UNIT 2 REFRIGERATION CYCLE



Similar documents
How To Calculate The Performance Of A Refrigerator And Heat Pump

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

Chapter 3.4: HVAC & Refrigeration System

REFRIGERATION (& HEAT PUMPS)

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Condensers & Evaporator Chapter 5

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Increasing the evaporation temperature with the help of an internal heat exchanger

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

The Second Law of Thermodynamics

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Refrigeration Basics 101. By: Eric Nelson

Mohan Chandrasekharan #1

ME 201 Thermodynamics

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

An analysis of a thermal power plant working on a Rankine cycle: A theoretical investigation

Warm medium, T H T T H T L. s Cold medium, T L

DET: Mechanical Engineering Thermofluids (Higher)

Open Cycle Refrigeration System

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

How To Design A Refrigeration System

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Characteristics of Evaporators

ARP Food Industry, Portugal

How To Know If A Refrigeration System Is Efficient

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

The final numerical answer given is correct but the math shown does not give that answer.

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

Thermodynamics - Example Problems Problems and Solutions

UNIT 1 REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning with Psychrometry

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

High Pressure Ammonia Systems New Opportunities

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Waste Heat Recovery through Air Conditioning System

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

Chapter 10: Refrigeration Cycles

REFRIGERATION & AIR CONDITIONING SYSTEM

How Ground/Water Source Heat Pumps Work

Fundamentals of Mechanical Refrigeration Systems

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

How does solar air conditioning work?

DRAFT. Appendix C.2 - Air Conditioning Thermodynamics 1

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

Low GWP Replacements for R404A in Commercial Refrigeration Applications

C H A P T E R T W O. Fundamentals of Steam Power

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

4. HVAC AND REFRIGERATION SYSTEM

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

GEOTHERMAL POWER PLANT CYCLES AND MAIN COMPONENTS

Testing methods applicable to refrigeration components and systems

Energy savings in commercial refrigeration. Low pressure control

Stirling heat engine Internal combustion engine (Otto cycle) Diesel engine Steam engine (Rankine cycle) Kitchen Refrigerator

Energy Procedia Energy 00 Procedia (2011) (2012) 56 65

Purpose of Refrigeration

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Why and How we Use Capacity Control

The Second Law of Thermodynamics

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

UNDERSTANDING REFRIGERANT TABLES

ENGINEERING INFORMATION Hot water and steam service

Heat Recovery In Retail Refrigeration

Design of Cold Storage Structure For Thousand Tonne Potatoes

ES-7A Thermodynamics HW 1: 2-30, 32, 52, 75, 121, 125; 3-18, 24, 29, 88 Spring 2003 Page 1 of 6

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Creating Efficient HVAC Systems

1 Overview of applications and system configurations

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Research on the Air Conditioning Water Heater System

C H A P T E R 8 REFRIGERATION AND AIR CONDITIONING

Energy Efficient Ammonia Heat Pump. Energy and Climate Refrigeration and Heat Pump Technology

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut John F. Sima III P.E.

How To Clean Water From An Ammonia Refrigeration System

Rusty Walker, Corporate Trainer Hill PHOENIX

Glossary of Heating, Ventilation and Air Conditioning Terms

OUTCOME 2 INTERNAL COMBUSTION ENGINE PERFORMANCE. TUTORIAL No. 5 PERFORMANCE CHARACTERISTICS

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

AdSORPTION CHILLER NAK

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

How To Understand Evaporator

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

HVAC and REFRIGERATION

Transcription:

UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression Cycle with Saturated Vapour after Compression 2.2.2 Conditions for Highest COP 2.2.3 Carnot Refrigeration Cycle 2.2.4 Temperature Limitations 2.2.5 Difference between Refrigeration and Heat Pump Cycles 2.3 Vapour Absorption System 2.4 Illustrative Problems 2.5 Summary 2.6 Answers to SAQs 2. INTRODUCTION The term refrigeration may be defined as the process of removing heat from a substance under controlled conditions. It also includes the process of reducing and maintaining the temperature of a body below the general temperature of its surroundings. In other words, the refrigeration means a continued extraction of heat from a body whose temperature is already below temperature of its surroundings. In a refrigerator, heat is virtually pumped from a lower temperature to a higher temperature. According to Second Law of Thermodynamics, this process can only be performed with the aid of some external work. It is thus obvious that supply of power is regularly required to drive a refrigerator. Theoretically, a refrigerator is a reversed heat engine or a heat pump which pumps heat from a cold body and delivers it to a hot body. The substance which works in a pump to extract heat from a cold body and to deliver it to a hot body is known as refrigerant. Objectives After studying this unit, you should be able to know what is refrigeration cycle, understand about the vapour compression cycle, describe the vapour compression refrigeration cycle, and solve the problem on refrigeration system. Refrigeration cycle is the basis of all refrigeration systems. So refrigeration cycle should be known to understand the refrigeration system. Some basic refrigeration cycles are discussed here through different diagrams. 2.2 VAPOUR COMPRESSION CYCLE Vapour compression cycle is an improved type of air refrigeration cycle in which a suitable working substance, termed as refrigerant, is used. The refrigerants generally used for this purpose are ammonia (NH 3 ), carbon dioxide (CO 2 ) and sulphur-dioxide (SO 2 ). The refrigerant used, does not leave the system, but is circulated throughout the system alternately condensing and evaporating. In evaporating, the refrigerant absorbs its latent heat from the solution which is used for circulating it around the cold chamber and in condensing; it gives out its latent heat to the circulating water of the cooler. 7

Refrigeration and Air Conditioning The vapour compression cycle which is used in vapour compression refrigeration system is now-a-days used for all purpose refrigeration. It is used for all industrial purposes from a small domestic refrigerator to a big air conditioning plant. 2.2. Simple Vapour Compression Refrigeration System It consists of the following essential parts: Compressor Condenser The low pressure and temperature vapour refrigerant from evaporator is drawn into the compressor through the inlet or suction valve A, where it is compressed to a high pressure and temperature. This high pressure and temperature vapour refrigerant is discharged into the condenser through the delivery or discharge valve B. The condenser or cooler consists of coils of pipe in which the high pressure and temperature vapour refrigerant is cooled and condensed. 8 Receiver Figure 2. : Simple Vapour Compression Refrigeration System The refrigerant, while passing through the condenser, gives up its latent heat to the surrounding condensing medium which is normally air or water. The condensed liquid refrigerant from the condenser is stored in a vessel known as receiver from where it is supplied to the evaporator through the expansion valve or refrigerant control valve. Expansion Valve It is also called throttle valve or refrigerant control valve. The function of the expansion valve is to allow the liquid refrigerant under high pressure and temperature to pass at a controlled rate after reducing its pressure and temperature. Some of the liquid refrigerant evaporates as it passes through the expansion valve, but the greater portion is vaporized in the evaporator at the low pressure and temperature Evaporator An evaporator consists of coils of pipe in which the liquid-vapour. refrigerant at low pressure and temperature is evaporated and changed into vapour refrigerant at low pressure and temperature. In evaporating, the liquid vapour refrigerant absorbs its latent heat of vaporization from the medium (air, water or brine) which is to be cooled.

2.2.2 Theoretical Vapour Compression Cycle with Dry Saturated Vapour after Compression A vapour compression cycle with dry saturated vapour after compression is shown on T-s diagrams in Figures 2.2(a) and (b) respectively. At point, let T, p and s be the temperature, pressure and entropy of the vapour refrigerant respectively. The four processes of the cycle are as follows : Refrigeration Cycle Compression Process (a) T-s Diagram (b) p-h Diagram Figure 2.2 : Theoretical vapour Compression Cycle with Dry Saturated Vapour after Compression The vapour refrigerant at low pressure p and temperaturet is compressed isentropically to dry saturated vapour as shown by the vertical line -2 on the T-s diagram and by the curve -2 on p-h diagram. The pressure and temperature rise from p to p 2 and T to T 2 respectively. The work done during isentropic compression per kg of refrigerant is given by w h 2 h where h Enthalpy of vapour refrigerant at temperature T, i.e. at suction of the compressor, and Condensing Process h 2 Enthalpy of the vapour refrigerant at temperature T 2. i.e. at discharge of the compressor. The high pressure and temperature vapour refrigerant from the compressor is passed through the condenser where it is completely condensed at constant pressure p 2 and temperature T 2 as shown by the horizontal line 2-3 on T-s and p-h diagrams. The vapour refrigerant is changed into liquid refrigerant. The refrigerant, while passing through the condenser, gives its latent heat to the surrounding condensing medium. Expansion Process The liquid refrigerant at pressure p 3 p 2 and temperature T 3 T 2, is expanded by throttling process through the expansion valve to a low pressure p 4 p and Temperature T 4 T as shown by the curve 3-4 on T-s diagram and by the vertical line 3-4 on p-h diagram. Some of the liquid refrigerant evaporates as it passes through the expansion valve, but the greater portion is vaporized in the evaporator. We know that during the throttling process, no heat is absorbed or rejected by the liquid refrigerant. Vaporizing Process The liquid-vapour mixture of the refrigerant at pressure p 4 p and temperature T 4 T is evaporated and changed into vapour refrigerant at constant pressure and temperature, as shown by the horizontal line 4- on T-s and p-h diagrams. During evaporation, the liquid-vapour refrigerant absorbs its latent heat of vaporization 9

