OCTOPLUS WARNING AND MEASUREMENT CONTROL UNIT FOR TOXIC AND FLAMMABLE GASES



Similar documents
RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

ES-CAM2AU IP Camera.

CO2 Alarm. Operation. Application

Controller Automation, Model II+

NortechCommander Software Operating Manual MAN R6

S4000TH HART. HART Communication Manual

Manual for Fire Suppression & Methane Detection System

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

4 Starts to flash when the system triggers an alarm/fault

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE

MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss heating

WD-AMX Water Detection Controllers

Conventional Fire Detection and Extinguishant Control System Specification

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

PK5500 v1.1 Installation Instructions

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

ES-CAM3A Outdoor IP Camera

Memcom Emergency Telephone

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

7 Digital Photo Frame Instructional Manual

9452/9453 Installation and User Guide

ES-CAM2A IP Camera.

DC-8706K Auto Dial Alarm System

Digital Keypad Use s Manual

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

600-GD & 600-GDL 600 SERIES GAS DETECTOR

MADRIX NEO Quick Start Guide & User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

SmartLine. Conventional Fire Detection Control Panel. Extinguishant system Control Panel. User's Manual. GameOver

Water Leak Detection System

USER MANUAL. Model U ForeFront Alarm Card SALES OFFICE (301) TECHNICAL SUPPORT (301) An ISO-9001 Certified Company

VFS24/32HDIP. Public Display IP Monitor User Manual

User's Manual. Research Isometric Transducer 0 to 5 grams and 0 to 50 grams

Network Time Accessories LED CLOCK. (for NTP Synchronization)

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Energy Communication Unit (ECU)

T5000 T000 LCD Digital Fan Coil Thermostat

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

ALARMS-xx. Remote Alarm Unit Setup Guide RESET ALL

COMPLETE MANUAL. Version: Optic. September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s CHIAVARI (GE) Tel Fax mailto: len@len.it url: http//

Installation Handbook. Interactive Fire Alarm System Release 3. Repeater Panel BU-320 / Information Panel BV-320

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide

INSTALLATION GUIDE. FCC ID NOTICE

1CH VIDEO SERVER INSTALLATION GUIDE. Please read instructions thoroughly before operation and retain it for future reference.

LCD5500Z / PKP-LCD v3.x Installation Instructions

Ethernet Networking Installation & Operations Manual Humminbird ETHERNET

User Manual. Humidity-Temperature Chart Recorder. Model RH520

BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC

TP TP8-28 GSM. User quick guide Release: FW version: Control panel versions: Programming SW version: Update: Language:

Alarm Clock USER GUIDE

Communication bridge Xcom-MS User Manual

2-Way Wireless Indoor Siren Installation Guide

D-MAX WEB GUIDE CONTROLLER WITH OPERATOR INTERFACE PANEL QUICK START SETUP MANUAL

Security System User Guide

DAB+ / FM Tuner Model: TU-201

Business/ Home GSM Alarm System

BroadBand PowerShield. User Manual

SFC-200 SERIES LCD FIRE ALARM PANEL

1 QPro HelpFile 01.EN COPYRIGHT CONTRIVE

AC-115 Compact Networked Single Door Controller. Installation and User Manual

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

User Manual THR840DUK Digital Thermostat

25 Code GTO Digital Keypad

Ingenico. User Guide 5100M. Secure transaction and payment solutions

StackFlowMaster FPD580 TORBAR probe Stack gas metering systems. Measurement made easy. Introduction. For more information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

USER MANUAL. SAILOR 100 Satellite TV

SMM. Installation Operation Maintenance

Operating Instructions

Solar Powered Outdoor Siren Manual

How To Program An Autodialer

HM-W536 Install Guide

BW TECHNOLOGIES GasAlertMicroClip Soft Tools Instruction Sheet

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

FIRE AND BURGLAR ALARM SYSTEM BASED ON Central Panel «KODOS A-20» User Guide

GSM home alarm system s manual

Energy Communication Unit (ECU)

WIRELESS STATUS MONITOR

Home Security Alarm System

Packs Infotel Limited M30. ULTIMATE Operating Instructions. Version: Copyright Packs Infotel Limited 2015, all rights reserved.

