INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description



Similar documents
NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM S7010 S :111

INTELLIGENT FIRE ALARM CONTROL UNITS MMX-MNS TM

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

SFC-200 SERIES LCD FIRE ALARM PANEL

Intelligent Fire Detection & Alarm and Mass Notification System.

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

Fire Alarm System Plans Review Checklist Property location Date of Review

SECTION DETECTION AND ALARM

CATALOG NUMBER. Features. Description

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Life Alarm Fire Alarm Controls

25 Years of Manufacturing Excellence. Premier Quatro Addressable Fire Alarm System. Assessed to ISO 9001: 2008

HM-W536 Install Guide

Alliance System Ordering Guide

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

ARCHITECT AND ENGINEER SPECIFICATION SECTION DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE. DSC MAXSYS PC4020 V3.

TrueAlarm Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual

FAST, INTELLIGENT FIRE ALARM SYSTEMS THAT DELIVER IT ALL

Using your LED Plus keypad

Design Standards Fire Alarm Systems Division (1995 CMS); (2004 CMS) Amended Feb 2015

Fire Control Panels. Remote Annunciator Panels. UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features. Introduction

Versatile. EST3X Life Safety Solutions. An EDWARDS brand.

SECTION FIRE ALARM AND DETECTION SYSTEM

DTW Works Master Specification Version 2006

INTRUSION DETECTION SYSTEM Section

Faraday Intelligent Fire Detection Systems

SECTION FIRE ALARM AND DETECTION SYSTEMS

Fire Pump Controllers Remote Alarm Panels

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Control Panels Series Remote InfoAlarm Command Center for the 4010ES Fire Alarm Control Panel

Elite-RS Panel Installation Manual

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Operating the DS9400 Fire Alarm Control/Communicator

Installation Instructions & Owner s Operation Manual for Two to Eight Zone 2400 Series Fire Alarm Control Panels

TrueAlarm Fire Alarm Systems

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

SILENT KNIGHT MODEL 5207

AIS750 Series Alarm Annunciator

SECTION FIRE ALARM AND DETECTION SYSTEM

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

Repeaters and Mimics Data Sheet

PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

Product Guide CM-Relay

Potter Plus. Fire Alarm Control Panels

SECTION FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

PLAN REVIEW GUIDE FOR FIRE ALARM

HERNANDO COUNTY FIRE ALARM GUIDELINES

PFC-6030 Fire Alarm Control Panel

TX3 Communication & Security Solutions

VEGA Analogue Addressable Control Panels

Control/Communicator Installation Manual

Fire Alarm Control Panel. Family. Operating Manual

How To Understand Your Fire Alarm On An Iphone Or Ipad (Powerbook)

T1 Backhaul Connectivity Solution All Products :: Application Note

FIRE ALARM AND VOICE COMMUNICATION SYSTEM Request for Qualifications

Overview. Alarm console supports simultaneous viewing of both live and recorded video when alarm events are selected

SECTION FIRE ALARM AND DETECTION SYSTEM

Lighting and Fire Alarm Training System Add-On

ENGINEERING SPECIFICATIONS SENSAPHONE IMS-4000

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

D287/D288/D292/D293A/D293E

SECTION FIRE ALARM SYSTEM

ECR Shelf System Installation Guide Centralized Rack Mount Call Recording

SNMP-1000 Intelligent SNMP/HTTP System Manager Features Introduction Web-enabled, No Driver Needed Powerful yet Easy to Use

LCD5500Z / PKP-LCD v3.x Installation Instructions

FIRE ALARM SYSTEM Section Page 1

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

Conventional Fire Detection and Extinguishant Control System Specification

QMT-5300A, QMT-5302 and QZT-5302

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

Elvey is a leading distributor of electronic security equipment in Africa. Our vision is to assist in the protection of people and property by

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Product Information Fire alarm panel 8000 C

EST2 Installation and Service Manual. P/N Rev AUG00

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.

