A Study of a MV Cable Joint



Similar documents
Fault location on power cables. Fault location on power cables

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

UGVCL/SP/591/11KV HT AB CABLE

Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer

CABLE ACCESSORIES kv

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

APPLICATION ORIENTED DESIGN OF CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

Network Standard Advice No. 1420C 9/6/2011

Section kv Power Cables

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

Development of a 500-kV DC XLPE Cable System

AORC Technical meeting 2014

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

Medium Voltage Joints & Terminations

Modelling of Electrostatic Ignition Hazards in Industry: too Complicated, not Meaningful or only of Academic Interest?

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT ON SOLID DIELECTRIC DC CABLE

Transformer Bushings for GIS

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

VIPERFLEX ELECTRIC CABLE

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

How To Test For Safety On A Power Cable

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Coaxial Cable Feeder Influence on Yagi Antenna Dragoslav Dobričić, YU1AW

The new 525 kv extruded HVDC cable system

High Voltage Systems. Today. The history of cables

MV CABLE TYPE C

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

CONFLEX ELECTRIC CABLE

I-PEX MHF4 Micro Coaxial Connector

EDITION 2012 CABLE SYSTEMS

Festoon 715 P PUR cable for flexible application in festoon systems

Space charge build-up in XLPE-cable with temperature gradient

ScottishPower Distribution Cables & Equipment. Metal Theft

Flexible cables for submersible products

1. A wire carries 15 A. You form the wire into a single-turn circular loop with magnetic field 80 µ T at the loop center. What is the loop radius?

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

Cutting and stripping tools

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Effect of design parameters on temperature rise of windings of dry type electrical transformer

Bending, Forming and Flexing Printed Circuits

3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max

DEHN + SÖHNE. DEHNconductor System No Problems with Proximities

Thermal Control of the Extrusion Press Container

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Cable Strippers: High, Low and Medium Voltage

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of

Metal-Oxide Varistors (MOVs) Surface Mount Multilayer Varistors (MLVs) > MLN Series. MLN SurgeArray TM Suppressor. Description

CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR

COMPUTATION OF THREE-DIMENSIONAL ELECTRIC FIELD PROBLEMS BY A BOUNDARY INTEGRAL METHOD AND ITS APPLICATION TO INSULATION DESIGN

SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE

08. SEK IDC CONNECTORS

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables /15 kv XLPE insulated cables /20 kv XLPE insulated cables 35

How To Read A Pipe From A Sensor

OLI. Oil level indicator

48 SERIES Relay interface modules 10 A

The DC Motor. Physics 1051 Laboratory #5 The DC Motor

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

DOING PHYSICS WITH MATLAB COMPUTATIONAL OPTICS RAYLEIGH-SOMMERFELD DIFFRACTION INTEGRAL OF THE FIRST KIND

6 ELECTRICAL PARAMETERS

Draka Industrial Cable GmbH

EDS KV TRIPLEX CABLE

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope

Flexible Control Cables

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Catalog May Cable Accessories < 1 kv

Voltage Detection and Indication by Electric Field Measurement

Power Resistor Thick Film Technology

Comparative study for cables and busbars

Experimental results for the focal waveform and beam width in the focusing lens with a 100 ps filter

Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge

Respecting the environment

UPSETTING OF BIMETALLIC COMPONENTS IN CLOSED DIE

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES

Direct Attach Cable with Micro Coaxial Wire for Data Center

HV Submarine Cable Systems Design, Testing and Installation

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Gulf Cable & Electrical Ind. Co.

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

Vert-X 16-5V / % Ub. Applications Servodrives Dancer arm Operating table

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

A new technology for high current, low insertion force, low resistance and long cycle life power connectors

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Transcription:

SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction parameters of a medium voltage (MV) cable joint were examined in order to reduce the electric field magnitude inside the joint. The joint was covered with a heat shrinkable tube made of two or three layers. The permittivity of the layers was varied. The termination angle of the cable dielectric was also considered. Keywords: Electric field reduction, Dielectric properties. 1 Introduction Cross linked polyethylene (XLPE) cables have been in widespread use for decades. Manufactured cable lengths are typically below 1000 m, so several sections of cable may be needed to create a long distance cable line. Consequently, the line quality depends strongly on the reliability of the cable joints. It depends equally on the quality of terminations, but they are considered elsewhere. More details on the cable considered here are listed in Table 1. Numerical modelling of the cable joints offers an elegant way to study the electric and magnetic fields inside them, to identify critical spots, improve design and to reduce manufacturing costs [1]. In order to make a joint, the conductors of two consecutive sections of cable are stripped of insulator and joined together with a copper or aluminium ferrule. Sophisticated multilayer materials may be used to insulate the ferrule and fill in the space left by the missing dielectric. The joint is covered with heat shrinkable tube (HST) for protection. Different cable joints are in use, most often with capacitive/geometric, refractive or resistive control of the electric field inside the joint [2]. Two joints from Fig. 1 are described in this work. They combine geometric and high permittivity regulation of the field. The joints may come partially or entirely prefabricated or may be made on site. Good electrical properties of the cable joints depend on the skill of the technicians who assemble them. The termination angle of the cable dielectric is sometimes made according to their 1 Research Institute, Holding Kablovi a.d., Gine Pajevic 14, 35000 Jagodina, Serbia; E-mail: rasad@ptt.rs 2 Faculty of Engineering, FTN, University of Novi Sad, Trg Dositeja Obradovica 6, 21000 Novi Sad, Serbia; E-mail: pekaric@uns.ac.rs 3 Faculty of Engineering, FTN, University of Novi Sad, Trg Dositeja Obradovica 6, 21000 Novi Sad, Serbia; E-mail: miodragm@uns.ac.rs 1

R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov individual experience. Factory prefabricated parts are preferred in order to minimize human error as much as possible and to reduce assembling time [3]. Accordingly, the goal of this work was to increase the number of prefabricated parts and to reduce the possibility of individual error. Table 1 Manufacturing data for the Al/XLPE/PVC cable (1 120mm 2, 12/20kV). Conductor (1) Cross-section (mm 2 ) 120 Material Copper or Aluminium Diameter (mm) 15 Conductor screen Thickness (mm) 0.5 Cable insulation (2) Material XLPE Thickness (mm) 5.5 Insulation screen (3) Thickness (mm) 0.5 Metal screen Cross section (mm 2 ) 16 Outer PVC tubing Thickness (mm) 2 Outer diameter (mm) 34 Fig. 1 Medium voltage cable joint constructions: CJ1 - upper, CJ2 - lower. Legend: 1 - conductor, 2 - dielectric, 3 - cable screen end, 4 - ferrule insulation, 5 - ferrule, 6 - high permittivity layer or wrap (HPW), 7 - EP rubber, 8 - semiconducting layer. HST1: 6+7+8. HST2: 7+8. 2

A Study of a MV Cable Joint Item Table 2 Some data on the joint parts. Geometry Relative permittivity, ε r Dielectric end (2) θ = 10 90 2.3 Ferrule (5) Length 100 mm (70 mm Cu, 133 mm Al), φ = 20 mm N/A Ferrule insulation (4) 1-100 High permittivity layer, HPW (6) 1 3 mm thick 10-40 EP Rubber (7) 3 mm thick 3.4 Semiconducting layer (8) 1.5 mm thick 100 Some joint data may be found in Table 2. The first type of joint, labelled CJ1, was designed with a three-layer heat shrinkable tube, HST1. The second type of joint, labelled CJ2, was designed with high permittivity wrap, HPW, placed only on top of the cable screen end, under the two-layer heat shrinkable tube, HST2. A range of different values of permittivity were explored for the HPW and for the inner layer of HST1, but in the end both were designed from the same material for ease of comparison. 2 Numerical results According to our experience [4], cable joints need to be designed with increased permittivity materials and with carefully controlled geometry. Both CJ1, with three-layer heat shrinkable tube HSTl, and CJ2, the lower cost joint with two-layer heat shrinkable tube, from Fig. 1, were considered. The electric field inside the joints was calculated using a commercially available finite element method program. The calculations explored: 1. Permittivity of ferrule insulation, ε, (layer 4 from Fig. 1), 2. Angle θ at the boundary between the ferrule insulation and cable insulation, 3. Permittivity ε of the bottom layer (layer 6, from Fig. 1) of the HSTl as well as permittivity of the HPW of CJ2, 4. Thickness of layer 6 both for the HSTl and for the HPW of CJ2. 3

