Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
|
|
|
- Chad McCarthy
- 10 years ago
- Views:
Transcription
1 Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators) are widely used to cool and circulate air in cold storage warehouses and food processing facilities. Manufacturers of air coolers publish cooling capacities based on differing assumptions and rating methods. It is important for refrigeration design professionals to understand these different rating methods and to apply them appropriately. In extreme cases, air coolers can be grossly undersized even though nominal catalog ratings appear to satisfy the calculated refrigeration load. The article illustrates the differences in these rating methods and highlights the importance of selecting air coolers using ratings suited to the operating conditions. BACKGROUND Refrigeration air coolers (evaporators) are widely used to cool and circulate air in cold storage warehouses and food processing facilities. Manufacturers of air coolers publish cooling capacities based on differing assumptions and rating methods (Nelson 2010). In Europe, a number of manufacturers of commercial air coolers (i.e. coolers designed for use with R404a/R507) subscribe to the Eurovent certification program based on the European test standard EN 328 (EN 2002), however, no manufacturer is currently certified for industrial air coolers (i.e. coolers designed for use with ammonia refrigerant). In the U.S. the performance standard AHRI-420 exists (AHRI 2008), but no manufacturers participate in a certification program based on this standard. It is, therefore, important for refrigeration design professionals to understand the different rating methods being used and to apply them appropriately. In extreme cases, air coolers can be grossly undersized even though nominal catalog ratings appear to satisfy the calculated refrigeration load. The smaller size and lower first cost of air coolers which are inadvertently undersized due to misunderstood or misapplied ratings are seductively attractive to contractors and end users, however, the price difference will ultimately be more than paid for by the unsuspecting end user whose undersized air coolers cause lower-than-expected operating suction temperatures with associated increased energy consumption and loss of refrigerating capacity. AIR TEMPERATURE CHANGE As air passes across the fins of an evaporator coil, the temperature is reduced according to the following relationship (ASHRAE 2009): (1) where = cooling capacity (sensible only), Btu/h (kw) = mass flow rate of air, lbm/h (kg/s) = specific heat capacity of moist air, Btu/lbm F (kj/kg C) = dry bulb air temperature entering the coil ( air on temperature), F (C) = dry bulb air temperature leaving the coil, F (C) In a room being refrigerated by air cooling evaporators, the change in the temperature of the air (reduction) as it passes through the evaporator coils will equal the change in the temperature of the air (increase) as it circulates throughout the room. This means that in a well-designed cold room, the air temperature gradient found in the room will be roughly equal to, and will be determined in large part by the air temperature change in the evaporator coils. By Equation (1) the magnitude of the air temperature change (gradient) in the room will be determined by the air mass flow rate through the evaporators. For 1
2 example, if a relatively small air temperature gradient is desirable in a refrigerated room, then air coolers with relatively high air flow rate (i.e. high CFM/TR) for a given capacity must be selected. HEAT EXCHANGER EFFECTIVENESS One well known method used to calculate the sensible cooling capacity of evaporators is the effectiveness method (Kays and London 1964). Heat exchanger effectiveness is defined as the ratio of the actual amount of heat transferred to the maximum possible amount of heat that could be transferred with an infinite area. This method is extremely useful because cooling capacity can be calculated directly knowing only the dimensional characteristics of the coil and the initial temperature difference (entering air temperature minus the evaporating temperature). This initial temperature difference is referred to as DT1 (or TD ) in the refrigeration industry. Sensible cooling capacity is calculated as follows: 1 (2) where = cooling capacity (sensible only), Btu/h (kw) = mass flow rate of air, lbm/h (kg/s) = specific heat capacity of moist air, Btu/lbm F (kj/kg C) = effectiveness = / = dry bulb air temperature entering the coil ( air on temperature), F (C) = dry bulb air temperature leaving the coil, F (C) = average refrigerant evaporating temperature, F (C) For a given sized coil operating with constant air flow rate, the effectiveness can be considered constant over the small operating temperature ranges typical of refrigeration applications, and therefore, capacity can be considered to be proportional to the ratio of DT1. Hence, if evaporator coil sensible capacity is known for a given DT1, then capacity at a new initial temperature difference, DT1, can be found simply by multiplying the original capacity by the ratio DT1 /DT1. For example, a refrigeration air cooler has a rating of 10 TR at a DT1 of 10F. The capacity of the same cooler operating with a new DT1 of 12F will be very close to 10 x 12/10 = 10 x 1.2 = 12 TR. AVERAGE ROOM TEMPERATURE AND DTM RATINGS Control of the refrigeration system is normally accomplished by maintaining room air temperature, that is, compressors and coolers are cycled on or off depending on whether room temperature is rising or falling. Location of the air temperature sensing device relative to the location of evaporators will affect evaporator performance since a temperature gradient always exists in the room and, as seen above, evaporator performance is determined by the air on temperature (i.e. by DT1). Evaporators located high in the room (mounted on the ceiling, for example), will be exposed to the highest air temperature in the room and operate with the largest DT1. Conversely, floor mounted evaporators will be exposed to the coldest air in the room and operate with the smallest DT1. For the specific case where; 1) air coolers are ceiling mounted (i.e. operate at the warmest location in the room), and 2) the system control temperature sensor is mounted at a location where it will sense the average room temperature (i.e. at the midpoint elevation in the room), manufacturers of air coolers publish ratings based on mean (average room) temperature difference. This average temperature difference is termed DTM. DTM ratings for the same air cooler will always be higher than DT1 ratings since the effective initial temperature difference seen by the evaporator coil is higher by approximately ½ of the air temperature change. Figure 1 below illustrates how air temperature changes as it passes through an evaporator at two different operating conditions. Note that airflow is held constant for both operating conditions. The first condition with DT1 = 10F is shown as Figure 1(a). The second condition with DTM = 10F is shown as Figure 1(b). Because the DTM = 10F condition has the larger initial temperature difference of -6.7 (-20) = 13.3F, the cooling capacity and air temperature change are significantly larger than for the DT1 = 10F condition. It is interesting how the same evaporator can produce more cooling capacity simply by redefining temperature difference! 2
3 FIGURE 1 Temperature Profiles for DT1 vs DTM (a) DT1 = 10F (Air On) Temp Difference (b) DTM = 10F (Average) Temp Difference DT1 LMTD = 7.2 F DTM LMTD = 9.6 F Although DTM ratings may useful in the specific case of ceiling mounted air coolers (equipment size and first cost can be reduced), refrigeration system designers must be careful to recognize the limitations of this rating system and avoid the mistake of misapplying DTM ratings. Whenever air coolers are installed at a location in the room where the air on temperature to the coil is less than the highest temperature in the room, DTM ratings should not be used. This would be the case with cooler inlet air ducted from some lower temperature point in the room, or with floor mounted coolers. DT1 ratings used with actual anticipated air on temperature will always result in accurate ratings and correct air cooler selections. This method for air cooler selection is conservative and recommended whenever air on temperature to the coil is less than the maximum found in the room or process. CONVERTING DT1 TO DTM AIR COOLER RATINGS Equations (1) and (2) above were used to derive the relationships shown in Equations (3) and (4) below which can be used to convert from known a DT1 air cooler rating to a new DTM rating for the same cooler (IP) (3) (SI) (4) 3
