TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:



Similar documents
TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"

PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania

How To Test For An Architectural Test

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

TEST REPORT. Report No.: A Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

AST M F /GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

ICC-ES Evaluation Report

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: TYPE: Single Hung Window

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)

ATI Evaluation Service A Division of Architectural Testing Certification Services

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the A325 structural bolt. Rev.

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued November 1, Legacy report on the 1997 Uniform Building Code

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T TYPE: Two-Lite Storefront

The Stabilizer TM. Benefits. Supplemental support system for sagging beams and floor joists within a crawl space

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality

F-Series Camera Mounting Accessories

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Hilti, Inc South 122 nd East Avenue Tulsa, OK

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall

RPS - sales@rpssolar.com San Bruno Cove, San Diego, CA 92130

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

Wisconsin Building Products Evaluation

Mark Cramer Inspection Services, Inc.

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

Small Flat Panel Lift Arm FSA-1004 and KSA-1004

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS

TZ WEDGE ANCHOR FOR CRACKED AND UNCRACKED CONCRETE

Residential Deck Safety, Construction, and Repair

SECTION 1 GENERAL REQUIREMENTS

STANDARDS FOR TESTING AND RATING SCAFFOLD ASSEMBLIES AND COMPONENTS

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S

SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC # TESTED: MAY 23, 2008 REVISION

Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. CONTROL, NOT COMPROMISE.

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

Machine Screws, Dowel Pins and Hardware

Sports and High Mast Lighting Poles Phone: (866) Fax: (817)

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

Design of Cold-Formed Steel Shear Walls

POWERS Controls No. 4 Pneumatic Damper Actuator

Compression load testing straw bale walls. Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY.

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida

Guidelines for Earthquake Bracing Residential Water Heaters

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

Guidelines for Earthquake Bracing of Residential Water Heaters

PART E SPECIFICATIONS

CLEAR-DIVISIONS APERTO

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

American National, Unified Screw Threads

HOSE, TUBE, AND PIPE CLAMPS

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY

GAS DISTRIBUTION PRODUCTS STEEL SERVICE TEES

Objectives. Experimentally determine the yield strength, tensile strength, and modules of elasticity and ductility of given materials.

Submittal Information

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

HUS-H Screw Anchor. Technical data. Seismic design data. HUS-H Carbon steel screw anchor. HUS-H diameter 8, 10, 14. Seismic design data

James M. Pleasants Company

Index Page. Pumping Systems Intensifiers Gas Boosters High Pressure Generators

Sliding Barn Door Hardware Installation Instructions BALDUR and ODEN

Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor

Two most common lock nut groups: 1-Prevailing Torque Type Lock Nuts:

One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty

Stainless Steel Cable Assemblies to Enhance Any Railing and Any View!

FRAME PROFILE MASONRY METAL DOOR FRAME FLUSH MASONRY KD MITER CORNER JOINT. #8 Screw (MS002485) Required on all fire rated KD frames. Bend Tabs.

This Addendum supplements and clarifies the contents of Service Bulletin SB

TEST REPORT. Report No.: B Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95

Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

CLEAR-DIVISIONS VARIOFOLD

System. Stability. Security. Integrity. 150 Helical Anchor

Diameter. Swift Lift Round Recess Plug. Note: The diameter of the narrow recess plug is the same as the diameter of the round recess plug.

CRASH RAIL INSTALLATION HEIGHT

Architectural Testing

Solid Mechanics. Stress. What you ll learn: Motivation

LIFTING WIRE FOR HOT-DIP GALVANIZING BY THOMAS LANGILL, Ph.D.

Transcription:

TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized Steel Reinforcing Inserts Report No.: E2328.01-119-16 Report Date: 01/22/15 Test Record Retention Date: 12/09/18 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

TEST REPORT E2328.01-119-16 January 22, 2015 TABLE OF CONTENTS 1.0 General Information... 1 2.0 Axial Load Compression Tests... 3 3.0 Uplift Load Tests... 11 4.0 Punching Shear Load Tests... 12 5.0 Closing Statement... 14 Revision Log... 14 Appendix A - Drawings Appendix B - Photographs 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

