Datacenter Performance Per Energy (DPPE) October 5th, 2010 Survey and Evaluation Committee

Similar documents
DPPE: Holistic Framework for Data Center Energy. Efficiency. - KPIs for Infrastructure, IT Equipment, Operation (and Renewable Energy) -

Harmonizing Global Metrics for Data Center Energy Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency

DATA CENTER. Enhancing the Energy Efficiency and Use of Green Energy in Data Centers

New Data Center Energy Efficiency Evaluation Index DPPE (Datacenter Performance per Energy) Measurement Guidelines (Ver 2.05)

Green IT Promotion Council, Japan

Recommendations for Measuring and Reporting Overall Data Center Efficiency

AT&T Global Network Client for Windows Product Support Matrix January 29, 2015

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

ENERGY STAR for Data Centers

Data Center Energy Efficiency Looking Beyond PUE

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

Harmonizing Global Metrics for Data Center Energy Efficiency. Global Taskforce Reaches Agreement Regarding Data Center Productivity.

Achievements and Issues in Promoting Diagnosis on Energy Saving in Southeast Asia and Surrounding Regions

New Trends in Data Center Metrics

Energy saving technology for data centers. HVDC(High Voltage Direct Current) + 12V Server rack system

Green Evaluation Metrics and Software Tool for Data Center

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Newfoundland and Labrador Hydro Electricity Rates

Yield Reduction due to Shading:

Case 2:08-cv ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138. Exhibit 8

Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE

Data Centre Energy Efficiency: A Call To Action

Analysis One Code Desc. Transaction Amount. Fiscal Period

Enhanced Vessel Traffic Management System Booking Slots Available and Vessels Booked per Day From 12-JAN-2016 To 30-JUN-2017

2,1 MW Solar Park Danfoss Nordborg. 1 Real Estate

Direct Fresh Air Free Cooling of Data Centres

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress

Jon Buschke 3059 Austin Ave Simi Valley, CA (805)

The Green/ Efficiency Metrics Conundrum. Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power

Presenter: Bruce Clay Clay Energy Fiji

VISIT 2010 Fujitsu Forum Europe 0

Data Centers: Definitions, Concepts and Concerns

General Recommendations for a Federal Data Center Energy Management Dashboard Display

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Reducing Data Center Energy Consumption

Capgemini UK Infrastructure Outsourcing

Computing & Telecommunications Services Monthly Report March 2015

CENTERPOINT ENERGY TEXARKANA SERVICE AREA GAS SUPPLY RATE (GSR) JULY Small Commercial Service (SCS-1) GSR

FREE ONLINE APPLICATION OF CALCULATION

ICT and the Green Data Centre

BYRNE DIXON HAS BRIGHT IDEAS. Reducing data centre energy usage

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)

Future Energy Systems - The challenges of meeting demand and

Energy Savings from Business Energy Feedback

Green and Smart Data Center -- Energy Saving --

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

Gross/Active PV Surface Area: ,40 / ,29 m². Energy Produced by PV Array (AC):

Server Technology, Inc.

Your guide to electricity pricing in Ontario

THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS

PTC Creo 2.0 Hardware Support Dell

Power Generation Division

A Market Transformation Programme for Improving Energy Efficiency in Data Centres

Mailing Address 4650 Adohr Ln. Camarillo, CA Year Financial Analysis. $1,051 / mo (avg) Cost Breakdown. System Description

Green Computing: Datacentres

Applying ICT and IoT to Multifamily Buildings. U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS

DCMA Software Contract Management Services CMM Based Insight Initiative

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization

FEAR Model - Review Cell Module Block

World s Greenest High Performance Data Center

Introduction of the Latest Intelligent Green Management Solution

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How

5-Minute Primer for Commercial Building Energy Audits

Green IT Solutions From Desktop to Datacenter. Dave Spear Sr. Engagement Manager & Sustainability Advocate dave.spear@microsoft.

