TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Size: px
Start display at page:

Download "TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection"

Transcription

1 Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions below. After the lab, you will need to deliver a post-report which contains what you have done in the lab, data, related graphs and answers of the questions. Pre-Study Questions 1. Why do we use relays in the power systems? 2. What is the ANSI/IEEE code of distance relays? 3. What is the basic principle of distance protection? How it works? 4. What is the purpose of reach point? How will relays operate regarding to this setting? 5. What are the basic distance protection zones? Why different zones should be defined? 6. What are the main tripping characteristics for distance protection? 7. What is the difference between impedance and mho characteristic? 8. Why modern distance relays offer quadrilateral characteristics? 9. Why R-X diagram is commonly used? 10. What do the four quadrants of the R-X diagram show? 1. Objective To study the principles of distance protection. 2. Theory [1-4] Relays are used to detect abnormal conditions in the power systems. After detection of a fault, relays close circuit breakers and disconnect faulty circuits from the general supply system in order to minimize the damage. There is a list of ANSI/IEEE codes of different types of protection relays as follows [5, 6]: ANSI /IEEE Standard Device Numbers 2 - Time Delay Starting or Closing Relay 67 - AC Directional Overcurrent Relay 21 - Distance Relay 68 - Blocking or out of step Relay 25 - Synchronizing or Synchronism-Check Device 69 - Permissive Control Device 27 - Undervoltage Relay 74 - Alarm Relay 30 - Annunciator Relay 76 - DC Overcurrent Relay 32 - Directional Power Relay 78 - Phase-Angle Measuring Relay 37 - Undercurrent or Underpower Relay 79 - AC-Reclosing Relay 38 - Bearing Protective Device 81 - Frequency Relay 40 Field (over/under excitation) Relay 85 Pliot Comm., Carrier or Pilot-Wire Relay 46 Rev. phase or Phase-Bal. Current Relay 86 - Lockout Relay 47 - Phase-Seq. or Phase-Bal. Voltage Relay 87 - Differential Protective Relay 49 - Machine or Transformer Thermal Relay 94 - Tripping or Trip-Free Relay 50 - Instantaneous Overcurrent 51 - AC Time Overcurrent Relay B Bus 59 - Overvoltage Relay F - Field 60 - Voltage or Current Balance Relay G Ground or generator 63 - Pressure Switch N Neutral 64 - Ground Detector Relay T Transformer 1

2 2.1. Basic Principle A distance relay has the ability to detect a fault within a pre-set distance along a transmission line or power cable from its location. Every power line has a resistance and reactance per kilometer related to its design and construction so its total impedance will be a function of its length. A distance relay therefore looks at current and voltage and compares these two quantities on the basis of Ohm s law. Since the impedance of a transmission line is proportional to its length, for distance measurement it is appropriate to use a relay capable of measuring the impedance of a line up to a predetermined point (the reach point). Distance relay is designed to operate only for faults occurring between the relay location and the predetermined (reach) point, thus giving discrimination for faults that may occur in different line sections. The basic principle of distance protection involves the division of voltage at the relaying point by the measured current. The calculated apparent impedance is compared with the reach point impedance. If the measured impedance is less than the reach point impedance, it is assumed that a fault exists on the line between the relay and the reach point Zones of Protection Careful selection of the reach point settings and tripping times for various zones of measurement enables correct coordination between distance relays on a power system. Basic distance protection will comprise one instantaneous (Zone 1) and one or more time delayed zones (Zone 2, Zone 3, Zone 4 ). Typical reach and time settings for a 3-Zone distance protection are shown below: Zone 1: this is set to protect between 80% of the line length AB and operates without any time delay. This under-reach setting has been purposely chosen to avoid over-reaching into the next line section to ensure selectivity since errors and transients can be present in the voltage and current transformers. Also manufacturing tolerances limit the measurement accuracy of the relays. Zone 2: this is set to protect 100% of the line length AB, plus at least 20% of the shortest adjacent line BC and operates with time delay t2. ( 0.5s) It not only covers the remaining %20 of the line, but also provides backup for the next line section. Zone 3: this is set to protect 100% of the two lines AB, BC, plus about 25% of the third line CD and operates with time delay t3. ( 1.5s) It should be noted that, digital distance relays may have up to six zones, some set to measure in the reverse direction. 2