GSM Voice Auto Dialer & SMS Sender JC-999

VFR-400 Installation, Operation, and Instruction Manual

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

Specifications Control Features. User Interface. Communicator. Programmable Outputs. Access Control. System Response

C. Conform to requirements of Americans with Disabilities Act (ADA).

Fire detection equipment

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

INSTALLATION MANUAL PC2525. Version 1.1

Integrated Building Management and Security System. Building Automation & Security.

TX3 Series TELEPHONE/CARD ACCESS SYSTEMS. System Introduction (Sales Training)

Transcription:

INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2017-12NDS Network Fire Alarm Control Unit offers modular components to meet a wide variety of applications. Designed for peer-to-peer network communications, the MMX-2017-12NDS allows for a maximum of 63 nodes, while providing reliability, flexibility and expandability. The MMX-2017-12NDS base unit consists of one intelligent signaling line circuit (SLC) capable of supporting 99 analog sensors and 99 addressable modules. In addition the base unit also consists of Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a large 4 x 20 back-lit alphanumeric LCD display. The MMX-2017-12NDS network configuration allows the control unit to be connected to a Secutron network to provide additional input circuits, visual zones, programmable notification appliance circuits, and relays. The network interface module allows the control units to communicate on a peer-to-peer network. The network capabilities allow site specific customization and the ability to meet local and national requirements. Features Fire Alarm Control One expandable to seventeen Intelligent Signaling Line Circuits (SLC) Modular design Each SLC Loop is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Style 6 or 7 (Class A) or Style 4 (Class B) Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each Large 4 by 20 character Back-lit LCD Display with user friendly menu Supported languages: English, French, Arabic* and Hebrew* (*960 character back-lit LCD display only) Panel Security to protect site configurations Correlatable Switch Inputs which allows for multifunctional outputs Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble Group bypass with built-in false alarm prevention technology RS-232 output for remote system printer or CRT Two Event History Logs comprised of a 6000 Alarm History Log for alarm related events and a 6000 Event Log for all events Supports three configuration files (current, previous and next configuration) with hot swap support Supports Conventional Hardwire Adder Modules Built-in One Man Walk Test operation Configurable for Canadian Two Stage operation Configurable for Coded Operation Real time 3D graphical monitoring and control using Open Graphic Navigator BACnet support Supports Boolean logic functions Built-in Ethernet port Remote diagnostics via a built-in web server UL listed for Smoke Control Network Features Up to 63 nodes Peer-to-peer network communications Style 4 (Class B) or Style 6 or 7 (Class A) wiring configuration Proprietary Arcnet Network Communications protocol Supports copper and/or fiber optic network cable S6619 S6619 7165-1656:0132 NYC Fire Dept. APPROVED Issue 3 SECUTRON Page 1 of 6 Canada 25 Interchange Way, Vaughan (Toronto), Ontario L4K 5W3 Telephone: (905) 695-3545 Fax: (905) 660-4113 Web Page: www.secutron.com U.S.A. 4575 Witmer Industrial Estates, Niagara Falls, NY 14305 Telephone: (888) 695-3545 Fax: (888) 660-4113 E-mail: mail@secutron.com Not to be used for installation purposes.