Refrigeration and Air Conditioning from the medium (air, water or brine) which, is to be cooled, This heat which is absorbed by the refrigerant is called refrigerating effect and it is briefly written as R E. The process of vaporization continues up to point which is the starting point and thus the cycle is completed. We know that the refrigerating effect or the heat absorbed or extracted by the liquid-vapour refrigerant during evaporation per kg of refrigerant is given by R E h h 4 h hf 3 where hf 3 Sensible heat at temperature T 3, i.e. enthalpy of liquid refrigerant leaving the condenser. It may be noticed from the cycle that the liquid-vapour refrigerant has extracted heat during evaporation and the work will be done by the compressor for isentropic compression of the high pressure and temperature vapour refrigerant. Coefficient of performance, C.O.P. (Refrigerating effect)/( Work done) h h h h 4 2 h h f h h Effect of Suction Pressure 3 2 The suction pressure (or evaporator pressure) decreases due to the frictional resistance of flow of the refrigerant. Let us consider a theoretical vapour compression cycle -2-3-4 when the suction pressure decreases from p s to p s as shown on p-h diagram in Figure 2.3. It may be noted that the decrease in suction pressure : (a) decreases the refrigerating effect from (h h 4 ) to ( h (b) h4 Increases the work required for compression from (h 2 h ) to ( h2 h ). ), and 20 Figure 2.3 : Effect of Suction Pressure Since the C.O.P, of the system is the ratio of refrigerating effect to the work done, therefore with the decrease in suction pressure, the net effect is to decrease the C.O.P. of the refrigerating system for the same refrigerant flow. Hence with the decrease in suction pressure the refrigerating capacity of the system decreases and the refrigeration cost increases. Effect of Discharge Pressure In actual practice, the discharge pressure (or condenser pressure) increases due to frictional resistance of flow of the refrigerant. Let us consider a theoretical vapour compression cycle l-2-3-4 when the discharge pressure increases from p D to p D as shown on p-h diagram in Figure 2.4 resulting in increased compressor work and reduced refrigeration effect.

Refrigeration Cycle 2.2.3 Conditions for Highest COP Effect of Evaporator Pressure Figure 2.4 : Effect of Discharge Pressure Consider a simple saturation cycle -2-3-4 with Freon 2 as the refrigerant as shown in Figure 2.5 for operating conditions of t k 40 C and t 5 C. Now consider a change in the evaporator pressure corresponding to a decrease in the evaporator temperature to 0 C. The changed cycle is shown as -2-3-4 in Figure 2.5. It is therefore, seen that a drop in evaporator pressure corresponding to a drop of 5 C in saturated suction temperature increases the volume of suction vapour and hence decreases the capacity of a reciprocating compressor and increases the power consumption per unit refrigeration. Figure 2.5 : Effect of Evaporator Pressure It is observed that a decrease in evaporator temperature results in : (a) Decrease in refrigerating effect from (h h 4 ) to (h h 4 ) (b) Increase in the specific volume of suction vapour from v to v (c) (d) Decrease in volumetric efficiency, due to increase in the pressure ratio, from to v v' Increase in compressor work from (h 2 h ) to (h 2 h ) due to increase in the pressure ratio as well as change from steeper isentropic -2 to flatter isentropic -2. v Vp Since Q0 mq0 q0... (2.) v and W * * m w... (2.2) 2