3 2.3. Tripping Characteristics The shape of the operation zones has developed throughout the years. An overview of relay characteristics can be seen below: i. Impedance Characteristic: If the relay s operating boundary is plotted on an R-X diagram, its impedance characteristic is a circle with its center at the origin of the coordinates and its radius will be the setting (the reach point) in ohms. The relay will operate for all values less than its setting i.e. for all points within the circle. This type of relay, however, is non-directional. It can operate for faults behind the relaying point. It takes no account of the phase angle between voltage and current. It is also sensitive to power swings and load encroachment due to the large impedance circle. ii. Mho Characteristic: The limitation of the impedance characteristic can be overcome by a technique known as selfpolarization. Additional voltages are fed into the comparator in order to compare the relative phase angles of voltage and current, so providing a directional feature. This has the effect of moving the circle such that the circumference of the circle passes through the origin. Angle θ is known as the relay s characteristic angle. It appears as a straight line on an admittance diagram. 3

4 By use of a further technique of feeding in voltages from the healthy phases into the comparator (known as cross polarization) a reverse movement or offset of the characteristic can be obtained. This is called the offset mho characteristic. iii. Combined Characteristic: Relays with combined characteristics are obtained by added a mho circle with lines parallel to the resistive and reactive axes which cross each other at the setting point. iv. Quadrilateral Characteristic: Modern distance relays offer quadrilateral characteristic, whose resistive and reactive reach can be set independently. It therefore provides better resistive coverage than any mho-type characteristic for short lines. This is especially true for earth fault impedance measurement, where the arc resistances and fault resistance to earth contribute to the highest values of fault resistance. Polygonal impedance characteristics are highly flexible in terms of fault impedance coverage for both phase and earth faults. For this reason, most digital relays offer this form of characteristic Significance of R-X Diagram In general, all electromechanical relays respond to one or more of the conventional torqueproducing input quantities: (a) voltage, (b) current, (c) product of voltage, current and the angle θ between them and (d) a physical or design force such as a control spring. Similar considerations hold for solid-state relays as well. For distance relay, analyzing the response of the relay for all conditions is difficult because the voltage varies for each fault, or varies for the same fault but with different system conditions. To resolve this difficulty, it is common to use an R X diagram. By utilizing only two quantities, R and X (or Z and θ), we avoid the confusion introduced by using the three quantities E, I and θ. There is an 4

5 additional significant advantage in that the R X diagram allows us to represent both the relay and the system on the same diagram. Consider an ideal (zero resistance) short circuit at location F in the single-phase system shown below. The distance relay under consideration is located at line terminal A. The subscript p represents primary and s represents secondary quantities. In terms of the secondary quantities of voltage and current transformers, the relay sees as. where and are the current transformer (CT) and voltage transformer (VT) turns ratios. When a fault occurs, this impedance may be plotted as a point on the complex R X plane. Now consider the fault at location F as shown in the figure below. The line AB makes an angle θ with the R axis, where θ is the impedance angle of the transmission line. (For an overhead transmission line, θ lies between 70 and 88 ). When the fault is on the transmission line, the apparent impedance plots on the line AB; for all other faults or loading conditions, the impedance plots away from the line AB. Often it is convenient to plot the source impedance also on the R X diagram. 3. Practical Information In this lab, the distance protection function (21) of SIPROTEC 4-7SA610 [7] and Kingsine K68i Protection Relay Test Set [8] will be used. Order number of the relay is as follows: 7SA610 Order number includes many information about the relay, such as; housing, binary inputs and outputs, measuring inputs, language settings and its functions. It can be seen in the catalog of the relay. 5