R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov In order to choose the appropriate set of joint parameters, two quantities were calculated: 1. Maximum electric field strength, E, and max 2. Tangential electric field component E. tan Many calculations were peormed in search of the best way to reduce the maximum field magnitude, E, max and if possible at the same time to reduce the tangential component E tan (magnitude of the electric field vector parallel to the boundary suace). The area affected by the increased field intensity was also assessed. The relative permittivity, ε, of the ferrule insulation was found to play a great role in field formation. In the case of CJ1, a higher permittivity forced the electric field out of the ferrule insulation, so that the highest magnitude of field was compressed in the narrow space inside HSTl. As pointed to by the arrow in Fig. 2, the voltage gradient was very high both at the top of the ferrule insulation and on the upper edge of the cable dielectric. Not shown here, in the case of CJ2, there was a bit more room inside HST2. The ferrule insulation was made of a rubber-based material with good plasticity. A lower ferrule insulation permittivity, ε, between 5 and 10, turned out to be better at reducing the total field. It allowed more room for the field to expand into. The voltage gradient was less abrupt on top of the ferrule insulation (see Fig. 3). The main electric stress was located close to the conductor, at the cable dielectric end, as pointed to by the arrow. The family of curves in Fig. 4 were calculated for different angles θ, ranging from 10 to 90 degrees. Different angles gave different geometries for the dielectric cone: for θ = 90 no dielectric cone around the conductor, for θ= 28 10 mm long cone, for θ = 15 20 mm long cone and for θ= 10 30 mm long cone. Larger θ (shorter cone at the end of the cable insulation) resulted in a lower total field magnitude. Smaller θ (longer cone) was found to reduce the tangential field component along the cable insulation boundary but at the same time significantly increased the maximum total field magnitude inside the joint. Although the tangential field component may be important, the total field magnitude is crucial. Fig. 4 illustrates how the maximum strength of the total electric field inside joint CJ1 changes as a function of the ferrule insulation relative permittivity. The range 1 100 was explored numerically. As can be seen from Fig. 4, a relative permittivity in the range 5 10 was found to be best for total field reduction. A larger permittivity, ε = 10 and more, as in semiconducting or 4

A Study of a MV Cable Joint conducting materials, was found to produce an extremely high total field at certain points and thus obstruct the quality of the joint. The idea of having conducting or semiconducting parts in the joint was tested based on some earlier designs of high voltage cables [4]. In this case, for a given geometry, the introduction of additional conducting or semiconducting material did not prove beneficial. Fig. 2 A detail of the calculated voltage of CJ1-40/90 (ferrule insulation ε = 40, cable end boundary angle θ = 90 ). Fig. 3 A detail of the calculated voltage of CJ1-7/28 (ferrule insulation ε = 7, cable end boundary angle θ = 28 ). 5

R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov 5 4 3 2 1 0 Emax(k V/mm) 2 2.3 3 4 5 6 7 8 9 10 20 40 100 Relative ferrule insulation permittivity θ=90 θ=28.8 θ=15.3 θ=10.4 Fig. 4 Maximum electric field strength of CJ, as a function of ferrule insulation permittivity ε, and of boundary angle θ. Fig. 5 represents the calculated radial and axial change of electric field inside CJ1-7/28. Observe how the field magnitude drops in the high permittivity layers. Both the inner layer of the three-layer HST1 and the HPW of CJ2 were designed from the same material with a relative permittivity ε = 10 or ε = 40. The electric field strength changes both with radial and axial distance from the centre of the joint, as can be observed in Fig. 5. The centre of the joint corresponds to the height z = 0. The height z = 0.08 m is closer to the cable dielectric end and the height z = 0.1 m is closer to the cable screen end. The ε, pushes the field outside the layer and the high permittivity of layer 6, maximum total field strength in the neighbourhood goes up. This is one of the main reasons why, to compensate, the ferrule insulation relative permittivity must be kept below 10. At the most critical height, at the cable screen end, the maximum total field strength was calculated as E max = 5.28 MV/m, for ε = 10, compared to E max = 4.83 MV/m, for ε = 40 (See Figs. 5a3 and 5b3). The higher permittivity ε = 40 seems to work better. 6