4 where = capacity at mean (room) temperature difference, Btu/h (kw) = capacity at initial (air on) temperature difference, Btu/h (kw) DT1 = initial temperature difference = Air On Temp - Evap Temp, F (C) DTM = mean (room) temperature difference = Ave Room Temp Evap Temp, F (C) = air specific heat, Btu/lbm F (kj/kg C) = air density, lbm/ft3 (kg/m3) = actual volumetric air flow rate, ft3/min (m3/h) Example: An air cooler has a DT1 rating of 120,000 Btu/h at DT1 = 10F and -10F air on temperature. The cooler has a published airflow rating of 18,850 CFM. Assume the coil is operating with average air density = lbm/ft3, and average air specific heat = 0.24 Btu/lbm F. Note this is the same cooler shown in Figure 1 above. Find the DTM rating for the same cooler with DTM = 10F. From Equation (3): 120, ,050 / 120, , As is seen from the example, DTM ratings are typically significantly higher than DT1 ratings for the same air cooler operating under the same conditions. In the case of the example, the DTM rating is +33% greater than the DT1 rating! Note that the above equations apply only to sensible capacity calculations and ratings and do not account of the effects of latent cooling on coil performance and temperature change. The effects of latent load on coil performance and ratings are covered in the following sections. LATENT LOAD AND SENSIBLE HEAT RATIO (SHR) Whenever cooling coil surfaces operate at temperatures below the dew point of the air being cooled, water vapor in the airstream is condensed to liquid (at temperatures above 32F (0C)) or deposited to form frost (below 32F (0C)). The cooling effect associated with this dehumidification of the airstream is termed latent cooling. The sum of the sensible cooling load and latent cooling load is termed the total load. The ratio of the sensible cooling load divided by the total cooling load is called the Sensible Heat Ratio (SHR) and defines the slope of the air process line on a psychrometric chart. (5) Accurate prediction of the refrigeration load, both sensible and latent components, is critical to proper refrigeration system equipment selection and successful operation. Various types of sensible cooling loads must be anticipated and included in the calculation, such as: lighting, electric motors, forklifts, product cooling/freezing, transmission of heat through walls, ceilings, and floors, and cooling of infiltration air. Latent cooling loads are present whenever moisture is added to the air in the refrigerated space. Sources of introduced moisture typically include: infiltration air, respiring food products, surface moisture on products, packaging, and other objects entering the space, human respiration, and humidification equipment (above freezing). The SHR determined from the load calculation will come to equilibrium with the SHR of the air passing through the air cooler evaporator coil. In general, as air temperature decreases the amount of water vapor held in air decreases by the law of partial pressures, and the minimum possible SHR increases. 4
5 Relative humidity of the refrigerated space can be predicted by plotting the air process line on a psychrometric chart with the end point plotted on the saturation curve at the predicted coil surface temperature, and the air process line extending from left to right at a slope equal to the SHR. The intersection of this line with a vertical line drawn through the entering air dry bulb temperature indicates the relative humidity of the air entering the coil. Table 1 below shows typical Sensible Heat Ratios for various air temperatures at 95% air on relative humidity. TABLE 1 SHR FOR 95% RH AIR ON AND DT1 = 10F AT VARIOUS TEMPERATURES Room Temperature, F (C) SHR 45 (7.2) (0) (-12.2) (-17.8) (-23.3) (-34.4) 0.97 IMPACT OF LATENT LOAD (SHR) ON AIR COOLER RATINGS Evaporator coils are typically constructed of plate fins bonded to tubes. Fins are referred to as secondary surface while tubes are referred to as primary surface. For purposes of calculating evaporator performance, primary surface is considered to be 100% effective in its contribution to the total heat transfer surface area while secondary surface has a surface effectiveness less than 100% due to the change in surface temperature from the root to the tip of the fin. The capacity of the evaporator surfaces to transfer mass (condense water, or deposit frost, from the airstream) is a function of the difference in water vapor pressure between the coil surface and air stream and the surface mass transfer coefficient. The mass transfer process is much more thermally effective than the sensible heat transfer process, that is, the heat flux through the evaporator surfaces during the mass transfer process is extremely high (AHRI 2001). Consequently, if the surface effectiveness of the coil were to remain constant, the increase in the evaporator cooling capacity during combined sensible and latent cooling would be equal to the sensible cooling capacity divided by the SHR, as follows: However, the increase in heat flux through the fin surfaces has the effect of decreasing fin efficiency and overall surface effectiveness due to an increase in the fin surface temperature gradient (Xia & Jacobi 2005). The result is a slightly lower total cooling capacity than that predicted by Equation (6). Using a computer model developed to accurately calculate fin efficiency and surface effectiveness for both sensible and combined sensible and latent heat transfer, a prediction of the increase in evaporator coil performance as a function of SHR was made. Results of the predicted capacity increase as a function of SHR for an ammonia refrigeration evaporator coil operating over a wide range of room temperatures (+35F to - 30F) and having typical fin spacings and geometry with DT1 = 10F are shown in Figure 2 below. (6) 5