1.0 General Information 1.1 Product TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. 3300 Pinson Valley Parkway P.O. Box 170729 Birmingham, Alabama 35217-0729 Report No.: E2328.01-119-16 Test Dates: 09/24/14 Through: 12/09/14 Report Date: 01/22/15 Test Record Retention Date: 12/09/18 Gorilla Column PVC base / cap plates and PVC bushings used in conjunction with 2-3/8 in diameter and 3-1/2 in diameter galvanized steel reinforcing inserts for PVC porch post systems 1.2 Project Description Architectural Testing was contracted by Homeland Vinyl Products, Inc. to evaluate the structural performance of their Gorilla Column PVC base / cap plates and PVC bushings used in conjunction with 2-3/8 in diameter and 3-1/2 in diameter galvanized steel reinforcing inserts for their PVC porch post systems. The evaluation was for concentric axial loads in compression, uplift loading and punching shear loading.

Page 2 of 15 1.3 Product Description All test specimens used for testing reported herein were supplied by Homeland Vinyl Products Inc. Each post assembly included a section of galvanized steel post reinforcing, 10-3/4 in by 10-3/4 in by 1-1/2 in (overall thickness) PVC base / cap plate and a 4-1/8 in by 4-1/8 in by 1-1/2 in (overall thickness) PVC bushing. Connection details for each test specimen were as follows: 2-3/8 in Diameter Steel Porch Post Reinforcing Insert: Axial Load and Uplift Load Testing: 2-3/8 in O.D by 2-3/16" I.D. by 0.090 in thick wall (nominal 13 gauge) galvanized steel post attached to the PVC bushing with four #12-14 x 1-1/2" (0.160 in minor diameter) hex washer head, stainless steel selfdrilling screws. The bushing attached to the PVC cap / base plate with four 1/4"-14 x 3/4" (0.184 in minor diameter) trim head, phillips drive, zinc coated carbon steel screw, type AB point. Punching Shear Load Testing: 2-3/8 in O.D by 2-3/16" I.D. by 0.090 in thick wall (nominal 13 gauge) galvanized steel post attached to the PVC bushing with four #12-14 x 1-1/2" (0.160 in minor diameter) hex washer head, zinc coated carbon steel self-drilling screws using a 1/8 in pre-drill. The bushing attached to the PVC cap / base plate with four 1/4"-14 x 3/4" (0.184 in minor diameter) trim head, phillips drive, zinc coated carbon steel screw, type AB point. 3-1/2 in Diameter Steel Porch Post Reinforcing Insert: Axial Load and Uplift Load Testing: 3-1/2 in O.D. by 3-5/16" I.D. by 0.091 in thick wall (nominal 13 gauge) galvanized steel post attached to the PVC bushing and cap / base plate with four #12-14 x 1-1/2" (0.160 in minor diameter) hex washer head, stainless steel self-drilling screws. Punching Shear Load Testing: 3-1/2 in O.D. by 3-5/16" I.D. by 0.091 in thick wall (nominal 13 gauge) galvanized steel post attached to the PVC bushing and cap / base plate with four #12-14 x 1-1/2" (0.160 in minor diameter) hex washer head, zinc coated carbon steel self-drilling screws using a 1/8 in pre-drill. The galvanized steel post was attached to the bushing only with one #10-16 x 3/4" (0.138 in minor diameter) pan head, square drive, carbon steel selfdrilling screw using a 1/8 in pre-drill. See photographs in Appendix B for additional product information. Drawings are included in Appendix A to verify the overall dimensions and other pertinent information of the tested product, its components, and any constructed assemblies.

Page 3 of 15 1.4 Qualifications Architectural Testing in York, Pennsylvania has demonstrated compliance with ANS/ISO/IEC Standard 17025 and is consequently accredited as a Testing Laboratory (TL-144) by International Accreditation Service, Inc. 1.5 Witnessing Mr. Jeff Havercroft of Homeland Vinyl Products and Mr. Mike Burkart of Waymark Products were present to assemble test specimens and witness punching shear testing on 09/23/14. Mr. Jeff Havercroft of Homeland Vinyl Products was present to assemble test specimens and witness concentric axial load and uplift load testing on 12/03/14 and 12/09/14, respectively. 2.0 Axial Load Compression Tests 2.1 Test Equipment The test fixture consisted of a flat steel support attached to a rigid steel column at the top. The bottom consisted of a hydraulic jack positioned on a leveling fixture, fitted with a flat steel bearing plate and a 50,000 pound capacity load cell. Test duration, load, and deflection were recorded electronically throughout the test. 2.2 Test Setup The columns were installed into the compression fixture with no physical connections between the column and fixture. The compression fixture was plumbed using a "PLS-5" laser plumbing device, and while applying a minimal preload to hold the test sample in place, the column was leveled with a 78 in level. An electronic linear displacement transducer was positioned at the mid-point of each of two axes on each column to measure lateral displacements about the X- and Y-Axes of the column. Reference photographs in Appendix B for test setups. 2.3 Test Procedure Each test sample was inspected prior to testing to verify size and general condition of the materials, assembly, and installation. No potentially compromising defects were observed prior to the tests. Each test began with a small initial load and was loaded at a steady, uniform load rate until the test sample failed. Lateral displacements, test load, and time were electronically recorded throughout the test. The ultimate load and mode of failure were recorded for each test.