Refrigeration and Air Conditioning Expressions for the dependence of capacity and unit power consumption may now be written as follows : 0 0 2 Q q h h... (2.3) and v v W m q h h * * 0 4... (2.4) w h2 h Effect of Condenser Pressure An increase in condenser pressure, similarly results in a decrease in the refrigerating capacity and an increase in power consumption, as seen from the changed cycle -2-3-4 for t k 45 C in Figure 2.6. The decrease in refrigerating capacity is due to a decrease in the refrigerating effect and volumetric efficiency. The increase in power consumption is due to increased mass flow (due to decreased refrigerating effect) and an increase in specific work (due to increased pressure ratio), although the isentropic line remains unchanged. Accordingly, one can write for the ratios Q Q ' 0 0 ' v ' h h4... (2.5) h h 4 v W W *' ' * ' c c h h ' 4 h h 4 h h ' 2 2 h h... (2.6) Figure 2.6 : Effect of Condenser Pressure It is obvious that COP decreases both with decreasing evaporator and increasing condenser pressures. It may, however, be noted that the effect of increase in condenser pressure is not as server, on the refrigerating capacity and power consumption per ton of refrigeration, as that of the decrease in evaporator pressure. Effect of Suction Vapour Superheat 22 Superheating of the suction vapour is advisable in practice because it ensures complete vaporization of the liquid in the evaporator before it enters the compressor. Also, in most refrigeration and air-conditioning systems, the degree of superheat serves as a means of actuating and modulating the capacity of the expansion valve. It has also been seen that for some refrigerants such as Freon 2, maximum COP is obtained with superheating of the suction vapour.

Refrigeration Cycle Figure 2.7: Effect of Suction Vapour Superheat It can be seen from Figure 2.7, that the effect of superheating of the vapour from t t 0 to t is as follows : (a) Increase in specific volume of suction vapour from v to v (b) Increase in refrigerating effect from (h h 4 ) to (h h 4 ) (c) Increase in specific work from (h 2 h ) to (h 2 h ) It is to be noted that (h 2 h ) is greater than (h 2 h ). This is because, although the pressure ratio is the same for both lines, the initial temperature t, is greater than t and the work given by the expression RT p / p 2 Increases with the initial temperature. That is why isentropic lines on the p-h diagram become flatter in higher temperatures. An increase in specific volume decreases the capacity. On the contrary, an increase in refrigerating effect will increase the capacity effect of super- heating is to theoretically reduce the capacity in ammonia systems and to increase it in Freon 2 systems. Effect of Liquid Subcooling It is possible to reduce the temperature of the liquid refrigerant to within a few degrees of the temperature of the water entering the condenser. In some condenser designs it is achieved by installing a sub-cooler between the condenser and the expansion valve. The effect of sub-cooling of the liquid from t 3 tk to t 3 is shown in Figure 2.8. It will be seen that sub-cooling reduces flashing of the liquid during expansion and increases the refrigerating effect. Consequently, the piston displacement and horsepower per ton are reduced for all refrigerants. The percent gain is less pronounced in the case of ammonia because of its larger latent heat of vaporization as compared to liquid specific heat. Figure 2.8 : Effect of Liquid Subcooling 23

Refrigeration and Air Conditioning Normally, cooling water first passes through the subcooler and then through the condenser. Thus, the coolest water comes in contact with the liquid being subcooled. But this results in a warmer water entering the condenser and hence a higher condensing temperature and pressure. Thus, the advantage of subcooling is offset by the increased work of compression. This can be avoided by installing parallel cooling water inlets to the subcooler and condenser. In that case, however, the degree of subcooling will be small and the added cost of the subcooler and pump work may not be worthwhile. It may be more desirable to use the cooling water effectively in the condenser itself to keep the condensing temperature as near to the temperature of the cooling water inlet as possible. 2.2.4 Carnot Refrigeration Cycle In refrigeration system, the Carnot cycle considered is reversed Carnot cycle. We know that a heat engine working on Carnot engine has the highest efficiency. Similarly, a refrigeration system working on the reversed cycle, has the maximum coefficient of performance. 24 (a) p-v Diagram Figure 2.9 : Reversed Carnot Cycle (b) T-s Diagram A reversed Carnot cycle, using air as the working medium is shown on p-v and T-s diagrams in Figures 2.9(a) and (b) respectively. At point, let p, v, T be the pressure, specific volume and temperature of air respectively. The four processes of the cycle are as follows: Isentropic Compression Process The air is compressed isentropically as shown by the curve -2 on p-v and T-s diagrams. During this process, the pressure of air increases from p to p 2, specific volume decreases from v to v 2 and temperature increases from T to T 2. We know that during isentropic compression, no heat is absorbed or rejected by the air. Isothermal Compression Process The air is now compressed isothermally (i.e. at constant temperature, T 2 T 3 ) as shown by the curve 2-3 on p-v and T-s diagrams. During this process, the pressure of air increases from p 2 to p 3 and specific volume decreases from v 2 to v 3. We know that the heat rejected by the air during isothermal compression per kg of air, q 2-3 area 2-3-3-2 T 3 (s 2 s 3 ) T 2 (s 2 s 3 ) Isentropic Expansion Process The air is now expanded isentropically as shown by the curve 3-4 on p-v and T-s diagrams. The pressure of air decreases from p 3 to p 4, specific volume increases from v 3 to v 4 and temperature decreases from T 3 to T 4. We know that during isentropic expansion, no heat is absorbed or rejected by the air.

