HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install



Similar documents
HP UPS R1500 Generation 3

HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide

HP 16/18-Port Cable Management Kit Installation Guide

HP ProLiant DL165 G7 Server. Installation Instructions

PS6500 Storage Arrays Rack Mount Instructions

MCR1900 Media Converter 19-Slot Chassis

ProLiant DL380 Generation 2 Server Maintenance and Service Guide

About the BitStorm 6051 POTS Splitter

BX7000 Multi-Access Gateway Getting Started Guide

UPDATEUPDATEUPDATE. Converting the tower chassis to a rack-mount chassis. A - M To mount outer member to rack

Express5800/120Ed. Rack Mount Kit Installation Procedures PN:

Intel RAID Maintenance Free Backup Unit 4 Quick Installation User's Guide

HP SATA/SAS hard drive and Solid State Drive installation

Hard Disk Drive (HDD)

Memory Modules User Guide

Wall-Mounting your HP computer. User Guide

Rack installation instructions

HP ProLiant DL380 G5 High Availability Storage Server

HP R12000 and R18000 DirectFlow UPS User Guide

Small form factor bay converter and hard drive installation

StorTrends 3400 Hardware Guide for Onsite Support

Universal Vehicle Power Supply 9007AX01. Installation Instructions

AU-110 racking guide NBXPN: 023

Rack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances

Refer installation of power supplies to qualified service personnel.

Rack Installation Instructions

The power module is Feature Number 8800-F2-901.

5-Slot Housing and FrameSaver 9000 Series Access Carrier AC Power Supply Installation Instructions

Cascade Profiler Fibre Channel SAN Attached Storage Installation Guide. Version 8.2 March 2009

Advantium 2 Plus Alarm

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

Memory Modules. Document Part Number: This guide explains how to replace and upgrade memory in the computer. May 2006

HP 22-in-1 Media Card Reader

Installation and Operation Guide PD4600 Series Converter Replacement

QuickSpecs. HP 480/277 Volt Solutions. Overview

Tyan Computer. Transport PX22. Service Engineer s Manual

Mounting HP Desktop Mini Rack Mount Tray Kit HP Desktop Mini Security/Dual VESA Sleeve

QuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview

Replacing Redundant AC Power Supplies in an EX4500 Ethernet Switch Without Disrupting Service

Service Guide. Gateway M275

UPGRADING AND SERVICING GUIDE

Upgrading and Servicing Guide

HP Common Slot Power Supplies Overview

Installing your upgrade processor

Replacement Instructions. Warning: During this procedure, keep small parts away from children.

About this Manual. Support for Your Product

Installing Your 960 or 980 Server into a Rackmount Cabinet

Co-location Interconnect Power Panel (CIPP) Installation Guide

HP ProLiant Moonshot Cartridge User and Maintenance Guide

Mazda CX up B

ATS Overhead Table Shelf System INSTRUCTION MANUAL

DE1600 DSA E-Series iscsi Disk Arrays. Installation Manual

PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit

Inspiron 15. Service Manual Series

How To Set Up An Inverter

Memory Modules. Document Part Number: This guide explains how to replace and upgrade memory in the computer.

HP 2400/2500 Ultra Light Docking Station User Guide

HP Pavilion All-in-One MS200 series PC. Upgrading and Servicing Guide. Printed in

CUSTOM AUXILIARY FORWARD LIGHTING KIT

Interface Adapters PS/2 Interface Adapter 1 pack B21 PS/2 Interface Adapter 8 pack B21 USB Interface Adapter 1 pack B21

Replacement Instructions. Warning: During this procedure, keep small parts away from children.

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

INSTALLATION INSTRUCTIONS

HP Port Switches Quick Setup Guide

Acano solution. Acano Solution Installation Guide. Acano. January B

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.

How To Install A Power Supply (Uplast) With A Battery Pack

HP ProLiant s6500 Chassis Setup and Installation Guide

Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

HP Common Slot Power Supplies Overview

Dell Inspiron 660s Owner s Manual

BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability. Quick Start Guide NOTES

Compaq Presario Desktop Products. Upgrading and Servicing Guide

A QUICK AND EASY GUIDE TO SETTING UP THE DELL POWEREDGE C8000

Server Technology, Inc.