ZC-24DO CANopen I/O Module: 24 Digital Outputs

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

How to read this guide

FT-100 Fire Training Fog Machine User Manual English

conventional system operation

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

1.3 MEGAPIXEL WIRELESS NETWORK CAMERA SERIES

8 Digital Photo Frame Instructional Manual

AIM TECHNICAL MANUAL PATENT PENDING STOP REMEMBER TO ACTIVATE UNIT BEFORE TESTING. See page 9 for Activation Instructions

User manual Rev 1.3 Contents

CL90i Please read these instructions before operating the product. 3 - Beam Self-Leveling Cross Line Laser

Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Wiring Instructions and Operating Manual 12 POINT ULTRABEAM REMOTE MONITORING SYSTEM

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

Transcription:

OCTOPLUS WARNING AND MEASUREMENT CONTROL UNIT FOR TOXIC AND FLAMMABLE GASES USER'S MANUAL

Copyright 2013 by Dalemans s.a. Article IMP00000062 Revision V2R0 of 25/11/2013 Any reproduction, whether partial or entire, made of this document, by whatever means, without the prior, written consent of Dalemans s.a. is strictly forbidden. All of the information contained in this document is non-contractual and is subject to modification without warning. Dalemans s.a. Rue Jules Mélotte, 27 B-4350 Remicourt (Belgium) Tel. +32(0)19 54 52 36 Fax +32(0)19 54 55 34 Email : info@dalemans.com

QUICK GUIDE B. Data viewing... 10 1X B. Data viewing... 10 Display data of one particular detector 1X Display data of current detector D. Restricted modifications... 13 10" 1X Cut off alarm... 12 Parameters - Time... 13 - Date... 14 - Language... 14 10" C. Reset... 12 Messages - Failures... 15 Siren - Cut off alarm Alarms - Reset levels of alarm Test alarms... 16 Max. Value - Reset max. values View - Status Relays... 17 - Battery Voltage... 18 - Maximum Values... 18 10" E. Advanced modifications... 19 Password : 1234 Parameters modification - Levels of alarm... 20 - Location... 21 - Sensor number... 21 - Inhibit output relays... 22 - Versions... 22 Front Panel key switch Hidden key switch (inside the Control Unit - see page 19) USER MANUAL 3

This page intentionally left blank USER MANUAL 4

TABLE OF CONTENTS A. INTRODUCTION... 9 a. Start-up, standby screen... 9 b. Notes... 9 Symbols... 9 B. DATA VIEWING... 10 STOP 1X... 10 MENU 1X... 10 a. Alarms... 11 Fail LED's... 11 Scanning display... 11 Explorer menu... 11 C. RESET... 12 RESET 1X... 12 RESET 10 seconds... 12 D. RESTRICTED MODIFICATIONS... 13 a. Parameters... 13 Time... 13 Date... 14 Language... 14 b. Messages... 15 Failures... 15 c. Test alarms... 16 d. View... 17 Status Relays... 17 Battery Voltage... 18 Maximum Values... 18 E. ADVANCED MODIFICATIONS... 19 a. Parameters modification... 20 Levels of alarm... 20 Location... 21 Sensor number... 21 b. Output relays inhibit... 22 c. Versions... 22 F. FAIL CODES... 23 Mother Board inputs... 23 Other... 23 G. INDEX... 24 USER MANUAL 5

ENVIRONMENT The crossed-out wheelie bin logo on this product indicates that you are held to respect the regulation in force on the collection and recycling of waste electrical and electronic equipment (WEEE). These provisions are intended to preserve the natural resources used for manufacturing this product and to avoid the dispersion of substances potentially harmful for the environment and human health. Therefore, to dispose of your end-of-life product, you MUST hand it over to a designated collection point for the recycling of electrical and electronic equipment. For further information about the collection points in your area, contact your local city authority. USER MANUAL 6