MMX-2017-12NDS Network Series Fire Alarm Control Units MMX-2017-12NDS Mid-Size Network Main Control Unit The MMX-2017-12NDS Midsize Network Main Control Unit comes complete with one intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7, Four Style Z/Y (Class A/B) NAC Circuits (1.7 Amps each), a 4 line by 20 character back-lit LCD display and a 12 Amp Power Supply. The MMX2017-12NDS provides space for the FNC-2000 Network Controller Module, up to 16 adder modules/loop controllers and 3 internal annunciator adder display modules. The MMX-2017-12NDS mounts in the MMX-BBX-1072ARDS enclosure. MMX-BBX-1072ARDS Enclosure The MMX-BBX-1072ARDS enclosure supports one MMX-2017-12NDS and up to 40 AH Batteries. The enclosure features the universal CAT-30 lock and a removable red door for easy installation and servicing. Adder Loop Controller Modules Fire Network Controller Modules ALCN-792M Quad Loop Controller Module The ALCN-792M Quad Loop Controller Module provides two Signaling Line Circuits (SLC) to the MMX system consisting of 99 Analog Sensors and 99 Addressable Modules per loop. The ALCN-792M can be expanded with the use of the ALCN-792D Daughter Board Module. The ALCN-792M occupies one module slot. FNC-2000 Fire Network Controller Module The FNC-2000 provides network capability to the MMX2017-12NDS. One Fire Network Controller Module is required per network node. In addition the FNC-2000 provides an interface for adding an optional FOM-2000SP Fiber Optic Network Adder Module. The FNC-2000 mounts in the MMX-2017-12NDS main chassis. ALCN-792D Daughter board for Quad Loop Controller Module The ALCN-792D Daughter Board provides an additional two SLC when connected to the ALCN792M Quad Loop Controller Module. The daughter board mounts on top of the ALCN-792M. Dimensions for Annunciator Module Enclosures Model Dimensions MMX-BB-1001R 9 H x 12.75 W x 1.2 D MMX-BB-1002R 18 H x 12.75 W x 1.2 D MMX-BB-1003R 26.4 H x 12.75 W x 1.2 D MMX-BB-1008R 33 H x 22.5 W x 1.25 D MMX-BB-1012R 45 H x 22.5 W x 1.25 D Page 2 of 6 Dimensions: 32 1/2 H x 25 W x 6 1/2 D FOM-2000-SP Fiber Optic Network Adder Module The FOM-2000-SP Fiber Optic Network Adder Module allows for the use of fiber optic cabling on the MMX-201712NDS. It seamlessly connects to the interface on the FNC-2000 Fire Alarm Network Controller Module. Electrical Specifications Primary Input Power 120V 60Hz / 240V, 50Hz 4 Amps / 2 Amp (primary) Power Supply Ratings 12 Amps. max. (secondary) For NAC Circuits 24VDC unfiltered, 10 Amps. max. Battery Type 24VDC, Gel-Cell/Sealed Lead-Acid Battery Charging Capability 17-65 AH batteries SECUTRON INC. Not to be used for installation purposes. Issue 4

Adder Hardwire Modules Adder Auxiliary Modules DM-1008A Eight Initiating Circuit Module The DM-1008A provides 8 Style B (Class B) or 4 Style D (Class A) Initiating Circuits configurable for Alarm, Supervisory or Trouble zones. The DM-1008A occupies one module slot in the MMX-2017-12NDS main chassis. UDACT-300A Digital Alarm Communicator Module The UDACT-300A Digital Alarm Communicator Module allows the MMX-2017-12NDS to transmit addressable point information to a central station. The UDACT-300A occupies one module slot in the MMX-2017-12NDS main chassis. SGM-1004A Four Notification Appliance Circuit Module The SGM-1004A provides 4 Style Z/Y (Class A/B) Notification Appliance Circuits configurable as Silenceable or Non-Silenceable. Each NAC circuit is rated at 1.7 Amps. The SGM-1004A occupies one module slot in the MMX-2017-12NDS main chassis. RM-1008A Eight Relay Circuit Module The RM-1008A provides the MMX-2017-12NDS with eight individual configurable relays per module. Each relay provides one Form C contact rated at 28 VDC @1 Amp (resistive load) as well as a Green LED to indicate that the relay is active. The RM-1008A occupies one module slot in the MMX-2017-12NDS main chassis. Graphics Software Open Graphic Navigator (OpenGN) The Open Graphic Navigator (OpenGN) software is an advanced fire alarm management and warning system that provides building ready monitoring, control and software management solutions that allows a user to monitor remote sites from multiple operator workstations located anywhere in the world. The OpenGN software is available in two versions: Network (OPENGN-ENT) and Non-Network (OPENGN-MINI). Issue 3 PR-300 Polarity Reversal/City Tie Module The PR-300 Polarity Reversal/City Tie Module provides the system with a supervised City Tie (24 VDC/200 ma max.) and Polarity Reversal connection (24 VDC (open circuit), 8 ma max. (shorted)). The PR-300 occupies one module slot in the MMX-201712NDS main chassis. Programmable Modules FDX-008 Fan Damper Control Module The FDX-008 Fan Damper Control Module provides individually programmed circuits which can be used for fan or damper control. The FDX-008 connects to the main control unit or the RAXN-LCD and occupies one display position in an MMX-BB-1000 or MMX-BB-5000 Series enclosure. IPS-2424DS Programmable Input Switches Module The IPS-2424DS provides 24 programmable switches that can be configured for ancillary functions such as zone bypass or added common control functions. The IPS2424DS connects to main control unit or the RAXN-LCD when mounted remotely. The IPS-2424DS occupies one display position in an MMX-BB-1000 or MMX-BB-5000 Series enclosure. SECUTRON INC. Not To Be Used For Installation Purposes. Page 3 of 6