6 The relay supports distance protection (21/21N), high resistance earth-fault protection for single and three phase tripping (50N, 51N, 67N), pilot protection (85), fault locator (FL), phase overcurrent protection (50/51/67), over/under voltage protection (59/27), over/under frequency protection (81O/U) and auto-reclosure function (25). For communication, the relay supports IEC Ethernet, IEC , Profibus, RS232 and RS 485. For distance protection, the relay provides 6 zones that can be set to forward, reverse, nondirectional and inactive. Load zones for phase-phase and phase-earth can be set separately. 4. Procedure You don t need to set up any connection. Only study the connection scheme. In the lab, you will measure several distance and trip time values from the relay regarding to specified fault impedances in the relay test set. 5. Connection Scheme Connection scheme will be provided soon. 6. References 1. L. G. Hewitson, M. Brown, R. Balakrishnan, Practical Power System Protection, Elsevier, S. H. Horowitz, A. G. Phadke, Power System Relaying, John Wiley & Sons, H. M. Tran, H. Akyea, Numerical Distance Protection Relay Commissioning and Testing, MSc Thesis, Chalmers University of Technology, Göteborg, Sweden, IEEE Standard C : IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations Catalog of Siemens SIPROTEC 4-7SA6 : Distance Protection Relay for all Voltage Levels Questions for the Post-Report 1. What is the meaning of mho? Is there any relation between the units mho and ohm? 2. What is the key advantage of distance protection over overcurrent protection? (look up in [4]) 3. What are the under-reach and over-reach concepts? (look up in [4]) 6

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

Transmission Protection Overview

Transmission Protection Overview Transmission Protection Overview 2012 Hands-On Relay School Brian Smyth Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with transmission

More information

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear. OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in

More information

Pilot-wire differential relay for lines with two or more terminals

Pilot-wire differential relay for lines with two or more terminals Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Test & Data Management Software

Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

FREJA Win Software for FREJA relay testing system

FREJA Win Software for FREJA relay testing system Software for FREJA relay testing system A Megger Group Company Software for FREJA relay testing system In FREJA Win, the all-round General instrument program serves as a convenient, easy to understand,

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Numerical Differential Protection

Numerical Differential Protection Numerical Differential Protection Principles and Applications Publicis Corporate Publishing 1 Introduction 8 1.1 Protection Principle 8 1.2 Numerical Differential Protection 9 2 Deflnitions 10 3 Mode of

More information

TDMS Test & Data Management Software

TDMS Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Application of Overreaching Distance Relays

Application of Overreaching Distance Relays Outline 1. Introduction. Background Application of Overreaching Distance elays Why we are writing this document. A. Zone Descriptions B. Purpose of overreaching distance zones; step-distance and pilot

More information

FREJA 300 Relay Testing System

FREJA 300 Relay Testing System Relay Testing System A Megger Group Company FREJA 300 Relay testing system The FREJA 300 relay testing system is a computer-aided relay testing and simulation system. The weight of FREJA 300 is only 15

More information

EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS

EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS N.VIJAYSIMHA 1*, CH.CHENGAIAH 2 1* M-TECH (PSOC), Department of Electrical and Electronics Engineering, Sri Venkateshwara University

More information

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331) Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

CT Application Guide for the 489 Generator Management Relay

CT Application Guide for the 489 Generator Management Relay g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates

More information

SIPROTEC Protection Technology

SIPROTEC Protection Technology SIPROTEC Protection Technology The Basis for Highest Availability of Supply Siemens AG 2012. Siemens All rights reserved. AG 2012 Infrastructure and Cities Objectives of this Brochure Objective The following

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1 Current Transformers Bonneville Power Administration Steve Laslo For the Hands On Relay School (3-12) Revision 1.1 February 21, 2012 1 Basic Theory: CT as a Voltage Transformer February 21, 2012 2 CT as

More information

Eaton s E-Series protective relay family

Eaton s E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family

More information

Impedance Matching. Using transformers Using matching networks

Impedance Matching. Using transformers Using matching networks Impedance Matching The plasma industry uses process power over a wide range of frequencies: from DC to several gigahertz. A variety of methods are used to couple the process power into the plasma load,

More information

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z +

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z + Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Quick Review of Reflection Coefficient The Smith chart is a method of graphing reflection coefficients and impedance, and is often useful