WARNINGS The fitter commits himself to comply with EC standards and with the installation instructions. The installation must be carried out by qualified personnel. All our products are tested and inspected before shipping. These instructions must be read carefully by any person who has or will have the responsibility for the installation, the use and/or the maintenance of this equipment. The warranty provided by Dalemans will be voided if installation, use and maintenance of this equipment are not in accordance with the instructions given in this manual. By respecting these instructions you guarantee the correct operation of the apparatus. Should you require any further information about the use or the maintenance of this product, do not hesitate to contact Dalemans PRIOR to carrying out installation works. Each apparatus must be installed, operated and maintained according to the instructions, the warnings and the operational limits detailed in this manual. Use only Dalemans original parts when you assume the maintenance of this product as specified in this manual. The use of non-dalemans spare parts may seriously impair the performances of the apparatus. Repair or maintenance attempts carried out without observing the procedures described in this manual or without the assistance of our after-sales service may prevent the equipment from working properly and, consequently, from ensuring the safety of the occupants of the building and of the plants. This product must be installed in a dry and clean place. Install a protective screen or enclosure to avoid any direct exposure to the sun or possible projections of water or of polluting agents. Do not hesitate to contact Dalemans for any additional information about the use or the maintenance of this product. Dalemans reserves the right to modify its products in the advent of technical or other developments, at any moment and without warning. DISCLAIMER Dalemans cannot be liable for direct or indirect damages arising out of the non-observance of its instructions. Every effort has been made to ensure the accuracy of the information given in this document. Nevertheless, Dalemans s.a. declines any responsibility in the event of errors or omissions in this document. COPYRIGHT The plans, drawings and information contained in this manual are the property of Dalemans s.a. and may not, by whatever means, be reproduced, communicated, translated or used without prior, written permission. USER MANUAL 7

This page intentionally left blank USER MANUAL 8

A. INTRODUCTION a. Start-up, standby screen OFF Turn ON the power switch of the mother board to power on the Control Unit. ON OctoPLUS V 2.0.1 DALEMANS S.A. OctoPLUS Scan Control Units At start-up, the screen displays : - Software version - Scanning of the Control Units. Control unit Nr 1 - Detector Nr 3 Location (user modifiable) D1.3:Detector 3 6 PPM CO 2 MENU RESET STOP Measured Gas level Function keys After start-up, the screen scans and displays the data of the detectors in sequence. The display is updated every 3 seconds. b. Notes The zoom frame shows the key to press to perform the function. No Alarm CUnit: 1 Det : 1234 Press matching key to perform function The screen can display up to 4 rows. Last row is dedicated to the function keys. When stopping the display on a particular detector, data are displayed for 30 seconds then the screen starts again scanning the detectors in sequence. Symbols Validate selection Navigate through the menu Exit menu Press key 1X Keep key pressed for at least 5 seconds. Hidden key (inside the Control Unit - see page 19) Ensure to always validate selection. You can navigate through menu or screen using the arrow keys : Move selection horizontally Move selection vertically Increase/decrease value USER MANUAL 9

B. DATA VIEWING Measures, levels of alarm, averages, measuring ranges, faults Data of detectors can be displayed in two ways : STOP 1X Press key STOP when the desired detector appears on the display. D1.3:Detector 3 6 PPM CO 2 MENU RESET STOP MENU 1X Press key MENU D1.3:Detector 3 6 PPM CO 2 RESET MENU STOP Use keys to select Control Unit and detector then press to view data of the selected detector. State of alarm of the selected detector No Alarm Cards: 12 Det : 12342 Selected control unit Selected detector D1.3:Detector 3 6 PPM CO 2 START Return to displaying detectors in sequence View configuration of the selected detector View next detector D1.3:Detector 3 DetNr:D0003 Range:0-3002 START Range:0-300 Lev. F:2.50 ma Lev.A1:50 ppm Lev.A2:100 ppm Lev.A3:150 ppm Lev.A4:200 ppm Avg. :6 ppm Measuring range Fault Level Levels of alarm Measure average according to configuration USER MANUAL 10

a. Alarms The front panel of the OctoPLUS has yellow and red LED's to give failure and/or alarm warning. Main Power failure Battery failure General failure Main Power ON Levels of Alarm (A1 - A4) LED indicators General failure : yellow LED ON when general failure and/or battery failure is detected. e.g. : broken cable, battery voltage too low, Main Power failure : yellow LED ON when OctoPLUS switches on battery upon main power supply failure (230 Vac). Battery failure : yellow LED ON when battery failure is detected (e.g. battery voltage too low). Levels of Alarms : red LED ON when an alarm is detected (gas concentration over level of alarm). Failures and alarms can be read in the scanning screen or by MENU function. Use STOP or MENU function to display a detector (see previous page). Scanning screen Explorer menu Control unit Nr 1 - Detector Nr 3 State of alarm of the detector D1.3:Detector 3 6 PPM CO Alarm:F A1 A2 START Alarm Centr: 12 Det : 12342 Fail Active levels of alarm Selected control unit Selected detector D1.3:Detector 3 6 PPM CO Alarm:F A1 A2 START Fail Active levels of alarm USER MANUAL 11