Quick Setup Guide. Tandberg Data DPS1000 Series Model: DPS1100 and DPS1200, Release: 1.3

HP ProDisplay P19A LED Backlit Monitor. User Guide

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

DE1600 DSA E-Series iscsi Disk Arrays. en Quick Install Guide

Inspiron 13. Service Manual Series. Computer Model: Inspiron Regulatory Model: P57G Regulatory Type: P57G001

Unpacking, Installation, and Customization

Intersection Preassembled 19-inch Rack

Installing the Video Input and TV Tuner Cards in a Compact Computer or a Dual PCI-Slot Tower Computer

AI120 AIswitch Series 120 Chassis

MegaRAID LSIiBBU08 Intelligent Battery Backup Unit. Quick Installation Guide

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

Intel NUC Kit DC3217IYE User Guide. Intel NUC Kit DC3217IYE

How to Set Up Your NSM4000 Appliance

HP Integrity rx2660 Server Installation Guide

RM410. Hardware Installation Guide. Quick Start Guide. Rack Mounting Kit. Version 1.00 Edition 1, 12/2012

Rack Mount Kit Install Guide: Intel Entry Server Chassis SC5295-E UP/DP/WS/BRP Intel Entry Server Chassis SC5299-E DP/WS/BRP

Rack Installation Instructions

Mobile Data Power Model: MDP-25

Single Station Remote Alarm

Transcription:

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install Carrier-Grade Instructions HP Part Number: AM275-9001A Published: July 2012 Edition: 3

Copyright 2009, 2012 Hewlett-Packard Development Company, L. P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. NEBS is a trademark of Telecordia Technologies Incorporated. Audience assumptions This document is for the person who installs, administers, and troubleshoots servers and storage systems. HP assumes you are qualified in the servicing of computer equipment and trained in recognizing hazards in products with hazardous energy levels.

1 Converting to carrier-grade This document provides information for the carrier-grade version of the commercial HP ProLiant DL380 G6 Server. This chapter provides the steps required to convert the commercial HP ProLiant DL380 G6 Server to its carrier-grade version. The conversion to carrier-grade consists of the following actions: Installing fans Changing the system maintenance switch Installing the ground lug Before you start The conversion kit (581031-B21) is intended for the DL380 G6 (E5540) Carrier-Grade Server only. This kit includes all the parts you need to convert the server to the NEBS-compliant version. NEBS certified configuration details are available from your HP sales representative. Conversion kit contents Table 1 Carrier-grade conversion kit parts list Description Part Number Quantity ASSY, FAN DL380G6 BAG, ZIP LOCK TERM, RING, VIN 12-10 AWG #10 LOCK WASHER HP ProLiant DL380 G6 Carrier-Grade Server RBI-Carrier-Grade Conversion Instructions BOX, TT 9.5 X 7.5 X 2.25 BAG, BUBBLE WRAP 6 X 8.5 Screw, 6-32 taptite, struck slot T15 Torx 463172-001 108344-001 545155-001 T10127-A00 AM275-9001A 111158-002 100473-001 192308-002 2 1 1 2 1 1 1 1 Preventing electrostatic discharge Overview To prevent damage to the system, you must take precautions when setting up the system or handling parts. A discharge of static electricity from a finger or other conductor might damage system boards or other static-sensitive devices. This type of damage can reduce the life expectancy of the device. To prevent electrostatic damage, take the following precautions: Avoid hand contact by transporting and storing parts in static-safe containers. Keep electrostatic-sensitive parts in containers until they arrive at static-free workstations. Before removing parts from containers, place parts on a grounded surface. Avoid touching pins, leads, or circuitry. Make sure you are grounded properly when touching a static-sensitive component or assembly. The following graphic provides an overview of the carrier-grade conversion process. Before you start 3

4 Converting to carrier-grade

2 Cabling Installing the ground lug To meet the bonding and grounding criteria for NEBS compliance, a dedicated ground lug is required. To install the ground lug, see the steps illustrated in the following figure: 1 Star washers 2 Grounding lug (545155-001) 3 T15 Torx screw (192308-002) The following figure illustrates the finished assembly of the ground lug. Installing the ground lug 5