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

7SR22 ARGUS-M 7SR21 7SR224 DOCUMENTATION SET

7SR22 ARGUS-M 7SR21 7SR224 DOCUMENTATION SET (7) (7) (5) Applications Installation Guide Guide RECLOSER-M 7SR21 ARGUS-M 7SR21 CONTROLLER 7SR224 7SR22 ARGUS-M 7SR21 DOCUMENTATION SET This document is part of a set. The full list of documents in the

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS Sethuraman Ganesan ABB Inc. Allentown, PA ABSTRACT More and more sub-stations are retrofitted with numerical relays, meters and monitoring

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4

TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4 Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE

More information

How To Protect Your Power Supply From Dangerous Currents And Voltages

How To Protect Your Power Supply From Dangerous Currents And Voltages ids ACOS 300 Protection equipment for medium and highvoltage grids ACOS 300 Protection Devices Already minor incidents, such as branches dropping on overhead lines or underground cables damaged by construction

More information

Generator Differential Relay Electrical Apparatus

Generator Differential Relay Electrical Apparatus Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Protection of Phase Angle Regulating Transformers

Protection of Phase Angle Regulating Transformers Protection of Phase Angle Regulating Transformers A report to the Substation Subcommittee of the IEEE Power System Relaying Committee prepared by Working Group K1 IEEE Special Publication Members of the

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

15LINE PROTECTION WITH PILOT RELAYS

15LINE PROTECTION WITH PILOT RELAYS 15LINE PROTECTION WITH PILOT RELAYS Pilot relaying is the best type for line protection. It is used whenever high-speed protection is required for all types of short circuits and for any fault location.

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

E-Series protective relay family

E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays E-Series protective relay family Reliable protection for every application Eaton s E-Series relay

More information

FIT TIER 2 Application

FIT TIER 2 Application FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Ampere's Law. Introduction. times the current enclosed in that loop: Ampere's Law states that the line integral of B and dl over a closed path is 0

Ampere's Law. Introduction. times the current enclosed in that loop: Ampere's Law states that the line integral of B and dl over a closed path is 0 1 Ampere's Law Purpose: To investigate Ampere's Law by measuring how magnetic field varies over a closed path; to examine how magnetic field depends upon current. Apparatus: Solenoid and path integral

More information

S-Parameters and Related Quantities Sam Wetterlin 10/20/09

S-Parameters and Related Quantities Sam Wetterlin 10/20/09 S-Parameters and Related Quantities Sam Wetterlin 10/20/09 Basic Concept of S-Parameters S-Parameters are a type of network parameter, based on the concept of scattering. The more familiar network parameters

More information

Directional Comparison Blocking System Fundamentals

Directional Comparison Blocking System Fundamentals Directional Comparison Blocking System Fundamentals Russell Patterson Patterson Power Engineers, LLC Elmo Price ABB Inc. Miriam Sanders Quanta Technology Introduction This paper discusses the fundamentals

More information

Loss of ac Voltage Considerations For Line Protection

Loss of ac Voltage Considerations For Line Protection Loss of ac Voltage Considerations For Line Protection A report prepared for the Line Protection Subcommittee Of the IEEE Power Engineering Society, Power System Relaying Committee Line Protection Subcommittee

More information

Capacitor Protection Relay SPAJ 160 C. Product Guide

Capacitor Protection Relay SPAJ 160 C. Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase

More information

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Introduction to Paralleling of LTC Transformers by the Circulating Current Method TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load

More information

Cahier technique no. 196

Cahier technique no. 196 Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for

More information

Experiment 7: Familiarization with the Network Analyzer

Experiment 7: Familiarization with the Network Analyzer Experiment 7: Familiarization with the Network Analyzer Measurements to characterize networks at high frequencies (RF and microwave frequencies) are usually done in terms of scattering parameters (S parameters).

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR 1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.

More information

Local Back-up Protection for an Electric Power System

Local Back-up Protection for an Electric Power System MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................