A Study of a MV Cable Joint z = 0 (a1); z = 0 (b1); z = 0.08m (a2); z = 0.08m (b2); z = 0.1m (a3); z = 0.1m (b3); Fig. 5 The electric field radial profile at different axial distances from the centre of joint CJ1-7/28, ε = 7, θ = 28 ; (a) ε = 10 ; (b) ε = 40. 7

R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov It is worth mentioning that a relative permittivity ε = 40 simultaneously reduced the tangential component of field in CJ1 to an acceptable value below 500 kv/m: Inside CJ1-7/28, we calculated a maximum tangential component E tan = 621 kv/m for ε = 10, compared to a maximum E tan = 362 kv/m for ε = 40. The higher permittivity ε = 40 seems to fulfil both search criteria. A relative permittivity higher than ε = 40 may affect the creep distance and was not considered for safety reasons. The thickness explored for the HPW was in the range from 1 to 3 mm. The electric field at the cable screen end was well controlled by a 1 mm thick high permittivity bottom layer of HST1, in the case of CJ1. In the case of CJ2, a 1 mm thick HPW was used. A greater thickness was found unnecessary. For electric field regulation at the cable screen end (layer 3 in Fig. 1), a cover with increased permittivity was found essential. 3 Experimental results According to the calculations, both designs, CJ1 and CJ2 should have similar electrical properties. CJ2 may have 10 20% cheaper parts but it has a longer installation time and offers more opportunity for human error. The price reduction does not seem to justify the effort to assemble CJ2. For this reason, only CJ1 was manufactured and tested experimentally. The total length of the joint was chosen so that the voltage would not damage the insulating material. According to IEC 112, the creep distance for fair conditions should be kept above 16 mm/kv. In our design, tracking between the two consecutive cable screen ends was set to 320 mm for a 20 kv copper cable or to 390 mm for a 20 kv aluminium cable. Only CJ1 was chosen for experimental studies. The main conclusions from the numerical results - that better joints may be made with moderate permittivity, below 10, for the ferrule insulation and with an angle θ between 28 and 90 degrees, were tested experimentally. Three different samples of CJ1 were prepared for experimental testing. The results of the experimental tests are summarized in Table 3. The first design, labelled CJ1-40/90, was manufactured with an increased ferrule insulation permittivity of ε = 40 and with boundary angle θ = 90 (no cone at the dielectric end). The second, labelled CJ1-7/28, had a lower ferrule insulation permittivity of ε = 7 and a boundary angle θ = 28.8 (10 mm long cone). Both constructions peormed well and both passed the tests according to the VDE 0278 standard. CJ1-7/28 peormed slightly better in respect of partial discharges, as can be seen from row 11 of Table 3. In spite of the good 8

9 A Study of a MV Cable Joint numerical results, an angle θ = 90 was not considered convenient for jointmaking. Perpendicular inteaces make it difficult to install the ferrule insulation. Because of this, joints with small cones up to 10 mm in length ( θ between 28 and 90 degrees) were considered to be better adapted to fabrication. Table 3 The peormance tests results according to VDE 0278. Legend: CJ1-40/90 (ferrule insulation permittivity ε = 40 and θ = 90 ), CJ1-7/28 (ferrule insulation permittivity ε = 7 and θ = 28 ). No. Item Test voltage (kv) CJ1-40/90 CJ1-7/28 1. AC 50Hz, 1 min 55 Passed Passed 2. Partial discharges 24 0 pc 0 pc Impulse voltage (10 3. positive, 10 negative, 1.2/50 μ S) 125 Passed Passed Current cycling 4. (5+3 hours, cond. temp. 30 Passed Passed 95 C 3 cycles) 5. Partial discharges 24 0 pc 0 pc 6. Current cycling (5+3 hours, cond. temp. 30 Passed Passed 95 C 60 cycles) 7. Partial discharges 24 4 pc 0 pc 8. Current overload 1 sec. 250 C Passed Passed 9. Partial discharges 24 10 pc 4 pc 10. Current cycling (5+3hours, cond. temp. 30 Passed Passed 95 C, 63 cycles) 11. Partial discharges 24 20 pc 10 pc 12. DC voltage 30 min 96 Passed Passed 13. AC voltage 50 5 min 5 min 60 30s* 30s* *Flashover at cable termination The third manufactured cable joint, labelled CJl-100/28, with semiconducting material on top of the ferrule, of relative permittivity ε = 100 and boundary angle θ = 28.8 (10 mm long cone), did not pass the test. Such an outcome confirmed the numerical prediction that the ferrule insulation must not be replaced by semiconducting material.