Isothermal Expansion Process The air is now expanded isothermally (i.e. at constant temperature, T 4 T ) as shown by the curve 4- on p-v and T-s diagrams. During this process, the pressure of air decreases from p 4 to p and specific volume increases from v 4 to v. We know that the heat absorbed by the air during isothermal compression per kg of air, q 4- area 4--2-3 T 4 (s s 4 ) T 4 (s 2 s 3 ) T (s 2 s 3 ) We know that work done during the cycle per kg of air Heat rejected Heat absorbed Refrigeration Cycle q 2-3 q 4- T 2 (s 2 s 3 ) T (s 2 s 3 ) Therefore, coefficient of performance of the refrigeration system working on reversed Carnot cycle, C.O.P. HeatAbsorbed WorkDone T s2 s3 T T s s T T T 2 2 3 2 2.2.5 Temperature Limitations for Reversed Carnot Cycle We have seen that the C.O.P. of the reversed Carnot cycle is given by, C.O.P. T T T 2 where T Lower temperature, and T 2 Higher temperature. The C.O.P. of the reversed Carnot cycle can be improved by (a) Decreasing the higher temperature (i.e. temperature of hot body, T 2 ) or (b) Increasing the lower temperature (i.e. temperature of cold body, T ). It may be noted that temperature T and T 2 cannot be varied at will, due to certain functional limitations. It should be kept in mind that the higher temperature (T 2 ) is the temperature of cooling water or air available for rejection of heat and the lower temperature (T ) is the temperature to be maintained in the refrigerator. The heat transfer will take place in the right direction only when the higher temperature is more than the temperature of cooling water or air to which heat is to be rejected, while the lower temperature must be less than the temperature of substance to be cooled. Thus if the temperature of cooling water or air (i.e. T 2 ) available for heat rejection is low, the C.O.P. will be high. Since T 2 in winter is less than T 2 in summer, therefore, C.O.P. in winter will be higher than C.O.P. in summer. In other words, the Carnot refrigerator works more efficiently in winter than in summer. Similarly, if the lower temperature (T ) is high, the C.O.P. of the Carnot refrigerator will be high. 25

Refrigeration and Air Conditioning 2.2.6 Difference between Refrigeration and Heat Pump System The major difference between the refrigeration and heat pump system is that refrigerator delivers heat from lower temperature to a higher temperature, whereas heat pump delivers heat from higher temperature to lower temperature body. The difference between refrigerator and heat pump is shown in the Figure 2.0 schematically. Higher Temperature Higher Temperature RE RE Refrigerator HP Heat Pump HP Lower Temperature Lower Temperature Figure 2.0 : Schematic Representation of Refrigerator and Heat Pump 2.3 VAPOUR ABSORPTION SYSTEM The vapour absorption refrigeration is heat operated system. It is quite similar to the vapour compression system. In both the systems, there are evaporator and condenser. The process of evaporation and condensation of the refrigerant takes place at two different pressure levels to achieve refrigeration in both the cases. The method employed to create the two pressure levels in the system for evaporation and condensation of the refrigeration makes the two processes different. Circulation of refrigerant in both the cases is also different. In the absorption system the compressor of the vapour compression system is replaced by the combination of absorber and generator. A solution known as the absorbent, which has an affinity for the refrigerant used, is circulated between the absorber and the generator by a pump (solution pump). The absorbent in the absorber draws (or sucks) the refrigerant vapour formed in the evaporator thus maintaining a low pressure in the evaporator to enable the refrigerant to evaporate at low temperature. In the generator the absorbent is heated. There by releasing the refrigerant vapour (absorbed in the absorber) as high pressure vapour, to be condensed in the condenser. Thus the suction function is performed by absorbent in the absorber and the generator performs the function of the compression and discharge. The absorbent solution carries the refrigerant vapour from the low side (evaporator absorber) to the high side (generator-condenser). The liquefied refrigerant flows from the condenser to the evaporator due to the pressure difference between the two vessels; thus establishing circulation of the refrigerant through the system. 26