Ashley Institute of Training Schedule of VET Tuition Fees 2015

Elevating Data Center & Mission Critical Energy Efficiency

The Japanese Experience Countering Spam ITU TELECOM WORLD 2006

ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER

Proposal prepared for Happy Solar Owner

Driving Action through. Title Style. Moderated by: Sarah Zaleski U.S. DOE

Figure 1: Comparison of Projected Electricity Use,

FCR The Driver of All Other Metrics

BEHIND UNDERSTANDING AND MANAGING. SaaS BUSINESSES. Recurly counts some of the world s most successful subscription businesses as its customers

FY 2015 Schedule at a Glance

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

DOE Data Center Energy Efficiency Program

Green HPC - Dynamic Power Management in HPC

Green Computing: Datacentres

How to Calculate a Data Center's Energy Conservation Rate

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

Daikin Altherma Hybrid Heat Pump

BS EN Energy Management Systems VICTORIA BARRON, PRODUCT MARKETING MANAGER, BSI

Sea Water Heat Pump Project

Data driven approach in analyzing energy consumption data in buildings. Office of Environmental Sustainability Ian Tan

POLICY FEEDING RENEWABLE. How the Energy Bill might affect green electricity suppliers and also renewable generators

The Green Grid, Metrics and DCMM. Presented by: Jay Taylor

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Identifying Energy Saving Opportunities in the Data Center

From Legacy to Agile BBV System-Event, Bern Christof Zogg, Director Developer & Platform Group

Managing Power Usage with Energy Efficiency Metrics: The Available Me...

Auditing a data centre but to what standard?

Department of Public Welfare (DPW)

Idle Data Analysis & Charts for the Draft 3 ENERGY STAR Computer Server Specification 10/31//08

Deep Dive Think Tank: Energy Costs and Strategies for Reduction

Challenges for Energy Efficiency in Local and Regional Data Centers

Transcription:

Datacenter Performance Per Energy (DPPE) October 5th, 2010 Survey and Evaluation Committee

Introduction It is necessary to create a usable and agreeable Metrics to express energy efficiency of the entire data center with both IT equipments and Data Center infrastructure. TGG created PUE metric is widely used and accepted throughout the world. Power Usage Effectiveness (PUE) was introduced by The Green Grid in 2007. However, there is an increasing need for a metric which could do more precise measurement of the entire data center. PUE maybe understood as a metric which has a focus on the Data Center Infrastructure. PUE = Overall consumption by Data Center Consumption by IT equipments Category Infrastructure (Power, A/C etc) Change in PUE number Improvement on Energy Consumption will change PUE Throughout the world, EPA Energy Star, EU Code of Conduct and such, the PUE is widely accepted as a current primary metric of the Data Center energy efficiency indicator. IT Equipment (Server, Storage, NW) Effort of Energy Consumption will not appear on PUE i.e. Highly Efficient IT Equipment will not necessary yield good PUE number. 2

Development of DPPE DPPE is developed by the Green IT Promotion Council (GIPC) of Japan. GIPC & JEITA Project Organizational Chart GIPC Organization Chart Diffusion Education Committee Educational activities Providing information globally Toyako Environment Showcase International forums Governing Board Policy Committee Technology Study Committee Technology Roadmap formation Propose innovative technologies Make plans supporting diffusion of new technologies Steering Committee Management Office JEITA Survey & Evaluation Committee Quantitative surveys and analysis of CO2 reduction Estimate future economic/social activities Develop DPPE Outline of the DPPE development Under Survey & Evaluation Committee, started as a sub working group in 2008 to discuss a new metric for the Data Center Energy Efficiency. Members: NTT Data, Intel, Nomura Research Institute, Daiwa Institute of Research, IBM Japan, NEC, Fujitsu and others. MOU with The Green Grid for joint Collaboration Years 2008 2009 2010 Activities Defined initial DPPE metrics Surveyed Japanese Data Centers 1 st Work Shop with EU & US Refined DPPE metrics Continuous discussion with TGG 2 nd Work Shop with EU & US Developing measurement guideline Conducting measurement discussion with EU & US 3

Our Scope of the Data Center Model A Data Center is; Infrastructure with Cooling and Electrical Plant, and IT equipments are categorizing two types of different Hardware Groups, which are receiving and outputting both Energy and Information Flow (Data). Input Data Center Output Natural Environment Renewable energy Grid power Power consumption Facility IT equipment Rejected Heat Reuse Input Data Operation Output Data 4