R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov 4 Conclusion There are many solutions for MV cable joints. Our efforts were directed at improving the design, based on numerical calculations and on site experience. The main goal of this study was to reduce the maximum field strength, E, max and tangential component, E tan, parallel to the boundary suaces, as much as possible, thus protecting the cable joint from accelerated aging. Two parameters were monitored in order to choose the best joint design: 1. Total electric field strength and 2. Tangential field components along boundaries. Two similar cable constructions were explored. The first type, CJ1, incorporated a three-layer heat shrinkable tube, HST1. The second type incorporated a two-layer heat shrinkable tube, HST2, on top of the HPW. The electric field magnitude inside the joints was calculated by the finite element method. The calculations showed that: The maximum electric field strength in the joint is affected a great deal by the permittivity of the ferrule insulation, ε. A relative permittivity of the ferrule insulation, ε, between 5 and 10 was found to be the most suitable. Materials with higher permittivity must not be used. The angle between the ferrule insulation and cable insulation, θ, affects the peak magnitudes of both the total field and tangential components of field along the boundary suaces. These demands oppose each other. A smaller θ was able to reduce the tangential components but at the same time it increased the total field magnitude, which was not permissible. An angle θ in the range 28 90 was found to be acceptable. A larger θ is better in theory, but not practical in reality. High permittivity of the HST1 inner layer, in the case of CJ1, as well as of the HPW, in the case of CJ2, ε, was essential in order to reduce the field magnitude at the cable screen end. A value ε = 40 was found to be suitable. Increased thickness of either the inner layer of the HST1 or of the HPW, in the case of CJ2, did not affect the field to any large extent. A thickness of 1 mm was found to be appropriate. Besides this, the cable insulation should be left intact as much as possible; a longer insulation cone results in a larger contact suace that has to be 10

A Study of a MV Cable Joint additionally treated on site with sandpaper and lubricated with silicon oil. A larger contact suace may also cause more micro discharges. As a result of this work, a cutting tool can be designed for on site preparation of an optimally shaped dielectric cone. All other parts of the joint labelled CJ1, including ferrule, ferrule insulator and three-layer HST1, can be factory prefabricated. Future work should employ a genetic algorithm-based search or some other optimization technique for the best possible joint design. 5 Acknowledgement The work is a part of the TR 18043 project of the Ministry of Science and Technology Development of Serbia. The financial support is highly appreciated. 6 References [1] B. Jaekeli: Numerical Simulation for Investigating EMC Problems in Industrial Life, Serbian Journal of Electrical Engineering, Vol. 5, No. 1, May 2008, pp. 67 76. [2] K.H. Osteohldt, U. Glockner, R. Bach: Technological Change of the Medium Sets, Elektrizitaetswirtschaft, Vol. 96, No. 20, 1997, pp. 1122 1129. [3] Y. Nakanishi, A. Fujimori, S. Fukunaga, T. Tanabe, M. Kobayashi, N. Shiseki, K. Ando: Development of Prefabricated Joint for 275 kv XLPE Cable, IEEE Transaction on Power Delivery, Vol. 10, No. 3, July 1995, pp. 1139 1147. [4] S. Nikolajevic, N. Pekaric-Nadj, R. Dimitrijevic: A New Concept in Construction of Cable Termination for Medium Voltages, IEEE Transaction on Power Delivery, Vol. 13, No. 3, July 1998, pp. 712 718. 11