Remote LCD Annunciators RAXN-LCD Remote LCD Annunciator The RAXN-LCD Remote LCD Annunciator provides the same functions as the main display on the fire alarm control unit. The RAXN-LCD occupies one display position in the MMX-BB-1000 or MMX-BB-5000 Series enclosure. Remote LED Annunciators RAM-1032TZDS Main Remote LED Annunciator The RAM-1032TZDS Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. The RAM-1032TZDS has indicators for A.C. On, Common Trouble and Signal Silence and controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence and Signal Silence. The RAM-1032TZDS occupies one display position in the MMX-BB-1000 or MMX-BB-5000 Series enclosure. RAXN-LCDG Remote Graphic LCD Annunciator The RAXN-LCDG Remote Graphic LCD Annunciator is equipped with a 24 line x 40 character back-lit graphical LCD display that is used to display 9 events per page. Each event is displayed over 2 lines with 40 characters per line allowing emergency information to be displayed in an easy to read format. The RAXN-LCDG occupies one display position in the MMX-BB-1000 or MMX-BB-5000 Series enclosures. RAX-1048TZDS Programmable LED Annunciator Module The RAX-1048TZDS Programmable LED Annunciator Module provides 48 programmable bi-colored LEDs. The RAX-1048TZDS connects to the main control unit or either the RAXN-LCD or RAM-1032TZDS when mounted remotely. The RAX-1048TZDS occupies one display position in the MMX-BB-1000 or MMX-BB-5000 Series enclosure. Graphic Annunciator Driver Modules MGD-32 Master Graphic Driver Module The MGD-32 Master Graphic Driver Module provides common control inputs for the common control switches such as System Reset, Signal Silence, Auxiliary Disconnect, Fire Drill, Lamp Test, Acknowledge and General Alarm. The MGD-32 can also drive up to 32 supervised outputs. These output points are capable of driving LEDs or incandescent lamps. The MGD-32 mounts in a graphic annunciator wallbox or in the MMX-BB-5000 enclosures. An external power supply is required for incandescent lamps and lamp test. Page 4 of 6 AGD-048 Adder Graphic Driver Module The AGD-048 Adder Graphic Driver Module can be used with the MGD-32 to support an additional 48 supervised outputs. The AGD-048 mounts in a graphic annunciator wallbox or in the MMX-BB-5000 Series enclosure. SECUTRON INC. Not to be used for installation purposes. Issue 4