Page 4 of 15 2.4 Test Results Test loads were concentric axial compression. X- and Y-Axis displacements were measured at the column's mid-height. Specimen No. 1 2-3/8 in O.D. by 108 in Steel Reinforcing Test Date: 12/03/14 Test Load (lb) Displacement (inches) X-Axis Y-Axis 13 0.00 0.00 1258 0.02 0.02 2200 0.04 0.05 3477 0.08 0.07 4132 0.09 0.10 5389 0.12 0.14 6589 0.14 0.20 9032 0.16 0.29 10106 0.16 0.31 11374 0.17 0.35 12049 0.20 0.40 13630 0.28 0.57 14197 0.30 0.79 14850 Ultimate Load

Page 5 of 15 2.4 Test Results (Continued) Specimen No. 2 2-3/8 in O.D. by 108 in Steel Reinforcing Test Date: 12/03/14 Test Load (lb) Displacement (inches) X-Axis Y-Axis 42 0.00 0.00 1147 0.03 0.02 2237 0.03 0.02 3170 0.03 0.02 4118 0.03 0.03 5271 0.03 0.08 6158 0.03 0.13 7336 0.04 0.17 8200 0.04 0.19 9177 0.05 0.21 10202 0.05 0.24 11724 0.05 0.27 12423 0.05 0.30 13044 0.05 0.34 14480 0.05 0.48 15044 0.05 0.75 15488 Ultimate Load

Page 6 of 15 2.4 Test Results (Continued) Specimen No. 3 2-3/8 in O.D. by 108 in Steel Reinforcing Test Date: 12/03/14 Test Load (lb) Displacement (inches) X-Axis Y-Axis 50 0.00 0.00 1209 0.05 0.04 2049 0.05 0.04 3018 0.05 0.09 4252 0.05 0.16 5172 0.05 0.18 6382 0.05 0.21 7059 0.05 0.21 8289 0.06 0.24 9523 0.07 0.26 10407 0.08 0.29 11708 0.08 0.34 12418 0.09 0.40 13046 0.11 0.48 14231 0.14 0.64 15201 0.21 1.02 15254 Ultimate Load

Page 7 of 15 2.4 Test Results (Continued) Specimen No. 4 3-1/2 in O.D. by 120 in Steel Reinforcing Test Date: 12/03/14 Test Load (lb) Displacement (inches) X-Axis Y-Axis 70 0.00 0.00 1110 0.05 0.04 2073 0.06 0.06 3177 0.07 0.06 4276 0.07 0.06 5174 0.07 0.06 6529 0.09 0.06 7104 0.09 0.06 8262 0.09 0.06 9492 0.09 0.06 10110 0.09 0.06 11260 0.09 0.06 12169 0.09 0.06 13441 0.09 0.06 14291 0.09 0.06 15286 0.09 0.06 16225 0.09 0.06 17388 0.09 0.06 18201 0.09 0.06 19281 0.09 0.06 20009 0.09 0.06 21528 0.09 0.06 22352 0.09 0.06 23007 0.09 0.06 24363 0.09 0.06 26056 0.09 0.08 27326 0.09 0.10 28275 0.09 0.13 29232 0.09 0.13 30535 0.09 0.16 31029 0.16 0.20 32286 0.20 0.25 33169 0.33 0.44 34122 Ultimate Load

