Enhanced Quality with a Touch of Style

Size: px
Start display at page:

Download "Enhanced Quality with a Touch of Style"

Transcription

1 Rudolf Current Transformer Enhanced Quality with a Touch of Style

2 Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying a revolutionary unique design encase using ABS/PC material, we provide enhance quality with a touch of style. The various differentiating factors govern the manufacturing of Rudolf current transformer lie in both the choice of worldclass raw material and a % testing to complete the supply. We are committed to provide our customer with undiscounted quality and complete assurance of compliance to international standard. Basic Features Correct selection of current transformer is important as the fundamental usage of CT is: 1) to obtain proportional current in accordance to specify accuracy and objectives; 2) to insulate control & measuring / protection from power circuit. Company Introduction Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for the Asian market. We are the first local electrical switchgear components manufacturer that launches our own Asian identity Today we aim to become a knowledgebased, technology driven engineering organization, with emphasis on providing solution for electrical distribution and control, in area of instruments, distribution & protection and power quality solution in area of power quality audit & power quality system and motor controller. With our present headquarter in Singapore and subsidiaries that are located in Australia, Malaysia, Philippines and Vietnam, we are well equipped to service both local market and countries in the Asia Pacific. Product Introduction Rudolf, creating a world class standard in the supply of current transformer, offers a comprehension range for both the measuring and protection applications. Ranges available are: Encapsulated type; Tape wound ring type; Split core encapsulated type; Class X tape wound ring type; Designed to meet the highest standards in accordance to IEC 0441, Rudolf current transformer provides you with a worldclass product manufactured with our assurance to comply with international standard. Application Measuring current transformer is intended to supply to indicative devices, integrated meter and similar apparatus. They are characterized by their accuracy and for saturating at moderate overcurrent. This effect protects the measuring instruments from possible overcurrent. Protective current transformer is intended to supply to protective relays whereby accuracy of CT need to be kept especially during overload conditions. Construction The highgrade silicon steel core is annealed, varnished then insulated with polycarbonate core caps. The secondary winding is toroidally wound by high precision semiautomatic machinery. For the tape wound ring type current transformer, the PEW coated windings are then covered with elephantite paper, varnished and doubletapped with PVS tapes. For the encapsulated type current transformer, the windings are enclosed in a compact and heat resistant split cap. Selection criteria 1) Application protection or measurement 2) Information on associated relay or instrument nominal current accuracy burden ) loss contribute from power loss in power line distance between transformer & instruments diameter of cable use for connection 4) environmental features indoor/ outdoor operating temperature etc...

3 Rudolf Current Transformer Important of burden Burden is the impedance of the secondary circuit in ohms and power factor. For the measurement instrument or protection relay operating via a transformer, in order to operate them, the primary current has to induce the power required in the secondary current of the instrument or relay. This induced power must be equal or higher than the losses in the power line + consumption of the measurement instrument or protection relay. The burden imposed on a current transformer consist mainly of: The impedance of pilot wire between current transformer and instruments/relay The impedance of the instrument / relay The sum of the above constitute the external burden required Table illustrating some typical instruments and its typical consumption Instrument Moving iron instruments Moving coil instruments Analogue power meter Maximum demand meter Digital meter Energy meter Recording instruments Burden consumed 0.1VA 0.VA 0.22.VA 2..0VA 0.1.0VA 1.01.VA 2.0.0VA Table guide for pilot lead burden VA BURDEN ON A SEC C.T. 1 1 mm 2 1. mm mm 2 2. mm mm 2 mm VA BURDEN ON IA SEC C.T APPROX. DISTANCE (DOUBLE WIRE RUN) C.T. TO RELAY (IN METERS)