Figure 2. is a schematic diagram of the absorption cycle. As can be seen from the figure, the refrigerant and absorbent have separate flow paths. The refrigerant path is: Evaporator Absorber Generator Condenser Evaporator and for the absorbent it is, Absorber Generator Absorber The absorbent solution passing from the generator to the absorber is hot and ha to be cooled. On the other hand the absorbent solution sent to the generator is cooled and has to be heated in the generator for the regeneration of the refrigerant. A shell and tube heat exchanger is introduced between the generator and the absorber. Refrigeration Cycle Figure 2. : Schematic Diagram of Absorption System of Refrigeration Figure 2.2 : Schematic Sketch of a Lithium-Bromide Absorption Machine Single Stage There is number of vapour absorption system depending on the absorbent e.g. ammonia absorbent system, lithium bromide absorption system etc. Ammonia absorbent systems were used in the early stages of refrigeration. This system uses ammonia as the refrigerant and water as absorbent. In lithium bromide absorption system lithium bromide salt solution is used as the absorbent and water as the refrigerant. A concentrated solution of lithium bromide has a great affinity for water. Since water is the refrigerant, the refrigerant operating temperature in the evaporator has to be above the freezing point of water (0 o C) of water. 27

Refrigeration and Air Conditioning 28 2.4 ILLUSTRATIVE PROBLEMS Example 2. Solution Carnot refrigeration cycle absorbs heat at 270 K and rejects heat at 300 K. (a) (b) (c) (d) Calculate the coefficient of performance of this refrigeration cycle. If the cycle is absorbing 30 kj/min at 270 K, how many kj of work is required per second. If the Carnot heat pump operates between the same temperatures as the above refrigeration cycle, what is the coefficient of performance. How many kj/min will the heat pump deliver at 300 K if it absorbs 30 kj/min at 270 K. Given : T 270 K; T 2 300 K Example 2.2 (a) (b) (c) (d) Coefficient of performance of Carnot refrigeration cycle We know that coefficient of performance of Carnot refrigeration cycle, T (C.O.P.) R T T 2 Work required per second Let 270 300 270 WR Work required per second Heat absorbed at 270 K (i.e. T ), Q ll30 kj/min 8.83 kj/s Q We know that (C.O.P) R W W R Q 8.83 ( C. O. P) 9 R W R 2. kj/s Coefficient of performance of Carnot heat pump R 9 Ans. We know that coefficient of performance of a Carnot heat pump, T2 (C.O.P.)p T T 2 300 300 270 Heat delivered by heat pump at 300 K Let Q 2 Heat delivered by heat pump at 300 K. Heat absorbed at 270 K (i.e. T), Q 30 kj/min (Given) We know that (C.O.P.)p Q2 Q Q 2 Q 2 256 kj/min Ans. 0 Ans. The capacity of a refrigerator is 200 TR when working between 6 C and 25 o C. Determine the mass of ice produced per day from water at 25 C. Also find the power required to drive the unit. Assume that the cycle operates on reversed Carnot cycle and latent heat of ice is 335 kj/kg. Ans.