Page 8 of 15 2.4 Test Results (Continued) Specimen No. 5 3-1/2 in O.D. by 120 in Steel Reinforcing Test Date: 12/03/14 Test Load (lb) Displacement (inches) X-Axis Y-Axis 240 0.00 0.00 1410 0.02 0.04 2229 0.02 0.04 3351 0.02 0.05 4047 0.02 0.05 5227 0.02 0.06 6357 0.02 0.07 7019 0.02 0.07 8232 0.02 0.08 9001 0.03 0.09 10229 0.03 0.11 11179 0.03 0.12 12029 0.03 0.12 13655 0.03 0.12 14075 0.03 0.13 15588 0.03 0.14 16155 0.03 0.14 17214 0.03 0.14 18043 0.03 0.15 19228 0.03 0.16 20642 0.04 0.16 21321 0.04 0.17 22377 0.04 0.18 23465 0.04 0.19 24393 0.04 0.20 25187 0.04 0.21 26109 0.04 0.22 27026 0.04 0.23 28160 0.04 0.25 29005 0.04 0.28 30380 0.04 0.34 31048 0.04 0.38 32216 0.04 0.47 33522 0.06 0.73 33671 Ultimate Load

Page 9 of 15 2.4 Test Results (Continued) Specimen No. 6 3-1/2 in O.D. by 120 in Steel Reinforcing Test Date: 12/03/14 Test Load Displacement (inches) (lb) X-Axis Y-Axis 94 0.00 0.00 1275 0.03 0.05 2282 0.03 0.05 3157 0.03 0.05 4273 0.03 0.05 5051 0.03 0.05 6210 0.03 0.05 7150 0.03 0.05 8240 0.03 0.05 9186 0.03 0.05 10031 0.03 0.05 11072 0.03 0.05 12232 0.03 0.05 13062 0.03 0.05 14223 0.03 0.05 15531 0.03 0.05 16378 0.03 0.05 17163 0.03 0.05 18172 0.03 0.05 19086 0.03 0.05 20028 0.03 0.05 21029 0.03 0.06 22564 0.03 0.06 23732 0.04 0.08 24006 0.05 0.08 25612 0.06 0.10 26225 0.06 0.12 27595 0.06 0.13 28385 0.07 0.15 29377 0.10 0.17 30906 0.11 0.21 31120 0.12 0.24 32343 0.14 0.32 33207 0.15 0.45 34694 Ultimate Load

Page 10 of 15 2.5 Test Summary Results are ultimate load capacity of individual specimens and should not be used as safe working values or design load values. 2-3/8 in O.D. by 108 in Post Specimen No. Ultimate Load (lb) Deviation From Average 1 14850-2.3% 2 15488 +1.9% 3 15254 +0.4% Average: 15197 Failure Mode Steel post reinforcing buckled and yielded to load 3-1/2 in O.D. by 120 in Post Specimen No. Ultimate Load (lb) Deviation From Average 1 34122-0.1% 2 33671-1.4% 3 34694 +1.6% Average: 34162 Failure Mode Steel post reinforcing buckled and yielded to load

Page 11 of 15 3.0 Uplift Load Tests 3.1 Test Equipment The specimens were tested to ultimate capacity in tension utilizing a SATEC Unidrive, Model MII 50 UD Universal Test Machine (ICN: Y002011). 3.2 Test Setup Short sections of galvanized steel posts were attached at each end to a base / cap plate, bushing and double pressure treated Southern Yellow Pine (SYP) wood boards. The PVC cap / base plates were secured to the wood boards with six 1/4" by 2-1/2" FastenMaster TimberLOK (0.164 in minor diameter, 0.260 in major diameter, 0.19 in shank diameter, hex washer head) heavy duty wood screws with 3/4 in diameter washers. Tests were conducted at lab ambient temperature (68ºF ± 4ºF). Reference photographs in Appendix B for test setup. 3.3 Test Procedure After securing each column into the test machine, the load was applied at a uniform rate of 0.05 in/min. until failure. The test duration, ultimate test load, and mode of failure were recorded for each test. 3.4 Test Results Results are ultimate load capacity of individual specimens and should not be used as safe working values or design load values. Reference photographs in Appendix B for mode of failure. 2-3/8 in O.D. Post Test Date: 12/09/14 Deviation From Average Specimen No. Ultimate Load (lb) 1 1372 +0.3% 2 1369 +0.1% 3 1363-0.4% Average: 1368 Failure Mode Base / cap plate fractured at the plate to bushing connection screws 3-1/2 in O.D. Post Test Date: 12/09/14 Specimen No. Ultimate Load (lb) Deviation From Average 1 2538-4.5% 2 2777 +4.5% 3 2660 +0.1% Average: 2658 Failure Mode Base / cap plate fractured