4 Rudolf Current Transformer Important of accuracy & phase angle Current error is an error that arises when the current value of the actual transformation ratio is not equal to rated transformation ratio. Current error (%) = {(Kn x Is Ip) x }/Ip Kn = rated transformation ratio Ip = actual primary current Is = actual secondary current Example: In case of a 00/A class 1 VA current transformer Kn = 00/ = 0 turn Ip = 00A Is = 4.9A Current error = {(0 x )x}/00 = 2% For protection class current transformer, the accuracy class is designed by the highest permissible percentage composite error at the accuracy limit primary current prescribed for the accuracy class concerned. Accuracy class includes: P, P Standard accuracy limit factor are:,, 1,, By phase angle Phase error is the difference in phase between primary & secondary current vectors, the direction of the vectors to be zero for a perfect transformer. You will experience a positive phase displacement when secondary current vector lead primary current vector. Unit of scale expressed in minutes / centiradians. Circular measure = (unit in radian) is the ratio of the distance measured along the arc to the radius. Angular measure = (unit in degree) is obtained by dividing the angle subtended at the center of a circle into deg equal division known as degrees". Table limits of current error and phase displacement for measuring current transformer (Classes 0.1 To 1) Accuracy Class +/ percentage current (ratio) error at percentage of rated current shown below +/ Phase displacement at percentage of rated current shown below Minutes Centiradians

5 Rudolf Current Transformer Table limits of current error and phase displacement for measuring current transformer For special application Accuracy Class 0.2S 0.S +/ percentage current (ratio) error at percentage of rated current shown below +/ Phase displacement at percentage of rated current shown below Minutes Centiradians Table limits of current error for measuring current transformers (classes and ) Accuracy Class +/ Percentage current (ratio) error at percentage of rated current shown below 1 Table limits of error for protection current transformer Accuracy Class Current error at rated primary current % Phase displacement at rated primary current Minutes Centiradians Composite error at rated accuracy limit primary current % P +/1 +/ +/1.8 P +/ Specifications Standard : IEC Rated operational voltage (Un) : 7V Rated frequency : /Hz Ambient temperature : / deg C Operating humidity : up to % relative humidity Rated short time thermal current (Ith) : ka Rated dynamic current (Idyn) : 2. x Ith Insulation : between primary /secondary conductor >0m : between toriod core/secondary conductor >0m Dielectric strength : 2kV 1 minutes Thermal class of insulation : B Casing : nonflammable, polycarbonate self extinguishing ABS/PC Index of protection casing : IP Index of protection cover : sealable IP Accuracy class : Measuring 0., 1, : Protection P, P Burden : ranging from VA Rated primary current : ranging from up to 00A Rated secondary current : /A or /1A

6 Rudolf Current Transformer Class X Current Transformer Class X current transformer is use in conjunction with high impedance circulating current differential protection relay, eg restricted earth fault relay. As illustrated in IEC0441, the class X current transformer is needed. The following illustrates the method to size a class X current transformer. Step 1: calculating knee point voltage Vkp Vkp = {2 x Ift (Rct+Rw)}/ k Vkp = required CT knee point voltage Ift = max transformer through fault in ampere Rct = CT secondary winding resistance in ohms Rw = loop impedance of pilot wire between CT and the K = CT transformation ratio Step 2: calculate Transformer through fault Ift Ift = (KVA x 0)/(1.72 x V x Impedance) KVA = transformer rating in kva V = transformer secondary voltage Impedance = transformer impedance Step : How to obtain Rct To measure when CT is produce Step 4: How to obtain Rw This is the resistance of the pilot wire used to connect the th class X CT at the transformer star point to the relay in the LV switchboard. Please obtain this data from the Electrical contractor or consultant. We provide a table to serve as a general guide on cable resistance. Example: Transformer Capacity : kva Transformer impedance : % Voltage system : 22kV / 41V phase 4 wire Current transformer ratio : 00/A Current transformer type : Class X PR Current transformer Vkp : 1V Current transformer Rct : 1.02 (measured) Pilot wire resistance Rw : 2 meters using.0mm sq cable = 2 x 2 x = 0.1 Ift = (kva x 0) / (1.72 x V x impedance) = ( x 0) / (1.72 x 41 x 0.0) = 7,98 round up 8,000A Vkp = {2 x Ift (Rct+Rw) } / k = {2 x 00 ( ) } / 0 = Rudolf Class X CT with knee point voltage of 1V is suitable to be use in this application.