Concept of the DPPE DPPE is designed to measure and indicate the Energy Efficiency of an entire Data Center, and it has 4 sub metrics for the specific area. Goals (1) Energy efficiency of an entire Data Center could easily be calculated. (2) Comparison of different Data Centers could be performed and studied. (3) Comparison of a year-around energy status monitor is possible on a continuous base. Data Center Performance Per Energy (DPPE) is expressed as a function of four sub-metrics. Each of 4 sub-metrics could be used separately as an independent metric with a meaning. Data Center Energy Efficiency = Sub-metric 1 Sub-metric 2 Sub-metric 3 Sub-metric 4 IT Equipment Energy Efficiency, IT Equipment Power Usage Green f ( Utilization, Effectiveness, Energy Coefficient) = DPPE Datacenter Performance Per Energy 5

Structure of DPPE (1): The entire effort for the Data Center Energy Efficiency is broken down to the 4 sub tasks, and their associated specific metric is provided for each Energy Efficiency purpose. Target To improve energy efficiency of Data Center as a whole Environment friendly, sustainable Data Center operation. Realization method Improve energy efficiency of IT equipments in Data Center Use introduced IT equipment with optimal efficiency Install IT equipment with less energy consumption Reduce energy consumption of facilities in Data Center Reduce % of energy Spend on facilities Versus total energy consumption Replace grid electricity purpose with Green energy Metrics ITEU IT Equipment Utilization ITEE IT Equipment Energy Efficiency PUE Power Usage Effectiveness GEC Green Energy Coefficient 6

Structure of DPPE (2): Four sub-metrics proposed 4 Sub Metrics are defined for the specific areas and Energy Efficiency tasks and needs. Sub-metric Name Basic Definition Corresponding action IT Equipment Utilization (ITEU) IT Equipment Energy Efficiency (ITEE) Power Usage Effectiveness (PUE) = IT equipment usage in DC = (IT equipment rated capacity) (Rated Energy Consumption of IT equipment) DC Total Energy Consumption = (Energy Consumption of IT Equipment) Effective operation of IT equipment Installation of energy efficient IT equipment Energy saving in facility Green Energy Coefficient (GEC) = Green energy DC Total Energy Consumption Use of Green Energy Note) DC : Data Center 7

Structure of DPPE (3): DPPE & its 4 sub metrics explained DPPE, a total productivity of Datacenter, can be calculated, when all four sub metrics are measured. The concept of DPPE is based on the following formula: DPPE = DC Work DC energy Green energy = IT equipment work rate IT equipment work Capacity DC energy Green energy = IT equipment work rate IT equipment work capacity IT equipment energy IT equipment energy DC energy DC energy DC energy-green energy Note) DC power: Total power consumption of Data Center 8

DPPE (Data Center Performance Per Energy) DPPE is defined as a function of four sub-metrics. Metric: 1 DPPE= ITEU ITEE PUE 1 1 - GEC Comment: The purpose of expressing DPPE as a product of each sub-metric is to calculate DC capacity per non-green power. Because DPPE becomes infinite when GEC=1, the maximum value for GEC should be limited to 0.8 when calculating DPPE. 9

Data Center Information used in this Calculation Example High voltage PDU (1)Building scale of Data Center Item Machine room area Specification 1,200 m2 # Rack installed 300 Racks # Rack operating UPS Capacity 250 Racks Power Spec Sum =1500kW 2500 kva 2 (3) IT Equipment (in operation) Server 429 units Storage 420 sets NW Eqip. 84 sets (2) Power system chart Data Center Transformer Loss power 1,920kWh 2500kVA UPS Loss power 360kWh High voltage transformer 1,344kWh Loss power 72kWh PDU Solar power IT equipment 13,200kWh 6,000kWh Lighting CRAC Electrical energy on IT equipment : 13,200kWh Total energy consumption : (1,920+72+13,200+360+6,000)=21,552kWh PUE=13,200/21,552 =1.6 GEC : 1,344/6,000=0.22 10