Page 12 of 15 4.0 Punching Shear Load Tests 4.1 Test Equipment The specimens were tested to ultimate capacity in compression utilizing a SATEC Unidrive, Model MII 50 UD Universal Test Machine (ICN: Y002011). 4.2 Test Setup Short sections of galvanized steel posts were attached at each end to a base / cap plate, bushing and double pressure treated Southern Yellow Pine (SYP) wood boards. The PVC cap / base plates were secured to the wood boards with six 1/4" by 2-1/2" FastenMaster TimberLOK (0.164 in minor diameter, 0.260 in major diameter, 0.19 in shank diameter, hex washer head) heavy duty wood screws with 3/4 in diameter washers. Tests were conducted at lab ambient temperature (68ºF ± 4ºF). Reference photographs in Appendix B for test setup. 4.3 Test Procedure After securing each column into the test machine, the load was applied at a uniform rate of 0.05 in/min. until failure. The test duration, ultimate test load, and mode of failure were recorded for each test.

Page 13 of 15 4.4 Test Results Results are ultimate load capacity of individual specimens and should not be used as safe working values or design load values. Reference photographs in Appendix B for mode of failure. Note: Punching shear testing was conducted on the original post base / cap plate design. The differences between the redesigned base / cap plate and the original were determined to be insignificant and would not affect the punching shear test results. Reference drawings in Appendix A for drawings of both the original and the redesigned base / cap plates. 2-3/8 in O.D. Post Test Date: 09/24/14 Specimen Ultimate Load Deviation No. (lb) From Average Failure Mode 1 15256 +4.5% Cap / base plate fractured 2 18464 +26.4% under bushing 3 10088 1-30.9% The only visible damage was the #12 fasteners bent in a down-ward angle. There was no visible deformation of post mount base / cap or bushing. Average: 14603 1 This test was stopped at 10,000 lbs. per client s request. 3-1/2 in O.D. Post Test Date: 09/26/14 Specimen Ultimate Load Deviation No. (lb) From Average Failure Mode 1 26598 +10.8% Cap / base plate fractured just 2 20407-15.0% outside of the bushing 3 25032 +4.2% Bushing fractured at bushing to post connection screw Average: 24012

Page 14 of 15 5.0 Closing Statement Architectural Testing will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. Results obtained are tested values and were secured using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimens tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: Steven A. Neff Technician II Structural Systems Testing V. Thomas Mickley, Jr., P.E. Senior Project Engineer Structural Systems Testing SAN:vtm/jas Attachments (pages): This report is complete only when all attachments listed are included. Appendix A - Drawings (3) Appendix B - Photographs (7)

Page 15 of 15 Revision Log Rev. # Date Page(s) Revision(s) 0 01/22/15 N/A Original report issue This report produced from controlled document template ATI 00644, issued 01/17/13.

APPENDIX A Drawings

APPENDIX B Photographs

Photo No. 1 Typical Axial Load Compression Test Setup (108 in length post) Photo No. 2 Typical Axial Load Compression Test Setup (120 in length post)

Photo No. 3 Typical Uplift Load Test Setup Photo No. 4 Typical Uplift Load Test Failure - 2-3/8 in Diameter Post

Photo No. 5 Typical Uplift Load Test Failure - 3-1/2 in Diameter Post Photo No. 6 Typical Punching Shear Test Setup

Photo No. 7 Punching Shear Test Failure - 2-3/8 in Diameter Post (Specimens 1 and 2) Photo No. 8 Punching Shear Test Results Following 10000 lbs of Load - 2-3/8 in Diameter Post (Specimen 3)

Photo No. 9 Punching Shear Test Results Following 10000 lbs of Load - 2-3/8 in Diameter Post (Specimen 3 - Underside) Photo No. 10 Punching Shear Test Failure - 3-1/2 in Diameter Post (Specimens 1 and 2)

Photo No. 11 Punching Shear Test Failure - 3-1/2 in Diameter Post (Specimen 3) Photo No. 12 Original Base / Cap Plate (Bottom Surface Left; Top Surface Right)

Photo No. 13 Redesigned Base / Cap Plate (Bottom Surface Left; Top Surface Right) Photo No. 14 Bushing (Bottom Surface Left; Top Surface Right)