7 B B B F E F E F E Rudolf Current Transformer Encapsulated Current Transformer Selection Guide Ratio Standard burden (VA) Accuracy class Accuracy class 1 Accuracy class 0. /A /A 1/A /A 1/A 7. 0/A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A /A Dimension Drawing Subjected to change without prior notice G G D D Case type Dimension A B C D E F G H RE C H H A A G RE RE RE D RE RE RE C C H

8 All dimensions are in mm. 1A secondary on request Tape Wound Ring Type (measuring current transformer) Class.0 Class 1.0 Class 0. Type Ratio /A /A 1/A 1/A 0/A 1/A 0/A 2/A 0/A 0/A 0/A 2/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A /A 0/A 0/A /A /A /A /A 00/A /A /A 00/A /A 00/A 00/A /A 00/A 00/A /A 00/A 00/A 00/A ID OD SR Approx. Wt. In Kg Per mm C.T. Thickness SR 1 SR 2 SR SR 4 SR SR SR 7 SR 8 SR 9 Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm VA SR S SR 1S SR 2S TAPE WOUND RING TYPE (Measuring Current Transformer) extended range Type.0 Class Ratio /A /A 1/A 1/A 1/A 0/A 2/A 0/A 0/A 2/A 0/A ID OD Approx. Wt. In Kg Per mm C.T. Thickness Thickness in mm VA Thickness in mm Thickness in mm Rudolf Current Transformer Subjected to change without prior notice

9 Class/ALF Type Approx. Wt. In Kg Per mm C.T. Thickness Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm VA Thickness in mm P P P1 PR 1 PR 2 PR PR 4 PR PR PR 7 PR 8 PR 9 PR Ratio /A 1/A 1/A 0/A 1/A 0/A 2/A 0/A 0/A 2/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A /A 0/A 0/A /A /A /A /A 00/A /A /A 00/A /A 00/A 00/A /A 00/A 00/A /A 00/A 00/A 00/A ID OD Tape wound ring type (protection current transformer) All dimensions are in mm. 1A secondary on request Rudolf Current Transformer Subjected to change without prior notice

10 Tape wound ring type (protection current transformer) Class/ALF Type Approx. Wt. In Kg Per mm C.T. Thickness Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm Thickness in mm VA Thickness in mm P P P1 PR 1 PR 2 PR PR 4 PR PR PR 7 PR 8 PR 9 PR Ratio /A 1/A 1/A 0/A 1/A 0/A 2/A 0/A 0/A 2/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A /A 0/A 0/A /A /A /A /A 00/A /A /A 00/A /A 00/A 00/A /A 00/A 00/A /A 00/A 00/A 00/A ID OD All dimensions are in mm. 1A secondary on request Rudolf Current Transformer Subjected to change without prior notice

11 Rudolf Current Transformer Split Core Type The connection of a current transformer is done in series with the feeder wires, which must be interrupted. The subsequent connecting up of current transformers in already existing units or distributor or main boxes involves problems which are widely known and can cause a great deal of extra wage costs and time. Our TP transformer with separated core can solve this problem in a simple manner in the following way: It is a simple application, as the current circuit to be measured must not be interrupted. The separate measuring core of the transformer enables it to be subsequently moulded at any time. This constructive design enables the transformer to be applied universally. Its shape and the generous dimensions of the through channel facilitate the insertion of large cables and bars. It is fully isolated with selfextinguishing ABS casing UL94 VO. Its secondary connections can be capped with a bridge facility, thereby protecting the current transformer when the secondary circuits is open. There are different dimensions and current strengths from A to 00A and with the outputs.../a,...1a, and...a/1. V. Other outputs in voltage and current may be obtained on request. Ratio Burden (VA) Class 0. Class 1.0 Class.0 Dimension of case unit (mm) a b c d e f g h i Weight (Kg) Split Core Series TP 81 TP 812 TP 88 TP 8 TP 2 /A 1/A 0/A 2/A 0/A 0/A 2/A 0/A 0/A 0/A 0/A 0/A 0/A 0/A 2/A 0/A 0/A 0/A 0/A 7/A 0/A 0/A 0/A 0/A 7/A 0/A 0/A /A 12/A /A 0/A /A 00/A /A 00/A 00/A 00/A Subjected to change without prior notice