Typical MMX-2017-12NDS Networked System Configuration RS-485 RAXN-LCD and two RAX-1048TZ in an MMX-BB-1003R enclosure Node 1 MMX-2017-12NDS in an MMX-BBX-1072ARDS enclosure RS-485 RAXN-LCD in an MMX-BB-1001R enclosure Class A (Style 7) wiring Node 5 MMX-2003-12NDS in a UB-1024DS backbox with a DOX-1024DSR door Node 2 MMX-2003-12NDS in a UB-1024DS backbox with a DOX-1024DSR door Ethernet Class B (Style 4) wiring RS-485 RAXN-LCD in an MMX-BB-1001R enclosure Node 4 MMX-2017-12NDS in an MMX-BBX-1072ARDS enclosure OpenGN Graphics Software Node 3 MMX-2017-12NDS in an MMX-BBX-1072ARDS enclosure Current Consumption Model Number Description Standby Alarm MMX-2017-12NDS Main Chassis (12 Amp) 0.310 0.733 ALCN-792M Dual Analog Loops 0.130 0.145 ALCN-792M with ALCN-792D Quad Analog Loops 0.130 0.145 FNC-2000 Fire Network Controller Module 0.190 0.0190 FOM-2000-SP Fiber Optics Module 0.015 0.015 DM-1008A 8 Initiating Circuit Module 0.080 1 zone active: 0.125 2 zone active: 0.170 4 zone active: 0.275 6 zone active: 0.370 8 zone active: 0.465 SGM-1004A 4 Notification Appliance Circuit Module 0.060 0.258 RM-1008A 8 Relay Circuit Module 0.025 0.150 FDX-008 Fan Damper Control Module 0.015 0.035 UDACT-300A Dialer Module 0.045 0.120 PR-300 City Tie Module 0.035 0.300 RAX-1048TZDS Adder Annunciator Chassis 0.022 1 zone active: 0.026 2 zone active: 0.030 3 zone active: 0.035 4 zone active: 0.039 48 zone active: 0.262 RAM-1032TZDS Adder Annunciator Chassis 0.050 32 zone active: 0.300 AGD-048 Adder Graphic Driver Board 0.035 # of LEDs x 4mA IPS-2424DS Programmable Input Switches Module 0.010 0.015 Issue 3 SECUTRON INC. Page 5 of 6 Not To Be Used For Installation Purposes.

Ordering Information Model Description Network Fire Alarm Control Unit MMX-2017-12NDS Network Main Chassis with 12 Amp power supply. Mounts in the MMX-BBX-1072ADS(ARDS) enclosure. MMX-BBX-1072ARDS Black backbox enclosure for MMX-2017-12NDS c/w red door. Network Controller Modules FNC-2000 Fire Network Controller Module FOM-2000-SP Fiber Optic Network Adder Module Adder Loop Controller Modules ALCN-792M Network Quad Loop Controller Module ALCN-792D Daughter board for ALC-792M Quad Loop Controller Module Adder Hardwire Modules DM-1008A Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module SGM-1004A Four Class A/B (Style Z/Y) Notification Appliance Circuit Module (Rated at 1.7 Amps per circuit) RM-1008A Eight Relay Circuit Module c/w eight form C relays (Rated for 28 VDC @ 1 Amp max. per relay) Adder Auxiliary Modules UDACT-300A Digital Alarm Communicator Transmitter/Dialer Module PR-300 Polarity Reversal and City Tie Module Remote Annunciators RAXN-LCD Remote LCD Annunciator RAXN-LCDG Remote Graphic LCD Annunciator RAM-1032TZDS Main Remote LED Annunciator c/w 32 Bi-Colored LEDs RAX-1048TZDS Programmable LED Annunciator Module c/w 48 Bi-Coloured LEDs and 48 Trouble LEDs Programmable Modules IPS-2424DS Programmable Input Switches Module c/w 24 selector switches and 24 bi-coloured LEDs FDX-008 Fan Damper Control Module Enclosures for Remote Annunciators / Programmable Modules MMX-BB-1001 Remote Enclosure. Houses one module. Add suffix R for red door. MMX-BB-1002 Remote Enclosure. Houses two modules. Add suffix R for red door. MMX-BB-1003 Remote Enclosure. Houses three modules. Add suffix R for red door. MMX-BB-1008 Remote Enclosure. Houses eight modules. Add suffix R for red door. MMX-BB-1012 Remote Enclosure. Houses twelve modules. Add suffix R for red door. Graphic Driver Modules MGD-32 Main Graphic Driver Module c/w 32 Supervised Outputs AGD-048 Adder Graphic Driver Module c/w 48 Supervised Outputs Graphics Software OPENGN-MINI Open Graphic Navigator Software, Mini Edition for standalone MMX Systems OPENGN-ENT Open Graphic Navigator Software, Enterprise Edition for MMX Network Systems Page 6 of 6 SECUTRON INC. Not to be used for installation purposes. Issue 4 Secutron reserves the right to make changes at any time without notice in prices, colors, materials, components, equipment, specifications and models and also to discontinue models. Modul-R is a trademark of Secutron Inc.