More information

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

National Craft Assessment and Certification Program S P E C I F I C A T I O N S National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4 Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been

More information

Distribution Automation Handbook. Section 8.13 Backup Protection

Distribution Automation Handbook. Section 8.13 Backup Protection Distribution Automation Handbook Section 8.13 Backup Protection 2 Contents 8.13 Backup Protection... 3 8.13.1 Introduction... 3 8.13.1.1 REQUIREMETS FOR BACKUP PROTECTIO... 3 8.13.1.2 JUSTIFICATIO OF RESERVE

More information

Everything you need for protection scheme testing

Everything you need for protection scheme testing Power System Simulator for Testing Protection Relays and Schemes Everything you need for protection scheme testing The is the only instrument with the high power, flexibility and software to perform full

More information

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan claudio.mardegan@engepower.com www.engepower.com Phone: 55 3579-8777

More information

Shunt Capacitor Bank Fundamentals and Protection

Shunt Capacitor Bank Fundamentals and Protection 2003 Conference for Protective Relay Engineers - Texas A&M University April 8-10, 2003, College Station (TX) Shunt Capacitor Bank Fundamentals and Protection Gustavo Brunello, M.Eng, P.Eng Dr. Bogdan Kasztenny

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout

Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout Author s Name Name of the Paper Session DYNAMIC POSITIONING CONFERENCE October 15-16, 2013 POWER SESSION Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through

More information

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49 Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating. THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies

More information

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014 1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321) Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:

More information

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date

More information

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Alternating Current and Direct Current

Alternating Current and Direct Current K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating

More information

Study on Differential Protection of Transmission Line Using Wireless Communication

Study on Differential Protection of Transmission Line Using Wireless Communication Study on Differential Protection of Transmission Line Using Wireless Communication George John.P 1, Agna Prince 2, Akhila.K.K 3, Guy Marcel 4, Harikrishnan.P 5 Professor, Dept. of EEE, MA Engineering College,

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power

More information

Bus differential relay REB 103 3-phase 1MRK 505 007-BEN Page 1 Issued: September 2006 Revision: C Data subject to change without notice

Bus differential relay REB 103 3-phase 1MRK 505 007-BEN Page 1 Issued: September 2006 Revision: C Data subject to change without notice Bus differential REB 103 3-phase Page 1 Issued: September 2006 Revision: C Data subject to change without notice (SE970146) Features Percentage restrained differential for phase-to-phase and phase-to-earth

More information

Current Transformers Ratio / Polarity / Types

Current Transformers Ratio / Polarity / Types CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

ABB PSPS Erich Steinmann; Generator control-2013

ABB PSPS Erich Steinmann; Generator control-2013 ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise

More information

Electric utilities may vary in their application of end-to-end testing

Electric utilities may vary in their application of end-to-end testing An Application Case of End-to-End Relay Testing of Communication-Based Protection Schemes Using GPS-Synchronized Secondary Injection Feature by J. Ariza, Megger USA G. Ibarra, CFE, Mexico Electric utilities

More information

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law. 260 17-1 I. THEORY EXPERIMENT 17 QUALITATIVE STUDY OF INDUCED EMF Along the extended central axis of a bar magnet, the magnetic field vector B r, on the side nearer the North pole, points away from this

More information

Lab 8: DC generators: shunt, series, and compounded.

Lab 8: DC generators: shunt, series, and compounded. Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their

More information

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil

More information

Advances in Series-Compensated Line Protection

Advances in Series-Compensated Line Protection Advances in Series-Compensated Line Protection Héctor J. Altuve, Joseph B. Mooney, and George E. Alexander Schweitzer Engineering Laboratories, Inc. Presented at the 63rd Annual Georgia Tech Protective

More information

Protection of a Three- Winding Transformer

Protection of a Three- Winding Transformer Protection of a Three- Winding Transformer Three-winding transformer 110 kv/25 kv/10 kv Yyn0d5 25 kv-side: Solidly earthed Protection functions ANSI 87 T - Differential protection ANSI 87 N - Earth-fault

More information

Substation Grounding Study Specification

Substation Grounding Study Specification Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number

More information

Lab 1: DC Circuits. Student 1, student1@ufl.edu Partner : Student 2, student2@ufl.edu

Lab 1: DC Circuits. Student 1, student1@ufl.edu Partner : Student 2, student2@ufl.edu Lab Date Lab 1: DC Circuits Student 1, student1@ufl.edu Partner : Student 2, student2@ufl.edu I. Introduction The purpose of this lab is to allow the students to become comfortable with the use of lab

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information