12 Rudolf Current Transformer Ordering Information NRE Z0 Z0 00 1B B = cw bracket 1 = /1A B1 = cw bracket & /1A Type for tape wound for encapsulated 1 = SR/PR1 A = SR/PR 0 = RE01 2 = SR/PR2 C = SR/PR11 1 = RE11 = SR/PR D = SR/PR12 = RE1 4 = SR/PR4 E = SR/PR1 = RE1 = SR/PR F = SR/PR14 = RE1 = SR/PR G = SR/PR1 7 = RE71 7 = SR/PR7 H = SR/PR1 8 = RE81 8 = SR/PR8 9 = SR/PR9 Primary ratio 00 = /A Burden/Rs for class X secondary resistance Z0 = VA Z0 = VA 7Z = 7.VA 0 = VA 01 = 1VA 0 = VA Accuracy/Kpv for class X knee point Volt metering protection Z0 = class S0 = P 1Z0 = class 1 S = P 0Z = class 0. T0 = P 0Z2 = class 0.2 T = P T = P Application NRE = metering encapsulated NRM = metering tape wound NRP = protection tape wound NRX = class X Bridex Singapore Pte Ltd 1 Senoko Avenue, Singapore 7 Tel : 7 08 Fax : 7 07 Website : sales@bridex.com.sg R0EDCI000CTC01

Tape Wound, Split Core and Ebony Current Transformers

Tape Wound, Split Core and Ebony Current Transformers Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current

More information

Current transformers (CT) & Shunts

Current transformers (CT) & Shunts Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar

More information

Tape Wound, Split Core and Ebony Current Transformers

Tape Wound, Split Core and Ebony Current Transformers Tape Wound, Split Core and Ebony Current Transformers Table of contents Tape Wound Measuring and Protection Current Transformers 2 MR Series Measuring Range 3 PR Series Protection Range 4 Class PX Current

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Current & Instrument Transformers

Current & Instrument Transformers Reliable & Accurate Inputs for Measuring & Protection Equipment Current & Instrument Transformers Type MKE11 Inside the Catalogue Range Specifications Ordering Code Delivering Value to You M-Kris Electric

More information

keep your measure under control

keep your measure under control INSTRUMENTACIÓN INDUSTRIAL ZURC, S.A. keep your measure under control CURRENT For measuring instruments. Mounted in selfexinguishing, plastic, strengthened cases. Isolation voltage V Made as per UNEEN

More information

LOW-VOLTAGE CURRENT TRANSFORMERS

LOW-VOLTAGE CURRENT TRANSFORMERS LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor Type Cable Current Transformers Index Description... 3 Technical

More information

Medium-voltage transformers

Medium-voltage transformers Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: info@mbs-ag.com Web: www.mbs-ag.com Contents Current transformers Technical characteristics

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Current transformer selection guide

Current transformer selection guide The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24 1 X CURRENT TRANSFORMER MODEL 546 1.10" I.D. PAGE No 1-38 REV 15DEC00 TERMINAL OPTION LEAD WIRE OPTION 1.10 0 1.20 2.55 3.00 3.47 0.18 x 0.31 SLOT ( 2 PLACES) 8-32 BRASS STUD (2 PLACES) UL1015 #16 AWG LEAD

More information

Measurement devices Accessories for analogue and digital instruments

Measurement devices Accessories for analogue and digital instruments Accessories for analogue and digital instruments 1 2CSC96F0001 Current transformers Used to transform primary currents (max. 6000 A) into.../5 A and.../1 A low secondary currents indirectly supplying power

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Measurement and Instrumentation

Measurement and Instrumentation POWER QUALITY ENERGY PERFORMANCE Measurement and Instrumentation Transformers and shunts Transformers Overview of ranges Selection guide Info & advice Standard industrial transformers TCR TCRO ranges Adaptable

More information

Using Current Transformers with the 78M661x

Using Current Transformers with the 78M661x A Maxim Integrated Products Brand Using Current Transformers with the 78M661x APPLICATION NOTE AN_661x_021 April 2010 Introduction This application note describes using current transformers (CT) with the

More information

Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com

Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com CURRENT TRANSFORMER MODEL J " x 7" PAGE No 2-2 REV 8DEC00 TERMINAL OPTION LEAD WIRE OPTION 8-2 BRASS SCREW TERMINALS (2 PLACES) SEE NOTE 9 6 9 8 6 Ø 2 9 (4 PLACES) UL 05 #6 AWG LEAD WIRE, STANDARD LENGTH

More information

0.84" x 2.00" Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.