Cable information This section provides cabling information for installing the HP ProLiant DL380 G6 Carrier-Grade Server. NEBS chassis ground This carrier-grade product is intended for use in both common bonding networks and isolated bonding networks. The product is equipped with a NEBS-compliant chassis ground lug located on the rear of the product. The ground lug included with the product accepts wire gauges between 10 and 12 AWG. Network cabling Intra-building connections of the HP ProLiant DL-Series Carrier-Grade Servers require the use of shielded cables grounded at both ends. CAUTION: The intra-building ports of the equipment are suitable for connection to intra-building or unexposed wiring or cabling only. The intra-building ports of the equipment must not be metallically connected to interfaces that connect to the Outside Plant (OSP) or its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports, as described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition of primary protectors is not sufficient protection to connect these interfaces metallically to OSP wiring. 6 Cabling

3 Power supplies specifications and cable information HP 1200W PSU 48VDC Input Part Number 437573-B21 Input Voltage Range (DCV) 36-72 Frequency Range (Nominal) (Hz) DC Nominal Input Voltage (VDC) 36 48 72 Maximum Rated Output Wattage 1200 1200 1200 Nominal Input Current (ACD) 38 28 19 Maximum Rated Input Wattage Rating (Watts) 1380 1350 1365 Maximum Rated VA (Volt-Amp) 1380 1350 1365 Efficiency (%) of Maximum Rated Output Wattage 87 89 88 Power Factor N/A N/A N/A Leakage Current (ma) N/A N/A N/A Maximum Inrush Current (A peak) 20 25 35 Maximum Inrush Current duration (ms) 1 1 3 Maximum British Thermal Unit Rating (Btu-Hr) 4713 4610 4662 NOTE: Battery return terminals are isolated DC returns (DC-I). Power cable color codes Each DC power cable is shipped with a label that describes each lead. The label is located near the pigtail leads. The three leads are described in the following table: Cable color Black Blue Green/Yellow Description Positive return Negative input voltage Safety ground HP 1200W Power Supply Part Number - AC 500172-B21 Operational Input Voltage Range (Vrms) 100 to 240 Frequency Range (Nominal) (Hz) 50/60 Nominal Input Voltage (VDC) 100 120 208 200 220 230 240 Maximum Rated Output Wattage 800 900 1200 1200 1200 1200 1200 Power cable color codes 7

Nominal Input Current (A rms) 9.7 9.0 7.0 6.8 6.4 9.1 5.9 Maximum Rated Input Wattage Rating (Watts) 930 1034 1348 1348 1348 1348 1348 Maximum Rated VA (Volt-Amp) 970 1079 1406 1406 1406 1406 1406 Efficiency (%) of Maximum Rated Output Wattage 86 87 89 89 89 89 89 Power Factor 0.97 0.97 0.97 0.97 0.97 0.97 0.97 Leakage Current (ma) 0.42 0.50 0.83 0.87 0.92 0.96 1.00 Maximum Inrush Current (A peak) 30 30 30 30 30 30 30 Maximum Inrush Current duration (ms) 20 20 20 20 20 20 20 Maximum British Thermal Unit Rating (BTU-Hr) 3174 3530 4600 4600 4600 4600 4600 Replacing the fans and power supplies If a cooling fan or power supply fails, you must replace it. Replacement usually takes no longer than 5 minutes. For instructions on replacing these components, see the HP ProLiant DL380 G6 Server Maintenance and Service Guide on the HP website at http://www.hp.com/support/manuals. Under Servers, click ProLiant ml/dl and tc series servers, and select your product. 8 Power supplies specifications and cable information

