel Hybrid Power Project, National Renewable Energy Laboratory, NREL/CP , August 2001 [7] Gary Olson, Paralleling Dissimilar Generators: Part 2 Compatible Alternators, Power Topic #9016, Cummins Power Generation, 2010 About the Authors Tony Hoevenaars is President and CEO of MIRUS International Inc. a designer and developer of world class power quality improvement products. Prior to joining MIRUS in 1996, Tony was the Chief Facilities Electrical Engineer at an IBM manufacturing facility in Toronto where he gained extensive experience in solving power quality related problems, particularly in the area of harmonics. Tony is a Professional Engineer, member of IEEE and has published various papers on power quality including papers presented at various IEEE conferences. Michael McGraw is President of NSOEM Inc. a company he founded in 1996 that specializes in transformer and filter harmonic mitigation applications for land and offshore Oil & Gas systems and MV Solid State starting for large motors. Previously Mike was the OEM Sales Manager for MV Switchgear manufactured by Powercon Corp. Mike is a member of the IEEE. Powerline September/October
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Power System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
PM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
PI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
PI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
UCI274C - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
UCI274H - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers
Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute
HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
BCI184E - Technical Data Sheet
BCI184E - Technical Data Sheet BCI184E SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Copyright Material IEEE Paper No. PCIC-2003-15 Tony Hoevenaars, P. Eng. Kurt LeDoux, P.E. Matt Colosino Member IEEE Member,
Neutral Currents in Three Phase Wye Systems
POWER SYSTEMS ENGINEERING DATA PUBLISHED BY SQUARE D, OSHKOSH, WISCONSIN Subject: Neutral Currents in Three Phase Wye Systems by Robert Arthur Square D Company Oshkosh, Wisconsin (414) 46-80 and R. A.
PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS
PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section
PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards
ECONOMIC AND ELECTRICAL BENEFITS OF HARMONIC REDUCTION METHODS IN COMMERCIAL FACILITIES
ECONOMIC AND ELECTRICAL BENEFITS OF HARMONIC REDUCTION METHODS IN COMMERCIAL FACILITIES Jonathan K. Piel Engineering Manager Harmonics Limited [email protected] Daniel J. Carnovale, P.E. Power
Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives
White Paper: AUHF-WP001-A1 August 20, 2015 Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International
Figure. 1 - Split Phase 240/120V circuit (180 phase shift)
This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase
HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS
White Paper: MIRUS-TP003-A January 15, 2014 HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc.
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
Survey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
CT Application Guide for the 489 Generator Management Relay
g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Grounding of AC generators and switching the neutral in emergency and standby power systems
Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.
Physical Address: City: State: Zip Code:
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile Michael Coddington National Renewable Energy Laboratory Golden, Colorado,
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
The reliability of the grid
Power topic #9019 Technical information from Cummins Power Generation Power system considerations for cell tower applications White Paper By Wissam Balshe, Group Leader, Sales Application Engineering Industry
White Paper Mervin Savostianik P. Eng. Littelfuse, Inc.
Ground-Fault Protection with VFDs How to use a Sensitive Relay to Find Hard-to-Spot Ground Faults in VFDs on Resistance-Grounded Systems White Paper Mervin Savostianik P. Eng. Littelfuse, Inc. How to Use
The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction
The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
Voltage Unbalance and Motors
Voltage Unbalance and Motors Background Voltage unbalance occurs when the RMS line voltages on a poly-phase system are unequal. Voltages are seldom perfectly balanced between phases, but when this unbalance
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
Fault Characteristics in Electrical Equipment
1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
Wind-Diesel Hybrid System Options for Alaska. Steve Drouilhet National Renewable Energy Laboratory Golden, CO
Wind-Diesel Hybrid System Options for Alaska Steve Drouilhet National Renewable Energy Laboratory Golden, CO Wind-Diesel Hybrid Power Systems Basic Concept A wind-diesel hybrid system combines wind turbine(s)
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Tamura Closed Loop Hall Effect Current Sensors
Tamura Closed Loop Hall Effect Current Sensors AC, DC, & Complex Currents Galvanic Isolation Fast Response Wide Frequency Bandwidth Quality & Reliability RoHs Compliance Closed Loop Hall Effect Sensors
Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost
Power Quality Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost A voltage sag is defined as a decrease in voltage magnitude below 90% of nominal, but not a complete interruption. The typical
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Switchgear Application Issues for Mission Critical Power Systems, Part One
Switchgear pplication Issues for Mission Critical Power Systems, Part One BSTRCT With the advent of high reliability data centers and telecommunication facilities, designers of commercial power face new
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
Protect your home and family with Advanced Technology from Cutler-Hammer
Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths
ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
Open Phase Conditions in Transformers Analysis and Protection Algorithm
Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON [email protected] Abstract This paper first provides an in-depth analysis of open phase
Lecture - 4 Diode Rectifier Circuits
Basic Electronics (Module 1 Semiconductor Diodes) Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati Lecture - 4 Diode Rectifier Circuits
Cahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS An ALL-TEST Pro White Paper By Howard W Penrose, Ph.D. General Manager ALL-TEST Pro A Division of BJM Corp 123 Spencer Plain Rd Old Saybrook, CT 06475
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems
System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Power Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
Induction Motor Theory
PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.
Three Phase Electricity Supplies and Systems The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system. This consists of 3 separate phase conductors along
Current Probes, More Useful Than You Think
Current Probes, More Useful Than You Think Training and design help in most areas of Electrical Engineering Copyright 1998 Institute of Electrical and Electronics Engineers. Reprinted from the IEEE 1998
AC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION..........................2
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance
ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an