0.84 x 2.00 Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP. SPLIT CORE CURRENT MODEL 1SP 0.84" x 2.00" PAGE No 3-2 REV 18DEC00 UL 1015 LEAD WIRE, STANDARD LENGTH IS 36 E DIMENSIONS A = 0.84 MIN B = 2.00 MIN C = 3.31 MAX D = 3.09 MAX E = 0.61 MAX F = 0 MAX F C B

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1 Current Transformers Bonneville Power Administration Steve Laslo For the Hands On Relay School (3-12) Revision 1.1 February 21, 2012 1 Basic Theory: CT as a Voltage Transformer February 21, 2012 2 CT as

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Medium voltage circuit breaker

Medium voltage circuit breaker Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the

More information

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS VACUUMSCHMELZE GmbH & Co. KG (VAC) is one of the worldwide

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications 077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) Fig1. CPTR SMART CONTROL PRECISION CUSTOMIZED MANUAL OR AUTO SCR OR DIODE DRY TYPE SWITCH MODE DRY TYPE SCR OR DIODE OIL TYPE 1 INDEX PAGE 1. Cover 2. Index

More information

Calculation of the Current Transformer Accuracy Limit Factor Application Note

Calculation of the Current Transformer Accuracy Limit Factor Application Note Calculation of the Current Transformer Application Note kansikuva_bw 1MRS 755481 Issued: 09.11.2004 Version: A/09.11.2004 Calculation of the Current Transformer Application Note Contents: 1. Scope...4

More information

FACTORY AUTOMATION. Manual Laying loops for Loop detector LC10-1 and LC10-2

FACTORY AUTOMATION. Manual Laying loops for Loop detector LC10-1 and LC10-2 FACTORY AUTOMATION Manual Laying loops for Loop detector LC10-1 and LC10-2 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

ACTIV-8 PLUS Insulated Conductor Bar

ACTIV-8 PLUS Insulated Conductor Bar ACTIV-8 PLUS Insulated Conductor Bar A product made in Australia www.conductix.com.au ACTIV-8 PLUS ACTIV-8 is the most widely used and stocked conductor rail in use in Australia. It was designed by Conductix

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. 1) If the voltage at a point in space is zero, then the electric field must be A) zero. B) positive.

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

A product made in Australia. Insulated Conductor Rail ACTIV-8 PLUS

A product made in Australia. Insulated Conductor Rail ACTIV-8 PLUS A product made in Australia Insulated Conductor Rail ACTIV-8 PLUS ACTIV-8 PLUS The Industry Standard in Conductor Rails ACTIV-8 is the most widely used and stocked conductor rail in use in Australia. It

More information

High Voltage Power Supplies for Analytical Instrumentation

High Voltage Power Supplies for Analytical Instrumentation ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

Chapter 1. Network Structures

Chapter 1. Network Structures Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V

More information

CURRENT TRANSFORMERS INSTALLATION GUIDE

CURRENT TRANSFORMERS INSTALLATION GUIDE CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

PCB transformers. Short circuit proof PCB transformer VB. General Data. Advantages. Applications. Circuit diagram. Standards & 1 Certifications W v

PCB transformers. Short circuit proof PCB transformer VB. General Data. Advantages. Applications. Circuit diagram. Standards & 1 Certifications W v Short circuit PCB transformer General Data Rated input 230 Vac Rated output 6-2 x 24 Vac Rated power 0.35-3.2 VA Insulation class B Maximum ambient temperature 70 C Efficiency up to 58 % Degree of protection

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

Intersection Preassembled 19-inch Rack

Intersection Preassembled 19-inch Rack Intersection Preassembled 19-inch Rack The intersection preassembled 19-inch rack comes fully assembled, wired and ready to be installed in a server rack. The rack provides communications, power conversion

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

How To Build A Low Voltage Capacitor Lvcp

How To Build A Low Voltage Capacitor Lvcp Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched

More information

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Characteristics XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Complementary Detection system Kit composition [EAA] effective aperture angle Emission Main Range of product Product or

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Electric Rotary Actuator - On/Off or programmable control actuator

Electric Rotary Actuator - On/Off or programmable control actuator Electric Rotary Actuator - On/Off or programmable control actuator Direct mounting on quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Multi-voltage version Type

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

Protection from Short-circuit

Protection from Short-circuit Protection from Short-circuit Back-up Fuse-Link with ÜLA (controlled power dissipation) Test device for tripping device Special version with threat High-voltage Fuse-Link for voltage transformers (HSW)

More information

Current Transformers

Current Transformers Supersedes December 2002 General Description Eaton s low voltage current transformers are available in both solid core and split core designs. Engineered for electronic metering applications, all solid

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power: PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for

More information