C. RESET This function allows alarm cut-off and reset of levels of alarm and of measured values. RESET 1X RESET 10 seconds D1.3:Detector 3 6 PPM CO 2 MENU RESET STOP D1.3:Detector 3 6 PPM CO 2 MENU RESET STOP The OctoPLUS can be configured in two different modes : - Normal mode - Alarm cut-off mode Normal mode RESET 1X : stops alarm and reset level of alarm if gas concentration is below level of alarm. Alarm cut-off mode This function is especially used for resetting max. values and latched alarms. Reset Menu Siren Siren Alarms Max. Value RESET 1X : stops alarm. REST 2X : output relays return to normal position if gas concentration is below level of alarm. Note : "Normal" and "Cut-off alarm" mode configuration requires OctoPLUS configuration software. Select the item to reset with and press. Siren : Cut off alarm Alarms : Reset levels of alarm Max. Value : Reset Max. measured values Reset is immediately performed and confirmed by the following screen : Reset USER MANUAL 12

D. RESTRICTED MODIFICATIONS Time, date, language, messages, alarm test, relays status, battery voltage, max. values. a. Parameters D1.3:Detector 3 6 PPM CO 2 RESET MENU STOP Hold key MENU pressed until General Menu appears. Parameters Parameters Select Parameters using keys and press key. To exit menu select and press key. Time Clock Clock To change time, select Clock from the Parameters Menu (see above) using keys and press. Change Make your choice Time Date Select Time with keys then press. Change Time : 12:45 VAL Increase/decrease digit Select digit Move selection using keys, then adjust digit value with and press key to save. Note : Keys are inside the Control Unit enclosure (see page 19). Yes Accept value No Press YES to save or NO to discard the modifications. USER MANUAL 13

Date Change Make your choice Time Datee To change date select Date from the Clock Menu (see page 13) and press key. Day Month Change Date : Mon 21 Jan 1 VAL Increase/decrease digit Select digit Year 1 = Non-leap year 0 = Leap year Move selection using keys then adjust value with and press to save. Note : Keys are inside the Control Unit enclosure (see page 19). Change Date : Mon 21 Jan 1 Day out of range VAL Error message If wrong values are entered an error message will appear. Yes Accept value No Press YES to save or NO to discard the modifications. Language Clock To change the menu language, select Language from the Parameter Menu (see page 13) using keys and press. Clock Language Change Select Language NL FR UKe Select desired language using keys and press to save : NL : Dutch FR : French UK : English Accept value Press YES to save or NO to discard the modifications. Yes No USER MANUAL 14

b. Messages Failures D1.3:Detector 3 6 PPM CO 2 RESET MENU STOP To display failure messages hold key MENU pressed until appears. Parameters Messages From the, select Messages using keys and press. To exit menu select and press key. Messages Faults Faults Messages Select Faults using keys and press. Detector Nr. Control unit Nr. Fault ID Code Fault description M1 :92,Batt. Conn. M1.1:11,Fault zone M2.3:13,Fault zone REF Scroll down using keys to see the list of failures (Faults) which occurred on the system. REF : even if a failure is no longer active it still appears in the list of faults until you refresh the display by pressing the key REF. Scroll down Refresh display Exit menu Fault ID Code : every failure is identified by a code and a brief description. Faults ID Codes are listed at page 23. No Faults If there is no failure the message "No Faults" appears instead of the list of failures. USER MANUAL 15