Calculation example of DPPE (1) DPPE using calculation examples of sub-metrics so far explained 1) ITEU = 36 (%) 2) ITEE = 3.9 3) PUE = 1.6 4) GEC = 6.2 (%) 1 1 5)DPPE=0.36 3.9 1.6 1-0.062 = 0.935 Data Center in this example is not the energy saving type based on the state-of-the-art techniques but an example using techniques of 3-4 years ago. 11

Expression of DPPE Express in Cobweb Chart Example: Data Center of Company X 2 ITEE 5 3.9 1 IEU 100% 36% 0 6.2% 0.63 5DPPE=0.935 100% 4 GEC 6Profile Information including Grade (Operation rate is decreasing with more stand-by equipments. ) Scale (The structure is totally different between data center with just 1 unit of server and the center with 10000 units of servers. ) Application (Housing, hosting, cloud) Year of measurement are necessary. 1 3 1/PUE 6Profile 12

2 nd Workshop on Metrics of DC Energy Efficiency In Feb. 2010, the 2 nd International workshop of EU, U.S., and Japan was held. At the workshop all parties agreed to continue the work on establishing a method to measure the entire Data Center efficiency. 2 nd workshop on metrics of DC energy efficiency Agreement Discussion on metrics of DC energy efficiency 2 Feb 2010, in San Jose, Calif. U.S. Members: Japan: METI, GIPC, JEITA US: DOE, EPA, TGG Europe: EC All agreed that IT Equipment inclusive of entire Data Center based metric is needed. Source: http://www.greenit-pc.jp/topics/release/pdf/dppe_e_20100416.pdf 13

DPPE Measurement Trial in Japan In Japan, GIPC is doing the trial measurement of the DPPE to examine its usability and validate its method, also of its associated sub metrics. The definition and guideline of DPPE will be revised based on the result. Outline DPPE Measurement Trial to be planned within 2010 in Japan. Schedule Jul-Aug: 1 st phase of the measurement trial. Sept: Analyze the 1 st phase (measurements will continue until 6 months.) Purpose By measuring DPPE at actual DCs, find problems of DPPE, and verify the effectiveness of the metrics. Measurement at actual Data Center Try to examine at as many different types Trial measurement will be at least 6 months Gather all issues with actual measuring task Gather different Data Center specifics data Subjects Target subject Data Centers will be 20-30 in Japan. - Mainly, GIPC, JDCC, JISA, ASPIC and others member Data Centers will be ask to participate. Identify all issues Identify actual issue of measurement at the real Data Center. Try to cover Data Centers of different Service and Industry. Validate all issues Seasonal factor Location specifics, Size, and other environmental issue effects. Revise definition and guideline Note: Japan Data Center Council (JDCC), Japan Information Technology Service Industry Association (JISA), ASP SaaS Industry Consortium (ASPIC) 14

Roadmap of the Data Center Metrics Discussion (tentative) Japan, US and EU are now discussing on the definition and measurement guideline of datacenter energy efficiency metrics 2010 Apr May June July Aug Sep Oct Nov Dec 2011 Jan Feb Mar Taskforce Discussion Milestone PUE ERF& RER (#2) GEC ITEE &ITEU Productivity Proxies (#1a) DC Productivity (#1) DPPE High Priority (3) Define the process for measurement (1)(2) Identify/ (3) Define the process define the metric for measurement (1)(2) Identify/ (3) Define the process define the metric for measurement (1)(2) Identify/ define the metric (1)(2) Identify/ define the metric WS (Milan) (3) Define the process for measurement (3) Define the process for measurement (1)(2)(3) Identify/ define the metric, Define the process for measurement (1)(2)(3) Identify/ define the metric, Define the process for measurement WS (Japan) Carbon metric (#2) (1)(2)(3) Identify/ define the metric, Define the process for measurement Activities Japan Develop the DPPE measurement guideline (w detailed proposal of PUE measurement) Revise DPPE WP Measure DPPE in Japan Data Analysis (and Singapore); 1 st phase Measure DPPE in Japan (and Singapore); 2 nd phase Data Analysis Revise DPPE definition/ measurement guideline Note: (1)-(3) show # in the Goal section of the agreement, while (#1), (#1a), (#1b) and (#2) # in the Desired Outcomes section. 15

http://www.greenit-pc.jp 16 All Rights Reserved, Copyright GIPC 2009