4 Installing the fans WARNING! metal objects. To prevent personal injury from hazardous energy, remove watches, rings, or other 1. Power off the server. 2. Remove power to the server. 3. Remove the top cover. 4. Locate the fan blanks. 5. Remove and discard the fan blanks. 6. Install the fans into the board. Make sure the power connector on the fan lines up with the power connector on the board. 7. Replace the top cover. Changing the system maintenance switch settings WARNING! metal objects. To prevent personal injury from hazardous energy, remove watches, rings, or other 1. Power off the server. 2. Remove power to the server. 3. Remove the top cover. 4. Locate the system maintenance switches which are visible through the opening in the PCI riser cage. Changing the system maintenance switch settings 9

5. Change the #10 system maintenance switch setting to the On position. You can use a plastic ball-point pen to flip the system maintenance switch. 6. Replace the top cover. Verifying the system maintenance switch setting After you switch the setting, verify that the #10 system maintenance switch is in the On position. NOTE: The following instructions use ilo 2. For complete information and instructions on using ilo 2, see the HP Integrated Lights-Out 2 User Guide on the HP website at http://www.hp.com/ bizsupport/techsupport. 1. Log in to ilo 2. For instruction, see the HP Integrated Lights-Out 2 User Guide. 2. Select System Information on the left navigation bar. 10 Installing the fans

3. Select the Temperatures tab. If the temperature thresholds appear as shown below, the switch is set correctly. Incorrect thresholds If the thresholds don't show up correctly, you might have switched the wrong switch. Ensure the switch is reset to the factory defaults as described in the HP ProLiant DL380 G6 Maintenance and Service Guide on the HP website at http://h20000.www2.hp.com/bizsupport/techsupport. After you reset the switch settings to the factory defaults, repeat the above process for verifying the system maintenance switch setting. Changing the system maintenance switch settings 11

5 Installing the DL380 server into a seismic rack For information on the installation of the DL380 using the commercial rack mount kit, see the HP website at http://www.hp.com/support/manuals. Under Servers, click ProLiant ml/dl and tc series servers, and select your product. While not specifically designed for use in seismic rack solutions, the commercial kit was successfully evaluated in the AH343A HP Seismic Rack to the NEBS Zone 4 criteria as part of the DL380 Server NEBS certification. IMPORTANT: Perform all the steps in the kit with the exception of the steps specified here in this procedure which pertains only to installing a DL380 into a seismic rack. Hardware kit contents In addition to the supplied items, you might need: Screws that fit the rack The appropriate screwdriver for the screws Installing the rack mount kit CAUTION: Plan the rack installation so that the heaviest item is on the bottom of the rack. Install the heaviest item first, and then continue to populate the rack from the bottom to the top. NOTE: The following procedure was performed by HP personnel to install the rack mount kit. This information is provided as an example and a reference to assist in the installation of a DL380 Server into a seismic rack. 1. Unscrew the eight snap-in screws from the mounting rails, and discard the screws. 2. Obtain eight round-hole M5 cage nuts that are intended for use with the seismic rack. 12 Installing the DL380 server into a seismic rack

NOTE: The square-hole cage nuts that are provided in the rack kit do not fit in the round holes in the seismic rack. 3. Install the round-hole M5 cage nuts in the appropriate rack hole positions where you want to install the DL380 Server. Two cage nuts on the front of each rail. Two cage nuts on the back of each rail. 4. Line up the mounting rail with the cage nuts, and fasten the mounting rail to the rack with M5 screws. IMPORTANT: You must provide the screws to secure the slide mounting bracket assemblies. Hardware kit contents 13

NOTE: Apply some pressure when fastening the screws to the mounting rail. 5. Repeat steps 1 through 3 for the other mounting rail. WARNING! To reduce the risk of personal injury or equipment damage, be sure that the rack is adequately stabilized before sliding the inner slides into the slide mounting bracket assemblies. 6. To install the side rails on each side of the server, align each side rail to the server, and snap it into place. 7. Slide the server onto the mounting rails and into the rack. 14 Installing the DL380 server into a seismic rack

8. Snap the server into place. 9. Fasten the server to the rack, using the screws included in the rack kit as described in the rack kit instructions for preparing a server for shipment. a. Pull down the plastic retention lever on each side of the server. b. Insert the screws into each side. 10. Install the cable arm using the instructions in the rack kit. Hardware kit contents 15

*AM275-9001A* Printed in the US