Solution Given : Q 200TR; T 6 C 6 + 273 267 K; T 2 25 C; Tw 250 C : hfg 335 kj/kg Mass of ice produced per day We know that heat extraction capacity of the refrigerator 200 20 42000 kj/min heat removed from kg of water at 25 C to form ice at 0 C ( TR 20 kj/min) Mass Sp. heat Rise in temperature + hfg (ice) 4.87 (25 0) + 335 439.7 kj/kg Mass of ice produced per min 42000 95.52 kg/min 439.7 and mass of ice produced per day 95.52 60 24 37550 kg 37.55 tonnes Power required to drive the unit We know that C.O.P. of the reversed Carnot cycle T T T 2 267 298 267 8.6 COP. (Heat extraction capacity)/(work done per mm) Work done per min 42 000/8.6 4884 kj/min Power required to drive the unit Example 2.3 Solution 4884 8.4 kw Ans. 60 Five hundred kgs of fruits are supplied to a cold storage at 20 o C. The cold storage is maintained at 5 C and the fruits get cooled to the storage temperature in 0 hours. The latent heat of freezing is 05 kj/kg and specific heat of fruit is.256 kj/kg K. Find the refrigeration capacity of the plant. Given : m 500 kg; T 2 20 C 20 + 273 293K; T 5C 5 + 273 268 K; hfg 05 kj/kg, cf.256 kj/kg K We know that heat removed from the fruits in 0 hrs, Q m cf (T 2 T ) 500.256(293 268) 5700 kj and total latent heat of freezing, Q 2 m. hfg 500 05 52500 kj Total heat removed in 0 hrs, Q Q l + Q 2 5700 + 52500 68200 kj and total heat removed in one minute 68200/0 60 3.7 kj/min Refrigeration capacity of the plant 3.7/20 0.54 TR ( TR 20 kj/min) Ans. Refrigeration Cycle 29

Refrigeration and Air Conditioning Example 2.4 Solution A cold storage plant is required to store 20 tonnes of fish. The fish is supplied at a temperature of 30 C. The specific heat of fish above freezing point is 2.93 kj/kg K. The specific heat offish below freezing point is.26 kj/kg K. The fish is stored in cold storage which is maintained at 8 o C. The freezing point of fish is 4 C. The latent heat of fish is 235 kj/kg. If the plant requires 75 kw to drive it, find (a) (b) The capacity of the plant, and Time taken to achieve cooling. Assume actual C.O.P. of the plant as 0.3 of the Carnot C.O.P. Given : m 20 t 20000 kg; T 2 30 C 30 + 273 303 K; (a) (b) caf 2.93 kj/kg K; cbf.26 kj/kgk; T 8 C 8 + 273 265 K; T 3 4 C 4 + 273 269 k; hfg 235 kj/kg; P 75 kw 75 kj/s Capacity of the plant We know that Carnot C.O.P. T T T 2 265 303 265 Actual COP. 0.3 6.97 2.09 and heat removed by the plant 6.97 Actual COP. Work required 2.09 75 56.8 kj/s 56.8 60 9408 kj/min Capacity of the plant 9408 /20 44.8 TR Ans. Time taken to achieve cooling We know that heat removed from the fish above freezing point, Q m c AF (T 2 T 3 ) 20000 2.93 ( 303 269).992 0 6 kj Similarly, heat removed from the fish below freezing point, Q 2 m x c BF (T 3 T ) 20000.26 (269 265) 0.0 0 6 kj and total latent heat of fish, Q 3 m h fg (fish) 20000 235 4.7 0 6 kj Total heat removed by the plant 30 Q + Q 2 + Q 3.992 0 6 + 0.0 0 6 + 4.7 0 6 6.793 0 6 kj and time taken to achieve cooling 6.793 0 9408 6 722 min 2.03 h Ans.

2.6 SUMMARY Refrigeration Cycle A vapour compression refrigeration system is an improved type of air refrigeration system in which a suitable working substance, termed as refrigerant is used. It condenses and evaporates at temperatures and pressures close to atmospheric conditions. The refrigerant used, does not leave the system, but is circulated throughout the system alternately condensing and evaporating. The vapour absorption system uses heat energy, instead of mechanical energy as in vapour compression systems, in order to change the conditions of the refrigerant required for the operation of the refrigeration cycle. In vapour compression system compressor is used to withdraw the vapour refrigerant from the evaporator. It then raises its temperature and pressure higher than the cooling agent in the condenser so that the higher pressure vapour can reject heat in the condenser. But in the vapour absorption system, the compressor is replaced by an absorber, a pump, a generator and a pressure reducing valve. These components in vapour absorption system, perform the same functions as that of a compressor in vapour compression system. In this system, the vapour refrigerant from the evaporator is drawn into an absorber where it is absorbed by the weak solution of the refrigerant forming a strong solution. This strong solution is pumped to the generator where it is heated by some external source. During the heating, the vapour refrigerant is driven off by the solution and enters into the condenser where it is liquefied. The liquid refrigerant then flows into the evaporator and thus the cycle is completed. 2.7 ANSWERS TO SAQs Refer the relevant preceding texts in the unit or other useful books on the topic listed in the section Further Readings to get the answers of the SAQs. 3