c. Test alarms D1.3:Detector 3 6 PPM CO 2 RESET MENU STOP To perform alarm simulation, enter by holding the key MENU pressed. Parameters Scroll down and select Test Alarms using keys and press. Messages Test Alarms Control unit Nr Select Sens. Card: 1 Det : 1234 Use keys to select Control unit and Detector for which the alarm test has to be performed. Press key. Detector Nr Gas level Loop current Test Alarms 0ppm I: 4,00mA A1: No Alarm START STOP Press key START to start the test. Press STOP to stop the test. Press to exit test. Start test Stop test Exit menu No Alarm D A1 A2 A3 A4 : no active alarm : Fail alarm active : Level of alarm A1 active : Level of alarm A2 active : Level of alarm A3 active : Level of alarm A4 active During alarm test, yellow and red LED's of the control panel and output relays operate according to software configuration. USER MANUAL 16

d. View Status of output relays, battery voltage, max. measured values, D1.3:Detector 3 6 PPM CO 2 RESET MENU STOP To enter the View Menu, hold the key MENU pressed. Parameters Select View using keys and press. Test Alarms View Status Relays Display values Status Relays This function allows viewing the status of each output relay and checking whether it is activated or not. Display values Status Relays From View Menu, select Status Relays using the keys and press. Control unit Nr View next Relay board Relay board Nr Relay Nr Status Relays CR1.1. 12345678 00000XXX The screen displays status of output relays for each Control unit. Press key to view next Relay Board. Relay Board Nr 1 relates to the 5 relays of the Mother Board of the Control unit. 0 = Relay not activated 1 = Relay activated X = Relay not installed Exit menu Relay Boards from Nr 2 on relate to additional Relay Boards (8 relays). USER MANUAL 17

Battery Voltage Display values Status Relays This function allows reading the battery level. Display values Status Relays Bat. voltage From View Menu (see above), scroll down and select Bat. voltage using the keys. Press key. Control unit Nr View next control unit Battery voltage Cards: 1 U bat: 24,07V Battery voltage Exit menu The screen displays the battery voltage level for each Control unit. Press key to view next Control unit. Maximum Values Display values Status Relays This function allows reading the maximum values measured by the detectors. Display values Bat. voltage Max. Value From View Menu (see page 17), scroll down and select Max. Value using the keys. Press key. Control unit Nr Select Sens. Cards: 1 Det : 1234 Detector Nr Use keys to select Control unit and Detector whose you want to view max. value then press key. Control unit Nr Detector Nr Max. Value Det. : D1.1 Value: 7 ppm Max. measured Value Exit menu USER MANUAL 18

E. ADVANCED MODIFICATIONS For modifying advanced parameters such as relays inhibition, level of alarm or detector number, a PIN code is required. Advanced Modification Menu requires the use of a switch key which is inside the Control unit. To open the OctoPLUS Housing : 1. Remove the transparent lid (Fig. 1). Fig. 1 Fig. 2 2. Unscrew the 4 screws with a suitable flat screwdriver and remove the lid (Fig. 2). Front side Display Circuit Board Rear side To enter Advanced Modification Menu hold the key SW151 pressed. This key switch is on both sides of the Display Circuit Board (Fig. 3). SW151 Fig. 3 Password : 1234 Enter Password 0000 VAL To enter password, move selection with keys, change value of digit with keys, and press. Increase/decrease digit Select digit Adv. Modification Modification To proceed with advanced modification, select desired option with keys and press. Modification Inhibit Relays Version Info To exit menu, select and press key. USER MANUAL 19

a. Parameters modification Levels of alarm, detector location, detector number. Adv. Modification Modification Alarm Levels To enter Parameters Modification menu, from Advanced Modification menu (see previous page), select Modification with keys and press. To proceed with modification, select the parameter to modify with keys and press. Alarm Levels Location Sensor Nb To exit menu, select and press key. Levels of alarm Alarm Levels Control unit Nr Select Sens. Cards: 1 Det : 1234 Detector Nr Change Select Level DEF A1 A2 A3 Use keys to select Control unit and Detector you want to modify then press key. Select the level of alarm to modify with the keys then press. Note : scroll further levels with key. Change alarm level DEF: 02,50 VAL Increase/decrease digit Yes Select digit Accept value No Move selection with keys, increase/decrease digit value with keys then press VAL. DEF : Level of alarm Fail A1 : 1 st level of alarm A2 : 2 nd level of alarm A3 : 3 rd level of alarm A4 : 4 th level of alarm Press YES to save or NO to discard the modifications. USER MANUAL 20