6 Capacity Factor, Qtotal / Qsens only FIGURE 2 Total Cooling Capacity Factor vs SHR Sensible Heat Ratio, SHR Air cooler ratings which include latent cooling will appear higher (in some cases significantly higher) than all sensible ratings. Care must be taken, therefore, to correctly predict the cooling load SHR and the resulting relative humidity in the refrigerated space. From the above it should be apparent that selecting an air cooler with a rating based on a relatively high room relative humidity (SHR less than 1.0) for a room with an actual SHR equal to or close to 1.0 will result in undersized air coolers. For example, a long term cold storage warehouse is designed for +0F (-17.8C) room temperature with a calculated SHR nearly equal to 1.0 (i.e. packaged products and minimal infiltration). From Table 1, the SHR for +0F air temperature and 95% relative humidity would be From Figure 2, an air cooler rated on a total cooling basis at +0F and 95% air on relative humidity would show a nominal capacity +11% greater (capacity factor = 1.11) than a sensible only rating. In this case, therefore, air coolers selected using ratings based 95%rh air on would be significantly undersized. CONCLUSIONS U.S. air cooler manufacturers have traditionally published capacity ratings based on SHR = 1.0 (all sensible) and DT1. European manufacturers typically include latent cooling in their air cooler ratings, indicated by an air on relative humidity typically between 85% and 95%. European manufacturers also publish ratings based on either DT1 or DTM, or both. The discussion above illustrates the differences in these rating methods and highlights the importance of selecting air coolers using ratings suited to the operating conditions. Misapplication of DTM and/or total cooling ratings can result in severely undersized air coolers and the consequent failure of the refrigeration system to perform to energy efficiency and cooling capacity expectations. 6
7 BIBLIOGRAPHY AHRI Standard 410. Forced-Circulation Air-Cooling and Air-Heating Coils. Air-Conditioning Heating & Refrigeration Institute. Arlington, VA. Section AHRI Standard 420. Performance Rating of Forced-Circulation Free-Delivery Unit Coolers for Refrigeration. Air- Conditioning Heating & Refrigeration Institute. Arlington, VA ASHRAE ASHRAE Handbook - Fundamentals. American Society of Heating Refrigerating and Air-Conditioning Engineers. Atlanta, GA. Chap. 4, pp EN Standard EN 328. EN Heat exchangers - Test procedures for establishing the performance of forced convection unit air coolers for refrigeration. European Norm Kays, W.M., A.L. London Compact Heat Exchangers - Second Edition. McGraw-Hill Book Company. Chap. 2, pp Xia, Y., A.M. Jacobi Air-side Data Interpretation and Performance Analysis for Heat Exchangers with Simulataneous Heat and Mass Transfer: Wet and Frosted Surfaces. International Journal of Heat and Mass Transfer. Vol. 48 (2005) For more information contact Colmac Coil Manufacturing, Inc. [email protected]; P: or P.O. Box 571, Colville, WA ; Copyright 2012 Colmac Coil Manufacturing, Inc. 7
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
Moisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA [email protected] 805 687-3175 Matching great technology to market need! Topics SHR
Frost. On Air-Cooling Evaporators. refrigeration applications at temperatures below freezing. These heat exchangers
The following article was published in ASHRAE Journal, February 2009. Copyright 2009 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University
THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving
Energy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!
Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers
COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
UNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
Refrigeration Manual. Part 3 - The Refrigeration Load
Refrigeration Manual Part 3 - The Refrigeration Load FOREWORD The practice of refrigeration undoubtedly goes back as far as the history of mankind, but for thousands of years the only cooling mediums were
Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.
Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010
Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the
Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the
Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture
Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2
Humid Air Water vapor in air Oxygen 21% Trace Glasses 1% Argon (A) Water vapor (H 2 O) Carbon dioxide (CO 2 ) Neon (Ne) Helium (He) Krypton (Kr) Hydrogen (H) Ozone (O 3 ) Nitrogen 78% Humid Air Water vapor
Testing methods applicable to refrigeration components and systems
Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Tech Byte 27: Small Computer Room and IT Closet Cooling
Questions Answered in This Paper Sensible cooling capacity is the measuring stick for IT cooling capacity needs. What is the sensible cooling capacity of the comfort split system in comparison to the precision
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
High Altitude HVAC. Silvertip Integrated Engineering Consultants [email protected] www.silvertipconsultants.com
Presentation to: Rocky Mountain ASHRAE 2013 Tech Conference April 19, 2013 High Altitude HVAC Design Considerations by: Michael D. Haughey, PE, HBDP, CEM, LEED TM AP 2013 Silvertip Integrated Engineering
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
The Development of a Frost-Less Heat Pump
The Development of a Frost-Less Heat Pump V. C. Mei, R. E. Domitrovic, and F. C. Chen, Oak Ridge National Laboratory J. K. Kilpatrick, Tennessee Valley Authority ABSTRACT There are two major concerns associated
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
Dedicated Outdoor Air-Dual Wheel System Control Requirements
4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance
Akton Psychrometric Chart Tutorial and Examples
Akton Psychrometric Chart Tutorial and Examples December 1999 Akton Associates Inc. 3600 Clayton Road, Suite D Concord, California 94521 (925) 688-0333 http://www.aktonassoc.com Copyright 1999 Akton Associates
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
New Trends in the Field of Automobile Air Conditioning
New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic
How To Understand And Understand Psychrometrics
Air Conditioning Psychrometrics Course No: M05-005 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 [email protected]
Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives
Chapter 14 GAS VAPOR MIXTURES AND -CONDITIONING At temperatures below the critical temperature, the gas phase of a substance is frequently referred to as a vapor. The term vapor implies a gaseous state
Humidification Strategies for Data Centers and Network Rooms
Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE
P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering
COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES
COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 TIME SCHEDULE MODULE TOPICS PERIODS 1 Introduction 22 Principles
Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for
HVAC and REFRIGERATION
This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled
Refrigeration and Air Conditioning with Psychrometry
Refrigeration and Air Conditioning with Psychrometry Refrigeration is a process of maintaining low temperature in comparison to surrounding temperature. Refrigeration is the process of removing heat from
DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
USE OF AIR SIDE ECONOMIZER FOR DATA CENTER THERMAL MANAGEMENT. A Thesis Presented to The Academic Faculty. Anubhav Kumar
USE OF AIR SIDE ECONOMIZER FOR DATA CENTER THERMAL MANAGEMENT A Thesis Presented to The Academic Faculty By Anubhav Kumar In Partial Fulfillment of the Requirements for the Masters Degree in the School
Molds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Performance Test of Solar Assisted Solid Desiccant Dryer
Performance Test of Solar Assisted Solid Desiccant Dryer S. MISHA 1,2,*, S. MAT 1, M. H. RUSLAN 1, K. SOPIAN 1, E. SALLEH 1, M. A. M. ROSLI 1 1 Solar Energy Research Institute, Universiti Kebangsaan Malaysia,
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
AIR CONDITIONING TECHNOLOGY
AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
saving energy in comfort Factsheet Recair Enthalpy
saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated
HVAC Made Easy - Overview of Psychrometrics
PDHonline Course M135 (4 PDH) HVAC Made Easy - Overview of Psychrometrics Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Defining Quality. Building Comfort. Heating and Cooling Coils
Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
Thermal Mass Availability for Cooling Data Centers during Power Shutdown
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
How do I measure the amount of water vapor in the air?
How do I measure the amount of water vapor in the air? Materials 2 Centigrade Thermometers Gauze Fan Rubber Band Tape Overview Water vapor is a very important gas in the atmosphere and can influence many
AIRCONDITIONING Cooling Loads Calculations
Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)