Location Alarm Levels Location Control unit Nr Select Sens. Cards: 1 Det : 1234 Detector Nr Change location DETECTOR CO VAL Use keys to select Control unit and Detector you want to modify then press key. Move selection with keys, change digit with keys then press VAL. Increase/decrease digit Select digit Yes Accept value No Press YES to save or NO to discard the modifications. Sensor number Location Sensor Nr Control unit Nr Select Sens. Cards: 1 Det : 1234 Detector Nr Change Sens. Nr. D0001 VAL Use keys to select Control unit and Detector you want to modify then press key. Move selection with keys, change digit with keys then press VAL. Increase/decrease digit Select digit Yes Accept value No Press YES to save or NO to discard the modifications. USER MANUAL 21

b. Inhibit output relays The purpose of this function is to inhibit output relays for 30 seconds in order to allow testing the detectors without any actuation of the output devices (e.g. valve, ventilation, ). Adv. Modification Modification Enter in Advanced Modification menu (see page 19). Adv. Modification Modification Inhibit Relays Select Inhibit Relays with keys and press. Yes Inhibit Relays No Press Yes to inhibit relays or No to abort and exit menu. c. Versions This function allows viewing the version of the software of the OctoPLUS. Adv. Modification Modification Enter in Advanced Modification menu (see page 19). Adv. Modification Inhibit Relays Version Info Select Version Info with keys and press. Version Cards: 1 Use key to Select the Control unit to view and press. Version Display : V2.0.1 Mot. Board: V2.0.1 Display Mot. Board Config. Press key to scroll down. Display : Version of the software of the display board. Mot. Board : Version of the software of the mother board. Config. : Version of the configuration. USER MANUAL 22

F. FAIL CODES Mother Board inputs The first digit of the fail code gives the address of the mother board. The second digit gives the address of the input concerned by the failure. Examples : 18 : failure on input Nr 8 of mother board Nr 1. 25 : failure on input Nr 5 of mother board Nr 2. 61 : failure on input Nr 1 of mother board Nr 6. Possible fail codes for mother board Nr 1 11-12 - 13-14 - 15-16 - 17-18 Possible fail codes for mother board Nr 2 21-22 - 23-24 - 25-26 - 27-28 Possible fail codes for mother board Nr 3 31-32 - 33-34 - 35-36 - 37-38 Possible fail codes for mother board Nr 4 41-42 - 43-44 - 45-46 - 47-48 Possible fail codes for mother board Nr 5 51-52 - 53-54 - 55-56 - 57-58 Possible fail codes for mother board Nr 6 61-62 - 63-64 - 65-66 - 67-68 Possible fail codes for mother board Nr 7 71-72 - 73-74 - 75-76 - 77-78 Possible fail codes for mother board Nr 8 81-82 - 83-84 - 85-86 - 87-88 Other 01 Communication failure on clock. 02 Communication failure on EEPROM. 03 Program failure with reference to configuration. 04 Communication failure on display. 08 EEPROM failure. 90 Battery too low. 91 Main power failure (230 Vac). 92 Battery not connected. USER MANUAL 23

G. INDEX ALARM Cut off... 12 Display... 11 Test... 16 BATTERY Alarm LED... 11 Level... 18 CLOCK... 13 DATE... 14 DETECTOR Alarm LED... 11 Range... 10 Viewing Data... 10 ERROR CODES... 23 FAIL Display... 15 Fail Codes... 23 LED... 11 FUNCTION KEYS... 9 LANGUAGE... 14 LEVELS OF ALARM Modification... 20 Reset... 12 MAX. VALUES... 18 MESSAGES... 15 PARAMETERS Date... 14 Language... 14 Levels of Alarm... 20 Location... 21 Password... 19 Sensor Number... 21 Time... 13 RELAYS Inhibit... 22 View... 17 RESET Alarms... 12 Levels of Alarm... 12 Max. Values... 12 Siren... 12 SIREN... 12 SYMBOLS... 9 TEST ALARMS... 16 TIME... 13 VERSION INFO.... 22 VIEW Battery Level... 18 Max. Values... 18 Output Relays... 17 USER MANUAL 24

NOTES